HomeMy WebLinkAboutE-9.03PART I - ELECTRICAL GENERAL PROVISIONS 1.1 RELATED DOCUMENTS A THE PROVISIONS OF THE INSTRUCTIONS TO BIDDERS, GENERAL. CONDITIONS SUPPLEMENTARY CONDITIONS ALTERNATES ADDENDAS, AND DMSION 1 ARE A PART OF THIS SPECIFICATION. CONTRACTONS AND SUBCONTRACTORS SHALL EXAMINE SAME AS WELL AS OTHER DMSIONS OF THE SPECIFICATIONS WHICH AFFECT WORK UNDER THIS DMSION. 1.2 SUMM^BY A THIS SECTION INCLUDES GENERAL ADMINISTRATIVE AND PROCEDURAL REQUIREMENTS FOR ELECTRICAL INSTALLATIONS COMMON TO ALL SECTIONS OF DIVISION 16. THE ADMINISTRATIVE AND PROCEDURAL REQUIREMENTS IN THIS SECTION EXPAND AND SUPPLEMENT THE REQUIREMENTS SPECIFIED IN DMSION 1. 1.3 DESCRIPTION OF WORK A AND ALEAOT EH R DIRAWINGSL'AS WELLNIASS L)HE SPECIR ONSPFOR CALL THE DIVISIONS ARECA PART OF THE CONTRACT DOCUMENTS. B. DRAWINGS AND SPECIFICATIONS ARE TO BE CONSIDERED AS SUPPLEMENTING EACH OTHER. WORK SPECIFIED BUT NOT SHOWN OR SHOWN BUT NOT SPECIFIED SHALL BE PERFORMED OR FURNISHED AS THOUGH MENTKSNED IN BOTH SPECIFICATIONS ANQ DRAWINGS. C. VISIT THE SITE OF THE WORK AND BECOME FAMILIAR WITH CONDITIONS AFFECTING THE INSTALLATION. SUBMISSION OF A PROPOSAL SHALL PRESUPPOSE KNOWLEDGE OF SUCH CONDITIONS AND NO ADDITIONAL COMPENSATION SHALL BE ALLOWED WHERE EXTRA LABOR OR MATERIALS ARE REQUIRED BECAUSE OF IGNORANCE OF THEE CONDITIONS. 1.4 WORK INCLUDES A INCLUDE ALL LABOR MATER EQUIPMENT SERVICES AND PERMITS NECESSARY FOR THE PROPER COMPLETIOII OF PAL LECTRICAL WORK SHINN ITEMS OMITTED BUT NECESSARY TO MAKE THE ELECTRICAL SYSTEM COMPLETE AND WORKABLE, SHALL BE UNDERSTOOD TO FORM PART OF THE WORK. B. IT IS THE PURPOSE OF THE ELECTRICAL DRAWINGS TO INDICATE THE APPROXIMATE LOCATION OF ALL EQUIPMENT OUTLETS, ETC. ASCERTAIN EXACT LOCATIONS AND ARRANGE WORK ACCORDINGLY. THIS RIGHT IS REERVED TO EFFECT REASONABLE CHANGES IN THE LOCATION OF OUTLETS UP TO THE TIME OF ROUGHING -IN, WITHOUT ADDITIONAL COST TO THE OWNER. CHANGES IN LOCATION OF OUTLETS OR EQUIPMENT NECESSITATED BY INTERFERENCE WITH THE WORK OF OTHER TRADES SHALL BE MADE ONLY WITH THE CONSENT OF THE ARCHITECT AND ENGINEER OR WNERS REPRESENTATIVE, AND AT NO ADDITIOEN�AL COST. ry�� C. MEANS "HEATINGI VEI{DIATTIINGn,ANC AIR OCCVIONDITICNNG' AND YGSP MEANST PROVIDED NDDEER (OTHER SECTIONS'. FURNISH MEANS R PURCHASE AND DELIVER TO THE PROJF,CT SITE '70 PUUNLOAD AT THE DEIIVEESRYRYPOINT AT NTTHHEE SITE AND PERFORM EVERYY OPERATION NECESSARY FOR PROPER INSTALLATION PER CODE AND MANUFACTURERS REQUIREMENTS TO ESTABUSH SECURE MOUNTING AND CORRECT OPERATION AT THE PROPER LOCATION III THE PROJECT.' D. WORK INCLUDE, BUT IS NOT LIMITED TO: 1. RE -USE OF AND NEW PANELBOARDS AND CIRCUIT BREAKERS 2. FEEDERS AND BRANCH CIRCUIT WIRING 3. HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS DEVICES NEW DEVICES TO THE EXISTING FIRE ALARM SYSTEM CRONS TO MECHANICAL HVAC AND PLUMBING EQUIPMENT S. AND TAGS MAINTENANCE INSTRUCTIONS AND MANUALS E. THE ELECTRICAL DESIGN IS BASED ON THE CURRENT ADOPTED EDITION NEA 70 - THE NATIONAL ELECTRICAL CODE". THE CONTRACTOR SHALL INCLUDE IN THEIR BID TH COST OF INSTALLING MATERIALS AND EQUIPMENT NECESSARY TO SATISFY ALL LOCAL, AND OR STATE CODES. 1.5 WORK OR MATERIALS NOT INCLUDED A THE EXACT WIRING REQUIREMENTS SHALL BE AS RECOMMENDED BY THE MANUFACTURER OF THE EQUIPMENT AND SHALL BE VERIFIED BY THE ELECTRICAL CONTRACTOR WITH THE EQUIPMENT MANUFACTURER BEFORE SUBMITTNG THE BID. B. STARTERS SUPPLIED AS AN INTEGRAL PART OF THE EQUIPMENT SHALL BE FURNISHED UNDER THE DMSION PROVIDING THE EQUIPMENT. POWER WIRING DISCONNECT SHALL BE UNDER DMSION 16. ALL OTHER STARTERS AND AUXILIARY CONTROL EQUIPMENT SHALL BE SUPPLED AND WIRED UNDER DMSION 16, UNLESS OTHERWISE SHOWN. 1.6 RELATED WORK SPECIFIED ELSEWHERE A DMSION 13 - SPECIAL CONSTRUCTION B. DIVISION 15 - MECHANICAL 1.7 CODES. PERMITS. AND FEES A INSTALL WORK IN FULL ACCORDANCE WITH qUL AND REGULATIONS OF STATE, COUNTY AND CITY AUTHORITIES HAVING JURISDICTION IPHJ OVER PREMISE. THIS SHALL INCLUDE SAFETY REQUIREMENTS OF THE STATE OF IND DEPARTMENTS OF COMMERCE AND NATURAL RESOURCES. DO NOT CONSTRUE THIS AS REUEVING CONTRACTOR FROM COMPLIANCE WITH ANY REQUIREMENTS OF SPECIFICATION WHICH ARE IN EXCESS OF CODE REQUIREMENTS AND NOT IN CONFLICT THEREWITH. WORK SHALL BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE PROVISIONS OF THE NATIONAL ELECTRICAL CODE AS INTERPRETED BY THE LOCAL AUTHORITY HAVING JURISDICTION AS WELL AS ANY FURTHER MODIFICATIONS OR REGULATIONS PUBLISHED BY LOCAL OR STATE AUTHORITIES. C. GIVE PROPER AUTHORITIES NOTICE AS REQUIRED BY LAW RELATIVE TO THE WORK IN THEIR CHARGE. COMPLY WITH THE REGULATIONS REGARDING TEMPORARY ENCLOSURE, OBSTRUCTIONS, OR EXCAVATIONS AND PAY ALL LEGAL FEE INVOLVED. D. SECURE AND PAY FOR PERMITS AND CERTIFICATE OF INSPECTIONS INCIDENTAL TO THIS WORK AS REQUIRED BY ALL FOREGOING AUTHORITIES. BE RESPONSIBLE FOR PAYMENTS TO