1. EXACT LOCATION OF MECHANICAL, PLUMBING, KITCHEN, FURNITURE SYSTEMS, OWNER
FURNISHED EQUIPMENT, ETC. THAT REQUIRE ELECTRICAL CONNECTIONS ARE SHOWN ON
THE MECHANICAL, PLUMBING, AND/OR ARCHITECTURAL DRAWINGS. COORDINATE EXACT
LOCATIONS WITH RESPECTIVE CONTRACTORS AND/OR VENDORS PRIOR TO ANY
ROUGH —INS.
2. RENEW AND COORDINATE WITH ALL TRADES' CONTRACT DOCUMENTS TO DETERMINE
SPECIFIC MOUNTING LOCATIONS FOR EQUIPMENT WITH ELECTRICAL CONNECTIONS.
COORDINATE EXACT MOUNTING LOCATIONS WITH THE SPECIFIC TRADE AND ARCHITECT.
3. MINIMUM CONDUCTOR SIZE FOR 277 VOLT BRANCH CIRCUITS SHALL BE 12—AWG. FOR
277 VOLT BRANCH CIRCUITS WITH HOMERUNS OVER 150 LINEAR FEET A MINIMUM WIRE
SIZE OF 10—AWG SHALL BE PROVIDED FROM FIRST JUNCTION/OUTLET BOX TO BRANCH
CIRCUIT PANELBOARD.
4. MINIMUM CONDUCTOR SIZE FOR 120 VOLT BRANCH CIRCUITS SHALL BE 12—AWG. FOR
120 VOLT BRANCH CIRCUITS WITH HOMERUNS OVER 100 LINEAR FEET, A MINIMUM WIRE
SIZE OF 10—AWG SHALL BE PROVIDED FROM FIRST JUNCTION/OUTLET BOX TO BRANCH
CIRCUIT PANELBOARD. FOR 12D VOLT BRANCH CIRCUITS WITH HOMERUNS OVER 150
LINEAR FEET, A MINIMUM WIRE SIZE OF 8—AWG SHALL BE PROVIDED FROM FIRST
JUNCTION/OUTIET BOX TO BRANCH CIRCUIT PANELBOARD.
S. ALL WIRING SHALL BE IDENTIFIED BY PANELBOARD AND CIRCUIT NUMBER(S) IN ALL
CABINETS, JUNCTION BOXES, WIRING TROUGHS, ENCLOSURES, SPLICE OR TERMINATION
POINTS, ETC.
6. A NEW TYPED PANELBOARD DIRECTORY CARD SHALL BE PROVIDED FOR ALL PANELS
INSTALLED OR MODIFIED UNDER THIS CONTRACT. NEW DIRECTORY CARDS SHALL BE
LOCATED ON THE INSIDE DOOR OF ASSOCIATED PANELS.
7. FINALIZE ALL SECURITY DEVICE LOCATIONS WITH ARCHITECTURAL DRAWINGS PRIOR TO
ROUGH —IN.
8. PER N.E.C. ARTICLE 620, ELEVATOR PIT AND MACHINE ROOM UGHDNG SHALL NOT BE
CONNECTED TO THE LOAD SIDE OF GFCI TYPE RECEPTACLE(S).
EXISTING BUILDING FIRE ALARM SYSTEM NOTES:
I. PRIOR TO BID SUBMITTAL, THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE WITH
BUILDING MANAGEMENT AND THE BUILDING APPROVED FIRE ALARM SYSTEM VENDOR TO
VERIFY THE EXISTING SYSTEM, OPERATIONS, COMPONENTS, PANEL LOCATIONS, CABLING,
ROUTING REQUIREMENTS, ETC.
2. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WMH BUILDING MANAGEMENT AND THE
FIRE ALARM SYSTEM VENDOR FOR ALL NEW COMPONENTS AND OR SYSTEM
MODIFICATIONS AS REQUIRED TO ACCOMMODATE RE —USE OF EXISTING PND OR NEW FIRE
ALARM DEVICE(5) AND CODE COMPLIANCE OPERATION.
3. FIRE ALARM DEVICE LOCATIONS ARE DIAGRAMMATIC ONLY. THE FIRE ALARM SYSTEM
VENDOR SHALL BE RESPONSIBLE TO VERIFY ALL NEW AND/OR EXISTING DEVICE
SPECIFICATIONS AND CHARACTERISTICS BASED ON EACH SYSTEM DEVICE SPECIFICATIONS.
PROVIDE FINAL DEVICE COUNTS AND LAYOUT DRAWINGS OF DEVICE LOCATIONS TO MEET
ALL STATE AND LOCAL FIRE ALARM CODE REQUIREMENTS.
4. PROVIDE ALL NEW EQUIPMENT AND DEVICES AS REQUIRED FOR A COMPLETE AND CODE
COMPLAINT SYSTEM. THE ELECTRICAL CONTRACTOR AND FIRE ALARM SYSTEM VENDOR
SHALL BE RESPONSIBLE TO PROVIDE ALL SERVICES REQUIRED TO PROVIDE A 'COMPLETE
AND OPERATIONAL SYSTEM' PER ALL LOCAL MUNICIPALITY AND STATE CODE
REQUIREMENTS. THIS INCLUDES BUT IS NOT LIMITED TO: PRODUCING FIRE ALARM PLAN
DRAWINGS AND SPECIFICATIONS FOR PERMITTING, SHOP DRAWINGS, AND INSTALLATION.
ALL DOCUMENTS MUST INCLUDE ALL SIGNALING CIRCUIT LOADS, VOLTAGE DROPS, WIRING
DIAGRAMS WIRE SIZE, BATTERY CALCULATIONS, ETC. PER MUNICIPAL CODE OF THE CITY
OF INDIANAPOLIS, AND STATE OF INDIANA CODE REQUIREMENTS.
