HomeMy WebLinkAboutM801 DETAILSWIDTH OF EQUIPMENT
OR 30" MIN.
FLEXIBLE DUCT
S.A. 1
r-----------
I
PLENUM
AIR
I
FILTER
PROVIDE INLET ATTENUATOR
WHERE NOTED
FAN POWERED TAB V
NO SCALE
RELEASED FOR CONSTRUCTION
Subject t6 compliance with all regulations
of State and Local Codes
City of Cannel (�
�VT�L1lEw3Ci1,DML
REHEAT COIL
ALINED DISCHARGE DUCTWORK
>'7flGC
�<Yd1uIGIluLEdu�l
FAN
FAN POWERED
TERMINAL AIR BOX
DOUBLE
9116" DIA. BOLT HOLES
LOWER PORTION OF DUCT SUPPORT
SHOWN IN POSITION.
9116" DIA. x 8" LONG SLOT
1/2" CIA. ZINC -PLATED BOLT, NUT AND
WASHERS (TYPU o-0®
NOMINAL4x2 CHANNEL, 10 GA, PAINT c
GRIP GALVANIZED, BENT PLATE
DUCTWORK SUPPORT. CONTINUOUS
WELDED. SPRAY ALL WELDS AND HOLES
WITH COLD GALVANIZING. (TYP.) x
INSULATION AND
PREFABRICATED EQUIPMENT SUPPORT
CURB. VERIFY ROOFING MATERIAL AND
PROVIDE WITH OR WITHOUT CANTAS
REQUIRED. NEW CURBS SHALL NOT
PREVENT WATER ON ROOF FROM
DRAINING TO EXISTING ROOF DRAIN.
NOTES:
1. MAINTAIN THE TOP OF THE GUSSET JUST BELOW THE SLOT
AND AT A 450 ANGLE. AS THE SUPPORT HEIGHT INCREASES,
AND THE GUSSET MEET IN THE MIDDLE OF THE BASE, PROVIDE
ONE DIAGONAL BRACE BETWEEN THE VERTICAL LEGS.
2. DUCT ROOF SUPPORT SHALL BE RATED FOR 30 PSF SNOW
LOAD AND 20 PSF WIND LOAD.
3. PAINT RAIN COVER AND DUCT SUPPORTS TO MATCH DUCT.
4. CROSS BRACE SUPPORTS AS INDICATED ON THE PLAN.
CROSS BRACING SHALL BE INSTALLED FROM BASE OF
SUPPORT TO TOP OF THE ADJACENT SUPPORT TO LIMIT
LATERAL MOVEMENT.
MINIMUM 18 GAUGE, G90 PAINT GRIP
GALVANIZED RAIN CAP OVER DUCT.
FIELD OR FACTORY PAINT ALL ROOF
MOUNTED DUCTWORK AND SUPPORTS
WITH PPG DURANAR COATING WITH
COLOR AS SELECTED BY ARCHITECT.
10 GA PAINT GRIP GALVANIZED BENT
PLATE BAND ABOVE DUCT.
WELD BOTTOM BAND TO TOP OF
CHANNELS.
4"HIGH AT CENTERLINE OF DUCT.
PROVIDE TAPERED ROOF INSULATION
TO MATCH DUCT CAP.
I
�
I
II
I�
/ 450 GUSSET ON EACH SIDE. SEE NOTE 1.
3/8" ZINC -PLATED LAG SCREWS. (TYPU
AT VERTICAL LEG
12" O.C. (MAX.)
BOTTOM OF SLOT
12" MIN.. 36" MAX.
(NOTE 1)
TOP OF CURB
12" MIN.
ROOF CUTTING AND PATCHING SHALL
BE PERFORMED BYA CERTIFIED
CONTRACTOR TO MAINTAIN EXISTING
ROOF WARRANTY.
DUCT ROOF SUPPORT DETAIL (RECTANGULAR
FLASH ROOF MEMBRANE
TO CURB. (NOTE 1)
ROOF DECK
ROOF DECK
PREFAB CURB WITH
WOOD NAILER.
DAMPER
MOD.
