HomeMy WebLinkAboutE800 DETAILST-0" MAXIMUM FROM BOX TO HANGER (TYPICAL) 9132" DIA. STEEL ROD
SUSPENSION FROM BUILDING
CONDUIT CLAMP (TYPICAL) STRUCTURE WITHIN OUTLET BOX (T"OF
(TYPICAL).
8'-0" MAXIMUM SPACING
BETWEEN HANGERS (TYPICAL).
STEEL OUTLET BOX, SIZED PER N.E.C.
AND SUPPORTED RIGIDLY FROM
STRUCTURE (TYPICAL). INSTALL NO
CLOSER THAN 1'-0" FROM ANY FIXTURE.
CONDUIT (TYPICAL)
NOTES:
1. DO NOT SUPPORT CONDUIT OR BOXES FROM CEILING GRID HANGERS.
NO SCALE
PLASTER RING TO CO
WITHIN 1/8"OF FINAL;
SEE ARCHITECTURAL
PLANS FOR WALL COP
NOTES:
1. THE INTENT OF THE DETAIL IS TO ENSURE DEVICE ROUGH -INS ARE ALIGNED, SOLIDLY
MOUNTED AND THE SURFACE OF THE TRIM IS EITHER FLUSH WITH THE WALL SURFACE OR
WITHIN 1/8" OF THE WALL SURFACE. JUNCTION BOXES LARGER THAN 4" SQUARE SHALL BE
MOUNTED IN A MANNER THAT IS SIMILAR TO THE SYSTEM NOTED ABOVE OR ACHIEVES
THE SAME RESULTS.
2. PLASTER RINGS DEPTH SHALL BE 1/8" DEEPER THAN THE GYP BOARD APPLIED TO THE
WALL. PLASTER RING SHALL BE 314" FOR USE WITH 5/8" GYP BOARD.
3. MOUNTING BRACKET FOR 2 1/2" OR 3 1/2" STUDS SHALL BE CADDY #H23, OR B-LINE 313423.
MOUNTING BRACKET FOR FOR 4" OR 6" STUDS SHALL BE CADDY #H46TC OR B-LINE BB4-# .
FOR MULTIPLE BOXES BETWEEN STUDS, BRACKET SHALL BE CADDY #RBS16/#RBS24 OR B-
LINE BB6# OR BBF# FLOOR MOUNT SUPPORT WITH BBFC.
4. WHERE RECEPTACLE AND TECHNOLOGY DEVICES ARE SHOWN SERVING A COMMON
COMPUTER OR EQUIPMENT, OR SHOWN IN SIMILAR LOCATIONS ON THE DRAWINGS THE
DEVICES SHALL BE INSTALLED ON OPPOSITE SIDES OF A COMMON STUD OR IN ADJACENT
OPENINGS WITH MOUNTING BRACKETS.
BACKBOX MOUNTING DETAIL
4 NO SCALE
RELEASED FOR CONSTRUCTION
4'-0" MIN., F-0" MAX. LENGTH 318" FLEX
CONDUIT WITH 3#18 CONDUCTORS;
FACTORY WIRE INTO FIXTURE (TYPICAL).
SAFETY CHAIN (OR WIRE) TO
STRUCTURE INSTALLED WITH ONE
LINK MORE THAN TAUT LENGTH.
LUMINAIRE RECESSED (TYPICAL).
T-BAR LAY -IN CEILING
SUSPENSION SYSTEM (TYPICAL).
STEEL OUTLET BOX, SIZE PER N.E.C. AND
SUPPORT RIGIDLY FROM STRUCTURE
THREADED BALL
SWIVEL HANGER
STEM, INSTALL FIXTURE WIRING
IN STEM (3#18 CONDUCTORS)
MOUNTED LUMINAIRE
NOTES
1. SELECT STEM LENGTH TO PROVIDE MOUNTING HEIGHT AS REQUIRED ON DRAWINGS.
2. PROVIDE TWO STEMS ON SINGLE LUMINAIRE AND ONE STEM PER LUMINAIRE WHEN JOINED
IN CONTINUOUS ROW.
3. LUMINAIRE TO BE MOUNTED LEVEL.
PENDANT MOUNTING DETAIL
�' NO SCALE
ADDITIONAL BOX
RATED WALLS: MOLDABLE FIRE
STOP PAD, FIVE SIDES OF BOX.
