HomeMy WebLinkAboutE-3.03GENERAL POWER PLAN NOTES: 1. EXACT LOCATION OF MECHANICAL, PLUMBING, KITCHEN, FURNITURE SYSTEMS, OWNER FURNISHED EQUIPMENT, ETC. THAT REQUIRE ELECTRICAL CONNECTIONS ARE SHOWN ON THE MECHANICAL, PLUMBING, AND/OR ARCHITECTURAL DRAWINGS. COORDINATE EXACT LOCATIONS WITH RESPECTIVE CONTRACTORS AND/OR VENDORS PRIOR TO ANY ROUGH —INS. 2. RENEW AND COORDINATE WITH ALL TRADES' CONTRACT DOCUMENTS TO DETERMINE SPECIFIC MOUNTING LOCATIONS FOR EQUIPMENT WITH ELECTRICAL CONNECTIONS. COORDINATE EXACT MOUNTING LOCATIONS WITH THE SPECIFIC TRADE AND ARCHITECT. 3. MINIMUM CONDUCTOR SIZE FOR 277 VOLT BRANCH CIRCUITS SHALL BE 12—AWG. FOR 277 VOLT BRANCH CIRCUITS WITH HOMERUNS OVER 150 LINEAR FEET A MINIMUM WIRE SIZE OF 10—AWG SHALL BE PROVIDED FROM FIRST JUNCTION/OUTLET BOX TO BRANCH CIRCUIT PANELBOARD. 4. MINIMUM CONDUCTOR SIZE FOR 120 VOLT BRANCH CIRCUITS SHALL BE 12—AWG. FOR 120 VOLT BRANCH CIRCUITS WITH HOMERUNS OVER 100 LINEAR FEET, A MINIMUM WIRE SIZE OF 10—AWG SHALL BE PROVIDED FROM FIRST JUNCTION/OUTLET BOX TO BRANCH CIRCUIT PANELBOARD. FOR 12D VOLT BRANCH CIRCUITS WITH HOMERUNS OVER 150 LINEAR FEET, A MINIMUM WIRE SIZE OF 8—AWG SHALL BE PROVIDED FROM FIRST JUNCTION/OUTIET BOX TO BRANCH CIRCUIT PANELBOARD. S. ALL WIRING SHALL BE IDENTIFIED BY PANELBOARD AND CIRCUIT NUMBER(S) IN ALL CABINETS, JUNCTION BOXES, WIRING TROUGHS, ENCLOSURES, SPLICE OR TERMINATION POINTS, ETC. 6. A NEW TYPED PANELBOARD DIRECTORY CARD SHALL BE PROVIDED FOR ALL PANELS INSTALLED OR MODIFIED UNDER THIS CONTRACT. NEW DIRECTORY CARDS SHALL BE LOCATED ON THE INSIDE DOOR OF ASSOCIATED PANELS. 7. FINALIZE ALL SECURITY DEVICE LOCATIONS WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH —IN. 8. PER N.E.C. ARTICLE 620, ELEVATOR PIT AND MACHINE ROOM UGHDNG SHALL NOT BE CONNECTED TO THE LOAD SIDE OF GFCI TYPE RECEPTACLE(S). EXISTING BUILDING FIRE ALARM SYSTEM NOTES: I. PRIOR TO BID SUBMITTAL, THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE WITH BUILDING MANAGEMENT AND THE BUILDING APPROVED FIRE ALARM SYSTEM VENDOR TO VERIFY THE EXISTING SYSTEM, OPERATIONS, COMPONENTS, PANEL LOCATIONS, CABLING, ROUTING REQUIREMENTS, ETC. 2. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WMH BUILDING MANAGEMENT AND THE FIRE ALARM SYSTEM VENDOR FOR ALL NEW COMPONENTS AND OR SYSTEM MODIFICATIONS AS REQUIRED TO ACCOMMODATE RE —USE OF EXISTING PND OR NEW FIRE ALARM DEVICE(5) AND CODE COMPLIANCE OPERATION. 3. FIRE ALARM DEVICE LOCATIONS ARE DIAGRAMMATIC ONLY. THE FIRE ALARM SYSTEM VENDOR SHALL BE RESPONSIBLE TO VERIFY ALL NEW AND/OR EXISTING DEVICE SPECIFICATIONS AND CHARACTERISTICS BASED ON EACH SYSTEM DEVICE SPECIFICATIONS. PROVIDE FINAL DEVICE COUNTS AND LAYOUT DRAWINGS OF DEVICE LOCATIONS TO MEET ALL STATE AND LOCAL FIRE ALARM CODE REQUIREMENTS. 4. PROVIDE ALL NEW EQUIPMENT AND DEVICES AS REQUIRED FOR A COMPLETE AND CODE COMPLAINT SYSTEM. THE ELECTRICAL CONTRACTOR AND FIRE ALARM SYSTEM VENDOR SHALL BE RESPONSIBLE TO PROVIDE ALL SERVICES REQUIRED TO PROVIDE A 'COMPLETE AND OPERATIONAL SYSTEM' PER ALL LOCAL MUNICIPALITY AND STATE CODE REQUIREMENTS. THIS INCLUDES BUT IS NOT LIMITED TO: PRODUCING FIRE ALARM PLAN DRAWINGS AND SPECIFICATIONS FOR PERMITTING, SHOP DRAWINGS, AND INSTALLATION. ALL DOCUMENTS MUST INCLUDE ALL SIGNALING CIRCUIT LOADS, VOLTAGE