TAB Al
AIRFLOW
VELOCITY AND
STATIC SENSOR w,
PRIMARY AIR FROM ZONE
CONDITIONING AHU PI
PRESSUREINDEPENDENT
TERMINAL AIR BOX (TAB)
HIGH GRADE SEALANT
SHEETMETAL SCREWS
6" ON CENTERS.
CADMIUM PLATED LAG
SCREWS 6" ON CENTERS
IT ABOVE TOP OF
INSULATION.
ROOF & ROOFING.
DUCTWORK
NOTES:
1. ALL ROOF FLASHING SHALL BE PER ROOF MANUFACTURER'S
RECOMMENDATIONS.
DUCT ROOF PENETRATION
J NO SCALE
ACTUATOR
V AIRTEMP
SUPPLY
AIR
AI
WALL MTD
0 �
TEMP SENSOR
• FMCS TAB CONTROLLER SHALL MODULATE THE TAB DAMPER AND TAB ELECTRIC REHEAT COIL
TO MAINTAIN SPACE TEMPERATURE OF 72-F (ADJ.) WITH 5-F (ADJ.) DEAD BAND BASED ON A
SIGNAL FROM A WALL MOUNTED TEMPERATURE SENSOR. SEE DRAWINGS FOR TEMPERATURE
SENSOR REQUIREMENTS. SPACES WITH ADJUSTABLE THERMOSTATS WILL ALLOW A+/- 3°F (ADJ.)
OFFSET FROM THE DDC SETPOINT.
AT FULL COOLING, THE TAB SHALL BE OPEN TO MAXIMUM CFM POSITION. THE REHEAT COIL
SHALL BE DE -ENERGIZED.
UPON A FALL IN SPACE TEMPERATURE, THE TAB SHALL MODULATE CLOSED UNTIL SPACE
SETPOINT IS MAINTAINED, OR UNTIL IT REACHES ITS MINIMUM SCHEDULED CFM POSITION PER
THE TAB SCHEDULE. THE REHEAT COIL SHALL REMAIN DE -ENERGIZED.
UPON A FURTHER FALL IN SPACE TEMPERATURE, THE ELECTRIC REHEAT COIL AND TAB SHALL
MODULATE OPEN IN UNISON TO MAINTAIN SPACE SETPOINT UNTIL TAB AIR FLOW REACHES ITS
MAXIMUM HEATING SETTING.
• THE FMCS SHALL UTILIZE OUTPUT FROM ALL TERMINAL AIR BOX POSITIONS TO RESET THE
SUPPLY DUCT DIFFERENTIAL STATIC PRESSURE.
ALARMS. INTERLOCKS & SAFETIES:
• SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF THE SPACE TEMPERATURE IS MORE
THAN 10-F (ADJ.) ABOVE OR BELOW SETPOINT.
• IF THE HIGH TEMPERATURE SAFETY DEVICE EXCEEDS MANUFACTURER'S SETPOINT, AN ALARM
SHALL BE SENT TO THE OPERATOR INTERFACE.
TAB CONTROL W/ ELECTRIC REHEAT an TAB-X
*IMEG o� a wIr euan,,d
n
OAMERICAN
M■
STRUCTUREPOINT
INC
7260 sManlana ehtian I IManapoN, Indiana M236
TEL 317.M7.R60 I FI1I317.393.0270
wxw.mu manooim.oan
*IMEG
8900 KEYSTONE XING PH: 317.848.5045
SUITE 210 FAX 317.844.2201
INDIANAPOLIS, IN www.imegeorp.com
46240
GEICO CORPORATE
FIRST FLOOR
RENOVATION PHASE 3
101 W. 103RD ST.
INDIANAPOLIS, IN 46290
' 4Z�/' No. `En'
PE10505421 '
STATEOF
j l
o11ONAV IL1"°°°�06/14/19
CERTIFIED BY
ISSUANCE INDEX
DATE:
06/14/19
PROJECT PHASE:
CONSTRUCTION DOCUMENTS
PHASE 3
REVISION SCHEDULE
NO.
DESCRIPTION
DATE
1
ADDENDUM 1
07-12-2019
2
ADDENDUM 2
07-17-2019
Project Number 18002480.01
DETAILS
DATE: 09/24/19
MEG CORP RESERVES PROPRIETARY
VPL PNC PARTCPATION OFII LORD. ®M1811 CORP.
REFERENCE SCALE IN INCH
M 801