HomeMy WebLinkAboutMIDTOWN FLATS POOL9 3.3Pool Light- Equipment Grounding Conductcr • A pool light jpquit? nt rollilin (bonding) conc:ull rri bo art I nsulated copper conductor. m ilimsim size of 12 AV Equipment Grounding (Bonding) Conductor Underwater Luminaire Section 680.23(F) To =olig[vit ytl Insulated equipment grounding (bonding) conductor, not smaller than 12 Al within a raceway 1680,23(F)(2)]. Time Clock or Snap Switch s; s Panelboard —y Junction PR1 t 1% Box I, / Transformer Minimum 16 AWG equipment grounding (bonding) conductor in a flexible cord 1680.23(B)(3)1- 8 AWG insulated/bare copper 1680.26(C)]. To Equipotential Bonding Grid RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and Local Codes City of Camel DATE: 10/16/19 Wet -Niche Luminaire 8 AWG insulated copper 1680,23(13)(1)]. @�c ri ;Motor s irfo ces Bonded Parts Secti 680.26, )l`2)(0) Electrical EquipmentSM jl � Section 680.26(8)(6) II a ° '.����a�� >��5,�•� �y "r ° �u�+�.awraxw�axa-�aec^axv.;a{ Equi otential Bonding Grief Me q a Irl' i• 1` I'.11'AI 1 r'iING Bc�rii JArk a. � .• ^ n.a�,^". S`^`..'®'n, . ��,'„l� �` ,ice 1 .�:.. �...i � �,.T �A»tl>r�E!* ��a�lf #Ir!rri , PI i^ iivo•'�• w4 Metal parts of electrical equipment associated with � 9 the water circulating system r1ip� I, a bonded o e � t... ��:, r�,��n„rar.��.• _s��+' :.. 11141�t L.%4 4J'V IrT4�� t4+t�IF4 p t equipotential grid, GROUNDING AND BONDING REQUIREMENTS FOR SWIMMING POOL AND DECK APPLIANCES: ALL METAL STRUCTURES, FITTINGS AND PARTS THAT ARE HORIZONTALLY WITHIN FIVE FEET OF THE POOL WALL AND VERTICALLY WITHIN TWELVE FEET ABOVE THE MAXIMUM WATER LEVEL OF THE POOL SHALL BE BONDED PER THE SECTION 680.261 OF THE NATIONAL ELECTRIC CODE (NEC) 2011 CODE. THE FOLLOWING PARTS REQUIRE BONDING (BUT NOT NECESSARILY LIMITED TO): REINFORCING METAL OF THE POOL SHELL, COPING STONES AND DECK. METAL CONDUITS, METAL DOOR FRAMES AND METAL WINDOW FRAMES WITHIN FIVE FEET OF THE INSIDE POOL WALL. METAL FORMING SHELLS AND MOUNTING BRACKETS OF LIGHTING FIXTURES. METAL FITTINGS SUCH AS HANDRAILS, LADDERS, METAL DRAINS AND DIVING BOARD (IF INSTALLED). METAL CASINGS OF ELECTRICAL EQUIPMENT SUCH AS PUMP MOTORS, POOL WATER HEATERS AND EQUIPMENT ASSOCIATED WITH POOL COVERS. CONNECT METAL PARTS TO A COMMON BONDING GRID THAT COVERS THE ENTIRE POOL TUB. THIS EQUIPOTENTIAL GRID SHALL EXTEND HORIZONTALLY UNDER THE DECK FOR NOT LESS THAN THREE FEET. ITEMS THAT CAN BE USED AS THE EQUIPOTENTIAL GRID PER THE CODE ARE: STRUCTURAL REINFORCING STEEL BOLTED OR WELDED CONNECTIONS. FIELD FABRICATED GRID CONSTRUCTED WITH A MINIMUM 8 AWG BARE SOLID COPPER CONDUCTORS FORA CONCRETE POOL AND DECK WITH NO REINFORCING METAL. BOND REBAR OR WIRE MESH WITH #8 AWG GARE SOLID COPPER CONDUCTOR AT A MINIMUM OR FOUR POINTS UNIFORMLY SPACED AROUND THE PERIMETER OF THE POOL WITH U.L. LISTED SPLICES. LOCATE SPLICES 18"-24" FROM THE INSIDE WALLS OF THE POOL. LOCATE THE #8 BONDING CONDUCTOR WITHIN THE CONCRETE SLAB OR 4" TO 6" BELOW THE SUB -GRADE. ALL BONDING SHALL BE DONE WITH #8 OR LARGER SOLID COPPER WIRE. USE NON -CORROSIVE CLAMPS LISTED AND STAMPED ON THE CONNECTORS. I@11J 12" x 12" ANY CONVENIENCE OUTLETS IN THE AREA SHALL BE GFIC PROTECTED IN A #8 AWG WEATHER-PROOF BOX WITH AN "IN -USE COVER' WIRE ENTIRE PERIMETER [HUCICI4NIP]C�P: SCHEMATIC EQUIPOTENTIAL BONDING GRID NOT TO SCALE STRICTLY FOLLOW SPECIFICAITONS ON THIS SHEET. REFER TO DIAGRAMS ON THIS SHEET. m m m N N dp NN U CNN 000n� 3 C n m C N tz O C % m 0 L p c a N 9 mb a � ro Y Q J U Z O O of O U f �OL � 37 Q Q LL J D Q Z O Z O M Q Q LL Z Z o O °_j a-CQ 2 2 Z G L � Q U DRAWING COMPLETION DATE JULV 12, 2019 oouuunnD naa ', � STf,P�Cly, 2 e pR00832537 POOI 3.3