HomeMy WebLinkAboutM601-HVAC-SCHEDULES-Rev.0Sequence of Operations Variable Air Volume Systems Variable Air Volume Rooftop Units • Fan shall modulate to maintain design static pressure during occupied mode. • Compressors shall be enabled during occupied mode. • Compressors shall be enabled and fan shall modulate to maintain design static pressure during unoccupied mode to maintain cooling setback temperature of 76"F (adj). • Gas Heat section shall be available during occupied heating mode only. • Modulating Economizer shall be available during all modes. Coolincl T •• RTU to stage and compressors to maintain a discharge air temperature of 550F (adj). •• Upon call from dual enthalpy controller, unit to enter economizer mode and shall modulate the mixing damper to maintain a discharge air temperature of 550F (adj). •• Gas heater shall not operate while in cooling mode or unoccupied mode. Heating •• RTUto maintain R aina discharge air temperature of 57°F (adj). •• Upon call from dual enthalpy controller, unit to enter economizer mode and shall modulate the mixing damper to maintain a discharge air temperature of 57°F (adj). •• Gas Heater shall operate and stage operation if supply discharge temperature falls below 55"F (adj). Outdoor l Ventilation •• RTU to maintain a minimum mof 500 CFM of outdoor air at all times. •• Upon call from dual enthalpy controller, unit to enter economizer mode and shall increase outdoor air to up to 100% but not less than 500 CFM. •• Any reduction in the necessary supply air volume shall be deducted from return air and the outdoor air shall not be less than 500 CFM during occupied schedule. •• RTU to protect itself from mixed air of s4l Outdoor air intake to modulate to reduce outdoor it to maintain at least 40OF mixed air temperature. Terminal Boxes (VAV) • Terminal Boxes shall operate via wall mounted Thermostat. • Terminal Boxes shall maintain a 72°F (adj) setpoint when occupied. • Terminal Boxes shall be capable of occupied/unoccupied setpoint programming. (Night Set Back) •• Cooling Mode ••• Upon call for cooling during occupied mode, Terminal Box shall modulate to open primary air damper from minimum position cool space. If space temperature continues to rise, the damper will open more fully until the space temperature decreases. When thermostat is satisfied, the damper shall modulate to minimum position (see schedule). ••• When in cooling mode, if the space temperature falls below l (adj), and the primary air damper is in minimum position, the 1st stage of electric heat shall energize to maintain setpoint (72°F) (adj). ting Mode 99 we VAV Boxes: •••• The terminal box shall continue to maintain the minimum supply volume. Upon call for heat in occupied mode, shall energize first stage of heat. If the space temperature fails to rise, the 2nd and 3rd stages shall be energized sequentially. When the thermostat is satisfied, the terminal box heater shall de -energize the sage of heat and use the lowest stage of heat to maintain 72°F (adj) space temperature. Humidifier • Energize to maintain 40% RH (adj.) upon call from humidistat. RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and meal Codes City of Camel DATE: 10/16/19 VAV Rooftop Unit Schedule External Cooling Performance Heating Performance Electrical Connection Air Outside Static Weight Mark Space Model Volume Air Net Net Remarks Pressure Gaa Gas Ibs (CFM) CFM (CFM) EDB EWB LDB LWB Sensible Total EDB LDB Input Output CPStaerDsconnect(w.g.) (°F) (OF) IOF) (OF) Cooling Cooling (OF) (°F) ByBy(MBH) (MBH)RTU-1 (MBH) (MBH) X 125,126,127 Dabn 3400 500 OA 77.6 64.5 54.5 54.1 97.06 119.20 59.6 97.9 200 160 30 MFR MFR 2482 See notes DPS010A Notes: 1. Gas pressure regulator suitable for site gas pressure. 