ALL PUBLIC UTIUTIES FOR WORK PERFORMED BY THEM IN CONNECTION WITH PROVISION OF SERVICE CONNECTIONS REQUIRED UNDER THIS DMSION OF SPECIATIONS. TURN OVER CERTIFICATE OF APPROVAL TO THE CONSTRUCTION MANAGER PAID OR OWNER PROMPTLY WHEN RECEIVED, AND BEFORE PAYMENT IS MADE FOR THE ORK. DELIVER ALL CERTIFICATE TO ARCHITECT IN DUPLICATE. E. PROVISIONS OF THE LATEST REVISIONS TO THE FOLLOWING CODE AND STANDARDS SHALL BE FOLLOWED WHERE APPUCABLE: 1. INDIANA ADOPTED STATE BUILDING CODES (IBC) 2. CITY OF INDIANAPOLIS BUILDING CODES 3. NFPA 70 - NATIONAL ELECTRIC CODE (NEC) 4. NFP 101 - LFE SAFETY CODE 5. T EIA - 568 569, AND J-STD- 7 7. FEDERAL OCCUPATIONALLITIS EAFEfYCPN) HF�TH ACT (OSHA) 1.8 COORDINATION WITH OTHER TRADES A CONSULT THE DRAWINGS, PRODUCT DATA AND SHOP DRAWINGS COVERING THE WORK FOR VARIOUS OTHER TRADES, THE FIELD LAYbUTS OF THE CONTRACTORS FOR THE TRADE AND MAKE ADJUSTMENTS ACCORDINGLY IN LAYING OUT THE ELECTRICAL WORK. B. KEEN FULLY INFORMED OF THE PROGRESS OF THE GENERAL CONSTRUCTION. INSTALL WORK THAT IS TO BE CONCEALED WITHIN THE BUILDING CONSTRUCTION IN SUFFICIENT TIME TO SECURE PROPER LOCATION WITHOUT DELAY TO THE WORK OF OTHER TRADE. ALL CONDUIT AND OUTLET BOXES CONCEALED IN MASONRY CONSTRUCTION SHALL BE INSTALLED DURING WALL CONSTRUCTION. ATTEND TO ELECTRICAL WORK DURING THE PROGRESS OF BUILDING -IN TO PREVENT MISALIGNMENTS AND DAMAGES TO THE ELECTRICAL WORK. C. EXAMINE THE WORK OF OTHER TRADE WHEN IT COMES IN CONTACT WITH OR IS COVERED DEFECTIVE IWORKIS OR SIINSTALLOWORK AIN AH MANNORVEWHICEI WILLFINPREVENNTT NPROP R INSTALLATION OF tHE WORK OF OTHER TRADES. D. PPANELING�WALLSCOVERINGSANTTRIM E EQUIPMLEENT Ef�CL AND SHHAALLLL LINEWUP NTTHNTEITHER BOTTOM QR TOP OF MASONRY COURSES. CHANGE t0 THE SPECIFIED MOUNTING HEIGHTS OF ANY DEVICE SHALL BE APPROVED BY THE WNER'S REPRESENTATIVE BEFORE ROUGH -IN. E. TAKE ALL FIELD MEASUREMENTS NECESSARY AND ASSUME RESPONSIBIUTY FOR THEIR ACCURACY. F. BEFORE BEGINNING CONSTRUCTION OF THE PROJECT THE CONTRACTOR SHALL PROVIDE TO THE MECHANICAL CONTRACTOR, MARKED -UP PRINTS INDICATING ALL ELECTRICAL ITEMS PIPING AND DUCTWORK. THESE SHALLLLTIINOLUDENTIBUTINNQT BE LIMITED TO PULL UBO%ES, CONDUIT, ETC. 1.9 EQUIPMENT AND MATERIALS A All EQUIPMENT DEVICE AND MATERIALS USED ON THIS PROJECT SHALL BE NEW AND U.L. LISTED AND LAI)ELED FOR THE APPUCATION. B. PROVIDE MATERIAL AND LABOR WHICH IS NEITHER DRAWN NOR SPECIFIED BUT WHICH IS OBVIOUSLY A COMPONENT PART OF AND NECESSARY TO COMPLETE WORT( AND WHICH IS CUSTOMARILY A PART OF WORK OF SIMILAR CHARACTER. C. EQUIPMENT AND MATERIALS FOR THE CONSTRUCTION SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE PROTECTED BY SAME UNTIL FORMA LY ACCEPTED BY THE OWNER. D. ALL MANUFACTURERS OF ELECTRICAL EQUIPMENT SHALL VERIFY TO THE SATISFACTION OF THE CONTRACTOR AND ENGINEER MAT THEIR EQUIPMENT WILL FUNCTION PROPERLY UNDER THE CONDITIONS OF USE, AS SHOWN ON THE DRAWINGS AND AS SPECIFIED HEREIN. DIMENSIONS, WEIGHTS, OPERATING CHARACTERISTICS AND ALL OTHER RELATED APPURTENANCE SHALL BE VERIFIED BEFORE SUBMITTAL OF SHOP DRAWINGS. 1.10 MATERIAL SUBSTITUTIONS A BIDS SHALL BE BASED UPON THE SPECIFIED PRODUCTS OR LISTED ALTERNATIVES. DRAWINGS AND SPECIFICATIONS ARE BASED ON THE PRODUCTS SPECIFIED BY TYPE MODEL AND SIZE AND THUS ESTABLISH MINIMUM QUAUTIES, WHICH SUBSTITUTES MUST MEET TO QUALIFY FOR REVIEW. B. SHOULD THE CONTRACTOR PROPOSE TO FURNISH MATERIALS EQUIPMENT AND DEVICE OTHER THAN THOSE SPECIFIED AND USTED THE CONTRACTOR SMALL SUBMIT A WRITTEN REQUEST FOR SUBSTITUTIONS, TO THE EGINtER AT LEAST TEN f101 BUSINESS DAYS PRIOR TO BID OPENING. THE REQUEST SFLALL BE PN ALTERNATE TO THE ORIGINAL BID AND gSg�H�ALL INCLUDE AND BE ACCOMPANIED WITH COMPLETE SPECIFICATIONS CUT SHEET (MANUFACCTURER BRRAANND NAMETHCATALOGG NUMBER, ETC)ON AND TECHNICALITDATAESFORPANLLL RITEEMS. INDICATE ANY ADDITIbNS OR DEDUCTIONS TO THE CONTRACT PRICE WITH THE SUBSTITUTION SUBMITTAL AND ON THE BID FORM. C. ACCEPTANCE OR REJECTION OF THE PROPOSED SUBSTITILDONS SHALL BE SUBJECT TO APPROVAL OF THE ARCHITECT AND ENGINEER. IF REQUESTED THE CONTRACTOR SHALL SUBMIT INSPECTION SAMPLES OF BOTH THE SPECIFIED AND THE PROPOSED SUBSTITUTE ITEMS. D. IF ANY SUBSTITUTIONS ARE APPROVED AN ADDENDUM LISTING THE APPROVED REM S WILL () BE ISSUED TO PLL BIDDING CONTRACTORS PRIOR TO THE BID DATE. E. IN ALL CASES WHERE SUBSTITUTIONS ARE PERMITTED THE CONTRACTOR SHALL BEAR ANY EXTRA COST OF EVALUATING THE EQUALITY OF THE MATERIAL AND EQUIPMENT TO BE INSTALLED. E WHERE ONLY ONE MAKE IS NAMED IN THE SPECIFICATIONS OR ON THE DRAWINGS, IT SHALL BE PROVIDED. G. VERBAL REQUESTS OR APPROVALS SHALL NOT BE BINDING ON THE ENGINEER OR OWNER. 