HomeMy WebLinkAboutE5.0SECTION 16010 - ELECTRICAL GENERAL PROVISIONS 1. THE PROVISIONS OF THE INSTRUCTIONS TO BIDDERS, GENERAL CONDITIONS, SUPPLEMENTARY CONDITIONS, ALTERNATES, ADDENDAS AND DIVISION 1 ARE A PART OF THIS SPECIFICATION. ELECTRICAL, ARCHITECTURAL, MECHANICAL AND ALL OTHER DRAWINGS AS WELL AS THE SPECIFICATIONS FOR ALL THE DIVISIONS ARE A PART OF THE CONTRACT DOCUMENTS. 2. VISIT THE SITE OF THE WORK AND BECOME FAMILIAR WITH THE CONDITIONS AFFECTING THE INSTALLATION. SUBMISSION OF A PROPOSAL SHALL PRESUPPOSE KNOWLEDGE OF SUCH CONDITIONS AND NO ADDITIONAL COMPENSATION SHALL BE ALLOWED WHERE EXTRA LABOR OR MATERIALS ARE REQUIRED BECAUSE OF IGNORANCE OF THESE CONDITIONS. 3. DEFINITIONS: A THE TERM "FURNISH" SHALL MEAN TO SUPPLY AND DEJVERY TO THE PROJECT SITE READY FOR UNLOADING, UNPACKING, ASSEMBLY, INSTALLATION, AND SIMILAR OPERATIONS. B. THE TERM "INSTALL" SHALL MEAN WORK WHICH INCLUDES THE ACTUAL UNLOADING, UNPACKING, ASSEMBLY, ERECTING, PLACING, ANCHORING, APPLYING, WORKING TO DIMENSION, FINISHING, CURING, PROTECTING, CLEANING, AND SIMILAR OPERATIONS. C. THE TERM *PROVIDE" SHALL MEAN TO FURNISH AND INSTALL, COMPLETE AND READY FOR THE INTENDED USE 4. INCLUDE ALL LABOR, MATERNAL EQUIPMENT, SERVICES AND PERMITS NECESSARY FOR THE PROPER COMPLETION OF ALL ELECTRICAL WORK SHOWN. ITEMS OMITTED, BUT NECESSARY, TO MAKE THE ELECTRICAL SYSTEM COMPLETE AND WORKABLE SHALL BE UNDERSTOOD TO FORM PARF OF THE WORK. 5. IT IS THE PURPOSE OF THE ELECTRICAL DRAWINGS TO INDICATE THE APPROXIMATE LOCATION OF AL EQUIPMENT, OUTLETS, ETC. ASCERTAIN EXACT LOCATIONS AND ARRANGE WORK ACCORDINGLY. THE RIGHT IS RESERVED TO EFFECT REASONABLE CHANGES IN THE LOCATION OF OUTLETS UP TO THE TIME OF ROUGHING -IN, WITHOUT ADDITIONAL COST TO THE OWNER. 6. TEMPERATURE AND INTERLOCK CONTROLS ARE PROVIDED AND WIRED BY A CONTROLS CONTRACTOR. LINE (120 VOLT) VOLTAGE CONTROL DEVICES, SUCH AS THERMOSTATS AND AQUASTATS, WHICH CONTROL FRACTIONAL HORSEPOWER, 120 VOLT MOTORS ARE FURNISHED BY MECHANICAL CONTRACTOR, AND ARE WIRED BY ELECTRICAL CONTRACTOR 7. SECURE AND PAY FOR PERMITS AND INSPECTIONS REQUIRED FOR THE ELECTRICAL WORK. B. WORK SHALL BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE PROVISIONS OF LOCAL AND STATE CODES, AS WELL AS THE LATEST ADOPTED VERSION OF THE NATIONAL ELECTRICAL CODE AS INTERPRETED BY THE LOCAL AUTHORITY HAVING JURISDICTION. 9. CONSULT THE DRAWINGS, PRODUCT DATA AND SHOP DRAWINGS COVERING THE WORK FOR VARIOUS OTHER TRADES, THE FIELD LAYOUTS OF THE CONTRACTORS FOR THE TRADE AND MAKE ADJUSTMENTS ACCORDINGLY IN LAYING OUT THE ELECTRICAL WORK. 10. WARRANT THAT EQUIPMENT AND ALL WORK IS INSTALLED IN ACCORDANCE WITH GOOD ENGINEERING PRACTICE AND THAT ALL EQUIPMENT WILL MEET THE REQUIREMENTS SPECIFIED. GUARANTEE AGAINST DEFECTS IN WORKMANSHIP AND MATERIALS; REPAIR OR REPLACE ANY DEFECTIVE WORK, MATERIAL OR EQUIPMENT WITHIN ONE YEAR FROM DATE OF ACCEPTANCE. 