HomeMy WebLinkAboutE1.00 0
GENERAL ELECTRICAL NOTES
1. ANY AND ALL "BUILDING STANDI AND/OR "BUILDING SPECIFICATIONS" SHALL BE CONSIDERED AN INTEGRAL PART OF THESE DOCUMENTS AND
THE CONTRACTOR SHALL BE RESPONSIBLE TO OBTAIN A COPY OF THESE REQUIREMENTS/THIS DOCUMENT AND COMPLY WITH ALL REQUIREMENTS
AND STANDARDS CONTAINED WITHIN.
2. THESE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND ARE INTENDED TO CONVEY THE SCOPE OF WORK AND INDICATE GENERAL ARRANGEMENT
OF LIGHTING FIXTURES, DEVICES, CONTROLS, ELECTRICAL FIXTURES, MOTORS, PANELBOARDS, EQUIPMENT, ETC. THE LOCATIONS OF ALL ITEMS
SHOWN ON THESE DRAWINGS OR CALLED FOR IN THE SPECIFICATIONS THAT ARE NOT DEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE. THE
EXACT LOCATIONS NECESSARY TO SECURE THE BEST CONDITIONS AND RESULTS MUST BE DETERMINED AT THE PROJECT. ALL LOCATIONS OF
WORK EXPOSED TO VIEW ARE SUBJECT TO APPROVAL OF THE ARCHI PRIOR TO INSIALIATION.
3. THE ELECTRICAL CONTRACTOR SHALL VERIFY EXISTING CONDITIONS TO INSURE THAT ALL NEW WORK WILL FIT INTO THE EXISTING STRUCTURE IN
THE MANNER INTENDED AND AS SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/OWNERS REPRESENTATIVE PRIOR TO
ANY ROUGH -INS, FABRICATIONS, OR PERFORMING ANY WORK IN THE AREA INVOLVING DIFFERENCES. NOTIFICATION SHALL BE IN THE FORM OF A
DRAWING OR SKETCH INDICATING FIELD MEASUREMENTS AND NOTES RELATED TO THE AREA
4. ANY DISCREPANCIES BETWEEN DRAWINGS AND SPECIFICATIONS SHALL BE PROMPTLY BROUGHT TO THE ATTENTION OF THE ENGINEER FOR
CLARIFICATION DURING THE BIDDING PERIOD. NO ALLOWANCE SHALL SUBSEQUENTLY BE MADE TO THE CONTRACTOR BY REASON OF HIS FAILURE
TO HAVE BROUGHT SAID DISCREPANCIES TO THE ATTENTION OF THE ENGINEER DURING THE BIDDING PERIOD OR OF ANY ERROR ON THE
CONTRACTOR'S PART.
5. ALL EQUIPMENT SHALL BE INSTALLED IN A NEAT, PROFESSIONAL AND WORKMANLIKE MANNER, RECTILINEAR TO BUILDING STRUCTURE
6. ALL COMPONENTS SHOWN ON THE RISER/ONE-LINE DIAGRAMS, BIR NOT ON THE PLAN OR VICE VERSA, SHALL BE INCLUDED AS IF SHOWN ON
BOTH.
7. REVIEW ALL TRADES' CONTRACT DOCUMENTS TO DETERMINE SPECIFIC MOUNTING LOCATIONS FOR ELECTRICAL EQUIPMENT. COORDINATE EXACT
MOUNTING LOCATIONS WITH THE ARCHOECF.
S. REFER TO ARCHITECTURAL ELEVATIONS TO DERIVE EXACT LOCATIONS OF ALL RECEPTACLES, OUREIS/JACKS, SWITCHES, ETC. LUMINAIRES AND
CEILING MOUNTED EQUIPMENT SHALL BE COORDINATED WITH THE ARCHITECTURAL REFLECTED CEILING PLANS.
9. EXACT LOCATION OF MECHANICAL EQUIPMENT THAT REQUIRE ELECTRICAL CONNECTION ARE SHOWN ON THE MECHANICAL DRAWINGS. FIELD VERIFY
EXACT LOCATIONS WITH MECHANICAL CONTRACTOR PRIOR TO ANY ROUGH -INS.
