HomeMy WebLinkAboutCeiling W A122LEGEND
NEW OR RELOCATED EXISTING TO REMAIN
LIGHT FIXTURE, 2'x4', METALUX LIGHT FIXTURE, 2'x4', PARABOLIC
CRUZE,3500K
L1LIGHT FIXTURE, 2'x2',METALUX LIGHT FIXTURE, 2'X2', PARABOLIC
CRUZE, 3500K ❑
® LIGHT FIXTURE, LED PENDANT, a LIGHT FIXTURE, 1'x4', INDIRECT
A VARYING LENGTHS; REFER TO
PLANS, 3500K
o
FOCAL POINT AVENUE B LED
ee
LIGHT FIXTURE, 1'x4', INDIRECT
B
4LENGTH CEILING GRID
FLANGE
71
RECESSED LIGHT FIXTURE, LED
r(
RECESSED LIGHT FIXTURE
3500K
A ®
LIGHT FIXTURE, PENDANT. $700
®
LIGHT FIXTURE, PENDANT
MATERIAL COST/FIXTURE
B ®
LIGHT FIXTURE, PENDANT, $700
®
LIGHT FIXTURE, PENDANT
MATERIAL COST/FIXTURE
LIGHT FIXTURE, 1'x4',LED
LIGHT FIXTURE, 1'x4',
®
FIXTURES TO MATCH EXISTING,
PARABOLIC, FIXTURES TO
3500K
RECEIVE NEW LED RETROFIT
KITS,3500K
®
EXIT LIGHT FIXTURE
®
EXIT LIGHT FIXTURE
EMERGENCY LIGHT FIXTURE
EMERGENCY LIGHT FIXTURE
$N
EIGHT SWITCH, DIMMER
LIGHT SWITCH
$N3
LIGHT SWITCH, 3-WAY
>
LIGHT SWITCH, 3-WAY
$NP
SWITCH, PROJECTOR
>
SWITCH, PROJECTOR
SCREEN
SCREEN
$NG
SWITCH, GARBAGE
$G
SWITCH, GARBAGE
DISPOSAL (ABOVE
DISPOSAL
COUNTERTOP(
$ E SWITCH, EXHAUST FAN
i — LIGHT CIRCUIT
CEILING GRID,
SUSPENDED, 2'x2'
GYPSUM BOARD CEILING
❑ EXPOSED TO DECK
RELOCATED DIFFUSER,
FJ LAY -IN, 2'x2'
® RELOCATED DIFFUSER,
LAY -IN, 4"x4' OR 4"XI'
®❑ EXHAUST FAN, 2'X2'
GENERAL NOTES
SWITCH, EXHAUST FAN
LIGHT CIRCUIT
I� CEILING GRID,
r- SUSPENDED, 2'x2'
GYPSUM BOARD CEILING
®DIFFUSER,
LAY -IN, 2'x2'
m DIFFUSER,
LAY -IN, 4"x4'
Io-1 EXHAUST FAN, 2'xZ
I. REUSE EXISTING CEILING GRID AND TILE UNLESS OTHERWISE NOTED.
EXISTING GRID IS 2x2 AT 8'-11'A.F.F. TILES ARE 2x2 ACOUSTICAL LAY
IN TILES. REPAIR ANY DAMAGED GRID AND REPLACE ANY
DAMAGED TILES WITH NEW TO MATCH EXISTING.
2. IF IN GOOD CONDITION, EXISTING CEILING TILES SALVAGED FROM
DECONSTRUCTION CAN BE SUBSTITUTED FOR NEW. PROVIDE LIKE
CEILING TILES IN INDIVIDUAL ROOMS WHERE POSSIBLE TO CREATE
UNIFORM LOOK.
3. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED
PER NEMA AND IBC. EMERGENCY BATTERY PACKS OR LIGHTS
CONNECTED TO AN EMERGENCY POWER SOURCE ARE REQUIRED IF
THE SPACE CONTAINS 50 PERSONS OR MORE. FIXTURES SHOWN ON
PLAN ARE FOR REFERENCE ONLY. IN RECEPTION AREAS,
CONFERENCE ROOMS AND OTHER HIGH PROFILE AREAS WITHIN
SUITE, ALL LOCATIONS OF SUCH DEVICES MUST BE APPROVED BY SDI
OR TENANT PRIOR TO INSTALLATION. FAILURE TO DO SO MAY RESULT
IN CONTRACTOR RELOCATING THESE ITEMS AT THEIR EXPENSE.