11. THE EXISTING ELECTRICAL AND TELEPHONE SERVICE AND ALL EXISTING COMMUNICATION SYSTEMS WITHIN THE BUILDING SHALL BE MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD. ANY SERVICE SHUTDOWNS THAT MAY BE REQUIRED SHALL BE SCHEDULED THROUGH THE OWNER AND SHALL BE DONE AT A TIME AS DIRECTED BY THE OWNER. NO ADDITIONAL COMPENSATION SHALL BE ALLOWED FOR THESE SHUTDOWN PERIODS EVEN THOUGH PREMIUM -TIME WORK MAY BE REQUIRED. PROVIDE TEMPORARY SERVICE TO EQUIPMENT OR SYSTEMS THAT CANNOT BE SHUTDOWN, AS DETERMINED BY OWNER. 12. PROVIDE A MINIMUM OF ONE WEEK'S NOTICE TO THE OWNER BEFORE ANY SERVICE SHUTDOWN IS SCHEDULED. 13. BIDS SHALL BE BASED UPON THE SPECIFIED PRODUCTS OR USED ALTERNATIVE. THE DRAWINGS AND SPECIFICATIONS ARE BASED ON THE PRODUCTS SPECIFIED BY TYPE, MODEL AND SIZE AND THUS E57ABIJSH MINIMUM QUALITIES WHICH SUBSTIMES MUST MEET TO QUALIFY FOR REVIEW. WHERE ONLY ONE MAKE IS NAMED, IT SHALL BE PROVIDED. VERBAL REQUESTS OR APPROVALS SHALL NOT BE BINDING ON THE ARCHITECT, ENGINEER OR OWNER. SHOULD THE CONTRACTOR PROPOSE TO FURNISH MATERIALS AND EQUIPMENT OTHER THAN THOSE SPECIFIED, HE SHALL SUBMIT A WRITTEN REQUEST FOR SUBSTITUTIONS TO THE ARCHITECT AT THE BID OPENING. INDICATE ANY ADDITIONS OR DEDUCTIONS TO THE CONTRACT PRICE ON THE BID FORM. 14. EQUIPMENT AND MATERIALS USED ON THIS PROJECT SHALL BE NEW AND U.L LABELED FOR THE APPLICATION. 15. KEEP ONE COMPLETE SET OF THE CONTRACT WORKING DRAWINGS ON THE PROJECT SIZE ON WHICH HE SHALL RECORD ANY DEVIATIONS OR CHANGES FROM SUCH CONTRACT DRAWINGS MADE DURING CONSTRUCTION. AFTER THE PROJECT IS COMPLETED, RECORD SETS OF DRAWINGS SHALL BE DELIVERED TO THE ARCHITECT IN GOOD CONDITION, AS A PERMANENT RECORD OF THE INSTALLATION AS CONSTRUCTED. 16. PROVIDE NAMEPLATES ON PANEIDOARDS, DISTRIBUTION EQUIPMENT, SAFETY SWITCHES, MOTOR STARTERS, JUNCTION BOXES, AND CONTROL DEVICES. UNLESS OTHERWISE INDICATED ON THE DRAWINGS, LETTERING SHALL INCLUDE THE NAME OR DESIGNATION OF EQUIPMENT, HORSEPOWER, VOLTAGE RATING AND SERVICE DESIGNATION. NAMEPLATES SHALL BE LAMINATED PHENOLIC WITH A BLACK SURFACE AND WHITE CORE. IDENTIFICATION WITH A DYMO TYPE INSTRUMENT IS NOT PERMISSIBLE THE INSIDE COVER OF ALL RECEPTACLE OUTLET PLATES SHALL BE PERMANENTLY MARKED TO INDICATE THE PANEL AND CIRCUIT NUMBER OF THE OUTLET. THE INSIDE COVER OF ALL BLANK PLATES FOR JUNCTION BOXES INSTALLED SHALL BE PERMANENTLY MARKED TO INDICATE THE SYSTEM. 17. AFTER INSTALLATION, TEST FOR GROUNDS, SHORT CIRCUITS AND PROPER FUNCTION OF EACH SYSTEM AND RELATED WIRING. FAULTS IN THE INSTALLATION SHALL BE CORRECTED. 18. INSULATION RESISFANCE TESTS SHALL BE MADE ON THE ELECTRICAL SYSTEM WITH AN APPROVED MEGOHMMETER. 19. A GROUND CONTINUITY TEST SHALL BE MADE ON THE ENTIRE GROUNDING SYSTEM FROM THE SERVICE TO EVERY OUTLET. 