HomeMy WebLinkAboutCLAY CORNER 53 - CC053 (AS DESIGNED)IECC 2009 Performance Compliance
Property
1508 MAIRN AVE
CARMEL, IN 46032
Model: PENNINGTON (C)
Community: CLAY CORNER 53
CC053 (AS DESIGNED)
CLAY CORNER 53
Organization
TSI Energy Solutions
Matthew Timmons
Builder
LENNAR HOMES
Design
Heating
Cooling
Water Heating
SubTotal - Used to determine compliance
Lights & Appliances
Onsite generation
Total
Inspection Status
Results are projected
Annual Energy Cost
IECC 2009 Performance
51,702
$264
$380
$2,346
$909
$0
$3,254
Requirements
C-M,
Energy Solutions
As Designed
S1,730
S228
S380
$2,337
S909
S0
$3,246
C4405.3 Performance -based compliance passes by 0.4%
R402.4.12 Air Leakage Testing Air sealing is S.DD ACH at 5D Pa. It must not exceed 7.DD ACH at 50 Pa.
C4402.5 Area -weighted average fenestration SHGC
402.5 Area -weighted average fenestration U-Factor
40322 Duct Testing
Mandatory Checklist Mandatory code requirements that are not
checked by Ekotrope must be met.
R4052 Duct Insulation
Design exceeds requirements for IECC 2009 Performance compliance by 0.4%.
As a 3rd party extension of the code jurisdiction utilizing these reports, I certify that this energy code compliance document has been created in accordance with the requirements of
Chapter 4 of the adopted International Energy Conservation Code based on Climate Zone 5. If rating is Projected, I certify that the building design described herein is consistent with
the building plans, specifications, and other calculations submitted with the permit application. If rating is Confirmed, I certify that the address referenced above has been
inspected/tested and that the mandatory provisions of the IECC have been installed to meet or exceed the intent of the IECC orwill be verified as such by another party.
Name: Matthew Timmons
Organization: TSI Energy Solutions
Signature:
Date:
9f 11119 at 7: 28 AM
Ekotrope RATER - Version 3.1.0.2249
IECC 2009 Performance compliance results calculated using Ekotrope RATER's energy and code compliance algorithm.
Ekotrope RATER is a RESIN ET Accredited HERS Rating Tool. All results are based on data entered by Ekotrope users.
Ekotrope disclaims all liability for the information shown on this report.
1508 MAIRN AVE
CARMEL, IN 46032
Builder: LENNAR HOMES
�J PTO Pi
Ceiling Attic, R-38
Above Grade Walls R-16
Foundation Walls R-11
Framed Floor N/A
Slab R-0.0 Perimeter, R-0.0 Under
Infiltration 5 ACH50
Window U-Value: 0.33, SHGC: 0.28
Building Features
Duct Supply R-10.0, Return R-10.0
Duct Leakage to Outside 260 CFM25 (4.991100 s.f.)
Total Duct Leakage 416 CFM25 (Post -Construction)
Heating Furnace • Natural Gas • 95.5 AFUE
Cooling Air Conditioner • Electric • 13 SEER
Water Heating Water Heater • Electric • 0.93 Energy Factor
As a 3rd party extension of the code jurisdiction utilizing these reports, I certify that this energy code compliance document has been created in accordance with the requirements of
Chapter 4 of the adopted International Energy Conservation Code based on Climate Zone 5. It rating is Projected, I certify that the building design described herein is consistent with the
building plans, specifications. and other calculations submitted with the permit application. If rating is Confirmed, I certify that the address referenced above has been inspected/tested and
that the mandatory provisions of the I ECC have been installed to meet or exceed the intent of the IECC or will be verified as such by another party.
Name: Matthew Timmons
Organization: TSI Energy Solutions
Signature:
Date: 9111119 at 7:28 AM
Ekotrope RATER - Version 3.1.0.2249
20091ECC compliance results calculated using Ekotrope RATER's energy and code compliance algorithm.
Ekotrope RATER is a RESIN ETAccredited HERS Rating Tool. All results are based on data entered by Ekotrope users.
Ekotrope disclaims all liability for the information sh own on this report.