10. ALL CIRCUITING SHALL BE RUN CONCEALED UNLESS SPECIFIED OTHERWISE
11. ALL RACEWAYS RUNNING THROUGH BUILDING EXPANSION JOINTS SHALL BE EQUIPPED WNH EXPANSION FIIDNGS.
12. CONDUIT HOME RUNS SHOWN ON THE DRAWING WITH MORE THAN (3) CURRENT CARRYING CONDUCTORS ARE SHOWN DIAGRAMATICALLY. THIS
CONTRACTOR SHALL NOT INSTALL MORE THAN (3) CURRENT CARRYING CONDUCTORS IN A RACEWAY UNLESS NATIONAL ELECTRIC CODE (N.E.C),
ARTICLE 310.15 DEPATNG FACTORS ARE APPLIED.
13. ALL UGHBNG AND GENERAL POWER BRANCH CIRCUITS SHALL INCLUDE A SEPARATE NEUTRAL CONDUCTOR, UNLESS SPECIFICALLY NOTED
OTHERWISE.
14. THE ELECTRICAL CONTRACTOR SHALL REFER TO THE ELECTRICAL SPECIFICATIONS FOR ACCEPTABLE CONDUIT TYPES/LOCATIONS. ALL CONDUIT
SIZES ON THE DRAWINGS ARE BASED ON THE LATEST EDITION OF THE N.E.C. CONDUIT FILL TABLES FOR ELECTRICAL METALLIC TUBING (E.M.T).
CONDUIT SIZES SHALL BE REVISED TO THE SIZE REQUIRED, RELATIVE TO THE ACTUAL CONDUIT TYPE TO BE INSTALLED.
15. N IS NOT INTENDED THAT THE PLANS INDICATE ALL THE NECESSARY BENDS, OFFSETS, PULL BOXES AND OBSTRUCTIONS. IT SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR TO INSTALL HIS WORK TO CONFORM TO THE STRUCTURE, MAINTAIN HEADROOM AND KEEP OPENINGS AND
PASSAGEWAYS CLEAR. REFER TO THE ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS AS REQUIRED.
16. IT 15 NOT INTENDED THAT THE PLANS INDICATE ALL CONDUIT ROUTES, PULL BOXES, ETC. CONTRACTOR SHALL BE RESPONSIBLE FOR
DETERMINING ACTUAL CONDUIT ROUTING. QUANTITY AND LOCATION OF PULL BOXES WITHIN ACCESSIBLE LOCATIONS.
17. PROVIDE SCREW -COVER PULL BOXES IN CONCUR RUINS AS REQUIRED TO UNIT THE NUMBER OF BENDS TO NO MORE THAN THREE (3) OR 270
DEGREES TOTAL SIZE PULL BOXES IN ACCORDANCE WITH NEC, ARTICLE 31428. DOCUMENT ON RECORD DRAWINGS, SIZE AND LOCATION OF
PULL BOXES USED IN FEEDER CONDUN RUNS.
18. ALL OUTLET BOXES IN WALLS SHALL HAVE A MINIMUM OF ONE (1) DEDICATED VERTICAL CONDUIT ENTERING AT THE TOP OF THE BOX.
HORIZONTAL CONDUIT CONNECTIONS SHALL ONLY BE PERMITTED UNDER WINDOWS OR UNLESS OTHERWISE NOTED ON DRAWINGS.
19. WHERE MULTIPLE DEVICES ARE INDICATED IN A COMMON LOCATION, GANG INTO A SINGLE COVER PLATE.
20. ALL EXISTING PANELS SWILL BE PROVIDED WITH ENGRAVED NAMEPLATES AS DESIGNATED ON PANEL SCHEDULES SECURED TO PANEL FACE AND
NEW ENGRAVED NAMEPLATES DENOTING ORIGIN OF FEEDER FROM WHICH PANEL IS SERVED.
T11
GR1404-LT-ENC- 013-Bill
SM-NEl-
GR1404-LT-INT-
4NCL-DTC-DV
LIGHTING CONTROL PANEL "LCPII
SCALE: NOT TO SCALE
ACUITY GR1400 BLUE BOX - SURFACE MOUNTED
NOTES:
1. LCP SHALL BE LOCATED AS CLOSE TO PANELBOARD AS PRACNCA OR A9 SHOWN ON PLAN.
PROVIDE WIRING FROM LOW VOLTAGE SWITCH TO RELAY CABINET FOR EACH RELAY AS
REQUIRED.