20. AFTER ALL TESTS AND ADJUSTMENTS HAVE BEEN COMPLETED, CLEAN ALL EQUIPMENT LEAVING EVERYTHING IN WORKING ORDER AT THE COMPLETION OF THIS WORK. CLEAN UGHTING FIX"LIRES, OL1"LLT BOX PLATES, PANEL AND CABINET INTERIORS AND EXTERIORS, ETC., OF DIRT, DUST , DEBRIS AND PAINT, AFTER ALL OTHER TRADES HAVE COMPLETED THEIR WORK. 21. PROVIDE A TEMPORARY ELECTRICAL SERVICE ADEQUATE IN SIZE FOR HEATING, FOR THE USE OF ALL TRADES AND FOR THE LIGHTING OF EACH ROOM DURING CONSTRUCTION. TEMPORARY WIRING SHALL BE TO OSHA REQUIREMENTS. TEMPORARY SERVICE CAN BE D(TENDED FROM THE OWNER'S EXISTING POWER DISTRIBUTION SYSTEM. THE OWNER MUST APPROVE OF THE POINT OF SUPPLY, THE METHOD OF EXTENSION AND THE ROUTING OF NECESSARY TEMPORARY FEEDERS. PROVIDE A TEMPORARY TELEPHONE SERVICE FOR THE USE OF ALL TRADES DURING CONSTRUCTION. 22. DO ALL CUTTING AND PATCHING IN EXISTING CONSTRUCTION AS NECESSARY FOR INSTALLATION OF THIS WORK. HAVE CUTTING DONE BY SKILLED MECHANICS AS CAREFULLY AS POSSIBLE AND WITH AS LITRE DAMAGE AS POSSIBLE 23. DETERMINE IF ANY STRUCTURAL ELEMENTS SUCH AS REPAIR OR POST TENSION CABLES EXIST IN FLOORS, WALLS OR ROOFS BY INSPECTION COORDINATED WITH THE LANDLORDS TENANT COORDINATOR OR STRUCTURAL ENGINEER AND BY USE OF X-RAY WHEN REQUIRED PRIOR TO ANY CUTTING OR CORE DRIVING. IF SUCH ELEMENTS EXIST, REPORT THIS IMMEDIATELY TO THE ARCHITECT AND LANDLORD'S TENANF COORDINATOR FOR RESOLUTION PRIOR TO CUTTING OR DRILLING. 24, OPERATION PRIOR TO COMPLETION: WHEN ANY MECHANICAL OR ELECTRICAL EQUIPMENT IS OPERATED WRING CONSTRUCTION THE WARRANTY PERIOD SHALL NOT COMMENCE UNTIL THE EQUIPMENT IS OPERATED BY THE OWNER. PROPERLY CLEAN AND ADJUST THE EQUIPMENT AND COMPLETE ALL PUNCH LIST ITEMS BEFORE FINAL ACCEPTANCE BY THE OWNER. THE DATE OF ACCEPTANCE AND THE START OF THE WARRANTY MAY NOT BE THE SAME DATE. ALL INCANDESCENT LAMPS OPERATED FOR MORE THAN 50 HOURS DURING CONSTRUCTION SHALL BE REPLACED NTH NEW LAMPS PRIOR TO OWNER ACCEPTANCE. 25. FIRE AND SMOKE INTEGRITY: SEAL BUILDING OPENINGS THROUGHOUT, CAUSED BY INSTALLATION OF ALL TYPES OF ELECTRICAL EQUIPMENT(CONDUR, CABLE/WIRE, PANELS EC.) WHERE OPENINGS ARE IN FLOORS OR FIRE RATED WALLS CONFIGURE THE PENETRATION IN CONFORMANCE WITH UL LISTED CRRE LAL INSURE FIRE AND SMOKE BARRIER INTEGRITY THROUGHOUT. WHERE INTUMESCENT SEALER/CAULKING IS REQUIRED USE MATERIALS OF 3M OR DOW CORNING. 26. BIDDING CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF LOCAL CODES AND ORDINANCES AND SHALL INCLUDE IN THEIR BIDS THE COSTS FOR ALL WORK INSTALLED IN STRICT ACCORDANCE WITH GOVERNING CODES, THE PLANS AND SPECIFICATIONS NOT WITHSTANDING. THE CONTRACTOR SHALL ALERT ARCHITECT, ENGINEER OR OWNER OF ANY APPARENT DISCREPANCIES BETWEEN GOVERNING CODES AND DESIGN INTENT. SECTION 16050 - BASIC MATERIALS AND METHODS 1. ALL BOXES SHALL BE RIGIDLY SUPPORTED FROM THE BUILDING STRUCTURE INDEPENDENT OF THE CONDUIT SYSTEM. ALL BOXES SHALL BE 4" SQUARE BOXES MINIMUM WITH RASED COVERS SUITABLE FOR THE WALL MATERIAL. 