4. LAYOUT SHOWN IS INTENDED TO MEETASHRAE 90.1 STANDARDS.
ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COMPLIANT
INSTALLATION. IF ADJUSTMENT IS REQUIRED TO MEET ASHRAE 90.1,
CONTRACTOR MUST NOTIFY SDI. OVER 50% OF TH E LIGHTING WILL
BE REPLACED WITH NEW, SO ASHRAE WATTAGE REQUIREMENTS WILL
NEED TO BE MET.
5. ALL NEW SWITCHES TO BE OCCUPANCY SENSORS, PROVIDE
COMBO UNIT WITH BOTH ULTRASONIC AND INFRARED
TECHNOLOGY WITH A ONE BUTTON OVERRIDE. OCCUPANCY
SENSORS ARE TO BE LOCATED SUCH THAT OCCUPANCY WITHIN
ANY PORTION OF INCLUDED AREA IS DETECTED. PROVIDE CEILING
MOUNTED OCCUPANCY SENSORS IN OPEN AREAS AS REQUIRED.
6. ALL EXISTING AND NEW DEVICES AND FACE PLATES TO BE WHITE.
REPLACE WITH NEW AS REQUIRED. WHERE POSSIBLE, GANG
MULTIPLE SWITCHES TO ACCOMMODATE MULTI -SWITCH PLATE
WHEN SWITCHES ARE SHOWN ADJACENT ON PLAN,
7. ELECTRICAL WORK IS LIMITED TO DESIGN -BUILD SCOPE AND 15
OUTLINED IN THESE DRAWINGS. ALL ELECTRICAL WORK IS LIMITED
TO ADDITIONS OR RELOCATIONS OF ELECTRICAL OUTLET DEVICES
AND LIGHTING THAT DO NOT EXCEED THE CAPACITY OF THE
EXISTING ELECTRICAL SERVICE IN THE BUILDING. ELECTRICAL
RELEASED FOR CONSTRUCTION PLANS CAN°BETFILED AND
DES.
Subject to compliance with all regulations
of State and meal Codes
City of Camel
�VTI�tDws�D�
DATE: \ 10/02/19
MECHANICAL NOTES
I. MECHANICAL WORK IS LIMITED TO A DESIGN- BUILD SCOPE AND IS
OUTLINED IN THESE DRAWINGS. NO NEW MAIN MECHANICAL
APPLIANCES OR MAIN EQUIPMENTARE BEING PROVIDED. ALL
MECHANICAL WORK IS LIMITED TO RELOCATION OF DIFFUSERS AND
FLEX DUCT PER NEW WALL LAYOUT. IF IN GOOD CONDITION, EXISTING
H.V.A.C. DIFFUSERS SALVAGED FROM DECONSTRUCTION MAY BE
SUBSTITUTED FOR NEW. NO NEW HARD DUCTWORK OR EQUIPMENTS
BEING ADDED; MECHANICAL CONTRACTOR IS TO NOTIFY
APPLICABLE PARTIES IF ADDITIONAL WORK IS REQUIRED SO THAT
ADDITIONAL PLANS CAN BE FILED AND MUST COMPLY WITH THE
I NDIANA MECHANICAL CODE AND ALL OTHER APPLICABLE CODES.
PLAN NOTES
NOTE: NOTALL PLAN NOTES ARE USED ON EACH SHEET. ALL SCOPE OF WORK IN
RESTROOMS TO BE PRICED SEPARATELY AS LANDLORD'S COST,
R01 CONTROL OPEN OFFICE AREA LIGHTING WITH SWITCH AT THIS LOCATION. EACH
QUADRANT TO BE ON ITS OWN SWITCH. PROVIDE MULTIPLE SWITCHES AS REQUIRED:
CONFIRM FINAL LOCATIONS WITH TENANT.
R02 TRANSITION FROM CEILING GRID TO EXPOSED CEILING TO BE A 5'WIDE DRYWALL
BULKHEAD EXTENDING FROM 8'-10' AFF TO DECK (PAINT IN PTI FLAT FINISH(.