2. HEADEND SHALL CONTAIN ASTRONOMICAL TIME CLOCK, PROGRAMMABLE MATRIXING AND
OCCUPANT WARNING VIA UGHT FLASHING.
3. PROVIDE UGDNG RELAYS IN PANELS AS SHOWN. REFER TO DRAWINGS FOR BRANCH
CIRCUITS WIRED VIA RELAY PANTS.
4. PROGRAM UGHTING SCHEDULE AND HOURS OF OPERATION WITH OWNER.
5. PROVIDE LOW -VOLTAGE OVERRIDE SWITCH CONTROLS ( $LV) AS INDICATED ON DRAWINGS
LC&D 'CH' SERIES. LDW-VOLTAGE OVERRIDE SWITCH CONTROLS SHALL INMATE AN
OVERRIDE OF A MAXIMUM TIME OF NO MORE THAN FOUR (4) HOURS
6. PROVIDE TWO (2) HOUR TRAINING ON PROGRAMMING OF SYSTEM AND SYSTEM OPERATION.
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and meal Codes
City of Carmel Y�
�NrtY�\o'nQRDA�
ELECTRICAL SYMBOL/ABBREVIATION LEGEND
SYMBOL
DESCRIPTION
WO.
U.N.O.ABBREVIATION
DESCRIPTION
HOME RUN TO PANEL ALL UNMARKED HOMERUNS TO CONTAIN 2-12 AWG & 1-12 AWG
GND IN 3/4' CONDUIT, UNLESS NOTED OTHERWISE.
AHJ
AUTHORITY HAVING JURISDICTION
AC
ABOVE COUNTER
$m
DUAL TECHNOLOGY WALLBOX VACANCY SENSOR - SEE DETAIL THIS DRAWING
4B'
EM
EMERGENCY
DUAL TECHNOLOGY DIMMABLE WALLBOX VACANCY SENSOR - SEE DETAIL THIS DRAWING
48'
EX
EXISTING REMAIN
m /0 /0
SINGLE / DUPLEX / DOUBLE DUPLEX RECEPTACLE
18'
GFl
FA GROUND FAULT INTERRUPTING
RECEPTACLE WITH GROUND FAULT PRCTECDON
18"
NIL
NIGHT UGHT
DOUBLE DUPLEX RECEPTACLE WITH GROUND FAULT PROTECTION
TYP
TYPICAL
LINO
UNLESS NOTED OTHERWISE
v
COMMUNICATIONS JACK, PROVIDE SINGLE GANG BOX WITH 3/4' CONDUIT (WITH BUSHINGS &
PULLWIRE) TO 12' ABOVE CLUNG SPACE. COORDINATE WITH CORE PROJECT MANAGER
19'
W
WALL MOUNTED -SEE DETAIL
Q
JUNCTION BOX
** ALL DEVICES ARE TO BE WHITE IN
COLOR WITH MATCHING FACEPLATES
INCLUDING DATA DEVICE FACEPLATES **
PANELBOARD
D
NON -FUSED DISCONNECT
CR
CARD READER
❑FS
ELECTRIC STRIKE
�F
FIRE ALARM SYSTEM PULL STATION
�(
FIRE ALARM SYSTEM COMBINATION HORN/STROBE
0
FIRE ALARM SYSTEM STROBE
m
FIRE ALARM SYSTEM DUCT DETECTOR
®
FIRE ALARM SYSTEM REMOTE TEST STATION
PANEL:
PP2A (EXISTING)
MAIN: 225A MLO VOLTAGE: 120/208
PHASE> 3 FWRE 4 BUS TIPS: 225 AEC: 65,000
I ISOLATED GROUND BUS:
NO
MOUNTING:
SURFACE
LOCATION:
I ELECTRICAL ROOM
CKT
NOTE I
BKR
I LOAD DESCRIPTION
KVA
AO
Be
CO
KVA
I
LOAD DESCRIPTION
BKR
I NOTE
CKT
1
20/1 IT RM QUAD
20/1 IT RM QUAD
20/1 1 COUNSELING OFFICE RCPT
20/1 COPIER RECEPTION
20/1 BREAK ROOM COUNTERTOP
20/1 BREAK RM RCPC
20/1 MICROWAVE
20/1 1 REFRIGERATOR
20/1 COUNSELING OFFICE RCPT
20/1 COUNSELING OFFICE RCPT
20/1 WAITING RCPT
20/1 COUNSELING OFFICE RCPT
20/1 COUNSELING OFFICE RCPT
20/1 COUNSELING OFFICE RCPT
20/1 COUNSELING OFFICE RCPT
20/1 COPIER RM RCPT