2. CONDUITS SHALL BE A RIGID OR INTERMEDIATE GRADE GALVANIZED STEEL CONDUIT IN WET LOCATIONS, CONCRETE, EXTERIOR MASONRY WALLS AND EXPOSED LOCATIONS SUBJECT TO DAMAGE. B. GALVANIZED STEEL ELECTRICAL METALLIC TUBING IN DRY LOCATIONS, INTERIOR PARTITIONS AND CEILING SPACE C. FLEXIBLE METAL CONDUIT FOR FINAL CONNECTIONS TO TRANSFORMERS, MOTORS MID EQUIPMENT. UQUID-TIGHF FLEXIBLE METAL CONDUIT IN WET AND DAMP LOCATIONS. D. FLEXIBLE METALLIC TUBING FROM OUTLET BOX TO RECESSED UGH" FIXTURES IN SUSPENDED CEILINGS, SIX FOOT MAXIMUM LENGTH. E. SCHEDULE 40 PVC RIGID NON-METALLIC CONDUIT BURIED BELOW GROUND FLOOR SLAB AND FOR EXTERIOR UNDERGROUND. F. CONDUIT CONNECTIONS TO UNDERCABINE" TYPE LIGHTING FIXTURES SHALL BE 3/8" FLEXIBLE METAL CONDUIT OR MC TYPE CABLE FROM THE WALL OUTLET BOX TO THE FIXTURE HOUSING. G. RACEWAYS SHALL BE SIZED IN ACCORDANCE WITH N.E.C. WIRING TABLE OR AS NOTED ON DRAWINGS, WHICHEVER IS LARGER. MINIMUM CONDUIT SIZE SHALL BE ONE-HALF INCH. H. CONDUIT FITTINGS FOR RIGID CONDUIT SHALL BE THREADED CAST FERROUS ALLOY WITH GASKETS AND COVERS WHERE REQUIRED. CONDUIT FITTINGS FOR EMT TO BE SET SCREW TYPE. LOCKNUTS SHALL BE OF THE BONDING TYPE WHICH BITE INTO THE METAL OF THE BOX. BUSHINGS SHALL BE OF THE INSULATING TYPE I. METAL CONDUITS SHALL BE COUPLED AND SECURED TO ALL BOXES IN A MANNER THAT PROVIDES AN ELECTRICALLY CONTINUOUS GROUND PATH FROM POINT OF SERVICE TO ALL OUTLETS. J. RIGID CONDUITS SHALL BE TERMINATED IN SHEET STEEL WITH DOUBLE LOCKNUTS AND AN INSULATING BUSHING. EMPTY CONDUITS STUBBED SHALL BE THREADED AND CAPPED. K. NYLON PULL UNE SHALL BE INSTALLED IN ALL EMPTY CONDUITS. L CONDUIT ROUTING INDICATED ON THE DRAWINGS IS DIAGRAMMATIC ONLY AND IS NOT NECESSARILY THE INTENDED ACTUAL CONDUIT RUN. CONTRACTOR SHALL CHECK AND BE RESPONSIBLE FOR THE ACTUAL INSTALLATION WITH REGARD TO AVAILABLE SPACE AND SHALL COOPERATE WITH OTHER TRADES. M. ALL CONDUITS SHALL BE SIZED AND INSTALLED SO THAT THE REQUIRED NUMBER OF CONDUCTORS MAY BE PULLED IN WITHOUT INJURY OR STRAIN. N. CONDUIT RUNS SHALL BE LOCATED TO AVOID EQUIPMENT AND ACCESS TO EQUIPMENT OF OTHER TRADES. 0. CONDUITS SHALL BE CONTINUOUS AND SECURED TO ALL BOXES IN SUCH A MANNER THAT EACH CONDUIT SYSTEM SHALL BE ELECTRICALLY CONTINUOUS FROM THE POINT OF SERVICE TO ALL OUTLET BOXES. RUN CONDUITS CONCEALED UNLESS OTHERWISE INDICATED. WHERE IT IS NOT POSSIBLE TO INSTALL CONCEALED CONDUIT, PERMISSION MUST BE OBTAINED FROM THE ARCHITECT TO RUN SURFACE WIREMOLD OR CONDOR. THE ROUTING AND ELEVATION OF SUCH SURFACE MOUNTED RACEWAYS MUST BE COORDINATED WITH THE ARCHITECT BEFORE INSTALLATION. EXPOSED RACEWAYS SHALL BE RUN PARALLEL TO OR AT RIGHT ANGLES TO STRUCTURAL MEMBERS AND SHALL BE PANTED TO MATCH ADJACENT FINISHES. P. CONDUIT SUPPORTS SHALL BE ATTACHED TO BUILDING STRUCTURAL MEMBERS ONLY, AND NOT TO ANY BUILDING SUB -SYSTEMS SUCH AS SUSPENDED CEILINGS, MECHANICAL DUCTS OR PIPES. Q. ENDS OF EACH CONDUIT SHALL BE CAPPED WITH AN APPROVED CAP OR DISC TO PREVENT THE ENTRANCE OF FOREIGN MATERIALS DURING CONSTRUCTION. R. CONDUITS THAT PASS THROUGH FIRE OR SMOKE -RATED WALLS, CEILINGS, OR DECKS SHALL BE INSTALLED SO AS TO MAINTAIN THE FIRE OR SMOKE RATING. S. EXPANSION FITTINGS SHALL BE INSTALLED AT ALL POINTS WHERE CONDUITS CROSS BUILDING EXPANSION JOINTS. L CONDUIT ENTRIES INTO BUILDING SHALL BE MADE WATERTIGHT. ALL UNDERGROUND JOINTS SHALL BE SEALED. U. EXTERIOR UNDERGROUND CONDUITS SHALL BE INSTALLED 36 INCHES MINIMUM BELOW FINISHED GRADE. 