HomeMy WebLinkAboutM900 SCHEDULESMAKE-UP AIR UNIT SCHEDULE
VOTES:
1.REFER TO CAPTIVEAIRE SHEETS FOR ADDITIONAL INFORMATION.
2. ALTERNATE BID.
MAX. DIMENSIONS
fT
MIN.
TAG AREA
RPM
EXT.S.P.
EFFICIENCY
MIN. NISH TURNDOWN/
NAME SERVED LENGTH WIDTH HEIGHT
ED)
IN. W.C.
AFUE
OUTPUT STEPS
MAU-1
KITCHEN
202.25'
49"
48"
3168
1 1281
0.5
80
22
1
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulatims
of State and Local Codes
City of Carmel (�
�VT�11lEwxCi1,P1 V-a�
DATE: 09/24/19
LAT°F
TYPE
DEFL.
(NOTEPE)
(NOTEE)
VOLTAGE
PHASES
77.8
0.000
1.15
2
460
3
FUEL
SCCR IFUEL TYPE I PRESSURE PSI MANUFACTURER MODEL NOTES
0 1 CAPTIVEAIRE A2-E1.004-20D- 1, 2
TERMINAL AIR BOX SCHEDULE - FAN POWERED WITH ELECTRIC REHEAT
NOTES:
1. NEITHER RADIATED NOR DISCHARGE SOUND LEVELS SHALL EXCEED NC 35 AT 1.5" INLET STATIC PRESSURE WHEN TESTED PER AHRI STANDARD 885-2008 USING 518" 20-LB DENSITY
MINERAL
FIBER CEILING TILE.
2. TOTAL AIR PRESSURE DROP OF TAB AND REHEAT COIL SHALL NOT EXCEED 0.50" WC,
3. REBALANCE EXISTING BOX TO SCHEDULED VALUES.
4. SENSOR TYPES: 1 - SENSOR ONLY, 2 - SENSOR WITH ADJUSTMENT, 3 - SENSOR WITH OVERRIDE, 4 - SENSOR WITH ADJUSTMENT AND OVERRIDE, 5 - RELOCATE EXISTING SENSOR.
5. FURN ISH WITH INTEGRAL NEMA 1 CONTROL ENCLOSURE AND DOOR INTERLOCKING DISCONNECT.
6. FURNISH WITH LINE FUSING MERCURY CONTACTORS MOUNTED AND WIRED WITH IN THE CONTROL ENCLOSURE.
7. FURN ISH WITH AN ELECTRON IC AIR FLOW SENSOR, PRIMARY AUTOMATIC RESET THERMAL CUTOUT, AND SECONDARY MANUAL RESET THERMAL CUTOUT.
PRIMARY CFM
HEATING COIL
FAN
ELECTRICAL
SENSOR
MIN.
TAG
NEW/EXISTING/
EAT
LAT
S.P. IN.
TYPE
INLET
MODEL
NAME
AREA SERVED
RELOCATED
MAX.
MIN.
°F
°F
KW
CFM
W.G.
HIS
VOLTAGE
PHASES
(NOTE 4)
SIZE
MANUFACTURER
(NOTES 1, 2)
NOTES
TU-2-1-1
OPEN SEATING 125B
EXISTING
1400
400
60
75.1
6.7
1400
0.35
1/2
480
3
5
IT
TUTTLE 8 BAILEY
FPC
1, 2, 3
TU-2-1-2
OPEN SEATING 125B
EXISTING
1400
400
60
75.1
6.7
1400
0.35
1/2
480
3
5
IT
TUTTLE 8 BAILEY
FPC
1, 2, 3
TU-8-1-1
OPEN SEATING 125B
EXISTING
1620
490
60
80.0
5.6
1500
0.36
1/2
480
3
5
12"
TUTTLE 8 BAILEY
FPC
1, 2, 3
TERMINAL AIR BOX SCHEDULE - SINGLE DUCT
NOTES:
1. NEITHER RADIATED NOR DISCHARGE SOUND LEVELS SHALL EXCEED NC 35 AT 1.5" INLET STATIC PRESSURE WHEN TESTED PER AHRI STANDARD 885-2008 USING 518" 20-LB DENSITY MINERAL
FIBER CEILING TILE.
2. TOTAL AIR PRESSURE DROP OF TAB AND REHEAT COIL SHALL NOT EXCEED 0.50" WC.
3. REBALANCE EXISTING BOX TO SCHEDULED VALUES.
4. SENSOR TYPES: 1 - SENSOR ONLY, 2 - SENSOR WITH ADJUSTMENT, 3 - SENSOR WITH OVERRIDE, 4 - SENSOR WITH ADJUSTMENT AND OVERRIDE,
5 - RELOCATE EXISTING SENSOR.