1.11 QUALLLITEY ASSURANCE A fUL1�EISTi m (AND OLABELLEEb ASI DEEINEDDIN NFPAS 70, AR¶CLEER100I, BY ABTESSTIING EAGENGY AACCCCEPTABLE TO ALTIHORITIES RAVING JURISDICTION, AND MARKED FOR INTENDED USE. RELEASED FOR CONSTRUCTION Subject to compliance w]th all regulations of State and Local Codes e City of Camel (T gvm`�1a u'kw,Q- 1.12 SUBMITTALS A SHOP DRAWINGS AND PRODUCT DATA 1. PREPARE SHOP DRAWINGS AND PRODUCT DATA FOR ELECTRICAL EQUIPMENT WITH ADEQUATE DETAILS AND SCALE AS NECESSARY TO CLEARLY SHOW CONSTRUCTION. INDICATE OPERATING CHARACTERISTICS FOR EACH REQUIRED ITEM AND DESIGN CONDITIONS FOR EACH. CLEARLY IDENTIFY EACH REM ON THE DRAWINGS AS TO MARK, LOCATION, AND USE. 2. THIS CONTRACTOR SHALL REVIEW STAMP WITH APPROVAL AND SUBMIT WITH REASONABLE PROMPTNESS AND IN ORDERLY SEQUENCE SO AS TO CAUSE NO DELAY IN WORK OR IN THE WORK OF ANY OTHER CONTRACTOR ALL SHOP DRAWINGS AND SAMPLE REQUIRED BY THE CONTRACT DOCUMENTS. SHOD DRAWINGS NOT STAMPED WITH CONTRACTOR APPROVAL WILL BE RETURNED FOR REPROCESSING. THE SUBMITTALS WILL BE REVIEWED ONLY FOR GENERAL COMPUANCE AND NOT FOR DIMENSIONS, QUANTITIES, ETC. 3. IF THE SUBMITTAL SHOWS VARIATIONS EOM THE REQUIREMENTS OF THE CONTRACT DOCUMENTS FOR ANY REASON, THE CONTRACTOR SHALL MAKE MENTION OF SUCH VARIATION IN A LETTER OF TRANSMITTAL. THE CONTRACTOR SHALL NOTE IN RED ON THE SUBMITTAL ANY CHANGE IN DESIGN OR DIMENSION ON THE ITEMS SUBMITTED INCLUDING CHANGES MADE BY THE MANUFACTURER WHICH MAY DIFFER EOM CATALOG INFORMATION. 4. CONTRACTOR FURTHER AGREES THAT IF DEVIATIONS DISCREPANCIES, OR CONFLICTS BETWEEN SHOP DRAWING SUBMITTALS AND THE CONTRACT DOCUMENTS IN THE FORM OF DESIGN DRAWING AND SPECIFICATIONS ARE DISCOVERED EITHER PRIOR TO OR AFTER SHOP DRAWING SUBMITTALS ARE PROCESSED BY THE ENGINEER, THE DEIGN DRAWINGS, AND SPECIFICATIONS SHALL CONTROL AND SHALL BE FOLLOWED. 5. THE SUBMITTALS THAT ARE RETURNED SHALL BE USED FOR PROCUREMENT. THE RESPONSIBIUTY OF CORRECT PROCUREMENT REMAINS SOLELY WITH THE CONTRACTOR. THE SUBMITTAL REVIEW SHALL NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR ERRORS OR OMISSIONS AND DEVIATIONS FROM THE CONTRACT REQUIREMENTS. 6. IN CHECKING SHOP DRAWINGS THE ARCHITECT AND ENGINEER WILL MAKE EVERY EFFORT TO DETECT AND CORRECT ERRORS OMISSIONS6 AND INACCURACIES IN SUCH DRAWINGS. HOWEVER, FAILURE TO DETECT ERRORS, OMISSIONS AND INACCURACIES SHALL NOT REEVE THE CONTRACTOR OF REPONSIBIUTY FOR THE PROPER AND COMPLETE INSTALLATION IN ACCORDANCE WITH THE INTENT OF THE CONTRACT DOCUMENTS. 7. CONTRACTOR AGREE THAT SHOP DRAWING SUBMITTALS PROCESSED BY THE ENGINEER ARE NOT CHANGE ORDERS THAT THE PURPOSE OF SHOP DRAWING SUBMITTALS BY THE CONTRACTOR IS TO DEMONSTRATE TO THE ENGINEER THAT THE CONTRACTOR UNDERSTANDS THE DEIGN THAT THEY DEMONSTRATE THEIR UNDERSTANDING BY INDICATING WHICH EQUIPMENT AND MATERIAL THEY INTEND TO FURNISH AND INSTALL, AND BY DETAILING THE FABRICATION AND INSTALLATION METHODS THEY INTEND TO USE. 8. SHOP DRAWINGS SHALL CLEARLY INDICATE ALL DIMENSIONAL DATA FOR ALL PARTS OF THE ITEM, TYPES AND MATERIALS FOR ALL CONNECTIONS FlNISHE THE EXACT RELATION OF THE ITEM TO ADJACENT MATERIALS AND EQUIPMENT IN THE COMPLETE STRUCTURE INCLUDING CLEARANCE ANY NECESSARY ISOLATION AND FASTENING METHODS AND DEVICE AND MECHANICAL ANb ELECTRICAL CONNECTIONS. 9. SUBMIT NEWLY PREPARED INFORMATION DRAWN TO ACCURATE SCALE. HIGHUGHT ENCIRCLE OR OTHERWISE INDICATE DEVIATIONS EOM THE CONTRACT DOCUMENTS. Dd NOT REPRODUCE CONTRACT DOCUMENTS OR COPY STANDARD INFORMATION AS THE BASIS OF SHOP DRAWINGS. STANDARD INFORMATION PREPARED WITHOUT SPECIFIC REFERENCE TO THE PROJECT IS NOT CONSIDERED SHOP DRAWINGS AND WILL BE CAUSE FOR REJECTION. 10.SHOP DRAWINGS AND PRODUCT DATA SHALL BE SUBMITTED AS FOLLOWS: a. CONFORM TO SUBMITTAL REQUIREMENTS OUTLINED IN DMSION 1 OF THEE SPECIFICATIONS. b. WHERE CONTENTS OF SUBMITTAL LITERATURE INCLUDE DATA NOT PERTINENT TO THE SUBMITTAL, CLEARLY INDICATE WHICH PORTION OF CONTENT IS BEING SUBMITTED FOR REVIEW. 11.SHOP DRAWINGS SHALL INCLUDE FABRICATION AND INSTALLATION DRAWINGS, SETTING DIAGRAMS, SCHEDULES PATTERNS TEMPLATES AND SIMILAR DRAWINGS. ALSO, INCLUDE THE FOLLOWING INFORMATION: o. DIMENSIONS. b. IDENTIFICATION OF PRODUCTS AND MATERIALS INCLUDED. c. COMPLIANCE WITH SPECIFIED STANDARDS. d. NOTATION OF COORDINATION REQUIREMENTS. e. NOTATION OF DIMENSIONS ESTABUSHED BY FIELD MEASUREMENT. 12.WHERE ADDITIONAL INSTALLATION DRAWINGS WIRING DIAGRAMS OR OTHER DRAWINGS ARE SPECIFIED AS A PART OF THE SUBMITTAL THEY SHALL BE SUBMITTED AT THE SAME TIME WITH SHOP DRAWINGS AND PRODUCT DADA. PARTIAL SUBMITTALS ARE NOT ACCEPTABLE. 13.SHOP DRAWINGS SHALL BE SUBMITTED FOR ALL MATERIAL ITEMS AS OUTLINED IN THESE SPECIFICATIONS. ANY DEVIATIONS FROM CONTRACT REQUIREMENTS MUST BE CLEARLY INDICATED ON SHOP DRAWINGS AND JUSTIFICATION FOR THEIR CONSIDERATION MUST BE INCLUDED. 14.APPROVAL OF SUBMITTAL ITEMS SHALL NOT PRECLUDE REJECTION OF THOSE ITEMS UPON DISCOVERY OF DEFECTS IN THEM PRIOR TO FINAL ACCEPTANCE OF COMPLETE WORK. 15. LUMINAIRES° WIRING DEVICCEES, ETC.),TMEQUIPMENTEQITEMSENSHALLLE BEEQOF ETHE(IESAME MANUFACTURER. 