HomeMy WebLinkAboutA-3.03RELEA
Susie
POWER,
VOICE AND DATA SYMBOLS
POWER, VOICE AND DATA NOTES
®
AREA NOT IN CONTRACT
I.
UNLESS OTHERWISE NOTED, ALL CONVENIENCE OUTLETS TO BE WHITE IN COLOR.
2
NOTED, ALL DEDICATED OUTLETS TO BE GRAY IN COLOR, AND
ppppM -ROOM
NAME
BELLA EOTDHERWISE
ROOM -
ROOM NAME
301 -
ROOM NUMBER
3.
UNLESS OTHERWISE NOTED, ALL COVER PLATES TO BE WHITE IN COLOR.
ALL EQUIPMENT DESIGNATED BY THIS EQUIPMENT SYMBOL TO RECEIVE
ALL V-6' VERTICALLY
®
POWER AND RECEPTACLE TYPE AS REQUIRED. REFER TO EQUIPMENT
4.
CENTER OF OUTLETS AND CONNECTORS TO BE A.F.F. AND
SCHEDULE FOR MORE INFORMATION
MOUNTED, UNLESS OTHERWISE NOTED.
STANDARD DUPLEX ELECTRICAL OUTLET VERTICALLY ORIENTED AT 18'
5.
ALL DIMENSIONS SHOWN ARE TO THE CENTER OF THE RECEPTACLE, UNLESS
A.F.F. UNLESS NOTED OTHERWISE.
OTHERWISE NOTED. DEVICES SHOWN CLUSTERED TOGETHER ON THE POWER, DATA
AND VOICE PLANS) SHALL BE MOUNTED AS CLOSELY TOGETHER AS POSSIBLE.
Y
DEDICATED DUPLEX ELECTRICAL OUTLET VERTICALLY ORIENTED AT 18' A.F.F.
UNLESS NOTED OTHERWISE.
6.
ALL OUTLETS SHOWN WITH THE SIDE MARK 'GFI' ARE TO BE ON A GROUND FAULT
INTERRUPTION CIRCUIT.
«20A
20 AMP DEDICATED DUPLEX ELECTRICAL OUTLET VERTICALLY ORIENTED AT
18' A.F.F. UNLESS NOTED OTHERWISE.
7.
REFER TO THE DEMOLITION PLAN FOR ADDITIONAL INFORMATION RELATED TO POWER
AND CABLING DEMOLITION.
�GFI
STANDARD GROUND FAULT INTERRUPTER DUPLEX ELECTRICAL OUTLET
VERTICALLY ORIENTED AT 42' A.F.F. UNLESS NOTED OTHERWISE.
S.
ALL EXISTING AND NEW FLOOR SLAB PENETRATIONS FOR CONDUIT SHALL BE FULLY
PACKED AND SEALED IN ACCORDANCE WITH APPLICABLE BUILDING AND FIRE CODES.
PRIOR TO ANY FLOOR TRENCHING OR CORING, THE FLOOR MUST BE X-RAYED FIRST.
STANDARD QUADRAPLEX ELECTRICAL OUTLET VERTICALLY ORIENTED AT 18'
A.F.F. UNLESS NOTED OTHERWISE.
S.
G.C.'S ELECTRICIAN IS RESPONSIBLE FOR THE HARDWIRED CONNECTION OF FURNITURE
BASE FEEDS OF TENANT'S SYSTEMS FURNITURE. SYSTEMS FURNITURE ELECTRICAL
(3) STUBBED CONDUIT FOR POWER, DATA AND AV. FIRE SAFE AS REQUIRED
COMPONENTS TO BE CONNECTED TOGETHER BY THE TENANT'S FURNITURE
�-I
`=3D
IN ACCORDANCE WITH THESE DRAWINGS. COORDINATE LOCATION WITH
INSTALLER, AND VOICE/ DATA CABLING BY TENANT'S VOICE/ DATA CABLING VENDOR..
FCI
ARCHITECT AND FURNITURE VENDOR PRIOR TO CORING FOR COORDINATION
WITH THE TABLE LEG. SEE ENGINEER FOR FURTHER INFORMATION.
10.
REFER TO DETAIL 3/A-3.03 FOR WIRING DIAGRAMS FOR THE HERMAN MILLER
WORKSTATIONS. ALL RECEPTACLES INSTALLED IN MODULAR FURNITURE SHALL BE PER
POWER: ONE 1/2' EC STUB. ONE SHIELDED ELECTRICAL CABLE.