NEW/
CFM
COOLING
EXISTING/
SENSORTYPE
MIN.INLET
TAG NAME
AREASERVED
RELOCATED
MAX.
MIN.
(NOTE 4)
SIZE (IN.)DIA
MANUFACTURER
MODEL
NOTES
TU-2-1-4
SERVERY 126A
RELOCATED
1000
1 0
5
12"
TUTTLE B BAILEY
SDV
1,2,3
TERMINAL AIR BOX SCHEDULE - SINGLE DUCT ELECTRIC
REHEAT
NOTES:
1.
NEITHER RADIATED NOR DISCHARGE SOUND LEVELS SHALL EXCEED NC 35 AT 1.5" INLET STATIC PRESSURE WHEN TESTED PER AHRI STANDARD 885-2008
USING 5/8" 20-LB DENSITY MINERAL FIBER CEILING TILE.
2.
TOTAL AIR PRESSURE DROP OF TAB AND REHEAT COIL SHALL NOT EXCEED 0.50" WC.
3.
REBALANCE EXISTING BOX TO SCHEDULED VALUES.
4.
SENSOR TYPES: 1 -SENSOR ONLY, 2 -SENSOR WITH ADJUSTMENT, 3 -SENSOR WITH OVERRIDE, 4 -SENSOR WITH
ADJUSTMENT AND OVERRIDE,
5 -RELOCATE EXISTING SENSOR.
5.
FURNISH WITH INTEGRAL NEMA 1 CONTROL ENCLOSURE AND DOOR INTERLOCKING DISCONNECT.
6.
FURNISH WITH LINE FUSING MERCURY CONTACTORS MOUNTED AND WIRED WITHIN THE CONTROL ENCLOSURE.
7.
FURNISH WITH AN ELECTRONIC AIR FLOW SENSOR, PRIMARY AUTOMATIC RESET THERMAL CUTOUT, AND SECONDARY MANUAL RESET THERMAL
CUTOUT.
NEW /
CFM
ELECTRICAL
MINIMUM
COOLING
EXISTING/
SENSOR TYPE
INLET SIZE
TAG NAME
AREA SERVED
RELOCATED
MAX.
MIN.
EAT°F
LAT°F
KW
VOLTAGE
PHASE
(NOTE 4)
(IN.)DIA
MANUFACTURER
MODEL
NOTES
TU-2-1-5
SERVERY 126A
EXISTING
1720
510
55.0
75.0
6.5
480
3
5
10"
TUTTLE 8 BAILEY
SDV-10
1, 2, 3
TU-2-1-6
OPEN SEATING 125B
EXISTING
1000
300
55.0
75.0
6.5
480
3
5
8"
TUTTLE 8 BAILEY
BOVA0
TUE-1-2
COFFEE SHOP 123A, DINING LOBBY 125A,
EXISTING
1500
450
55.0
75.0
11.4
480
3
5
14"
TUTTLE 8 BAILEY
DESV-12
1, 2, 3
BACK ROOM 123B, OPEN SEATING 125B
TU-8-14
DISH ROOM 122A, KITCHEN 121A
EXISTING
1600
480
55.0
75.0
8.6
480
3
5
12"
TUTTLE 8 BAILEY
DESV-12
1, 2, 3
TU-8-1-8
FIRE 11M
EXISTING
260
200
60.0
75.0
1.0
277
1
5
5"
TUTTLE 8 BAILEY
SDV
1, 2, 3
TU-8-1-24
SECUR ITV 118A
NEW
220
70
60.0
95.0
1.5
480
3
4
5"
TITUS
DESV
NOTES 1, 2
TU-8-1-25
STOR. 120A
NEW
250
70
60.0
95.0
1.5
480
3
4
5"
TITUS
DESV
NOTES I,2
GRILLES REGISTERS & DIFFUSERS SCHEDULE
NOTES:
1. CONTRACTOR SHALL DETERMINE PROPER MARGIN STYLE TO MATCH CEILING CONSTRUCTION.
2. ALL RUN OUT DUCTWORK TO DIFFUSERS SHALL BE NECK SIZE UNLESS OTHERWISE NOTED.
3. RETURN GRILLE WITH DUCT BOOT.
TAG
NAME
MATERIAL
CONFIGURATION
MARGIN
(NOTE 1)
INLET SIZE
(IN.)(NOTE 2)
FACE SIZE
(IN.)