16.SUBMIT A MINIMUM OF SIX (6) COPIES OF SHOP DRAWIN S TO THE ARCHITECT. THE ARCHITECT AND ENGINEEAR SHALL EACH RETAIN ONE G(1) COPY AND RETURN THE REMAINDER TO THE CONTRACTOR WHO SHALL DISTRIBUTE COPIES AS REQUIRED TO PROPERLY CONDUCT THE WORK, INCLUDING REQUIREMENTS OF THE OPERATING MANUAL 17.SHOP DRAWINGS AND PRODUCT DATA INCLUDES: a. WIRING DEVICES b. UGHTING CONTROL DEVICES c. LUMINAIRES, LAMPS AND BALLASTS d. FIRE ALARM DEVICES AND SYSTEM MODIFICATION DRAWINGS DESIGNED AND STAMPED BY A STATE CERTIFIED FIRE ALARM SYSTEM DESIGNER, INCLUDING BUT NOT UNITED TO THE FOLLOWING: i. BATTERY CALCULATIONS ii. FLOOR PUNS INDICATING LOCATION OF ALL FIRE ALARM DEVICES. iii. VOLTAGE DROP CALCULATIONS FOR ALL WIRING AND WIRE TYPE. iv. MANUFACTURE MODEL NUMBER AND LISTING INFORMATION FOR ALL DEVICES AND WIRING BEING PROVIDED. v. LOCATION OF ALL REQUIRED SYNCHRONIZATION UNITS IF REQUIRED. vi. PWER EXTENDER PANELS, ADDRESSABLE MODULES, ETC. B. DESIGN DRAWINGS 1 SHOWDESIIXADTDRAWOCATION OFUBEQUIPMENTF CONDUTS� ETCEUNLESS NDMENNSONSEARE INSSTTALLEDDALONG STHEE GENERAL OPLANS SSHOWN ON QTHE DRAWNGSDUBUT KEEPI G BIN MIND ACTUAL BUILDING CONDITIONS WHICH MUST BE CONFIRMED WITHIN THE ACTUAL WORK. 2. IF THIS CONTRACTOR PROPOSES TO INSTALL EQUIPMENT REQUIRING SPACE CONDITIONS OTHER THAN THOSE AS SPECIFIED AND/OR SHOWN ON THE DESIGN DRAWINGS OR TO REARRANGE THE EQUIPMENT HE SHALL ASSUME FULL RESPONSIBILITY POR THE REARRANGEMENT OF THE SPACE AND SHALL OBTAIN THE FULL APPROVAL OF THE ARCHITECT BEFORE PROCEEDING WITH THE WORK. C. COORDINATION DRAWINGS 1. BEFORE BEGINNING CONSTRUCTION OF THE PROJECT THE CONTRACTOR SHALL PROVIDE TO THE MECHANICAL CONTRACTOR MARKED UP PRINTS INDICATING ALL ELECTRICAL WORK WHICH AFFECTS LOCATION OF HEATING, VENTILATING, AIR CONDITIONING, PLUMBING PIPING FIRE PROTECTION, AND DUCTWORK. REFER TO DMSION 1 AND DMSION 15 FOR RELATED WORK. 2 COORDINATING PENEETRATIONS AND CEIUNG MOIUNTEO ITEMS. SHOWN THE FOLLOWING: AIJD a. CEILING SUSPENSION ASSEMBLY MEMBERS. b. METHOD OF ATTACHING HANGERS TO BUILDING STRUCTURE. 0. DEVICES, MCOCUTVESPE KERS,NACCESS PAINELSTI, ETC%TURES, EXIT SIGNAGE, ARE ALARM D. RECORD DRAWINGS 1. UCH CONTRACTOR OR SUBCONTRACTOR FOR ELECTRICAL WORK SHALL KEEP ONE COMPLETE SET OF THE CONTRACT WORKING DRAWINGS ON THE PROJECT SITE ON WHICH THEY SHALL RECORD ANY DEVIATIONS OR CHANGES EOM SUCH CONTRACT DRAWINGS MADE DURING CONSTRUCTION. THESE CHANGES SHALL BE ACCURATELY RECORDED IN RED INK ON THE PRINTS. RECORD DRAWINGS SHALL SHOW CHANGES IN: b. LOCATION EQF ANY DENICECOR PIECE CF EQUIPMH�NT. ' OR PIECE OF EQUIPMENT. c. LOCATION OF ANY OUTLET OR DEVICE AND ASSOCIATED WIRING. d. ROUTING OF EEDER CONDUITS. e. BRANCH CIRCUIT NUMBER ASSIGNMENTS. 2. RECORD DRAWINGS SHALL BE KEPT CLEAN AND UNDAMAGED, AND SHALL NOT BE USED FOR ANY PURPOSE OTHER THAN RECORDING DEVIATIONS FROM WORKING DRAWINGS. 3. TO ETHE TENANT ANDI BUILLDINGGMMAANAGEMEINTT SIGN GOOD ECONDITION,AASL AE PERMANENNTT RECORD OF THE INSTAWTION AS CONSTRUCTED. ALL COSTS FOR PRODUCTION PRINTING, ETC. SHALL BE BORNE BY THE CONTRACTOR AND SHALL BE INCLUDED IN THE BID. 4. REFER TO DIVISION 1 SPECIACATIONS FOR ADDITIONAL REQUIREMENTS RELATED TO RECORD DRAWINGS. 5 WHIICH WERTEA THEN INSTALLATION OF THE WORK..GETH SE CHANGESS SHALLL HE ECCORRDED IN RED INK ON THE PRINTS. CHANGES SHALL BE ACCURATELY DIMENSIONED. 6. THIS CONTRACTOR SHALL KEEP AN UPDATED SET OF PRINT INCLUDING CHANGES, ON THE JOB SITE AT ALL TIMES AND SHALL SUBMT ONE I) SET OF UPDATED AND LEGIBLE 'AS -BUILT' PRINTS TO THE ARCHITECT WHEN THE ORK IS COMPLETE. 7. PREPARE RECORD DOCUMENTS IN ACCORDANCE WITH THE REQUIREMENTS IN DIVISION 1 SECTION 'PROJECT CLOSEOUT: 8 INSTALLED COG ONSR(ACCURATELY DIMENSIIONED): OMSION 1, INDICATE THE FOLLOWING a. CONCEALED EQUIPMENT, UNITS, DEVICES, ETC., REQUIRING PERIODIC MAINTENANCE OR REPAIR. 9. APPROVED SUBSTITUTIONS CONTRACT MOOIACATONS AND ACTUAL EQUIPMENT AND MATERIALS INSTALL] EQUIPMENT LOCATIONS (EXPOSED AND CONCEALLD , DIMENSIONED FROM PROMINENT BUILDING LINES. 1.13 OPERATING/MAINTENANCE MANUALS A. PREPARE FOUR (41 COMPLETE BOUND SETS OF OPERATING/MAINTENANCE MANUALS IN ACCORDANCE WITH DIVISION 1 SECTION 'PROJECT CLOSEOUT. CONTAINING OPERATING AND MAINTENANCE INSTRUCTIONS, AND MANUFACTURER START-UP REPORTS FOR ALL ELECTRICAL EQUIPMENT AND CONTROLS. B. SERVICE MANUALS SHALL BE ASSEMBLED INTO ONE VINYL COVERED THREE RING 'O TYPE BINDER WITH HARD COVER AND WITH WRITTEN INSTRUCTIONS FOR UCH SYSTEM LISTED IN THE SPECIFICATIONS. C. WRITTEN OPERATING INSTRUCTIONS SUBMIT DRAWINGS, WIRING DIAGRAMS EQUIPMENT CATALOG pgJA SHEETS AND MANUFACTURERS INSTRUCTIONS SHALL BE ACCOMMODATED INTO 8-1 /2" % 11 AND/OR 11 % 17 SIZE. UCH SECTION SHALL BE TABULATED AND INDEXED AS FOLLOWS: 1. FIRST PAGE --- TITLE OF PROJECT OWNER ADDRESS, DATE OF SUBMITTAL, NAME OF CONTRACTOR, AND NAME OF ARCHITECT AND ENGINEER. 