Energy Code Inspection Checklist
Property Organization
1508 MAIRN AVE TSI Energy Solutions
CARMEL, IN 46032 Matthew Timmons
Model: PENNINGTON (C)
Community: CLAY CORNER 53 Builder
LENNAR HOMES
CC053 (AS DESIGNED)
CLAY CORNER 53
General Building Information
Conditioned Area (sq ft) 5,213
Conditioned Volume (cubic ft) 45,982
Insulated Shell Area (sq ft) 9,580
inspection Status
Results are projected
C",
Energy Solutions
The building energy model in Ekotrope reflects the building assemblies and energy features listed below. Sometimes energy
features will change in the field from what has been modeled. The inspection process should identify any changes and ensure
that the home continues to meet the applicable energy code.
Slab
[ Name: BSMT(2,139 s.f., 217 ft. exterior perimeter)
R-0 perimeter insulation, R-0 under slab insulation.
Framed Floor
None Present
Foundation Wall
[ Name: CONDIAMB (Exterior Perimeter [ft]: 197, Height Above Grade [ft]: 1, Depth Below Grade [ft]: 8)
R: 11.00
Feet from top of wall to top of insulation: 0, Feet from top of wall to bottom of insulation: 4
E[ Name: CONDIGAR (Exterior Perimeter [ft]: 20, Height Above Grade [ft]: 1, Depth Below Grade [ft]: 8)
R: 11.00
Feet from top of wall to top of insulation: 0, Feet from top of wall to bottom of insulation: 4
Above Grade Wall
El Name: CONDIAMB 2X4 (2,413 s.f.)
R-3 continuous insulation, R-13 cavity insulation
Insulation Grade: I
[ Name: CONDIGAR (180 s.f.)
R-0 continuous insulation, R-13 cavity insulation
Insulation Grade: I
Energy Code Inspection Checklist
Property organization
1508 MAIRN AVE TSI Energy Solutions
CARMEL, IN 46032 Matthew Timmons
Model: PENNINGTON (C)
Community: CLAY CORNER 53 Builder
LENNAR HOMES
CC053 (AS DESIGNED)
CLAY CORNER 53
Name: CONDIATTIC (408 s.f.)
R-3 continuous insulation, R-13 cavity insulation
Insulation Grade: I
Rim Joist
El Name: RIM CONDIAMB (197 s.f.)
R: 13.575
Name: BAND CONDIAMB (67 s.f.)
R: 13.575
El Name: CONDIGAR (20 s.f.)
R: 10.876
Name: CONDIATTIC (64 s.f.)
R: 13.575
Roof
El Name: SECOND (2,139 s.f.)
R-27.55 continuous insulation, R-10.15 cavity insulation
Insulation Grade: I
Opaque Door
El Name: FRONT (24 s.f.)
U: 0.182
Name: GARAGE (18 s.f.)
U: 0.182
Glazing
Inspection Status
Results are projected
El Name: FRONT (120 s.f.), U: 0.330, SHGC: 0.28, Orientation: SOUTH
El Name: BACK(90 s.f.), U: 0.330, SHGC: 0.28, Orientation: NORTH
C",
Energy Solutions
2
Energy Cade Inspection Checklist
C-M
Energy Solutions
Property Organization Inspection Status
1508 MAIRN AVE TSI Energy Solutions Results are projected
CARMEL, IN 46032 Matthew Timmons
Model: PENNINGTON (C)
Community: CLAY CORNER 53 Builder
LENNAR HOMES
CC053 (AS DESIGNED)
CLAY CORNER 53
E] Name: LEFT SIDE (93 s.f.), U: 0.330, SHGC: 0.28, Orientation: WEST
El Name: LEFT SIDE GD (20 s.f.), U: 0.330, SHGC: 0.28, Orientation: WEST
El Name: BSMT (32 s.f.), U: 0.330, SHGC: 0.28, Orientation: WEST
El Name: RIGHT SIDE (73 s.f.), U: 0.330, SHGC: 0.28, Orientation: EAST
El Name: BSMT (16 s.f.), U: 0.330, SHGC: 0.28, Orientation: EAST
Skylight
None Present
Mechanical Ventilation
None Present
Mechanical Equipment
M Fuel -fired air distribution • Natural Gas • 100% Heating Load @ 95.5 AFUE
El Air conditioner • Electric • 100% Cooling Load @ 13 SEER
E] Water Heating • Electric • 100% Hot Water Load @ 0.93 Energy Factor
Air Leakage Control
ElTest Status: Blower -door tested
House is air -sealed as to achieve 3,832 CFM50 (5.00 ACH50) or less at final blower -door test.