20/1 DOPIER MAIL RM
20/1 RECEPTION COUNTERS
20/1 COUNSELING OFFICE RCPT
20/1 GROUP COUNSELING OFFICE
20/1 HALL RCPT
LOCK TOTAL KVA PER
FAULT INTERRUPTING
FAULT INTERRUPTING
DUTY
RATED
0.18
0.18
1.44
1.20
1.00
0.36
1.20
0.80
1.44
1.44
1.08
1.44
1.44
1.44
1.44
0.18
1.20
1.08
1.44
0.72
1.08
PHASE
0.2 0.0 SPARE 20/1
0.2 0.0 SPARE 20/1
1.4 0.0 SPARE 20/1
1.2 0.0 SPARE 20/2
1.0 0.0
0.4 0.0 SPARE 20/1
1.2 0.0 SPARE 20/1
0.0 0.0 SPARE 20/1
9.2 7.8 EXIST. SUB -PANEL 100/3
9.2 7.8
8.9 7.0
1.4 0.0 SPARE 20/1
1.4 0.0 SPARE 20/1
1.4 0.0 SPARE 20/1
1.4 0.0 SPARE 20/2
0.2 0.0
1.2 0.0 SPARE 20/2
1.1 0.0
1.4 0.0 SPARE 20/2
0.7 0.0
1.1 0.0 SPARE 20/1
14.9 1 14.2 1 16.1
IOTA KVA: 45.2
IOTA AMPS: 125.4
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
NOTES'
L
GFI
AFI
CD
H
HANDLE
GROUND
ARC
CONTINUOUS
HACR
LUMINAIRE SCHEDULE
TYPE
LAMP
WATTAGE
VOLTAGE
DRIVER
DESCRIPTION
CATALOG NUMBER
REMARKS
LLD
2'X4' RECESSED LED VOLUMETRIC LUMINAIRE, CURVED UNEAR PRISM DIFFUSER,
UTHONIA
A
3500K
31
UNV
0-10V
>80 CPo, 1% DIMMING
2BLT4-40L-ADP-GZI-LP835
4000LM
LLD
2'X2' RECESSED LID VOLUMETRIC LUMINAIRE, CURVED LINEAR PRISM DIFFUSER,
UTHONIA
***NOT USED THIS PROJI
Al
3500K
25
UNV
0-10V
>00 CPo, 1% DIMMING
2BLT2-33L-ADP-GZI-LP&35
330OLM
LLD
VX4' RECESSED LED VOLUMETRIC LUMINAIRE, CURVED UNFAR PRISM DIFFUSER,
UTHONIA
***NOT USED THIS PROJECT***
B
35GOK
32
UNV
0-10V
>80 CPo, 1% DIMMING
BLT4-30L-ADP-GZI-LPB35
4000LM
LLD
4' APERTURE RECESSED LED DOWNUGHT, MATTE DIFFUSE FINISH, >80 CRI
UTHONIA
***NOT USED THIS PROIECP**
C
3500K
15
UNV
0-10V
LUN4-35-10-LD4AR-ILA-MVOLT-GZ10
t000LM
SELF CONTAINED UNIVERSAL MOUNT LED EXIT SIGN WITH DUAL HEADS, WHITE
UTHONIA
X1
LED
3
UNV
_
THERMOPLASTIC HOUSING, QUANIIIY OF FACES AND DIRECTIONAL ARROWS AS
UMQM-LED-R-SD
SHOWN ON PUNS, SELF DIAGNOSTICS
SELF CONTAINED UNIVERSAL MOUNT LED EXIT SIGN, WHITE THERMOPLASTIC
UTHONIA
X2
LED
2
UNV
_
HOUSING, QUANTITY OF FACES AND DIRECTIONAL ARROWS AS SHOWN ON PUNS,
LQM-S-W-3-120/277-ELN-SD
SELF DIAGNOSTICS
SELF CONTAINED UNIVERSAL MOUNT LED EXIT SIGN WITH DUAL HEADS, WHITE
UTHONIA
***NOT USED THIS PRDJI
X3
LED
3
UNV
_
THERMOPU6'IIC HOUSING, QUANTITY OF FACES AND DIRECTIONAL ARROWS AS
LNQM-LED-R-SD-HO
SHOWN ON PUNS, SELF DIAGNOSTICS, REMOTE HEAD CAPACITY
SELF CONTAINED WALL MOUNTED EMERGENCY LIGHTING UNIT WITH DUAL HEADS,
UTHONIA
EM
LED
2
UNV
_
WHITE TERMOPLASDC HOUSING, SELF DIAGNOSTICS
ELM2L-WOLT-SDRT
EXTERIOR WEATHERPROOF DUAL HEAD LED EMERGENCY EGRESS LIGHT
UIHONW:
Wm*NOT USED THIS PRDJI
RH
LED
2
UNV
-
ERA-T-QWP-L0309-SD
WMINAIRE SCHEDULE GENERAL NOTES'.