2. SECOND PAGE --- INDEX 3. FIRST SECTION - - WRITTEN DESCRIPTION OF SYSTEM CONTENTS WHERE ACTUALLY LOCATED IN BUILDING, HOW EACH PART FUNCTIONS INDIVIDUALLY AND HOW SYSTEM WORKS AS A WHOLE. CONCLUDE WITH A LIST OF ITEMS REQUI,jINd SERVICE AND EITHER STATE THE SERVICE NEEDED OR REFER TO THE MANUFACTURERS DATA IN THE BINDER TINT DESCRIBES THE PROPER SERVICE. 4. SECOND SECTION --- A COPY OF EACH SUBMITTAL DRAWING WITH AN INDEX AT THE BEGINNING OF THE SECTION. 5. THIRD SECTION --- A COPY OF EACH MANUFACTURER'S OPERATING INSTRUCTIONS WI1,H AN INDEX AT THE BEGIN ING OF THE SE TIOR AND A COPY OF EACH MANUFACTURES START UP REPORT FOR FIRE ALARM, ETC. 6. FOURTH SECTION --- A COPY OF ALL TEST RESULTS, IN CHART FORM, PERFORMED BY THE CONTRACTOR $7. FIFTH SECTION --- COPIES OF ALL WARRANTIES, APPROVALS, ETC. D. (3)BCOPIESETOIDHEO ARCHITEOT OR DEELLIIVERYRTO TTHHEV WNER E APPROVAL, SUBMIT THREE 1.14PRODUCT DELIVERY. STORAGE. AND HANDUNG A. DELIVER PRODUCTS TO THE PROJECT PROPERLY IDENTIFIED WTH NAMES, MODEL NUMBERS, TYPE COMPLIANCE LABELS AND SIMIA INFORMATION NEEDED FOR IDENTIFICATION. MATERIALS MUST BE ADEQUATELY PACKAGED OR PROTECTED TO PREVENT DETERIORATION DURING SHIPMENT, STORAGE AND HANDLING. B. THE CONTRACTOR SHALL MAKE PROVISIONS FOR THE DEWERY AND SAFE STORAGE OF HIS MATERIALS AND EQUIPMENT IN COORDINATION WITH THE WORK OF OTHERS. MATERIALS AND EQUIPMENT SHALL BE DELIVERED AT SUCH STAGE OF THE WORK AS WILL EXPEDITE THE WORK AS A WHOLE AND SHALL BE MARKED AND STORED IN SUCH A WAY AS TO BE EASILY CHECKED AND INSPECTED. THE ARRIVAL AND PLACING OF LARGE EQUIPMENT ITEMS RESTRICTIONCOR PROBLEEM DUEETO SIZETANDEWEIGHT. AND SETTING WHEN THEE IS NO C. MAATEERIALSSHODULD NOTSBERSTORED DIRECTLY ONMTHEOGROUND ORRRFLOR AND SHALL BE KEPT AS CLEAN AND DRY AS POSSIBLE AND FREE EOM DAMAGE OR DETERIORATING ELEMENTS. D. IN GENERAL, DO NOT DELIVER ITEMS OF ELECTRICAL EQUIPMENT TO THE PROJECT SUBSTANTIALLY BEFORE THE TIME OF INSTAWTION. UNIT EACH SHIPMENT OF BULK AND MULTIPLE -USE MATERIALS TO THE QUANTITIES NEEDED FOR INSTALLATION WITHIN 3-WEEKS OF RECEIPT. 1.15 PROTECTION OF WORK AND PROPERTY A. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SAFEGUARDING WORK PROPERTY AND FACILITIES AGAINST DAMAGE BOTH HIS OWN AS WELL AS OTHERS, WITH WHICH HE MAY COME INTO CONTACT IN THE PERFORMANCE OF HIS WORK. B. DUCT OPNINGSS SHASIL BEBCLOSED WIITTHH CAPSSOR PLUGS DURING INSTALIATION.E ALIT FIXTUURES AND EQUIPMENT SHALL BE COVERED AND PROTECTED AGANST DAMAGE. ANY MATERIALS OR EQUIPMENT DAMAGED AT ANY STAGE IN THE CONSTRUCTION SHALL BE REPLACED Oft REPAIRED AND AT THE FINAL COMPLETION, ALL WORK SHALL BE IN A CLEAN, UNBLEMISHED CONDITION. C. FURNISH INFORMATION TO GENERAL CONTRACTOR AS TO SIZE AND LOCATION OF ALL BUILT-IN OPENINGS REQUIRED. DO NOT CUT REMOVE OR PIERCE: GENERAL Oft MECHANICAL INSULATION' FIRE RATED WALLS OR CEILINGS; OR STEEL WORK; WITHOUT PRIOR PERMISSION AND INSTRUCTION. 1.16 CUTTING AND PATCHING A GENERAL ALL CUTTING AND PATCHING FOR THE INSTALLATION OF THIS BRANCH OF THE WORK SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR. B. PERFORM CUTTING AND PATCHING IN ACCORDANCE WITH DIVISION 1 SECTION "PROCEDURES SEPARATE PRIME" IN ADDITION TO THE REQUIREMENTS SPECIFIED IN DMSION 1, PERFORM CUTTNG, FITTING AND PATCHING OF MECHANICAL EQUIPMENT AND MATERIALS REQUIRED TO: 1. INSTALL NEW WORK. 2. UNCOVER WORK TO PROVIDE FOR INSTALLATION OF ILL-TIMED WORK. 3. REMOVE AND REPLACE DEFECTIVE WORK. 4. REMOVE AND REPLACE WORK NOT CONFORMING TO REQUIREMENTS OF THE CONTRACT DOCUMENTS. 5. INSTALL EQUIPMENT AND MATERIALS IN EXISTING STRUCTURE. 6. UPON WRITTEN INSTRUCTIONS FROM THE ENGINEER UNCOVER AND RESTORE WORK TO PROVIDE FOR ENGINEER OBSERVATION OF CONCEALEC WORK. 7. CUT, REMOVE AND LEGALLY DISPOSE OF SELECTED ELECTRICAL EQUIPMENT, COMPONENTS AND MATERIALS AS INDICATED, INCLUDING BUT NOT LIMITED TO REMOVAL OF CONDUITS AND CONDUCTORS, JUNCTION BOXES LUMINAIRES AND TRIM, AND OTHER ELECTRICAL ITEMS MADE OBSOLETE BY THE NEW WORK. C PROTECTION OF INSTALLED WORK: DURING CUTTING AND PATCHING OPERATIONS, PROTECT ADJACENT INSTALLATIONS. D. PROVIDE AND MAINTAIN TEMPORARY PARTITIONS OR DUST BARRIERS ADEQUATE TO PREVENT THE SPREAD OF DUST AND DIRT TO ADJACENT AREAS. E. ALL OPENINGS REQUIRED FOR THIS BRANCH OF WORK SHALL BE ACCOMPLISHED IN TIME TO BE INCORPORATED IN, AND BE COMPATIBLE WITH THE CONSTRUCTION PROGRAM, OTHERWISE THIS CONTRACTOR SHALL BE RESPONSIBLE AND PAY FOR ALL CHANGES MADE NECESSARY FOR HIS FAILURE TO DO SO. PIPE HOLES IN FLOORS AND WALLS SHALL BE CORE DRILLED. F. PATCH EXISTING FINISHED SURFACE AND BUILDING COMPONENTS USING NEW MATERIAL`j MATCHING EXISTING MATERIALS AND EXPERIENCED INSTALLERS. FOR INSTALLERS QUALIFICATIONS REFER TO THE MATERIALS AND METHODS REQUIRED FOR THE SURFACE AND BUILDING COMPONENTS BEING PATCHED. 