3. BUSHINGS. LOCKNUTS AND CONNECTORS: A WHERE RIGID OR INTERMEDIATE METAL CONDUIT ENTERS A BOX, SECURE THE CONDUIT TO THE BOX WITH A LOCKNUT ON THE OUTSIDE AND INSIDE. PROVIDE BUSHINGS FOR CONDUIT TERMINALS AT BOXES. FOR CONDUCTORS THRU 18 ANG BUSHINGS SHALL BE GALVANIZED,NON-INSULATING TYPE AND FOR CONDUCTORS LARGER THAN 18 AWG BUSHINGS ARE TO BE INSULATING TYPE. IF THE CONDUIT FITTING PROVIDES EQUIVALENT PROTECTION OF THE CONDUCTORS, THE BUSHING MAY BE ELIMINATED. 4. FEEDER AND BRANCH CIRCUIT CONDUCTORS: A FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE U.L LABELED, 98% CONDUCTIVITY COPPER -STAMPED AT 2 FF. INTERVALS WITH CONDUCTOR SIZE AND INSULATION TYPE B. FEEDER CIRCUIT CONDUCTORS SfWl BE TYPE "XHHW-2' OR "THHN; 600 VOLT, STRANDED COPPER, 90 DEGREE C BATED. ELECTRICAL SPECIFICATIONS C. BRANCH CIRCUIT CONDUCTORS SHALL BE TYPE THWN/THHN-2; 600 VOLT, 9OC COPPER. WIRE SIZES /8 AWG AND LARGER SHALL BE STRANDED. OR BRANCH CIRCUIT CONDUCTORS SHALL BE TYPE 'MC' THHN-2, 600 VOLT 90 DEGREE C COPPER WITH INSULATED GREEN GROUND WIRE ENCLOSED IN AN ALUMINUM OR GALVANIZED STEEL ARMOR 'CONDUIT' THAT IS APPROVED FOR EXPOSED OR CONCEALED APPLICATIONS. D. MINIMUM WIRE SIZE SHALL BE 112 AWG OR LARGER AS REQUIRED TO LIMIT VOLTAGE DROP AT FURTHEST OUTLET TO 3%. 5. WIRE AND CABLE INSTALLATION: A PULL WIRE AND CABLES INTO CONDUIT USING IDEAL INDUSTRIES YELLOW 190", OR EQUIVALENT. B. COLOR CODE WIRE AND CABLE FOR CIRCUITS AS CALLED FOR IN THE NATIONAL ELECTRICAL CODE COLOR CODING OF FEEDERS SHALL BE BY MEANS OF COLORED TAPE AT TERMINALS. C. INDMDUAL BRANCH CIRCUITS ARE SHOWN ON THE DRAWINGS FOR CLARITY. LIGHTING AND RECEPTACLE CIRCUITS MAY BE GROUPED FOR HOMERUNS, SO LONG AS CONDUCTOR AMPACITES ARE DEBATED PER NEC REQUIRMENTS. NEUTRAL CONDUCTORS IN RECEPTACLE CIRCUITS SERVING DATA EQUIPMENT LOADS SHALL NOT BE SHARED. D. WIRING FROM LEGALLY REQUIRED EMERGENCY AND STANDBY POWER GENERATION SOURCES SHALL BE KEPT INDEPENDENT OF EACH OTHER AND INDEPENDENT OF ALL OTHER BRANCH CIRCUIT WIRING, AND SHALL NOT ENTER THE SAME RACEWAY, CABLE BOX, OR CABINET WITH OTHER WIRING, UNLESS SPECIFICALLY ALLOWED BY THE NATIONAL ELECTRICAL CODE 5. WIRING DEVICE: A LOCAL UGHT SWITCHES SHALL BE 20 AMPERE 120/277 VOLTS, AC SPECIFICATION GRADE, WITH GROUNDING TERMINAL., AS MANUFACTURED BY HUBBELL, OR EQUIVALENT, JCS-122 SERIES. B. FLUORESCENT DIMMERS SHALL BE LUTRON "NOVA T-STAR" SERIES, }NTT -10 FOR 120 VOLT, INTF-40-277 FOR 277 VOLT. 3-WAY, 2 LOCATION FLUORESCENT DINNERS SHALL BE LUTRON "NOVA T-STAR" SERIES, /NTF-103P FOR 120 VOLT, INTF-103P-277 FOR 277 