3M TAPE MPPI UL R9700.
THREADED ROD
SUPPORT PER
LUMINAIRE
4" BOX
CEILING T'S J
FIXTURE �
SUPPORT BOX AND CONDUIT
FROM STRUCTURE
CEILING TIE WIRE
FLEX CONDUIT
LENGTH: 4'-0" MIN. 6'-0" MAX.
ADJUSTABLE SUPPORT BRACKET,
2 PER LUMINAIRE. (ATTACH TO
CEILING GRID CHANNELS)
LAY -IN CEILING
i1 EXIT SIGN MOUNTING DETAIL
J NO SCALE
120 VOLT CIRCUIT, SEE PLANS
1/2"CONDUIT TO SECURITY DOOR ACCESS CONTROLLER
AND POWER SUPPLY BY
MANAGEMENTSYSTEM nnnc el mot lco i;�
FIRE ALARM DOOR RELEASE SW CONDUIT
6"x6"x4" JUNCTION
BOX WITH LOW
VOLTAGE DIVIDER
t
I'
IJI
PLASTER RING TO COME
IIIq
WITHIN I/8"OF FINAL SURFACE.
STUD
ADDITIONAL BOX SUPPORT
F
SEE ARCHITECTURAL PLANS
FOR WALL CONSTRUCTION.
PLAN
VIEW
NOTES:
NOTES:
1. HORIZONTAL CONDUIT CONNECTION BETWEEN BOXES LESS THAN 2'-0" NOT PERMITTED.
SEE SPECIFICATIONS AND DRAWING NOTES FOR ADDITIONAL SPACE REQUIREMENTS
BETWEEN DEVICES,
SIDE BY SIDE DEVICE OPENINGS
1 /2"
CONDUIT
a
DM
DOOR MONITOR SENSOR
4"x2 1/2"xi 7/8" DEEP
DEVICE BOX IN FRAME.
CRi
ACCESSIBLE CEILING
WHERE APPLICABLE
� 314" CONDUIT
CARD READER CONTROL
STATION. BACK BOX AT+48"
A.F.F. 4" x 4" BOX MINIMUM,
VERIFY WITH EQUIPMENT
SUPPLIER PRIOR TO ROUGH -IN.
1. ALL CONDUIT SHALL BE CONCEALED IN WALLS OR DOOR FRAME, TO ABOVE ACCESSIBLE
CEILING.
2. ALL JUNCTION BOXES, CONDUIT AND 120 VOLT CONDUCTORS SHALL BE By CONTRACTOR,
UNLESS SHOWN OTHERWISE.
3. ALL CONNECTIONS BY DOOR SUPPLIER CONTRACTOR.
4. VERIFY REQUIREMENTS WITH EQUIPMENT SUPPLIERAND OWNERS REPRESENTATIVE
PRIOR TO ROUGH IN.
DOOR SECURITY DETAIL
6 NO SCALE
+IMEGo��W��o,,o
MEG GORP RESERVES FRORRETARY RMMS. INCLUDING COPYRIGHTS. TO THIS
n
OAMERICAN
M■ STRUCTUREPOINT
INC
72605MpManE Suman I IMianapolle, Indiana M256
TEL 317.547.5560 1 RUX317.593.0270
wxw.mu ummoim.oan
*IMEG
8900 KEYSTONE XING PH: 317.848.5045
SUITE 210 FAX 317.844.2201
INDIANAPOLIS, IN www.imegeorp.com
46240
GEICO CORPORATE
FIRST FLOOR
RENOVATION PHASE 3
101 W. 103RD ST.
INDIANAPOLIS, IN 46290
N0.
11400159
STATE OF t415
V
S/jNA �1111E��o(`°+O/n6/ 1L/4/n/ 19
�l
:RTIFIED BY
ISSUANCE INDEX
DATE:
06114119
PROJECT PHASE:
CONSTRUCTION DOCUMENTS
PHASE 3
REVISION SCHEDULE
NO. DESCRIPTION DATE
Project Number 18002480.01
DETAILS
Subject to compliance with all regulations
of State and Local Codes
City of Cannel (�
AV1:\GL on,V.:T,DA�L
DATE: 09/24/19
VPLPHD PARTCPATION OF IMEG CORP. *ARIMES CORP.
REFERENCESGIFININCNES
n a
E800