DROPS, WIRING DIAGRAMS WIRE SIZE, BATTERY CALCULATIONS, ETC. PER MUNICIPAL CODE OF THE CITY OF INDIANAPOLIS, AND STATE OF INDIANA CODE REQUIREMENTS. RACK (g6 AWG) RACK (g6 AWG) RACK (16 AWG) "TGB" IN 4th FLOOR TELECOM ROOM 403 AO NI ,1111,1111,1111111111111 M some @ • I@1.1a • • • L GROUND BAR ASSEMBLY — 1/4"z IN 12" NEMA BAR RTH CHATSWOY13622-012 COMPLETE WITH INSULATORS AND MOUNTING BRACKETS. LU NEMA COPPER GS. SIZED PER CONDUCTOR SIZE INDICATED ON DRAWINGS. (TYPICAL) ALONG 'TIB" IN TELECOM ROOM GROUND BAR DETAIL "TGB" SCALE: NOT TO SCALE NOTES: 1. VERIFY EXACT MOUNTING LOCATION OF TGB WITH IT DEPARTMENT PRIOR TO ANY ROUGH —IN. TO EXISTING POWER AS REQUIRED FACR 3/4'C TO FACP (FIRE ALARM CONTROL PANEL) 3/4"C TO ACCESS C NTROL PANEL JB MD CEILING CARD READER/ELECTRIC STRIKE DETAIL CR FLUSH MOUNTED BACK BOX ON SECURE SIDE OF DOOR FOR CARD READER. MOUNT PER ADA REQUIREMENTS. TO JB FACR FIRE ALARM CONTROL RELAY FOR DOOR RELEASE. JB JUNCTION BOX 8' X 10' W/COVER, ON SECURE SIDE OF SPACE 6' ABOVE ACCESSIBLE CEILING. DBI Eff] ELECTRIC STRIKE CONCEALED WITHIN DOOR FRAME. CR ES Q F—MD-1 MORON DETECTOR pg "REQUEST TO EXIT PUSHBURON — FLUSH MOUNTED ON NON —SECURE SIDE OF DOOR, MOUNTED PER ADA REQUIREMENTS. FLOOR SINGLE DOOR SECURITY DETAIL NOTES: L CARD READER PROVIDED BY LIBERTY MUNAL'S SECURITY VENDOR. ELECTRIC STRIKE PROVIDED BY DOOR HARDWARE VENDOR. 2. RELATED ELECTRICAL PROVIIDEY COMPLETE OPERATIIONALRDOORNPER ALL FOR AND LOCALE CODE REQUIREMENTS. 3. COORDINATE WITH LIBERTY MUTUAL'S SECURITY VENDOR PRIOR TO ANY ROUGH —IN THE EXACT RO INATE ALL CONDUITS AARm CONTRACTOR VENDOR FFORNF(RE MOUNTING INTERFACE POINTS AS REQUIRED. RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and Local Codes City of Camel �Nn,�31a>na>n�A� SCALE: NONE U::ICJ3 0314 I M1113irb P 11 NONNI 1 1110mmal M a Integrated I Engineering Consultants, Inc. 9700 ROCKSIDE RD. SUITE #290 CLEVELAND, OH 44125 IF): 216.901.6711 IF): 216.901.6712 w .ieo-inc.cc Electrical Power Plan SCALE: 1 2 CONDUCTOR, 116 AWG PLENUM RATED CABLE 1201 1OVA TRANSFORMER #10(G), _/000 CR/1 JUNCTION BOX 1/2" CONDUIT ' 1� 120V INPUT FROM LOCAL \ RECEPTACLE CIRCUIT PUSH BUTTON DOOR BELL (CHIME) DETAIL 40 NOTES: SCALE: NTS 1. PROVIDE EDWARDS SIGNALING CO. DOOR CHIME KIT #C212—W. KIT COMES WITH CHIME, TRANSFORMER, AND PUSH BUTTON. WIRING PER MANUFACTURER WIRING DIAGRAMS. PANEL "CR" 20BY/12OV-4-4W CR/22,24 C20/2 60/2 30/2 CR/14oe2D, 6 \ 0/2 CR/l8,20 ®20/2 HARDWIRE: 2-POLE 60A INPUT BREAKER HARDWIRE TERMINAL BLOCK 3W+G (L-L-N-G) TO CHASSIS. Enlar ed Telecom Room 403 Power Plan 62 9 a• ALE: ELECTRICAL CODED NOTES: Q WIRE INTO EXISTING TOILET ROOM RECEPTACLE CIRCUIT. ® 4' EMT CONDUIT WITH PULLSTRING AND INSULATING BUSHING AT BOTH ENDS. Q PROVIDE A COMPLETE DOORBELL SYSTEM WITH PUSHBUTTON, CHIME, AND TRANSFORMER. EDWARD SIGNALING JC212 SERIES —WHITE. WIRE INTO LOCAL RECEPTACLE CIRCUIT. OA SURFACE RACEWAY: WIREMOLD 4000 SERIES. PROVIDE ALL FTnNGS, CONNECTORS, END CAPS, ETC. FOR A COMPLETE INSTALLATION PER MANUFACTURERS REQUIREMENTS. COFFEE Enlar ed HIVE 414A Power Plan 6�LE: 3 9 aCALE REFRIGERATOR H E L L Y E R LEWIS= ARCHITECTURE INTERIOR DESIGN Project: 10 Liberty Mutual. INSURANCE 450 East 96th St 3rd Floor Indianapolis IN 46240 Drawing: Electrical Power Plan No. E-103 DATE: 10/23/19