SYSTEMS FURNITURE WIRING DIAGRAMS.
DATA: ONE 3/4' EC STUB FOR THREE Case NETWORK CABLES TO
THE MDF.
11.
ALL VOICE AND DATA CABLING TO BE BY THE TENANT'S CABLING VENDOR. G.C. TO
AV: ONE 1-1/4' EC STUB FOR ONE HDMI AND TWO AUDIO TO THE
COORDINATE CABLING VENDOR'S SCOPE OF WORK WITH HIS OWN. G.C. TO PROVIDE
MONITOR ('AV-)
CABLING VENDOR, IN ADVANCE, WITH SCHEDULE SHOWING TIME FRAME FOR CABLING
VENDOR TO RUN CABLES WHEN WALLS AND CEILING ARE OPEN SO THAT CABLING
AND INSTALLATION CAN BE ACCOMPLISHED WITHOUT HAVING TO DEMOLISH OR UNDO
FLUSH, RECESSED FLOOR OUTLET POKE THRU:
ANY WORK ALREADY COMPLETED.
®
WIREMOLD EVOLUTION 6ATCBK RECESSED POKE THRU ASSEMBLY OR
4D
APPROVED EQUAL, W/ (1) 20 AMP DUPLEX RECEPTACLE AND (4) DATA JACKS.
12.
O.C. TO PROVIDE SAFETY GROMMETS, BACK BOXES, CONDUIT WITHIN THE WALLS AND
FBI
G.C. TO PROVIDE ALL DEVICE PLATES AND CONDUIT AS REQUIRED FOR
PULL LINES FOR VOICE/DATA RECEPTACLES WHERE SHOWN ON O.W.B. PARTITIONS.
POWER AND DATA WHICH WILL TERMINATE ABOVE THE CEILING AT THE
ALL CABLING TO BE DONE BY THE TENANT'S CABLE VENDOR. PROVIDE J' CONDUIT
NEAREST PARTITION BY G.C.'S ELECTRICAL CONTRACTOR. ALL DATA CABLING
STUB UP AND TERMINATE 6' ABOVE CEILING, U.N.O.,
TO BE SUPPLIED BY TENANT'S SEPARATELY CONTRACTED CABLING VENDOR.
13.
ALL POWER, VOICE, DATA AND AV CABLING RUN IN OTHER TENANTS PLENUM SPACE
INDICATES WALL MOUNTED ELECTRICAL RACEWAY MOUNTED AT 18' A.F.F.
OR CROSSING A COMMON CORRIDOR MUST BE RUN IN CONDUIT. COORDINATE REQUIRED
UNLESS NOTED OTHERWISE.
CONDUIT SIZES WITH THE TENANTS CABLING AND AV VENDORS. REFER TO ENGINEERS
DRAWINGS FOR FURTHER INFORMATION.
VOICE/DATA RECEPTACLE (I VOICE PORT / I DATA PORT) AT IB' A.F.F.
UNLESS NOTED OTHERWISE - BACK BOX, SAFETY GROMMET AND PULL
14.
REFER TO DOOR AND HARDWARE SCHEDULES ON SHEET A-5.00 FOR DOORS WITH
IT/ID
STRING BY G.C.'S ELECTRICAL CONTRACTOR, CABLING AND TERMINATION
CARD READERS, ELECTRICAL LOCK SETS, ETC.
DEVICE BY OTHERS.
15.
AT RECEPTION DOORS 301A AND 3018 THE SECURITY VENDOR IS TO PROVIDE AND
CABLING CONNECTOR (1, 2, 3 OR 4 DATA PORT(S)) AT 18' A.F.F. UNLESS
INSTALL WALL MOUNTED SWITCH THAT WILL OPERATE THE DURESS INDICATOR
LIGHTS IN OPEN OFFICE f322 1329, 1333 AND /335. THE SWITCHES AND LIGHTS
N
NOTED OTHERWISE - BACK BOX, SAFETY GROMMET, PULL STRING, AND
SHALL BE PROVIDED AND INSTALLED BY THE SECURITY VENDOR. G.C. TO PROVIDE
ID/2D/3D/4D
WHEN REQUIRED, CONDUITS, BY G.C.'S ELECTRICAL CONTRACTOR. CABLING
J-BOXES AND PULL STRINGS AS REQUIRED. COORDINATE INSTALLATION WITH THE
AND TERMINATION DEVICE BY TENANT'S DATA CABLING VENDOR.