Infiltration Requirements for IECC in Climate Zone 5
2009 IECC Infiltration limit for the design home is 7 ACH50.
2012 IECC Infiltration limit for the design home is 3 ACH50.
2015 IECC Infiltration limit for the design home is 3 ACH50.
3
Energy Code Inspection Checklist
Property
1508 MAI RN AVE
CARMEL, IN 46032
Model: PENNINGTON (C)
Community: CLAY CORNER 53
CC053 (AS DESIGNED)
CLAY CORNER 53
Duct Leakage
Duct System 1
Organization
TSI Energy Solutions
Matthew Timmons
Builder
LENNAR HOMES
Inspection Status
Results are projected
NOT entirely within conditioned space, testing required
Leakage to Outside specified as: 260 CFM25 (4.99 / 100 s.f.)
Total Leakage specified as: 416 CFM25 (Post -Construction)
Duct Leakage Code Requirements for IECC
2009 IECC:
Postconstruction Leakage Test: Duct Leakage to Outdoors <= 8 CFM25 / 100 sq ft CFA.
Rough in Test with AHU: Total Duct Leakage <= 6 CFM25 / 100 sq ft CFA.
Rough in Test without AHU: Total Duct Leakage <= 4 CFM25 / 100 sq ft CFA.
2012 IECC and 2015 IECC Prescriptive Path:
Postconstruction Leakage Test: Total Duct Leakage <= 4 CFM25 / 100 sq ft CFA.
Rough in Test with AHU: Total Duct Leakage t= 4 CFM25 / 100 sq ft CFA.
Rough in Test without AHU: Total Duct Leakage <= 3 CFM25 / 100 sq ft CFA.
2015 Performance Path (Cost Compliance):
C",
Energy Solutions
Leakage testing is required UNLESS all ducts and air handlers are located entirely within the thermal envelope.
There is no pass/fail threshold for duct leakage on the performance path.
Project Notes
5N5
4
Building Summary
Property
Organization Inspection Status
1508 MAIRN AVE
TSI Energy Solutions Results are projected
CARMEL- IN 46032
Matthew Timmons
Model: PENNINGTON (C)
Community: CLAY CORNER 53
Builder
LENNAR HOMES
CC053 [AS DESIGNED]
CLAY CORNER 53
Genera?Building Information
Number Of Bedrooms
4
Number Of Floors
2
Conditioned Floor Area [sq_ ft.]
5;213
Unconditioned, attached garage?
Yes
Conditioned Volume [Cu. ft.]
45;982
Total Units in Building
1
Residence Type
Single family detached
Floor Number
Model
PENNINGTON (C)
Community
CLAY CORNER 53
Climate Zone
5A
C-M,
Energy Solutions
Foundation Wall
Name Library Type
Height Above Grade
Depth Below Grade Perimeter
Location
Enclosing
CONDIAMB R-11 Draped, 4Pt
1
8 197
Exposed Exterior
Conditioned Space
CONDIGAR R-11 Draped, 4Pt
1
8 20
Exposed Exterior
Conditioned Space
Foundation Wall Library List
Name Feet From Wall Top To
Feet From Wall Top To
Is Fully Insulated Continuous R-value
Cavity R-value Effective Insulation R-
Continuous Insulation
Continuous Insulation
value
Top
Bottom
R-11 Draped_ Oft 0
4
No N?A
NIA
11.00
Slab
Name Library Type
Perimeter Floor Grade
Carpet R Exposed Surface
Masonry Area
Area Location
Enclosing
BSMT Uninsulated
217 Below Grade 0 0 2:139.0 11:2 Exposed Exterior
Conditioned
Space
Slab Library Lis
Name Wall Construction
Slab Completel Underslab Perimeter Perimeter
Thermal Break
Effective R-value
Type
Insulated. Insulation
Width [ft] Insulation Depth [ft] Insulation R Value
Uninsulated Wood Frame / Other
No
0 0 0
No
D.00
1
Building Summary
Property
1508 MAIRN AVE
CARMEL- IN 46032
Model: PENNINGTON [C]
Community: CLAY CORNER 53
CC053 [AS DESIGNED]
CLAY CORNER 53
Framed Floor
Framed Floor Library List
Organization
TSI Energy Solutions
Matthew Timmons
Builder
LENNAR HOMES
Inspection Status
Results are projected
C-M,
Energy Solutions
Rim Joist
i
Name
Library Type
Surface Area
Location
BAND CONDIAMB
G1 R-13, R-3.0
67.0 fF
Exposed Exterior
CONDIATTIC
G1 R-13, R-3.0
64.0 fF
Attic
CONDIGAR
G1 R-13, OSB
20.0 W
Exposed Exterior
RIM CONDIAMB
G1 R-13, R-3.0
1970.fC`
Exposed Exterior
Rim Joist Library List
Name
Effective Insulation R-value
G1 R-13, OSB
10.876
G1 R-13, R-3.0
13.575
Name
Library Type
Surface Color
Surface Area