1.17 FIRE STOPPING A ANY CORE DRILLNG OR CUTTING OF FIRE RATED FLOORS, SHAFTS AND WALE SHALL BE FIRE STOPPED PRIOR TO FINISH PATCHING. ALL FIRE STOPPING MATERIALS SHALL BE U.L. CLASSIFIED , INTUMESCING COMPOUND DEVICE OR SHEET RATED TO FUNCTION FOR THIS PURPOSE. ACCORDING TO INSTRUCTIONS PROVIDED ALL PENETRATIONS IN 1-HOUR 2-HOUR AND 3-HOUR FIRE RATED WALLS FLOORS CR PARTITION ASSEMBLE SHALL BE SEALED WITH 3M BRAND FIRE BARRIER CAULK CP-25 OR COMPOSITE SHEET CS-195, OR EOUIVALENT. ALL PENETRATIONS SHALL BE SEALED IN ACCORDANCE WITH UL FIRE RESISTANCE VOLUME II. 1. CAUL( P-25 FILL MATERIAL TO COMPLETELY FILL THE ANNULAR SPACE BETWEEN THE INDIVIDUAL CONDUIT AND GYPSUM WALLBOARD WITH A MINIMUM DIAMETER BEAD OF CAUL( APPLIED TO THE PERIMETER OF CONDUIT LUL SYSTEM WL7 01). 2. MULTIPLE CONDUITS SHALL BE CONTAINED WITHIN A 28 GAUGE STEEL SLEEVE. CAULK CP-25 FlLL MATERIAL TO A DEPTH OF 1" COMPLETELY AROUND THE STEEL SLEEVE. A NOMINAL }5" DIAMETER BEAD SHALL BE APPLIED ON BOTH SIDES OF WALL ASSEMBLE. A MINIMUM 1" THICKNESS OF MINERAL WOOL BATT INSULATION SHALL BE PACKED FIRMLY INTO THE STEEL SLEEVE ON BOTH SIDES 9F WALL ASSEMBLY AS A PERMANENT FORM. PACKING MATERIAL SHALL BE RECESSED 5 8" EOM SURFACE OF WALL ON BOTH SIDES OF WAFL ASSEMBLY. ALL RECESSED CA TY WTH 1" OF CP-25 CAULK (UL SYSTEMS WIL 16. 3. A MINIMUM 1" THICKNESS OF MINERAL WOOL BATT INSULATION SHALL BE PACKED FIRMLY INTO THE MAXIMUM 2" ANNULAR SPACE AS A PER ENT FORM. A MINIMUM OF 1" OF CP-25 CAUL( SHALL FILL TH ECESSED CANtt µ(AFHOR WALLS, THIS SHALL BE APPLIED ON BOTH SIDES OF THE WALL pI SYSTEM CA11i144 . 4. COORDINATE WITH THE ARCHITECT FOR ALL EXACT MATERIAL AND RATINGS AND EXACT BEAU REM OR ARE STOPPING MATERIALS AND INSTALLATIONS PER ALL NFPA AND UL 1.18 INTERFERENCES A. BEFORE INSTAWNG ANY WORK THIS CONTRACTOR SHALL SEE THAT IT DOES NOT INTERFERE WITH CLEARANCE REQUIRED FOR LIGHTS, CONDUIT AND COUNGS AND FOR FINISH ON BEAMS, COLUMNS, PILASTERS WALLS OR OTHER STRUCTURAL OR ARCHITECTURAL MEMBERS AS SHOWN ON CONTRACT bRAWINGS. IF ANY WORK IS SO INSTALLED AND IT LITER DEVELOPS THAT ORIGINAL DESIGN CANNOT BE FOLLOWED, THIS CONTRACTOR SHALL, AT HIS WN EXPENSE MAKE SUCH CHANGES IN HIS WORK AS ARCHITECT MAY DIRECT TO PERMIT COMPLETION 5V WORK IN ACCORDANCE WITH PLANS AND SPECIFICATIONS. B. INSTALL ADDITONAL OFFSETS ON PIPING OR DUCTWORK WHERE REQUIRED TO OBTAIN MAXIMUM HEADROOM OR TO AVOID CONFLICT WITH OTHER WORK WTHDIT ADDITIONAL COST TO OWNER. 1.19 INTERRUPTION OF SERVICE A. WHEN WORK PROGRESS MAKES TEMPORARY SHUTDOWN OF SERVICES UNAVOIDABLE SHUTDOWN SHALL BE COORDINATED WITH AND APPROVED BY WNER SO AS TO CAUSE MINIMUM DISRUPTION TO ESTABLISHED OPERATING ROUTINE. ARRANGE TO WORK AS NECESSARY TO RE-ESTABUSH SERVICE WITHIN SHORTEST POSSIBLE DOWNTIME. IN THOSE INSTANCES WHERE THE LENGTH OF TIME REQUIRED FOR THE SERVICE INTERRUPTION IS NOT ACCEPTABLE TO THE OWNER, UNLESS OTHERWISE INDICATED FURNISH AND INSTALL TEMPORARY CONNECTIONS AS REQUIRED TO REDUCE THE LEdTH OF TIME OF SERVICE INTERRUPTION TO AN ACCEPTABLE LEVEL. B. REPORT ANY INTERFERENCE BETWEEN WORK UNDER THIS DMSION AND THAT OF ANY OTHER CONTRACTORS TO ARCHITECT AS SOON AS THEY ARE DISCOVERED. ARCHITECT WILL DETERMINE WHICH EQUIPMENT SHALL BE RELOCATED, REGARDLESS OF WHICH WAS FIRST INSTALLED, AND HIS DECISION SHALL BE FINAL 1.20 WORKMANSHIP A. WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE BEST PRACTICE OF THE TRADE AND IN A WORK LIKE MANNER AND SHALL NUT AND RECTILINEAR TO FlNISHE. B. ELECTRICAL WORK SHALL BE INSTALLED BY JOURNEYMEN ELECTRICIANS UNDER THE SUPERVISION OF A COMPETENT FOREMAN. 1.21 DEMONSTRATION OF COMPLETE ELECTRICAL SYSTEM A. BEFORE FINAL PAYMENT DEMONSTRATE TO THE OWNER'S SATISFACTION THE PROPER OPERATION OF EACH OF tHE SYSTEMS COMPRISING THIS CONTRACT. B. INSTRUCT THE OWNER'S MAINTENANCE PERSONNEL IN THE OPERATION AND MAINTENANCE OF ALL ELECTRICAL EQUIPMENT AND CONTROLS. C. DELIVER TO THE OWNER ALL SPECIAL TOOLS AND APPURTENANCES FOR PROPER OPERATION AND MAINTENANCE OF MF, E UIPMENT PROVIDED AND REQUEST RECEIPT FOR SAME. ATTACH TO THE CONTRACTORS REUUEST FOR FINAL PAYMENT. L22 CLEANING AND FINISHING A. GENERAL: FOLLOW THE REQUIREMENTS SPECIFIED IN DIVISION 1 SECTION "PROJECT CLOSEOUT." B. IN SO FAR AS THIS DMSION IS CONCERNED AT ALL TIME KEEP PREMISES AND BUILDING IN A NUT AND ORDERLY CONDITION FOLLOW EXPUCITLY ANY INSTRUCTIONS OF ARCHITECT AND OWNER IN REGARD TO STORING OF MATERIALS, PROTECTIVE MEASURE, CLEANING -UP OF DEBRIS, ETC. C LEAVING OEVERRYYIHHING FINW WOKRKNGS ORDE�"AT THEN OCOCMPLLETTION GOFYTNI�OMPMPLETEED THEIR WORK. CLEAN LUMINAIRES, OUTLET BOX PLATES PANEL AND CABINET INTERIORS AND EXTERIORS, ETC., OF DIRT, DUST, DEBRIS, PAINT, ETC. 1.23 GUARANTEE AND WARRANTIES A. ENGINEERINGPRACTICEMAND THHAE LLL EQUIPMENT WILL AMEET REQUIREMENO SPECIFImGANYY EQUIPMENT FAILING TO PERFORM OR FUNCTION AS SPECIFIED SHALL BE REPLACED WITH COMPLYING