VOLT. C. INCANDESCEN" DIMMERS SHALL BE LUTRON "NOVA T-STAR" LINEAR SLIDE SERIES - FOR UP TO 1500 WATT DIMMERS AND LUTRON 'NOVA" LINEAR SLIDE SERIES FOR 2000 WATT DIMMERS. D. DUPLEX RECEPTACLES SHALL BE 20A, 125V, 2 POLE, 3 WIRE GROUNDING. GENERAL PURPOSE "SPECIFICATION GRADE." DUPLEX RECEPTACLES: HUBBELL JCR5352. ISOLATED GROUND DUPLEX RECEPTACLE: HUBBELL ICR5352 IG - ORANGE. HOSPITAL GRADE DUPLE% RECEPTACLES: HUBBELL'8300H. TAMPER RESISTANT "SAFETY TYPE" DUPLEX RECEPTACLES: HUBBELL /HBLEIMG. E DUPLEX RECEPTACLES WHERE INDICATED ON THE DRAWINGS OR WHERE REQUIRED BY CODE SHALL RAVE AN INTEGRAL GROUND FAULT PROTECTOR AND SHALL BE 20A, 125V, 2 POLE, 3 WERE GROUNDING: HUBBELL #GFR5352. GROUND FAULT RECEPTACLES SHALL NOT BE THRU-WIRED. PROVIDE INDIVIDUAL DUPLEX RECEPTACLE AS SHOWN ON THE DRAWINGS. HOSPITAL GRADE GROUND FAULT DUPLEX RECEPTACLES: HUBBELL JHGF8300. F. ALL SWITCHES, DIMMERS, AND RECEPTACLES SHALL BE WHITE UNLESS OTHERWISE INDICATED WITHIN THESE SPECIFICATIONS. VERIFY COLOR WITH THE ARCHITECT PRIOR TO PROCUREMENT OF THE DEVICES. ALL COVERPLATES SHALL BE SMOOTH HIGH IMPACT THERMOPLASTC FINISH WITH COLOR TO MATCH THE DEVICES. EMERGENCY RECEPTACLES AND SWITCHES SHALL BE RED, WITH COVERPLATES TO MATCH THE FINISH OF THE OTHER COVERPLATES PROVIDED IN THE AREA IN UNFINISHED AREAS, USE CADMIUM PLATED, ROUND CORNER, STEEL COVERPLATES FOR SURFACE MOUNTED OL1"LLT BOXES. BOTH THE WIRING DEVICES AND THE COVERPLATES SHALL BE BY THE SAME MANUFACTURER. G. THE FOLLOWING ARE EQUIVALENT WIRING DEVICES: 1. RECEPTACLE: #5362 SERIES MANUFACTURED BY PASS AND SEYMOUR OR LEVITON. 2. UGH" SWITCHES: PASS AND SEYMOUR 120AC1 SERIES OR LLW"ON 11221 SERIES. 3. DINNERS: NO OTHER MANUFACTURERS ARE ACCEPTABLE 7. WIRING DEVICE INSTALLATION: A ADJACENT DEVICE SHALL BE MOUNTED IN GANGED BOXES WITH COMMON COVER PLATES. B. VERIFY MOUNTING HEIGHTS AND LOCATIONS WITH THE ARCHITECT BEFORE ROUGH -IN. REFER TO DETAILS AND INTERIOR WALL ELEVATIONS SHOWN ON THE ARCHITECTURAL DRAWINGS. C. OUTLETS SHALL NOT BE INSTALLED BACK TO BACK. D. ALL RECEPTACLES SHALL BE MOUNTED WITH THE GROUND OPENING ABOVE THE PHASE AND NEUTRAL OPENINGS. E ALL DEVICES SHALL BE SECURED WITH MORE THAN A SINGLE SCREW. 10. HANGERS AND SUPPORTS- H. SUPPORT CONDUIT RUNS DIRECTLY ADJACENT TO BUILDING CONSTRUCTION WITH SUITABLE ONE AND TWO -HOLE STRAPS AND/OR CLAMP -TYPE HANGERS SUPPORT CONDUIT RUNS NOT ADJACENT TO BUILDING CONSTRUCTION WITH SUITABLE, ADJUSTABLE HANGERS. DO NOT USE PERFORATED STRAP -TYPE HANGER, WIRE TIES OR PLUMBERS STRAP. I. PROVIDE ANGLE IRON FRAMES AND SUPPORTS FOR JUNCTION BOXS AND CABINETS TO PREVENT STRAIN ON ENTERING CONDUITS. GROUP EXPOSED CONDUITS TOGETHER. CONDUIT PENETRATIONS INCAUNGS SHALL BE TIGHT TO THE CONDUIT AND SEALED. J. SUPPORT RIGID STEEL, IMC, AND EMT RACEWAYS AT MAX. TEN FEET INTERVALS AND WITHIN THREE FEET OF OUTLET AND JUNCTION BOXS, CABINETS OR FITTINGS. SUPPORT WITHIN 12" OF EACH CHANGE IN DIRECTION. USE ONE -HOLE MALLEABLE IRON CLAMPS. SUPPORT MULTIPLE RUNS ON GALVANIZED UNISTRUT. K. DO NOT SUPPORT ELECTRICAL RACEWAYS, BOXES, FIXTURES AND EQUIPMENT FROM COUNG SUPPORT SYSTEMS, MECHANICAL SYSTEM SUPPORTS, OR MECHANICAL SYSTEMS. 