SWIMMING POOL REQUIREMENTS AND
SPECIFICATIONS:
SCOPE OF WORK:
A. Provide all labor, material, tools, and equipment necessary for
swimming pool, circulations pumps, pool filter systems, chemical
treatment, piping and finishes.
B. Include cost and securing of all permits required by all governmental
agencies and submittals to regulatory bodies, including stale and local
agencies.
STEEL REINFORCING:
A. Pool steel reinforcement shall be the responsibility of the Pool
Contractor, following plans prepared by a registered engineer or
architect.
QUALITY ASSURANCE:
A. Pool Contractor shall perform all work in compliance with the
requirements of the following agencies:
Indiana Swimming Pool Code, current edition.
International Building Code (Indiana Building Code, current edition)
Local Health and Building Regulations
OSHA
POOL CONSTRUCTION:
A. Construction shall be Gunite or Shote rele as specified by the American
Concrete Institute.
B. Final curing crush -strength of not less than 4,500 psi.
C. The walls of the pool are to be vertical and slope no greater than
eleven (11) degrees from plumb.
D. Provide a cove, not to exceed a 6" radius, shot at the floor and wall
intersections.
E. During the Gunite/Sholcrele application, all piping shall remain under
30 psi of air pressure.
SEQUENCING AND SCHEDULING:
A. The General Contractor and the Pool Contractor shall coordinate any
required pipe sleeves, conduits and building wall penetrations.
PIPE AND FITTING MATERIALS:
A. The swimming pool filler system piping shall be design pressure
Schedule 40 PVC, Rigid, Type 1 Grade 1, ANSI/ASTM D1785. Joints
shall be solvent -weld socket types as recommended by the pipe
manufacturer, fittings shall be PVC, normal impact Type 1,
ANSI/ASTM D2466, with solvent -weld socket ends for Schedule 40
pipe.
POOL SYSTEM SPECIALTIES:
A. Main drain suction line shall be plumbed to two (2) separate main drain
grates.
B. Skimmers shall be of PVC construction with two (2) 2" port threaded
outlets.
C. Returns shall be evenly spaced or as shown on drawings and in
accordance with the latest guidelines put forth by the state or local
RELEASED FOR CONSTRUCTION d in accordance with the latest guidelines put
)cal health departments.
Subject to compliance with all regulations laced on both the influent and effluent sides of
of State and Local Codes nce with the latest guidelines put forth by the
lepadments.
City of Camel
�Vrtll�tgxV�1D�
DATE: \ 10/16/19
a
4 a d
d A
FLINGS AS REQUIR641
O 4
a
? 1
d rd d
f� A
_ a
MIN. 4- COMPACTED FIL d
1 O
d� Q
FITTINGS AS REQUIRED
PIPE INSTALLATION:
A. Use fttings for all changes in direction, changes in size, and all branch
connections.
B. When possible, locate groups of pipes parallel to each other, spaced to
permit servicing of valves.
C. Locate all recirculating pipes in the Floor of the pool, teeing or angling
up the walls of the pool at the closest location to that fitting.
D. Install flow meter in accordance with the latest guidelines put forth by
the state or local health departments.
E. Pipes should be hung using pipe hangers when in proximity to the
pump room ceiling and under braced supports when in proximity to the
pump room floor.
F. Hydrostatically test the pool under 30 psi of air at least 24 hours prior
to covering any piping with a maximum drop of two (2) pounds.
Pressure shall remain on all lines while any covering of piping is taking
place.
POOL SURFACE FINISH:
A. Apply swimming pool plaster finish to all vertical and horizontal pool
surfaces except as designated to receive other finishes. Pod paint is
not acceptable.
B. Trowel apply finish from''/." to'/:" thickness, trowel to even, smooth,
hard surfaces free of surface blemishes and depressions.
TILE:
A. Apply 6"x6" swimming pool tile at water line, as selected by Owner.
Pool contractor shall submit sample boards or tiles for Owner's
selection.
B. Surface accepting Tile shall be clean, dry, and free of oily or waxy build-
up.
C. Clean glaze of tile using water and detergent as work progresses.
D. "NO DIVING" and depth indicator tiles shall be in accordance with the
latest codes and guidelines put forth by the stale and/or local health
departments.
COPING:
A. Install precast or brick coping in accordance with ANSI At 08-1976
standards, grout with a color compatible with color of coping.
B. Coping shall meet all codes and standards of state and/or local health
departments.
DECK APPLIANCES:
A. Install stainless steel handrails at the pool step entry/exit as shown on
drawings. P
B. One three (3) step stainless steel ladder shall be placed al the deep
end of the pool as shown on drawings.
C. All deck anchors shall be brass.
D. All escutcheon plates shall be stainless steel and free of marring and
defects.
MAINTENANCE ACCESSORIES:
A. One (1) 1 %" 35 foot long vacuum hose.
B. One (1) wall adapter.
C. One 18bacuum cleaner head.
D. One (1) telescoping pole with locking nut.
E. One (1) 18" curved wall brush.
F. One (1) 12' algae brush.
G. One (1) dip net.
H. One (1) DPD test kit.
SAFETY EQUIPMENT:
A. One (1) 24" U.S. Coast Guard approved life buoy with a minimum 30
foot throw line.
B. One (1) solid non-adjustable pole with life hook.
C. One (1) spine board with straps.
D. One (1) 24-unit first aid kit with disposable gloves.
FILLING OF POOL:
A. Pool Contractor shall coordinate timing of fill with the General
Contractor and/or Owner to assure construction is complete.
B. Do not fill the pool until the filter system is ready to be placed in
operation.