EQUIPMENT WITHOUT COST TO THE OWNER. B. THIS CONTRACTOR SHALL GUARANTEE AGAINST DEFECTS OF ALL MATERIALS WORKMANSHIP AND THE COMPLETE OPERATION OF ALL EQUIPMENT AND APPARATUS INSTALLED BY HIM FOR ANDESIHHALL GUARANTEEEE TOR REPAAIIR UN REPLACEEATTI HHI OWNPEXPENSEE ANY P�RDFYTTHE APPARATUS WHICH MAY SHOW DEFECT DURING THAT TIME PROVIDED SUCH DEFECT IS IN THE OPINION OF THE ARCHITECT DUE TO IMPERFECT MATERIAL OR WORKMANSHIP AND NOT TO CARELESSNESS OR IMPROPER USE. PPART 2__P rE DULL L'F; DL- P@ Dt >Lfl S 2.1 RACEWAYS A. ELECTRICAL METAWC TUBING EM SHALL BE ELECTRO-GALVANIZED AND MANUFACTURED IN ACCORDANCE WTH ANSI C80.3. n B. FLEXIBLE METAL CONDUT (FFMC) SHALL CONSIST OF CONTINUOUS LENGTHS OF SPIRALLY WOUND AND INTERLOCKED GALVANIZED STEER MANUFACTURED IN ACCORDANCE WITH UL 1. LIQUID TIGHT FLED%IBLE METAL CONDUIT (LFMC SHALL BE USED IN WET LOCATIONS. C. CONDUIT EXPANSION FITTINGS SHALL BE THREADED HOT -DIPPED GALVANIZED MALLEABLE IRON WITH INTERNAL BONDING ASSEMBLY. D. PROVIDE THREADED MALLEABLE IRON OR STEEL CONNECTORS AND COUPLINGS WITH INSULATED THROATS- MANUFACTURED ELBOWS; LOCKNUTS; AND PLASTIC OR BAKELITE BUSHINGS AT TERMINATIONS AS NECESSARY. COUPLNGS AND CONNECTORS SHALL BE GLAND AND RING COMPRESSION OR STAINLESS STEEL MULTIPLE POINT LOCKING OR STEEL CONCRETE -TIGHT SET SCREW. COMPRESSION COUPLINGS AND CONNECTORS SHALL FORM POSITIVE GROUND. SET -SCREW CONNECTORS AND COUPLINGS SHALL HAVE WALL THICKNESS EQUAL TO CONDUIT, CASE-HARDENED, HEX -HEAD SCREWS AND SEPARATE GROUND WIRE. BUSHINGS FOR RIGID STEEL AND CONNECTORS FOR EMT SHALL HAVE INSULATING INSERTS THAT MEET REQUIREMENTS OF UL 514 FWAE TEST. E. ACCEPTABLE MANUFACTURE FOR METALLIC RACEWAY SHALL BE AS FOLLOWS: 1. ALFLIX 2. ELECTRI-FLEX 3. GRINNEL CO. 4. 0-Z COONEY 2.2 OUTLET BOXES A OUTLET BOXES ON CONCEALED WORK SHALL BE AT LEAST 4 11R16" SQUARE OR OCTAGONAL$ GALVANIZED PRESSED STEEL WITH PLASTER RINGS AS REQUI ED. OUTLET BOXES FOR EXPO ED CONDUIT WORK SHALL BE CAST ALUMINUM ALLOY WITH CAST ALUMINUM ALLOY COVERS. B. WHERE INSTALLED IN PATER BOXES SHALL BE FITTED WITH GALVANIZED STEEL PLASTER COVERS OF REQUIRED DEPTH f0 FINISH FLUSH WITH FINISHED WALL OR CEILING. C. SWITC,U BOXES RECEPTACLE BOXES AND OTHER OUTLET BOXES SHALL BE STANDARD 4 11 16 SQUARE WITH PLASTER RINGS OR GANG COVE AS REQUIRED. D. OUTLET BOXES FOR VARIOUS SYSTEMS AND COMPONENTS SHALL BE AS REQUIRED BY EQUIPMENT MANUFACTURER. E. PROVIDE ONLY ENOUGH CONDUIT OPENINGS TO ACCOMMODATE CONDUITS AT INDIVIDUAL LOCATION. EACH BOX SHALL BE URGE ENOUGH TO ACCOMMODATE NUMBER AND SIZE OF CONDUITS WIRES AND SPUCES TO MEET NEC REQUIREMENTS BUT SHALL BE AT LEAST SIZE SHOWN dR SPECIFIED. NECESSARY VOLUME SHALL BE 06TXINED BY USING BOXES OF PROPER DIMENSIONS. 2.3 JUNCTION BO%ES AND PULL BOXES A PROVIDE CODE GAUGE GALVANIZED STEL JUNCTION AND PULL BOXES FOR CONDUIT 1-1 4, TRADE SIZE AND URGER WHERE NECESSARY TO FACILITATE INSTALLATION, OF REQUI ED DIMENSIONS WITH ACCESSIBLE, REMOVABLE SCREW -ON COVERS. PROVIDE JUNCTION AND PULL BOXES IN SPECIAL SIZES AND SHAPES DETERMINED IN FIELD WHERE NECESSARY. B. JUNCTION BOX COVERS SHALL BE ACCESSIBLE. DO NOT INSTALL JUNCTION BOXES ABOVE SUSPENDED CEILINGS EXCEPT WHERE CEIUNG IS REMOVABLE OR WHERE ACCESS PANEL IS PROVIDED. C. PULL BOXES SHALL BE SUPPORTED ADEQUATELY TO MAINTAIN SHAPE. URGER BOXES SHALL RAVE STRUCTURAL STEEL BRACING WELDED INTO RIGID ASSEMBLY FORMED ADEQUATELY TO MANTAIN ALIGNMENT IN SHIPMENT AND INSTALLATION. SECURE COVERS WITH CORROSION -RESISTANT SCREWS. 1. PULL BOXES EXPOSED TO RAIN OR IN WET LOCATIONS SHALL BE WEATHERPROOF. 2. PROVIDE CLAMPS, GRIDS AND OTHER APPURTENANCES TO SECURE CABLES WITHIN PULL BOX. NO CABLE SHALL BE UNSUPPORTED FOR MORE THAN 30 . 3. PULL BOXES CONNECTED TO CONCEALED CONDUITS SHALL BE MOUNTED WITH COVERS FLUSH WITH FINISHED WALL OR CELING. 2.4 WIRE AND CABLE A PROVIDE SINGLE -CONDUCTOR ANNEALED COPPER WIRE AND CABLE WITH INSULATION RATED 600 V OF SIZES SPECIFlEIS AND SCHEDULE ON DRAWINGS, FOR SECONDARY SERVICE, FEEDERS. BRANCH AND SYSTEM WIRING. B. METAL CUD CABLE SHALL BE 600 V COPPER WITH FULL-SIZED INSULATED GROUND CONDUCTOR. USE IS RESTRICTED BY REQUIREMENTS OF PARAGRAPH ENTITLE WIRING METHODS IN PART 3 OF THIS SECTION. MINIMUM SIZE SHALL BE 12-AWG UNLESS SPECIFIED OTHERWISE. C. WIRE 10-AWG AND URGER SHALL BE STRANDED 12-AWG AND SMALLER SHALL BE SOUD. WIRE AND CABLE SHALL HAVE THWN-THHN OR XRHW INSULATION. D. MOTOR CONTROL CIRCUITS AND SIGNAL WIRING MAY BE 14-AWG IF NEC REQUIREMENTS ARE MET. BRANCH CIRCUITS LONGER THAN 75 FOR 120 V AND 175' FOR 277 V SHALL BE AT LEAST 10-AWG FROM PANEL TO LAST OUTLET. E. WIRING WITHIN LUMINAIRES AND OTHER HIGH -TEMPERATURE EQUIPMENT SHALL HAVE 150'C INSULATION AS REQUIRED BY NEC. F. MAKE SPUCES IN BRANCH CIRCUIT WIRING WITH UL-LISTED SOLDERLES CONNECTORS RATED 600 V OF SIZES AND TYPES REQUIRED BY MANUFACTURERS RECOMMENDATIONS WITH TEMPERATURE RATINGS EQUAL TO THOSE OF WIRES. SPLICE CONNECTORS SHALL BE SCREW -ON. INSULATE SPUCES WITH INTEGRAL COVERS OR WITH PLASTIC OR RUBBER FRICTION TAPE TO PRESERVE CHARACTERISTICS OF WIRE AND CABLE INSULATION. G. MAKE TERMINATIONS AND SPUCES FOR CONDUCTORS 6-AWG AND LARGER WITH CORROSION -RESISTANT HIGH -CONDUCTIVITY PRESSURE INDENT HE% SCREW OR INTENDED SERVICENECCONNECTORS FOR CABLES 250 KCMIL AND IL REGERSSHALL HLAVE TWOO CLAMPING ELEMENTS OR COMPRESSION INDENTS. TERMINALS FOR BUS CONNECTIONS SHALL HAVE TWO BOLT HOLES. H. AAPACITY OF SPUCES AND CONNECTORS SHALL BE EQUAL TO THOSE OF ASSOCIATED WIRES AND CABLES. 