11. ALL EQUIPMENT MOUNTED ON EQUIPMENT ROOM WALLS SHALL BE ATTACHED TO 3/4- PLYWOOD BOARDS, PANTED WITH FIRE RESISTAN" PANT. SECTION 16400 - SERVICE AND DISTRIBUTION 1. GROUNDING. A GROUND ALL ELECTRICAL SYSTEM CONDURS, MOTORS, PANELS AND OTHER EXPOSED NON -CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT IN ACCORDANCE WITH ALL PROVISIONS OF THE NATIONAL ELECTRICAL CODE, STATE BUILDING CODE AND LOCAL OR REGIONAL CODES. B. GROUNDING OF THE ELECTRICAL SYSTEM SHALL BE BY MEANS OF AN INSULATED GROUNDING CONDUCTOR INSTALLED WITH FEEDER AND BRANCH CIRCUIT CONDUCTORS IN ALL CONDUITS. GROUNDING CONDUCTORS SHALL BE SIZED IN ACCORDANCE WITH N.EC. ARTICLE 250. C. SYSTEM NEUTRAL CONDUCTORS SHALL BE GROUNDED AT THE SOURCE. NEUTRAL CONDUCTORS SHALL NOT BE USED FOR EQUIPMENT GROUNDING. D. THE GROUNDING CONDUCTOR FOR BRANCH CIRCUITS FEEDING ISOLATED GROUND RECEPTACLES SHALL BE CONNECTED ONLY AT THE ISOLATED GROUND RECEPTACLE GROUND TERMINALS, AND AT THE GROUND BUS OF THE SERVING PANEL 2. BRANCH CIRCUIT PANEL BOARDS A BRANCH CIRCUIT PANEL BOARDS SHALL BE DEAD -FRONT CIRCUB BREAKER TYPE WITH VOLTAGE AMPERAGE, MAIN CIRCUIT BREAKER OR MAN LUGS ONLY, AS NOTED ON DRAWINGS. ALL PANEL BOARDS SHALL BE PROVIDED WITH SOLID NEUTRALS AND GROUNDING BUS WITH LUGS. B. CIRCUIT BREAKERS SHALL BE THERMAL MAGNETIC, MOLDED CASE BOLT -ON TYPE , WITH QUANTITY, AMPERAGE, AND POLES AS NOTED ON THE PANEL SCHEDULES. SHORT CIRCUIT INTERRUPTING CAPACITY SHALL BE AS NOTED ON THE DRAWINGS. TWO AND THREE POLE BREAKERS SHALL BE COMMON TRIP. AUTOMATIC TRIPPING SHALL BE INDICATED BY THE OPERATING HANDLE ASSUMING A MID -POSITION BETWEEN ON AND OFF. PROVIDE HACK BREAKERS AS REQUIRED BY ALL WAG EQUIPMENT MANUFACTURERS. C. PANEL BOARD ENCLOSURES SHALL BE GENERAL PURPOSE SURFACE- OR FLUSH -MOUNTED AS NOTED ON PANS, WITH GALVANIZED BACKBOX AND PAINTED FRONT WITH LOCKABLE DOOR A GLAZED DIRECTORY FRAME SHALL BE PROVIDED INSIDE THE DOOR, AND SHALL BE OF SUFFICIENT SIZE TO GIVE DESCRIPTION OF EACH CIRCUIT. ALL SECTIONS OF MULTI -SECTION PANELS SHALL BE SAME SIZE. D. TWO KEYS SHALL BE PROVIDED WITH EACH PANEL, AND ALL PANELS SHALL BE KEYED ALIKE E. SCREW FASTENED HANDLE LOCK -ON DEVICES SHALL BE PROVIDED ON BRANCH CIRCUIT BREAKERS FOR EMERGENCY, OUT, SECURITY AND NIGHT UGHTS. F. BRANCH CIRCUIT PANOBOARDS SHALL BE SQUARE D, TYPE 'NOOD', 120/208 VOLT, 3-PHASE, 4-WIRE OR TYPE NF, 277/48OV, 3-PHASE, 4-WIRE DISTRIBUTION PANEBOARDS SHALL BE SQUARE D, TYPE I-UNE. EQUIVALENT ALTERNATE. MANUFACTURERS: CORER HAMMER, GENERAL ELECTRIC OR SIEMENS. G. ALL UGHTING AND APPLIANCE PANELBOARDS SHALL HAVE A TYPENROTE74 CIRCUIT DIRECTORY THAT SHALL SHOW LOADING AS CONNECTED DURING CONSTRUCTION. H. THE BRANCH CIRCUIT NUMBERS USED ON THE DRAWINGS SHALL BE APPUED FOR THE CONSTRUCTION. HOWEVER, AT THE COMPLETION OF THE WORK, CIRCUIT NUMBER ADJUSTMENTS SHALL BE MADE AS REQUIRED TO PROVIDE BALANCED PHASE LOADING ON EACH PANELBOARD. I. FLUSH MOUNTED PANELBOARDS SHALL BE INSTALLED WITH A MINIMUM OF THREE EMPTY 3/4" CONDUITS STUBBED UP TO THE NEAREST ACCESSIBLE CEILING SPACE FOR CONVENIENT FUTURE EXPANSION. 