1. VERIFY ALL LUMINAIRE COLORS, TRIMS, LENGTHS, ETC. WITH THE ARCHITECT PRIOR TO PLACING FINAL PURCHASE ORDERS. SUBMISSION OF SHOP DRAWINGS WILL BE INTERPRETED AS HAVING BEEN COORDINATED
WITH THE ARCHITECTURAL DRAWINGS.
2. PROVIDE ALL LENGTHS, FEEDS, ACCESSORIES, CONNECTORS, WIRING, POWER SUPPUES, DRIVERS, EFC. FOR A COMPLETE INSTALLATION. THE E.C. SHALL VERIFY THE COMPLETE BILL OF MATERIAL WITH
MANUFACTURER'S REPRESENTATIVE AND INSURE ALL EQUIPMENT IS INCLUDED IN BID PRICE. COORDINATE INSTALLATION WITH ARCHITECTURAL DETAILS.
3. VERIFY FINAL LUMINAIRE LOCATIONS WITH OTHER CEILING MOUNTED EQUIPMENT SUCH AS DIFFUSERS, FIRE ALARM DEVICES, SPEAKERS, ETC., WITH ARCHRECTURAL REFLECTED CEILING PLANS.
4. VERIFY EXACT MOUNTING HEIGHT AND LOCATIONS OF ALL WALL MOUNTED AND PENDANT MOUNTED LUMINAIRES WITH ARCHITECTURAL PLANS AND ELEVATIONS PRIOR TO ROUGH -IN.
5. ANY PROPOSED ALTERNATE LUMINAIRES SHALL BE APPROVED BY THE ARCHITECT PRIOR TO FINAL BID PRICING.
6. SHOULD THE CONTRACTOR PROPOSE TO FURNISH MATERIALS, EQUIPMENT, AND DEVICES, OTHER THAN THOSE SPECIFIED AND LISTED, THE CONTRACTOR SHALL SUBMIT A WRITTEN REQUEST FOR SUBSTITUTIONS,
TO THE ENGINEER AT LEAST TEN (10) BUSINESS DAYS PRIOR TO BID OPENING. THE REQUEST SHALL BE AN ALTERNATE TO THE ORIGINAL BID AND SHALL INCLUDE A COMPLETE SPECIFICATIONS CUT SHEET
SUBMITTAL AS OUTLINED IN THE SPECIFICATIONS, COMPLETE WITH DESCRIPTIVE (MANUFACTURER, BRAND NAME, CATALOG NUMBER, ETC) AND TECHNICAL DATA FOR ALL ITEMS. INDICATE ANY ADDRIONS OR
DEDUCTIONS TO THE CONTRACT PRICE WITH THE SUBSTITUTION SUBMITTAL AND ON THE BID FORM.
7. ANY DIMMERS PROVIDED SHALL BE FULLY COORDINATED WITH SOURCE SERVED FOR COMPATIBILITY. LUMINAIRES SHALL BE CONIROILED WITH MANUFACTURERS APPROVED DINNERS FOR EACH SOURCE DIMMED.