Location
CONDIAMB 2X4
G1 R-13 BATT, R-3.0
Medium
2.413.0 ft'
Exposed Exterior
CONDIATTIC
G1 R-13 BATT, R-3.0
Medium
408.0 ft'
Attic
CONDIGAR
G1 R-13 Gar Walls
Medium
180.0 ft'
Llnoonddioned, attached garage
2
Building Summary
Property
Organization
Inspection Status
Energy
C-M
Solutions
1508 MAIRN AVE
TSI Energy Solutions
Results are projected
CARIAEL- IN 46032
Matthew Timmons
Model: PENNINGTON [C]
Community: CLAY CORNER 53
Builder
LENNAR HOMES
CC053 [AS DESIGNED]
CLAY CORNER 53
Wall Library List
Name
Effective R-value
G1 R-13 BATT, R-3.0
15.12
G1 R-13 Gar Walls
11.141
Glazing
Name Library Type
0
Wall Assignment Foundation Wall Overhang
Assignment
Depth Overhang Ft
Top
To Overhang Ft To
Bottom
Orientation
M
Surface Area
BACK U-.33, SHGG28
CONDIAMB 2X4
0
0 0
North
90.0 fF
BSMT U-.33, SHGG28
CONDIAMB
0
0 0
West
32.0 fF
BSMT 11-.33, SHGG28
CONDIAMB 2X4
0
0 ❑
East
16.0 fF
FRONT 11-.33, SHGC-28
CONDIAMB 2X4
0
0 ❑
South
1200.fts
LEFT SIDE 11-.33, SHGG28
CONDIAMB 2X4
0
0 ❑
West
93.0 ft
LEFT SIDE GD 11-33, SHGG28
CONDIAMB 2X4
0
0 ❑
West
20.0 ft
RIGHT SIDE 11-33, SHGG28
CONDIAMB 2X4
0
0 ❑
East
73.0 f'
Glazing Library List
Name
Shgc
U #actor
I1-33, SHGC-28
0.28
0.330
Skylight
Skylight Library List
3
Building Summary
Property Organization
1508 MAIRN AVE TSI Energy Solutions
CARMEL- IN 46032 Matthew Timmons
Model: PENNINGTON [C]
Community: CLAY CORNER 53 Builder
LENNAR HOMES
CC053 [AS DESIGNED]
CLAY CORNER 53
Opaque Door
Name Library Type Wall Assignmen
FRONT Fiberglass Door CONDIAMB 2X4
IGARAGE Fiberglass Door CONDIGA.R
Opaque Door Library List
i
Name
IFiberglass Door
ndatPon Wall
Assignment
0.182
Inspection Status
Results are projected
Solar
Absorptance
C-M,
Energy Solutions
PF
M
r
Surface Area Location
0.9 0.75 Medium 24.0 fr Exposed Exterior
0.9 0.75 Medium 18.0 fr Exposed Exterior
Roof Insulation i
Name Library Type Attic Exterior Area Clay or Concrete Roof Surface Color Surface Area
P.f.] Tiles
Location
SECOND R-38 Blown, GR1 2,139 No Medium 2,139.0 ff Attic
Roof Insulation Library List
Name Has Radiant Barrier Effective R-value
?•8 3 :a l No 38268
Whole House Infiltratic
Infiltration
I5 ACH at 50 Pa
Mechanical Ventilation
Blower -door tested 4
M
Building Summary
Property
Organization
Inspection Status
C-MEnergy Solutions
1508 MAIRN AVE
TSI Energy Solutions
Results are projected
CARIAEL- IN 46032
Matthew Timmons
Model: PENNINGTON [C]
Community: CLAY CORNER 53
Builder
LENNAR HOMES
CC053 [AS DESIGNED]
CLAY CORNER 53
Lighting
% Interior Fluorescent °% Interior LED Ughting
% Exterior Fluorescent
% Exterior LED Lighting
% Garage FI uorescent % Garage LED Ughting
Lighting
Lighting
Lighting
100
0
100
C 10C
Gnsite GenerationMEN&MM �
None Present
Gnsite Generation Library List
None Present
Solar Generation I
None Present
Solar Generation Library List
None Present
Conditioning Equipment
I
Name Library Type
Heating Percent Load
Cooling Percent Load
Hot Water Percent Load
Location
Airconditioner 4AC'42P
0%
100%
❑%
Conditioned Space
Fuel -fired air 915SA4206OS17
100%
0%
❑ %
Conditioned Space
distribution
Water Heating RE350`
0%
0%
100 %
Conditioned Space
A
Building Summary
Property
1508 MAIRN AVE
CARMEL- IN 46032
Model: PENNINGTON [C]
Community: CLAY CORNER 53
CC053 [AS DESIGNED]
CLAY CORNER 53
L Equipment Type: 4AC*42P
Fuel Type
Distribution Type
Motor Type
Cooling Efficiency
Cooling Capacity [kBtulh]
Organization Inspection Status
TSI Energy Solutions Results are projected
Matthew Timmons
Builder
LENNAR HOMES
Electric
Forced Air
PSG (Single Speed)
13 SEER
40
■
' Equipment Type: 915SA42060517
Fuel Type
Distribution Type
Motor Type
Heating Efficiency
Heating Capacity [kBtulh]
Use default EAE
EAE [kWh]
Equipment Type: RE350*
Fuel Type
Distribution Type
Hot Water Efficiency
Tank Capacity (gal.)
