HomeMy WebLinkAboutA000.5PLOTTED: January 4, 2017 / Annie Ki / 2450-BOURGES-MZ-BASE-EL-NC2G.DWG
A3-NC2G
3FB.4Northern Craftsman 2G3 Car Front EntrySide and Rear Elevation, Roof Plan and Attic Ventilation Schedule1900 E. Golf Road, - Suite 300Schaumburg, Illinois 60173Midwest Zone Office108/05/2016BID SET REVISIONS209/02/2016ADDITIONAL ELEVS.309/14/2016ADDITIONAL ELEVS.410/28/2016REVISIONS512/28/2016REVISIONS............
PLAN NAME
SHEET
PRODUCTION MANAGER
DATE / DESCRIPTION
NPC PLAN NUMBERLAWSON PLAN ID
GARAGE HANDING
REV #
NOTE: SCALES NOTED ON DRAWINGS RELATE TO FULL SIZE PLOTS ON 22x34 SHEETS - 11x17 SHEETS REPRESENT 1/2 SCALE PLOTS
INITIAL RELEASE DATE:CURRENT RELEASE DATE:
(c) Copyright Pulte Home Corporation - 2016
EM/ER06/13/2016
LEFT
BOURGES
2450.300.00.CPM
--
12/28/2016SCALE:ROOF PLAN1/8" = 1'-0"-
7:12
6:12
"A"2963ROOF AREA:SQ. FT.
\A1;34'-0"
\A1;4'-0"
OPT. POT VENTS
\pxql;PROVIDE ADEQUATE OPENING FOR AIR MOVEMENT BETWEEN ATTIC SPACES TO SUPPORT REQUIRED VENTILATION
\A1;1'-0"\PTYP.
OPT. GUTTER & DOWNSPOUTS
\A1;4'-0"\A1;4'-10"\A1;1'-0"
\A1;1'-0"\PTYP.
"B"202ROOF AREA:SQ. FT.
\A1;3'-0"
6:12
7:12
9:129:12
5.5:129:129:12
3.5:12
1TOP OF FOUNDATION
TOP OF PLATE
TOP OF PLATE
\A1;9'-1{\H0.750000x;\S1#8;}"\A1;OPT. 10'-1{\H0.7x;\S1#8;\H1.4286x;" }\A1;8'-2{\H0.750000x;\S7#8;}"\A1;9'-2{\H0.7x;\S7#8;\H1.4286x;" @ OPT. 10' PL.}
\A1;8'-1{\H0.750000x;\S1#8;}"\A1;OPT. 9'-1{\H0.7x;\S1#8;\H1.4286x;" }\A1;7'-2{\H0.750000x;\S7#8;}"\A1;8'-2{\H0.7x;\S7#8;\H1.4286x;"@ OPT 9' PL}
SCALE:RIGHT ELEVATION1/8" = 1'-0"-
\A1;OPT. MASONRY WRAP\A1;OPT. MASONRY RETURN 1
126
127
125.5
123.5
\A1;OPT.4 44
SCALE:LEFT ELEVATION1/8" = 1'-0"-
612
OPT. MASONRY WAINSCOT
\A1;OPT. MASONRY RETURN 1
126 127
125.5
OPT.
\A1;OPT.4 TOP OF FOUNDATION
TOP OF PLATE
TOP OF PLATE
\A1;9'-1{\H0.750000x;\S1#8;}"\A1;OPT. 10'-1{\H0.7x;\S1#8;\H1.4286x;" }\A1;8'-2{\H0.750000x;\S7#8;}"\A1;9'-2{\H0.7x;\S7#8;\H1.4286x;" @ OPT. 10' PL.}
\A1;8'-1{\H0.750000x;\S1#8;}"\A1;OPT. 9'-1{\H0.7x;\S1#8;\H1.4286x;" }\A1;7'-2{\H0.750000x;\S7#8;}"\A1;8'-2{\H0.7x;\S7#8;\H1.4286x;"@ OPT 9' PL}
SCALE:REAR ELEVATION1/8" = 1'-0"-
OPT. MASONRY WAINSCOT
ELEVATION NC2G
ATTIC VENT SCHEDULE
VENTILATION REQUIRED AND SUPPLIED IS BASED ON POT VENT VALUES AND RIDGE VENT VALUES SHOWN IN TABLE ABOVE
** CONTRACTORS INSTALLING VENTILATION ARE RESPONSIBLE FOR VERIFYING THAT VENTS USED WILL SUPPY VENTILATION TO MEET CODE REQUIREMENTS
* SCHEDULE HAS BEEN CALCULATED ASSUMING EAVE VENTILATION AT 50-60% OF TOTAL AND RIDGE AT 40-50% OF TOTAL REQUIRED VENTILATION
ROOF AREA "A"SQ FTG 2968 AT / NEAR RIDGE AT / NEAR EAVE
VENT TYPE
SQ. FT.
REQUIRED
RANGE
SQ. FT.
SUPPLIED
PERCENT
OF TOTAL
SUPPLIED
POT LARGE
(SQ. IN. EACH)
POT SMALL
(SQ. IN. EACH)
RIDGE VENT
(SQ. IN. PER LF)
EAVE VENT
(SQ. IN. EACH)
CONT. VENT
(SQ. IN. PER LF)
61.00 40.00 18.00 28.00 10.00
HIGH - POT
VENTS ONLY 3.96 4.95 4.66 46.89 11 0
AT EAVE 5.94 4.95 5.28 53.11 0 76.00
TOTAL (MIN)9.89 9.89 9.94 100.00
3
HIGH -
RIDGE VENT 3.96 4.95 4.75 48.03 0 0 38.00
AT EAVE 5.94 4.95 5.14 51.97 0 74.00
TOTAL (MIN)9.89 9.89 9.89 100.00 ADDITIONAL POT VENTS MAY BE REQUIRED IF THERE IS INSUFFICIENT RIDGE AVAILABLE
ROOF AREA "B"SQ FTG 202 AT / NEAR RIDGE AT / NEAR EAVE
VENT TYPE
SQ. FT.
REQUIRED
RANGE
SQ. FT.
SUPPLIED
PERCENT
OF TOTAL
SUPPLIED
POT LARGE
(SQ. IN. EACH)
POT SMALL
(SQ. IN. EACH)
RIDGE VENT
(SQ. IN. PER LF)
EAVE VENT
(SQ. IN. EACH)
CONT. VENT
(SQ. IN. PER LF)
61.00 40.00 18.00 28.00 10.00
HIGH - POT
VENTS ONLY 0.27 0.34 0.42 46.56 1 0
AT EAVE 0.40 0.34 0.49 53.44 0 7.00
TOTAL (MIN)0.67 0.67 0.91 100.00
3
HIGH -
RIDGE VENT 0.27 0.34 0.38 47.37 0 0 3.00
AT EAVE 0.40 0.34 0.42 52.63 0 6.00
TOTAL (MIN)0.67 0.67 0.79 100.00 ADDITIONAL POT VENTS MAY BE REQUIRED IF THERE IS INSUFFICIENT RIDGE AVAILABLE
09/23/19