FIRE ALARM SIGNAL,
SPEAKER OR LIGHT
RECEPTACLES BEHIND
E REFRIGERATORS AID DISCONNECT
_ VENDING MACHINES SWITCHES PANEIROARD
WALL TELEPHONES
FIRE ALARM PULL STATION
UGHIING CONTROLS
VOLUME CONTROLS D
DEVICES
CKSCOUNTERTOP
AND/OR BAPLASH
®F RECEPTACLES IN MECH/ELEC oo .
SPACES AND PAIACENT TO
LAVATORIES no 1 �k
® RECEPTACLES BEHIND
DOMESTIC WASHERS
AND DRYERS
GENERAL PURPOSE
RECEPTACLES
VOICE/DATA OUTLETS
FINISHED FLOOR
TYPICAL DEVICE MOUNTING DETAIL
N.T.B.
NOTES:
1. ALL MOUNTING HEIGHTS SHALL BE MEASURED FROM FINISHED FLOOR TO THE CEHTERUNE OF DEVICE EXCEPT FIRE ALARM
A/V DEVICES.
2. NO WIRING DEVICES OR OUTET BOXES SHALL BE MOUNTED BACK TO BACK.
3. ALL MOUNTING DEVICES SHALL BE INSTALLED AT MOUNTING HEIGHTS AS INDICATED ON THIS DETAIL UNLESS OTHERWISE
NOTED.
4. FOR ALL ELEVATIONS (WHERE APPLICABLE), CASEWORK DETAILS, FIRE WAUS, SMOKE WALLS, LOCATION OF COUNTERTOP
RECEPTACLES, LUMINAIRE SWITCHES, TELEPHONE OUTLETS, EQUIPMENT ROUGH -INS, HEADWALLS, EC., SEE ARCH
DRAWINGS. WHERE NO ARCHITECTURAL ELEVATIONS OR DETAILS OCCUR, THE ELECTRICAL CONTRACTOR SHALL USE MEANS
AND METHODS AS WELL AS THEIR FIELD KNOWLEDGE TO SPOT DEVICES IN THE BEST LOCATIONS FOR THE PROJECT.
I
MM VIO (+)
ON/OFF 0-10V
DIMMING oWorT
9 CRY (-) a
6
DIMMABLE VACANCY SENSOR SWITCH
WIRING DIAGRAM (VSD)
NOTES: SCALE NOT TO SCALE
1. VACANCY SENSOR SHALL BE 'SENSOR SWITCH' WSX-PDT-D-VA-WH.
2. PROVIDE 'LUMINAIRY' CABLE FOR ALL 0-10V DIMMING.
3. CONTRACTOR SHALL MAINTAIN VACANCY SETTING ON ALL SENSORS PROVIDED. 'OCCUPANCY
SEITNG SHALL NOT BE UTILIZED.
G
VACANCY SENSOR SWITCH
WIRING DIAGRAM (VS)
NOTES- SCALE: NOT TO SCALE
1. VACANCY SENSOR SHALL BE "SENSOR SWITCH' WSX-PDT-VA-WH.
2. CONTRACTOR SHALL MAINTAIN VACANCY SETTING ON ALL SENSORS PROVIDED. 'OCCUPANCY
SEITNG SHALL NOT BE UTILIZED.
a
LLI
m
-
5«m
a y
tJ
COO
O
y
w = `?
ESL
Q
m n
oom
mom
wUw
iro ome of wr.°I"e meal.': i,
.nN and renwM tw m gnw1y of
wlr,bm,&.ANIImL nnewoo W
brlp N Ar m.Auaft &,Yns,l.
Aw waw.m w,r wm b Am,n. PNm
WanenmrowmwWwmm�
m.raaaaA wnn.n consentW .1 want.
e OY C.ak, Art.11.01.
V a
N
C W
F
V N
TL
O
~ DID
Q Z �� $<
9�Ww=_
<0no
wounif _ ¢ 2 2
a =
X J
J
Z Z TN
W G 0
F 9 N
Rom N&- 9104
anon Flge ATO
Delp Ino
OM90I SO a PERMIT
E1e0
10/16/19
ELECTRICAL LEGEND,
SCHEDULES AND
DETAILS