VOLUME
DAMPER
REQUIRED
FINISH
MANUFACTURER
MODEL
NOTES
EGA
STEEL
EGGCRATE
LAY -IN
SEE PLANS
INLET+2
NO
WHITE
TITUS
50F
RG-1
STEEL
EGGCRATE
LAY -IN
22x22
24x24
NO
WHITE
TITUS
50F
EGGCRATE
LAV-IN
22x10
24x12
NO
WHITE
TITUS
50F
STEEL
EGGCRATE
LAY -IN
22x22
24x24
NO
WHITE
TITUS
50F
3
I
STEEL
EGGCRATE
LAY -IN
22x10
24x12
NO
WHITE
TITUS
50F
3
STEEL
PANELFACE
LAY -IN
SEE PLANS
24x24
NO
WHITE
TITUS
OMNI
STEEL
SINGLE DEFLECTION
11/4"
SEE PLANS
INLET+2
NO
WHITE
TITUS
301R
FAN SCHEDULE
NOTES:
1. FURN ISH WITH FACTORY MOUNTED AND WIRED STARTER AND DISCONNECT.
2. FURN ISH WITH LINE VOLT THERMOSTAT. SET 50 ABOVE SPLIT SYSTEM THERMOSTAT.
3. REFER TO CAPTIVEAIRE SHEETS FOR ADDITIONAL INFORMATION.
4. ALTERNATE BID.
TAG
NAME
AREASERVED
CFM
S.P. IN.
W.C.
FAN RPM
(NOTE F)
DRIVE
TYPE
MAX.
AMCA
BONES
MANUFACTURER
MODEL
NOTES
BHP
MINIS
VOLTAGE
PHASES
DISCONNECT
CONTROLLER/ STARTER
BY
(NOTE A)
TYPE
(NOTE B)
BY
(NOTE A)
TYPE
(NOTE C)
KEF-1
KITCHEN HOOD
3960
2.11
1421
DIRECT
31
3.187
5
460
3
CAPTIVEAIRE
DU200HFA
1, 2, 3,4
KEF-2
DISHWASHER
525
0.50
1232
DIRECT
10.5
OA23
.333
115
1
CAPTIVEAIRE
DU33HFA
1, 2,3
SCHEDULE GENERAL NOTES:
A. DISCONNECTAND CONTROLLER STARTER FURNISHED AND
INSTALLED BY
MFR=MANUFACTURER
EC = ELECTRICAL CONTRACTOR.
MC = FURNISHED BY MECHANICAL CONTRACTOR, INSTALLED BY
ELECTRICAL CONTRACTOR.
MFRIEC = FURNISHED LOOSE BY MANUFACTURER INSTALLED BY
ELECTRICAL CONTRACTOR....
B. DISCONNECT TYPE:
F = FUSED
NF = NON -FUSED
C. CONTROLLER STARTER TYPE:
FV = FULL VOLTAGE
W VE = W VE-DELTA
SS = SOLID STATE (SOFT START)
MS = MANUAL STARTER
VFD = VARIABLE FREQUENCY DRIVE
VFDIB = VARIABLE FREQUENCY DRIVE WITH BYPASS
D. FAN RPM SHALL NOT EXCEED 110 % OF SCHEDULED VALUE, WITH
THE SCHEDULED WHEEL TYPE. SUBSTITUTION OF BI OR BIA FANS
FOR FC IS ACCEPTABLE IF EFFICIENCY IS NOT LOWER.
E. NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF MOTOR NAM
PLATE RATING.
F. MUST BE WITHIN +/- 10 % OF SCHEDULED RPM.
G. CURB TYPE:
MFR = STANDARD CURB BY MANUFACTURER
GC= BY GENERAL CONTRACTOR
SAC = SOUND ATTENUATOR CURB
�IMEG o� W nT].LN.Y01+D
MEG GVRP RESERVES MOPWETARY RIGHTS. INCW DING COPYRIGHTS. TO THIS
DRAWING AND THE DATA SHGWN TIEREdI. SLID DRAW ING PNDM DLTAARE
THEIX0.USIWPRWERIYGF NEED 0041PFNDS11l NOTSEUSEDOR
REPRODUCED FOR ONYOTIER PROJECT W RHJUT THE EXPRESS W NITEN
WPROVKPND PARTCPATICN CF HADG WIRP. 020181ME13CORP.
REFEfENCESGLIEININCNg
0 1
GEICO
so
OAMMCAN
®■
STRUCTUREPOINT
7260 SM1adeland Smtion I Indianapolis, Indiana M256
TEL 317.547.5580 1 Fax31].543.02]0
www.almmumpoim.00m
8900 KEYSTONE XING PH: 317.848.5045
SUITE 210 FAX 317.844.2201
INDIANAPOLIS, IN www.imegeorp.com
46240
GEICO CORPORATE
FIRST FLOOR
RENOVATION PHASE 3
101 W. 103RD ST.
INDIANAPOLIS, IN 46290
06/14/19
CERTIFIED BY
ISSUANCEINDEX
DATE:
06/14/19
PROJECT PHASE:
CONSTRUCTION DOCUMENTS
PHASE 3
REVISION SCHEDULE
NO. I DESCRIPTION I DATE
Project Number 18002480.01
SCHEDULES