3. PROVIDE 75 DEGREE C RATED CONNECTIONS THROUGHOUT. SECTION 16500 - LIGHTING 1. REFER TO LUMINARE SCHEDULE FOR DETAILED SPECIFICATIONS. 2. RECESSED LUMINAIRES PROVIDED SHALL BE COMPATIBLE WITH THE CENNG TYPES INSTALLED. VERIFY ALL CENNG TYPES WITH THE DIVISION 1 CONTRACTOR, OR WITH THE ARCHITECT BEFORE PROCUREMENT OF LUMINAIRES. 3. RECESSED AND SURFACE MOUNTED LUMINAIRES MOUNTED IN, OR ON CEILINGS OTHER THAN ACCESSIBLE LAY -IN CEILING SYSTEMS, SHALL BE SECURELY SUPPORTED IN A MANNER APPROVED BY THE ARCHITECT. MOUNTING SHALL ALSO BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE ARTICLE 410, AND AS RECOMMENDED BY THE MANUFACTURER. 4. RECESSED LUMINAIRES IN ACCESSIBLE LAY -IN CEILING SYSTEMS SHALL BE SUPPORTED AS FOLLOWS: A THE GRID SYSTEM TEES SHALL BE SUPPORTED AT EACH CORNER OF EACH LUMINARE WITH A SUSPENDED CEUNG SUPPORT WIRE UP TO A BUILDING STRUCTURAL MEMBER, OR UP TO THE STRUCTURAL DECK. B. EACH LUMINARE SHALL ALSO BE SECURELY FASTENED TO THE GRID SYSTEM TEES BY MECHANICAL MEANS, SUCH AS BOLTS, SCREWS, RNETS OR BY CUPS IDENTIFIED FOR USE WITH THE TYPE CEILING FRAMING MEMBER INSTALLED. SECTION 16700 - COMMUNICATIONS 1. COMBINATION TELEPHONE/DATA OUTLET BOXES SWILL BE 4 INCHES SQUARE WITH SINGLE GANG PLASTER RINGS, UNLESS OTHERWISE NOTED. 2. TELEPHONE -ONLY, DATA -ONLY, FAX AND PAY TELEPHONE OUTLETS SHALL BE SIMILAR. 3. AL CONDUITS REQUIRED FOR COMBINATION TELEPHONE/DATA OUTLETS AS SHOWN ON DRAWINGS SHALL BE INSTALLED COMPLETE WITH BUSHINGS AND NYLON PULL WIRES. 4. PROVIDE CONDUIT FROM EACH OUTLET UP TO THE NEAREST ACCESSIBLE CORRIDOR CEILING SPACE AND PROVIDE A PLASTIC GROMMET AT EACH STUB. 5. PROVIDE MISCELLANEOUS COMMUNICATION SYSTEM DEVICES AS SHOWN AND SPECIFIED ON THE DRAWINGS. 6. INCLUDE SUFFICIENT WIRING, CONDUIT TERMINATIONS, ELECTRICAL BOXES, AND ALL OTHER NECESSARY MATERIAL AS RECOMMENDED BY THE SYSTEM SUPPLIERS. 7. PLENUM RATED CABLE SHALL BE USED IN PLENUMS IF CABLE IS NOT INSTALLED IN CONDUIT. v LLL M 0 o4w I< o m 00 a o m > 5 w m o a'O oay ¢oe COO m 0 wo n) m r, mom m wUw i� N~ile ei wr.laice we SW'e i, eeellewm mW rww ge ump r y of agwwga ,.0 me,was bYao [N tlr = huoan &mmu n Aww amwmm Aw s.+iew. i.n.e n.en w.mnW relmluA wne,n wereeeeA wnnen consent W weAen e e Y C L sk, A C L11 e C 1. V a N W I- N �9 T O 0 W J Z Ix Q n W W AM 0 C7 U_ 2 n < T It a = z _ I- IL w J J Z MU Z o TN 0 F N PhI Nm 9MW oown RXe ATO Oft rw OFl90Y M i PEFNU RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and meal Codes City of Cannel �XIT�\ontlTOAeL DATE: Xrof .ORB LS Andover MA .dwa 10/16/19 E&O BECITFIll IN EWIDAT10N6