RACK (g6 AWG)
RACK (g6 AWG)
RACK (16 AWG)
"TGB" IN 4th FLOOR TELECOM ROOM 403
AO NI ,1111,1111,1111111111111 M
some @ • I@1.1a • • •
L
GROUND BAR ASSEMBLY — 1/4"z IN 12" NEMA BAR
RTH
CHATSWOY13622-012 COMPLETE WITH INSULATORS
AND MOUNTING BRACKETS.
LU
NEMA COPPER GS. SIZED PER
CONDUCTOR SIZE INDICATED ON
DRAWINGS. (TYPICAL) ALONG 'TIB" IN TELECOM ROOM
GROUND BAR DETAIL "TGB"
SCALE: NOT TO SCALE
NOTES:
1. VERIFY EXACT MOUNTING LOCATION OF TGB WITH
IT DEPARTMENT PRIOR TO ANY ROUGH —IN.
TO EXISTING POWER
AS REQUIRED
FACR 3/4'C TO FACP (FIRE ALARM CONTROL PANEL)
3/4"C TO ACCESS
C NTROL PANEL JB
MD CEILING
CARD READER/ELECTRIC STRIKE DETAIL
CR FLUSH MOUNTED BACK BOX ON SECURE SIDE OF DOOR FOR CARD READER.
MOUNT PER ADA REQUIREMENTS.
TO JB FACR FIRE ALARM CONTROL RELAY FOR DOOR RELEASE.
JB JUNCTION BOX 8' X 10' W/COVER, ON SECURE SIDE OF SPACE 6' ABOVE
ACCESSIBLE CEILING.
DBI Eff] ELECTRIC STRIKE CONCEALED WITHIN DOOR FRAME.
CR ES
Q F—MD-1 MORON DETECTOR
pg "REQUEST TO EXIT PUSHBURON — FLUSH MOUNTED ON NON —SECURE SIDE
OF DOOR, MOUNTED PER ADA REQUIREMENTS.
FLOOR
SINGLE DOOR SECURITY DETAIL
NOTES:
L CARD READER PROVIDED BY LIBERTY MUNAL'S SECURITY VENDOR. ELECTRIC STRIKE
PROVIDED BY DOOR HARDWARE VENDOR.
2. RELATED ELECTRICAL
PROVIIDEY COMPLETE OPERATIIONALRDOORNPER ALL FOR
AND LOCALE
CODE REQUIREMENTS.
3. COORDINATE WITH LIBERTY MUTUAL'S SECURITY VENDOR PRIOR TO ANY ROUGH —IN THE
EXACT RO INATE ALL CONDUITS
AARm CONTRACTOR VENDOR FFORNF(RE MOUNTING
INTERFACE POINTS AS REQUIRED.
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Camel
�Nn,�31a>na>n�A�
SCALE: NONE
U::ICJ3
0314
I
M1113irb
P 11
NONNI
1
1110mmal
M
a Integrated
I Engineering
Consultants, Inc.
9700 ROCKSIDE RD. SUITE #290
CLEVELAND, OH 44125
IF): 216.901.6711
IF): 216.901.6712
w .ieo-inc.cc
Electrical
Power
Plan
SCALE:
1
2 CONDUCTOR, 116 AWG PLENUM RATED CABLE
1201
1OVA TRANSFORMER
#10(G),
_/000
CR/1
JUNCTION BOX 1/2" CONDUIT ' 1�
120V INPUT FROM LOCAL \
RECEPTACLE CIRCUIT PUSH BUTTON
DOOR BELL (CHIME) DETAIL 40
NOTES: SCALE: NTS
1. PROVIDE EDWARDS SIGNALING CO. DOOR CHIME KIT #C212—W. KIT COMES WITH
CHIME, TRANSFORMER, AND PUSH BUTTON. WIRING PER MANUFACTURER WIRING
DIAGRAMS.
PANEL "CR"
20BY/12OV-4-4W
CR/22,24 C20/2
60/2 30/2
CR/14oe2D, 6 \
0/2
CR/l8,20
®20/2
HARDWIRE: 2-POLE 60A INPUT BREAKER
HARDWIRE TERMINAL BLOCK 3W+G
(L-L-N-G) TO CHASSIS.
Enlar ed Telecom Room 403 Power Plan 62
9 a• ALE:
ELECTRICAL CODED NOTES:
Q WIRE INTO EXISTING TOILET ROOM RECEPTACLE CIRCUIT.
® 4' EMT CONDUIT WITH PULLSTRING AND INSULATING BUSHING AT BOTH ENDS.
Q PROVIDE A COMPLETE DOORBELL SYSTEM WITH PUSHBUTTON, CHIME, AND TRANSFORMER.
EDWARD SIGNALING JC212 SERIES —WHITE. WIRE INTO LOCAL RECEPTACLE CIRCUIT.
OA SURFACE RACEWAY: WIREMOLD 4000 SERIES. PROVIDE ALL FTnNGS, CONNECTORS, END CAPS,
ETC. FOR A COMPLETE INSTALLATION PER MANUFACTURERS REQUIREMENTS.
COFFEE
Enlar ed HIVE 414A Power Plan 6�LE: 3
9 aCALE
REFRIGERATOR
H
E
L
L Y E R
LEWIS=
ARCHITECTURE
INTERIOR DESIGN
Project:
10
Liberty
Mutual.
INSURANCE
450 East 96th St
3rd Floor
Indianapolis IN 46240
Drawing:
Electrical
Power Plan
No. E-103
DATE: 10/23/19