TRANSITION TO BE A CLEAN VERICAL BULKHEAD, FINISHED SUCH THAT
CONTRASTING PAINT COLORS CAN EASILY AND CLEANLY CUT AT WALL TO CEILING
LINE. VERTICAL FACE OF DRYWALL TO BE PAINTED COLOR OF ADJACENT WALL.
R03 COORDINATE ALL DETAILS FOR BULKHEAD(INCLUDING HEIGHT) AND ANY
STRUCTURAL REQUIREMENTS FOR MOVABLE WALLS WITH TENANT'S VENDOR.
CONSULT WITH SDI IMMEDIATELY IF DIMENSIONS OF BULKHEAD WILL VARY FROM
THOSE SHOWN ON PLANS. IF ENGINEERED STRUCTURAL PLANS ARE NEEDED,
DRAWINGS BY OTHERS.
R04 NO CEILING WORK AT THIS LOCATION.
R05 DESIGN INTENT IS FOR LINEAR LIGHT FIXTURES TO BE TIED INTO EXISTING RESTROOM
SWITCH.
ORO6 CLEAN ALL EXPOSED SURFACES AND PREPARE FOR K13 ACOUSTICAL
SPRAY -APPLIED PAINT AND DRYFALL PAINT (PT5) AS NOTED ON PLAN PER
MANUFACTURER'S RECOMMENDATIONS. PAINT EXISTING EXPOSED CEILING DECK,
EXPOSED DUCTWORK, SPRINKLER PIPING, JUNCTION BOXES, CONDUIT, STRUCTURAL
BEAMS AND FIREPROOFING IN ACCORDANCE WITH NFPA 13 6.3.8. PROVIDE RIGID
SPIRAL DUCT AND ROUND SUPPLY DIFFUSERS AS REQUIRED IN THIS AREA.
RO] PROVIDE NEW CEILING GRID AND TILE AS SHOWN TO MATCH AND ALIGN WITH
EXISTING SUCH THAT NEW AND EXISTING CEILINGS APPEAR CONTINUOUS.
OPROVIDE SWITCH BANKS AT THESE LOCATIONS. INTENT IS FOR ALL LIGHTING IN
ROB TOWN HALL TO BE DIMMABLE AND SEPARATED INTO (2) ZONES PER MIDDLE
MOVABLE WALL. COORDINATE REQUIREMENTS WITH TENANT.
OR09ENSURE LIGHTING IS 3500K CCi AND ALL FIXTURES TO BE DIMMABLE. PROVIDE
ADDITIONAL CIRCUITING CAPABILITY FOR FUTURE LIGHTING; COORDINATE ALL
DETAILS WITH TENANT.
R10 PROVIDE APPROPRIATE CEILING WORK FOR TENANT'S CEILING PROJECTOR AND
MOTORIZED, RECESSED PROJECTOR SCREEN.
EAS
WIN
® AREA NOT IN CONTRACT REFLECTED CEILING PLAN - WEST WING
0 2' 4' 8' 16'
❑ AREA OF WORK " —
N
THIS DRAWING. AND THE IDEAS,
DESIGNS AND CONCEPTS CONTAINED
HEREIN, ARE THE EXCLUSIVE
INTELLECTUAL PROPERTY OF SCH07
DESIGN, INC., AND ARE NOT TO BE
USED OR REPRODUCED IN WHOLE, OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF SCH07 DESIGN.
O
N
Z�
Oz
Z
00
N
LL.
J
Q
Q
z
Z
e
Q
V
o
=aZ
Y
r
�
LU
a
z
z
a�
Z
;
pp
O
J
W
Z
}
N
z
z
OZ
W
d
LU
O_
O
c'7
6*JII
DATE I DESCRIPTION
09.06.19 IREVIEWSET
09.13.19 PERMITSET
REVISIONS
MAR DATE DB DESCRIPTION
IN 0.
AR10700017
STATE OF
PROJECT NUMBER
2019.378
PROJ.MGR DRAWN BY
EH AMM
4TH FLOOR
WEST WING
REFLECTED
CEILING PLAN
A122