2. Delivery of unit is required on site by November 152019. Variable Air Volume Box Air Volume (CFM) Static Heating Performance Electrical Connection Space Price Pressure Becmc HeatEDB Mark Model Size Drop Min LDB CaP,aNc;N Stages(V) Vdtage Phase Starer DisconnectMax (o F) (oF) (0) By: By:VAV-125 125 SDV5 6 400 260 05 55.0 100.0 6 EMC 277 1 MFR MFR JRemarksServed VAV-126 126 SDV5 B B00 400 OS 55.0 100.0 5] EMC 277 1 MFR MFR VAV-127 127 SDV5 12 2200 420 05 55.0 100.0 3.7 EMC 277 1 MFR MFR Notes: 1. 3 Step controller 2. Derated elements,'%a nickel chrome dements. 2. Provide 7 day programmable time controller and thermostat. Humidifier - Steam Electrical Information Air Humidifier Entering Air Leaving Air Mark Space Model Volume Load Conditions Conditions Duct Size Dispersion Remarks CFM (CFM) Ib/hr ( ) F/ Rif (a ) °F/ Rif ( ) (W x H) Method Voltage Phase (V) (0) MCA MOCP Disconnect By: 125, 126, 127 vaporer Her VM-34 3400 90.51 51.213 57.0/63 22 x12 Ultra-SiCartsH-1 dispersion assembly dispersion assembly 480 3 40.9 60 MFR See notes Notes: 1. Modulating humidistat furnished by unit MFR. Installed in duct per MFR recommendation. 3. High limit control by unit MFR. 4. Air flow switch furnished by unit MFR. 5. Insulated dispersion manifold tubes. 6. Drain cooler by unit MFR. ]. Floor mounted RO provided by MFR located underneath humidifier. Exhaust Fan Electrical Connection Area Airflow Static Pressure Weight Mark Served Model (CFM) ) . . (inwg') Ibs ( ) Remarks Voltage Phase Power IV) 10) (bhp) EF-126 MRI Exam Greenheck 1249 0.5 460 3 0.28 60 See Notes CUE-101-A Notes: 1. Install fan on orb provided by Fan MFR. Provide tapered curb. 2. Gravity back daft damper by Fan MFR. 3. Direct drive with solid state speed controller. 4. Disconnect by Fan MFR. 5. Fan shall operate from 02 sensor in the space. Terminal Outlets Mark Function Price Model Airflow Range (CFM) Face Size (in.) Neck Size (in.) Color Remarks PD-1 Plaque Diffuser SPD 50-180 24x24 60 White 1,2,3 PD-2 Plaque Diffuser SPD 181-300 24x24 80 White 1,2,3 SR-1 Supply Register 520L 351-670 235/x 135/ 18 Rol White 1,2,3 ER-1 Exhaust Register 530 0-100 ]s/x75/ 6x6 White 1,2,3 ECR-1 Eggcmte Return 1 80 1 501-1500 24 x 12 22 x 10 White 1,2,3 Notes: 1.ProProvide factory extended panel for any diffuser which is smaller than the grid in which d is installed. 2. Sound baffle by Sheet Metal Contractor. 3. Provide plaster tame for diffusers, registers and grilles installed in gypsum board. c� W Z> I ccF�- e LU LUcr O C7 m Z Q LL, J z - J W I t i CERTIFIED BY. CORI RIGHT Try w.m•canma,.. arn,i none„e They,... Ron IW "Went and my, aupeyby erhy in bay ph, �°,'to be neparid In my (am or �:ba.�y mthatbgrowersk"arced RIM sloe nor Inat 11 Tire ormnng Gmarmy,. "\jE5 L nItG w. R�zc. No. a _* PE10100876 * SqTA�T,EO�qF �4` +,y G NALEt�. 09I30119 Z W C>-7j �O 00 L'N _0C N ai 0 G Q -'Rememe � �_ Z O mL -0 N W Z 2 d O W Z ra benbeeeee -a Q o c Z W rn N lv/1 � CT m l � r °O m o 0 z w z J rn Q o W v Z o V O aT SHEET N0. M601