SECURITY VENDOR.
WALL INFEED OF POWER ONLY INTO THE BASE OF THE SYSTEMS
16.
G.C. IS TO PROVIDE DOOR BELL AT DOOR 1301B, WHICH IS TO SOUND AT
Ed
FURNITURE ELECTRIFIED BASE. INFEED TO BE MOUNTED IN WALL AT f-0'
WORKSTATION IN OPEN AREA 1325.
A.F.F. TO CENTERLINE OF INFEED BOX. ELECTRICIAN TO HARDWIRE 'POWER
WHIP'.
17
D.C. IS TO SUPPLY AND CONNECT WATER LINES TO INTEGRAL ICE MAKERS AND
IN -DOOR WATER WITHIN REFRIGERATORS, AND COFFEE MAKERS. SEE POWER, VOICE k
WALL INFEED OF VOICE k DATA CABLING INTO THE BASE OF THE SYSTEMS
DATA PLAN FOR LOCATIONS OF EQUIPMENT.
FURNITURE. INFEED TO BE MOUNTED IN WALL AT I'-0' A.F.F. TO
18.
G.C. TO PROVIDE AND INSTALL HARDWIRED TIMING CONTROL DEVICES WITH 'NO -HOLD'
W
CENTERLINE OF INFEED BOX. G.C. TO ALSO PROVIDE, A COVER PLATE
WITH (2) 1-1/2' DIAMETER GROMMETS. ALL VOICE AND DATA CABLING TO
POSITIONS ONTO ALL OUTLETS TO SERVICE COFFEE MAKERS. TIMING DEVICES MUST
PROVIDE HOURS OF POWER, NOT MINUTES.
BE SUPPLIED BY TENANT'S SEPARATELY CONTRACTED CABLING VENDOR,
WHO WILL NEATLY BUNDLE/WRAP THE CABLES GOING THROUGH THE
19.
IN IDF
/303, FOR THE SECURITY SYSTEM ACCESS CONTROL PANEL: O.C. TO PROVIDE
GROMMETS TO THE BASE OF THE SYSTEMS FURNITURE.
(1) DEDICATED 110VAC 20 AMP CIRCUIT. THE TELE/DATA VENDOR IS TO PROVIDE (1)
VOICE DROP AND (1) DATA DROP. LOCATION OF POWER VOICE AND DATA TO BE
ELECTRICAL FLOOR INFEED OF POWER AND VOICE/DATA INTO THE BASE OF
CONFIRMED WITH THE SECURITY VENDOR PRIOR TO INSTALLATION.
THE SYSTEMS FURNITURE ELECTRIFIED BASE. POKE THRU TO BE WIREMOLD
EVOLUTION MULTI -SERVICE POKE THRU DEVICE, 6ATCFF OR APPROVED
20.
IN IDF 1303, FOR THE SECURITY ALARM PANEL: O.C. TO PROVIDE (1) DEDICATED 110VAC
EE
EQUAL. CONDUIT AS REQUIRED FOR POWER AND DATA IN PLENUM SPACE
20 AMP CIRCUIT AND THE TELE/DATA VENDOR IS TO PROVIDE (1) DEDICATED PHONE
BELOW BY G.C.'S ELECTRICAL CONTRACTOR, CONFIRM CONDUIT SIZES WITH
CABLING VENDOR. DIMENSIONS SHOWN ARE TO THE CENTERLINE OF INFEED
LINE.
BOX. INFEED TO BE FLUSH MOUNTED IN SLAB. ELECTRICIAN TO HARDWIRE
POWER WHIP'. ELECTRICAL CONTRACTOR TO MAKE CONNECTION- SEE
21
IN IDF 1303, G.C. TO PROVIDE AT A MINIMUM, (1) 4" CONDUIT RUN FROM THE BUILDING
POWER, VOICE It DATA NOTE 09. ALL VOICE AND DATA CABLING TO BE
DEMARCATION POINT TO THE TELECOM ROOM FOR LIBERTY MUTUAL'S TI LINE. ALL
SUPPLIED BY TENANT'S SEPARATELY CONTRACTED CABLING VENDOR, WHO
HOUSE PAIRS, FIBER OPTIC CABLE, AND ANY OTHER CABLE RUNNING FROM THE
WILL NEATLY BUNDLE/WRAP THE CABLES TO THE BASE OF THE SYSTEMS
BUILDING DEMARCATION POINT TO THE TELECOM ROOM SHALL BE IN CONDUIT.