INSTRUCTIONS AND TRAINING:
A. Pool Contractor shall coordinate the instruction of the operation of the
pool and its appliances to all interested parties on a selected normal
P PP
workday.
B. Provide to the Owner all manuals and written instructions on the pool
appliances.
SKIMMERS
VALVE
4
O
4
d
Q
a
d
PVC Ma N DRNN BOX
8' MAIN DRAIN
TWO REQUIRED
MUST BE ANTI -VORTEX
INSTALL STRICTLY ACCORDING TO MANUFACTURER'S
WRITTEN INSTRUCTIONS. MATCH MAIN DRAINS TO
REQUIRED FLOW.
INSTALL WITH MOUNTING PRODUCTS PROVIDED
BY THE MANUFACTURER, DESIGNED FOR INSTALLATIONS
OF THIS TYPE.
INSTALL STRICTLY ACCORDING TO NATIONAL SPA AND
POOL INSTITUTE STANDARDS ANSINSPI 1 THROUGH 6,
AND THE US CONSUMER PRODUCT SAFETY COMMISSION
GUIDELINES FOR EQUIPMENT HAZARDS PUBLICATION NO.
363-009801
DRAIN USED AS STANDARD: PENTAIR DEEP-8 MAIN DRAIN
WITH ANTI -VORTEX LID.
a
a
° d
d
Q VALVE HYDROSTATIC RELIEF O
4 VALVE
O
a4
4 d
O d
COLLECTION TUBE
O
O�
° 4 4
44 /
� Y
)MAIN L)HATN OX
4.1 TWO ANTI -VORTEX DRAINS
SCALE: 3" = 1'-0"
POOL DATA — MIDTOWN FLATS
POOL SURFACE AREA:
FOUNTAIN AREA:
DECK+ POOL SURFACE AREA:
NET DECK AREA:
SQUARE FEET
POOL VOLUME IN CUBIC FEET:
POOL VOLUME IN GALLONS:
TURNOVER RATE AND GPM:
FILTER MODEL AND SIZE:
FILTER RATE:
PUMP MODEL:
OCCUPANT LOAD:
TOTAL OCCUPANT LOAD:
POOL EQUIPMENT SCHEMATIC GATES (EXITS) REQUIRED:
NOT TO SCALE
NOTE:
TRANSFORMERS AND EQUIPMENT IN POOL EQUIPMENT
ROOM SHALL BE BONDED TO #8 AWG BARE SOLID COPPER POOL CLASS:
CONDUCTOR.
VO d
4
EARTH
d
O
Igh!zell
21
I
U
W
H
Q
Y
Q
U
Z
O
0
Of
O
C)
S
r
tEQUIRED
V
MIDTOWN FLATS POOL - EQUIPMENT TO BE FURNISHED �J
AND/OR INSTALLED BY POOL CONTRACTOR: 111FM�
1,236 SQUARE FEET ONE (1) 520 SF PENTAIR CARTRIDGE FILTER CLEAN $ CLEAR
154 SQUARE FEET ONE (1) 2 HP PUMP FOR 6 HOUR TURNOVER
4,385 SQUARE FEET ONE BROMINE FEEDER (PENTAIR 3315) M
2,990 SQUARE FEET ONE (1) FLOW METER I"I rn
vi
4,944 CUBIC FEET FOUR (4) SURFACE SKIMMERS BY HAYWARD (SP1092) r
Q
37,080 GALLONS ELEVEN (11) RETURN INLETS w
SIX (6) HOURS = 103 TWO (2) 500-WATT UNDERWATER POOL LIGHT O L J Q
GPM MINIMUM @ 60 FT. WITH NICHE AND JUNCTION BOXES rnN, 7 O Q
Z
OF HEAD FOUR (4)100-WATT UNDERWATER FOUNTAIN LIGHTS WITH NICHE '\ O ` 0
AND JUNCTION BOXES `J FD
LL Z Z
520 SF CARTRIDGE TWO (2) STAINLESS STEEL HANDRAILS FOR STEPS
TYPE BY PENTAIR 0 O Z J
(CLEAN AND CLEAR PLUS, MODEL CCP520) ONE (1) FILL SPOUT 0 0 W
[�
ONE REQUIRED TWO (2) 12"x12" VGB GRATES AND SUMP DRAINS rCJ >
150 GPM ONE (1) VACUUM FITTING AND VACUUM LINE `e` >Z 0 Lo U
.275 GPM/SQ FT. ONE HOSE BIBB WITHIN 50 FEET
DRAWING COMPLETION DATI
110 GPM AT 6 XFEO ONE (1)12-FOOT-LONG SOLID POLE WITH LIFE HOOK JULY 12, 2019
110 GPM AT 60 FT OF
HEAD.2 HP ONE (1) LIFE RING WITH THROW ROPE IN ACCESSIBLE LOCATION %0%
�6DVARD ST
1 E ¢
25 PERSONS - POOL ^ G Rta'Yp
199 PERSONS- DECK ONE (1) DIP NET INACCESSIBLE LOCATION A =�" No.
17 a AR00032537
224 PERSONS TOTAL ONE (1)16-FOOT-LONG TELESCOPING POLE IN ACCESSIBLE S STATE OF
LOCATION
TWO, 112 PERSONS
EACH EXIT ONE (1) WALL BRUSH
TWO EXITS REQUIRED THREE EXITS ONE (1) DPD TEST KIT
M"I
PROVIDED ONE (1) SPINE BOARD WITH STRAPS IN ACCESSIBLE LOCATION OO
CLASS C ONE (1) 24 UNIT FIRST AID KIT IN ACCESSIBLE LOCATION ONE (1)TELEPHONE BY BUILDING CONTRACTOR IN ACCESSIBLE W ■ 1
LOCATION ^ 1