Hot Water Capacity [kBtulh]
Recovery Efficiency
Natural Gas
Forced Air
PSG (Single Speed)
95.5 AFUE
58
No
636
Electric
Hydronic Delivery
0.93 Energy Factor
50
15.4
0.98
C-M,
Energy Solutions
Building Summary
Property
Energy Solutions
Organization Inspection Status C-M
1508 MAIRN AVE
TSI Energy Solutions Results are projected
CARIAEL- IN 46032
Matthew Timmons
Model: PENNINGTON [C]
Community: CLAY CORNER 53
Builder
LENNAR HOMES
CC053 [AS DESIGNED]
CLAY CORNER 53
Distribution System
Distribution Type
Forced Air
Heating Equipment
Fuel -fired air distribution
Cooling Equipment
Air conditioner
Sq. Feet Served
5213
# Return Grilles
5
Supply Duct R Value
10
Return Duct R Value
10
Supply Duct Area r]
1407.51
Return Duct Area [ft2]
1303.25
Leakage to Outdoors
260 CFM25 (4.991 100 s.f.)
Total Leakage
416 CFM25
Total Leakage Duct Test Conditions
Post -Construction
Use Default Flow Rate
Yes
Duct t
Duct Location
Conditioned Space
Percent Supply Area
50
Percent Return Area
50
Duct 2
Duct Location
Attic (well vented; under insulation)
Percent Supply Area
50
Percent Return Area
50
Duct 3
Duct Location
Conditioned Space
Percent Supply Area
0
Percent Return Area
0
Duct 4
Duct Location
Conditioned Space
Percent Supply Area
❑
Percent Return Area
❑
Duct 5
Duct Location
Conditioned Space
Percent Supply Area
❑
Percent Return Area
❑
Duct 6
Duct Location
Conditioned Space
Percent Supply Area
❑
Percent Return Area
❑
rCeiling Fan W
Has Ceiling Fan No
Cfm Per Watt 101
7
Building Summary
Property
1508 MAIRN AVE
CARMEL- IN 46032
Model: PENNINGTON [C]
Community: CLAY CORNER 53
CC053 [AS DESIGNED]
CLAY CORNER 53
Water Distribution MM
Water Fixture Type
Use Default Hot Water Pipe Length
Hot Water Pipe Length [ft]
At Least R3 Pipe Insulation?
Hot Water Recirculation System?
Recirculation System Pipe Loop Length [ft]
Drain Water Heat Recovery?
Clothes Dryer
Fuel Type
Cef
Field Utilization
Clothes Washer
Label Energy Rating
Electric Rate
Annual Gas Cost
Gas Rate
Capacity
I met
Appliances and Controls
Programmable thermostat?
Dishwasher Size
Dishwasher Efficiency
Range/Oven Fuel
Convection Oven?
Induction Range?
Refrigerator Consumption
r5N5
Organization Inspection Status
TSI Energy Solutions Results are projected
Matthew Timmons
Builder
LENNAR HOMES
Standard
No
65
No
No
30
No
Electric
Timer Controls
ff"W
704 kWh/Year
$0.081kWh
$23.00
$0.581Therm
2.874
❑.33053
Yes
Standard
270 kWh
Natural Gas
No
No
709 kWh/Year
C-M,
Energy Solutions
,