FURNITURE. SEE ENGINEER'S DRAWINGS FOR FURTHER INFORMATION.
CR
CARD ACCESS PROXIMITY READER FOR TENANT'S SECURITY SYSTEM BY
SECURITY VENDOR. BACK BOX, SAFETY GROMMET AND PULL STRING BY
G.C.'S ELECTRICAL CONTRACTOR.
MD
MOTION DETECTOR DEVICE FOR TENANT'S SECURITY SYSTEM BY SECURITY
VENDOR. USED TO SHUNT THE DOOR CONTACT IN ORDER FOR THE ACCESS
CONTROL SYSTEM TO RECOGNIZE THE DOOR IS OPENING BY SOMEONE
EXITING AND NOT FORCED OPEN FROM THE OUTSIDE. MOTION DETECTOR
DEVICE IS NOT TIED INTO THE DOOR HARDWARE.
DB
DOOR BELL. SEE NOTE 116.
SINGLE GANG MUD RING WITH TWO PULL STRINGS AT 18' AFF WITH 1-1/4'
AV1
CONDUIT TO THE FLOOR STUB BY G.C.'S ELECTRICAL CONTRACTOR. AV
TERMINATIONS BY THE TENANT'S AV VENDOR. AV VENDOR TO PROVIDE
REQUIRED FACEPLATES.
CHIEF MFG. PAC526 WITH TWO PULL STRINGS WITH 1-1/4' CONDUIT TO
AV2
THE PLENUM. BOX BY G.C.'S ELECTRICAL CONTRACTOR. AV TERMINATIONS
BY THE TENANT'S AV VENDOR. AV VENDOR TO PROVIDE REQUIRED
FACEPLATES. MOUNTING HEIGHT AS INDICATED ON PLANS.
SINGLE GANG ELECTRICAL BOX AT 4'-0' A.F.F. HORIZONTALLY MOUNTED FOR
J1
4
TENANT'S CRESTRON TPMC-4SM ROOM VIEW UNIT. TELEDATA CABLER TO
PROVIDE (I) MALE RJ45 CONNECTION FROM TELECOM ROOM TO JUNCTION
BOX.
DURESS INDICATOR LIGHT PROVIDED BY TENANT'S SEPARATELY
CONTRACTED SECURITY VENDOR.
(42)
INDICATES DEVICE MOUNTED VERTICALLY AT 424 A.F.F. TO THE CENTER OF
THE DEVICE. (VARIES)
EX
DENOTES ITEM IS EXISTING TO REMAIN
ALTERNATES
O PROVIDE ADD/ALTERNATE PRICING TO PROVIDE AND INSTALL DATA CABLING PER
LIBERTY MUTUAL INFORMATION TRANSPORT SYSTEMS STANDARDS" DOCUMENT.
PER STANDARD DOCUMENT AND ELECTRICAL PLANS, PROVIDE AND INSTALL THE
SPECIFIED 4-POST EQUIPMENT RACK IN TELECOM ROOM. PLEASE CHECK
ELECTRICAL PLANS TO DETERMINE IF THIS PROJECT IS VOIP.
® PROVIDE ADD/ALTERNATE PRICING TO SUPPLY AND INSTALL THE FOLLOWING
APPLIANCES: (2) REFRIGERATOR(S), (2) MICROWAVE(S), (1) UNDER -COUNTER
REFRIGERATOR AND (1) ICE MAKER. REFER TO THE APPLIANCE SCHEDULE FOR
SPECIFICATIONS. GENERAL CONTRACTOR PROVIDED EQUIPMENT SHALL BE INVOICED
TO LIBERTY MUTUAL SEPARATE FROM THE GENERAL CONTRACT.
PMENTSCHED
Code
Item
Manufacturer
Model No.
Comments
El
PERSONAL COMPUTER
-
-
PROVIDED AND INSTALLED BY LIBERTY MUTUAL
E2
WALL MOUNTED MONITOR
-
-
PROVIDED AND INSTALLED BY LIBERTY MUTUAL
E3
MULTI FUNCTION DEVICE
_
PROVIDED AND INSTALLED BY LIBERTY MUTUAL
APPLIANCE SCHEDULE
Code
Item
Manufacturer
Model No.
Comments
PROVIDED AND INSTALLED BY LIBERTY MUTUAL. SEE ALTERNATE 14. G.C.
T-23-HC
STAINLESS
TO PROVIDE WATERTITE MODEL 9000 PVC ICE MAKER OUTLET BOX W/
AP1
REFRIGERATOR
TRUE
STEEL, 3.3 CU.
CUT-OFF VALVE MOUNTED AT 180 A.F.F. WITH WATTS BRAIDED STAINLESS
FT.
STEEL CONNECTOR AND INTEGRAL SHUT OFF VALVE ON INLET SIDE.
REFER TO ENGINEERS DRAWINGS FOR FURTHER INFORMATION.
AP2
AVENUE C (VENDING)
-
-
PROVIDED AND INSTALLED BY LIBERTY MUTUAL
PROVIDED AND INSTALLED BY LIBERTY MUTUAL. O.C. TO PROVIDE
WATERTITE MODEL 9000 PVC ICE MAKER OUTLET BOX W/ CUT-OFF
AP3
COFFEE MAKER
-
-
VALVE MOUNTED ABOVE THE COUNTERTOP WITH WATTS BRAIDED
STAINLESS STEEL CONNECTOR AND INTEGRAL SHUT OFF VALVE ON
INLET SIDE. REFER TO ENGINEERS DRAWINGS FOR FURTHER INFORMATION.
IOOOW/R - 21LT
AP4
MICROWAVE
SHARP
STAINLESS
PROVIDED AND INSTALLED BY LIBERTY MUTUAL. SEE ALTERNATE /4.
STEEL
AP5
UNDER -COUNTER
U-LINE
29RB, BLACK
PROVIDED AND INSTALLED BY LIBERTY MUTUAL. SEE ALTERNATE f4
REFRIGERATOR
HID525 OR
PROVIDED AND INSTALLED BY LIBERTY MUTUAL. SEE ALTERNATE j4. O.C.
HID540 W/
TO PROVIDE WATERTITE MODEL 9000 PVC ICE MAKER OUTLET BOX W/
AP6
ICE MACHINE
SCOTSMAN
OVERFLOW
CUT-OFF VALVE MOUNTED AT IB' A.F.F. WITH WATTS BRAIDED STAINLESS
PROTECTION
STEEL CONNECTOR AND INTEGRAL SHUT OFF VALVE ON INLET SIDE.
PAN
REFER TO ENGINEERS DRAWINGS FOR FURTHER INFORMATION.
HST21-A
AP7
ICE MACHINE STAND
SCOTSMAN
STAINLESS
PROVIDED AND INSTALLED BY LIBERTY MUTUAL. SEE ALTERNATE f4.
STEEL
3ED FOR CONSTRUCTION
1 to compliance with all regulations
of State and Local Codes
City of Conrad
s n
L"
PON,
I
Bull
COLLAB
5-M
POWER, VOICE AND DATA PLAIN
THREE (3) 4 POST
DATA RACK AND
WIRE MANAGERS:
FLOOR MOUNTED
AND POWERED
THROUGHOUT
DED. QUAD 20 AMP.
5-15R
DED. L14-30R
2 POLE 60A INPUT
BREAKER HARDWIRE
TERMINAL BLOCK
DED.QUAD 20 AMP.
5-15R
I F;
ENLARGED PLAN - TELECOM ROOM #303
L
FIVE (5) DED.
L6-20R OUTLETS
PBX STATION
WALL FEED
_ VOICE STATION
WALL FEED
f6-AWG
GROUND BAR.
D
On
COLLAR
33B
e
SECURITY, ALARM
AND ACCESS
CONTROL PANELS
(STACKED) TO BE
HARDWIRED. SEE
NOTE f19 k 120
/CC 3
C
I��; - Ills I1111111��Q ��;
1 1
NOTE: DO NOT INSTALL RECEPTACLES, VOICE OR DATA DEVICES ON END PANELS UNLESS INDICATED ON ARCHITECTS I/e'
SCALE PLANS. IF DEVICES ARE INDICATED ON 1/8- SCALE PLAN - CIRCUIT WILL BE DESIGNATED.
wih
III
I��Ny
I�II�I
I I
I�II�I
M t
314BA
❑❑❑❑ \Y C/ V%-GCl
HIVE
314A
SEE NOTE
#18.
EE
SYMBOLS
C
ROOM
313
N
(B
SCALE: j
I /8" = F-W
PQ� DUPLEX RECEPTACLE MOUNTED IN MODULAR
FURNITURE BY FURNITURE INSTALLER. (RECEPTACLE
DESIGNATION INDICATED BY LETTER INDICATES
PHASE 'A', 'B' OR 'C'). (Computer) ADJACENT TO
RECEPTACLE INDICATES DEVICE FOR COMPUTER
TO BE CONNECTED TO.
p COMBINATION VOICE/DATA OUTLET MOUNTED IN
MODULAR FURNITURE. ONE VOICE AND ONE DATA
UNLESS OTHERWISE NOTED.
b VOICE OUTLET MOUNTED IN MODULAR FURNITURE.
ONE VOICE UNLESS OTHERWISE NOTED.
N DATA OUTLET MOUNTED IN MODULAR FURNITURE.
ONE DATA UNLESS OTHERWISE NOTED.
INDICATES THE EXTENT OF THE SYSTEMS
FURNITURE ELECTRIFIED BASE
FURNITURE SYSTEM WIRING
WIRING PROVIDED IN FURNITURE AND IT'S USE.
NI NEUTRAL SHARED WITH HI, H2 k H3 (110 AWG)
N2 NEUTRAL SHARED WITH H4 (110 AWG)
GI GROUND SHARED WITH HI, H2 k H3 (J12 AWG)
02 SHAREDGROUND WITH H4
( (OR ISOLATED IF INDICATED ON DRAWINGS)
H1 HOT - TO BE USED FOR PHASE A (j12 AWG)
H2 HOT - TO BE USED FOR PHASE B #12 AWO
H3 HOT - TO BE USED FOR PHASE C j12 AWG
H4 HOT - TO BE USED FOR 'D' CIRCUIT (f12 AWG)
1 I. ROTATION OF CIRCUITS SHALL REMAIN THE SAME FOR ODD NUMBERED WORKGROUPS. SIMPLY DELETE THE WORKSTATION NOT
SHOWN.
2. *HERMAN MILLER' MODULAR FURNITURE IS PROVIDED WITH AN 8 WIRE WHIP BY FURNITURE MANUFACTURER AND CONNECTED TO
FURNITURE BY FURNITURE INSTALLER,
3. ELECTRICAL CONTRACTOR SHALL CONNECT WHIP FROM MODULAR FURNITURE TO FLOOR POKE-THRU OR JUNCTION BOX OR WALL
JUNCTION BOX AS INDICATED ON THE ELECTRICAL DRAWINGS. ELECTRICAL CONTRACTOR SHALL CAP 'H4', 'N2' It 'G2' IN JUNCTION
BOX FOR POSSIBLE FUTURE USE WHERE ONLY THREE HOMERUNS ARE INDICATED TO MODULAR FURNITURE.
4. WHERE A FOUR CIRCUIT HOMERUN IS INDICATED ON THE DRAWINGS ELECTRICAL CONTRACTOR SHALL CONNECT OGI' k '02' GROUNDS
TOGETHER AT FEED LOCATION UNLESS ADDITIONAL GROUNDING CONDUCTOR IS INDICATED ON HOMERUN.
5. ELECTRICAL FEED TO MODULAR FURNITURE SHALL BE LOCATED PER ARCHITECTURAL DRAWINGS.
6. ALL VOICE AND DATA DEVICES AND WIRING ARE TO BE INSTALLED BY THE VOICE/DATA VENDOR. ELECTRICAL CONTRACTOR SHALL
PROVIDE FLOOR JUNCTION BOX OR POKE-THRU OR WALL JUNCTION AS INDICATED ON THE DRAWINGS AND FLEXIBLE WATERTIGHT
CONDUIT TO MODULAR FURNITURE FOR USE BY THE VOICE/DATA VENDOR. ALL JUNCTION BOXES AND CONDUIT SHALL BE SIZED PER
THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE.
SCALE. SCALE:
1/4..=I._o.. HERMAN MILLER MODULAR FURNITURE WIRING DIAGRAM N.T.S
H
E
L L
Y E R
LEWIS-
ARCHITECTURE
INTERIOR
DESIGN
Project:
Liberty
Mutual,
INSURANCE
450 East 96th St
3rd Floor
Indianapolis IN 46240
Scale: 1 /8" = 1'-0"
Drawing:
Power, Voice
and Data Plan
No. A-3mO3
�G�
DATE: 10/23/19