2.5 COLOR CODING A COLOR CODE SECONDARY SERVICE, FEEDERS AND BRANCH CIRCUIT CONDUCTORS AS FOLLOWS: 208Y 120 VOLT:CK 77 VOLT: WN PHASE B: RE PHASE B: ORANGE PHASE C: BLUE PHASE C: YELLOW NEUTRAL: WHITE NEUTRAL GRAY GROUND: GREEN GROUND: GREEN ISO GROUND:GREEN W/ YELLOW STRIPE B. BRANCH CIRCUIT CONDUCTORS 12-AWG AND 10-AWG SHALL HAVE SOLID COLOR COMPOUND, SOUD COLOR COATING. NEUTULS AND EQUIPMENT GROUNDS SHALL HAVE SOLID COMPOUND OR SOLID COLOR COATING (WHITE, GRAY AND GREEN). C. ACCEPTABLE MANUFACTURE FOR WIRE AND CABLE SHALL BE !S FOLLOWS: 1. AMERICAN INSULATED WIRE CORP.; A LEVITON COMPANY 2. SENATOR WIRE k CABLE COMPANY 3. SOUT14WIRE COMPANY 2.6 WIRE PULLING EQUIPMENT A PROVIDE POLYETHYLENE ROPE FOR PULUNG WIRE. B. PROVIDE FISH WIRES IN TELEPHONE CONDUITS AND OTHER EMPTY CONDUIT SYSTEMS REQUIRED, WITHOUT SPUCES AND WITH AMPLE EXPOSED LENGTHS AT EACH END. C. PROVIDE WIRE PUWNG LUBRICANTS THAT MEET APPLICABLE UL REQUIREMENTS AS NECESSARY. 2.7 WIRING DEVICES RECEPTACLES A CONVENIENCE RECEPTACLES STRAIGHT BLADE CONVENIENCE RECEPTACLE DEVICES SHALL BE HEAVY DUTY INDUSTRIAL OR DECORATIVE COMMERCIAL SPECIFICATION GRADE AS DIRECTED BY THE ARCHITECT AND SHALL AT A MINIMUM INCORPORATE THE FOLLOWING FEATURES AND BENEFITS. COLOR BY ARCHITECT. 1. RECE TACLESCK20 ASIDE (VIREDOLE, 3-WIRE, GROUNDING TYPE WITH SELF GROUNDING B. GFCI RECEPTACLES: STRAIGHT BLADE GFCI TYPE RECEPTACLE DEVICES SHALL BE TAMPER RESISTANT, WEATHER RESISTANT, FED -THROUGH TYPE. COMPLY WITH NENA WD 1, NENA WD 6 UL 498 NN UL 943 CLASS A, GROUP I SOUD STATE SENSING AND SIGNALING WITH FIVE (5 MILU-AMPERE FAULT TRIP LEVEL AND INCLUDE INDICATOR UGHT THAT IS UGHTED WHEN DECE IS TRIPPED AND SHALL AT A MINIMUM INCORPORATE THE FOLLOWING FUTURES AND BENEFITS. COLOR BY ARCHTECT. 1. GROUNDING CUECEPTACL S 20 AGI125IV 2-POLE, 3-WIRE, GROUNDING TYPE WITH SELF SWITCH S A AC SWITCHES: AC SWTCHES SHALL BE HEAVY DUTY INDUSTRIAL OR DECORATIVE COMMERCIAL SPECIFICATION GRADE AS DIRECTED BY THE ARCHITECT SHALL COMPLY WITH NENA WD1 AND U.L. 20 AND AT A MINIMUM INCORPORATE THE FOLLOWING FEATURES AND BENEFTS 1. AC TOGGLE SWTCHES 2DA 120A277 VOLT AC WITH GROUND SCREW AND SELF GROUNDING CLIP AND BACK AND SMITE WIRED. B. ACCEPTABLE MANUFACTURES/DEVICE NUMBERS FOR RECEPTACLE AND SWTCHES: RECEPTACLES - INDUSTRIAL SPECIFICATION GRADE CONVENIENCE }T OF RECEPTACLES (DECORATIVE) - COMMERCIAL SPECIFICATION GRADE HUBBELL STYLE LINE T CONVENIENCE DRZ� RECEPTACLES - GFCI TYPE HUBBELL STYLE LINE GFCI GFTR1r1 - EHRIAL LL SINGLE POLE PH% 9P THREE-WAY HBL1203 2223 1223-2 FOUR-WAY HBL1204 2224 1224-2 AC SWITCHES (DECORAT��IVV�EEg))g - COMMERCIAL SPECIFICATION GRADE ROCKERLETTYUP�E� SINGLE POLE OP DEDR 562T=2 THREE-WAY DS320 DEC8320 5623-2 FOUR-WAY DS420 DEC8420 5624-2 C. INSTALLATION 1. WIRING DEVICES AND WALL PLATES o. SINGLE AND COMBINATION TYPE TO MATCH CORRESPONDING WIRING DEVICE. i. SMOOTH HIGH -IMPACT THERMOPLASTIC MATERIAL FOR FINISHED SPACE: ii. GALVANIZED STEEL MATERIAL FOR UNFINISHED SPACES: iii. VOICE/DATA JACKS SHALL UTILIZE THE SAME TYPE OF PLATE USED FOR RECEPTACLES iv. DEVICE PLATES SHALL BE BY THE SAME MANUFACTURER AS THE WIRING DEVICE. v. DEVICE/PLATE COLOR SELECTED BY ARCHITECT. 2. RECEPTACLE ORIENTATION: a. HOR17ONTALLLYYUMOUNTED RECEPTACLES TO THE RIGHTT. RECEPTACLES UP AND ON 3. DO NOT USE OVERSIZE OR EXTRA -DEEP PLATES. REPAIR WALL FlNISHE AND REMOUNT OUTLET BOXES WHEN STANDARD DEVICE PLATE DO NOTE FLUSH OR DO NOT COVER ROUGH WALL OPENING. 4. ARRANGEMENT OF DEVICES: UNLESS OTHERWISE INDICATED. MOUNT FLUSH, WITH LONG DIMENSION VERTICAL GROUP ADJACENT SNITCHER UNDER A SINGLE, MULT-GANG WALL PLATE. 2.8 WIRING DEVICE PLATES A PROVIDE TYPE AND COLOR AS DIRECTED BY ARCHITECT. B. VOICE/DATA OUTLET PLATES SHALL BE SAME AS USED FOR RECEPTACLES. C. DEVICE PLATES SHALL BE BY MANUFACTURER OF WIRING DEVICES. D. OUTLETS SHALL BE FLUSH TO SURFACE. 2.9 LUMINAIRES A. PROVIDE LUMINAIRES EQUIPMENT, AND COMPONENTS WHERE SHOWN ON DRAWINGS AS LISTED IN LUMINAIRE SCHEDULE, AND AS SPECIFIED WIRED AND ASSEMBLED. PROVIDE A COMPLLETE SYSTEM' PER MPANUFAC�TURER S AINSTRUCCTIONS AND N E.CC. REQ ILA REMEN TS. FOR B. REFER TO LUMINAIRE SCHEDULE FOR SPECIFIC LAMP AND BALLAST TYPE AND MANUFACTURER REQUIREMENTS. C. PROVIDE POLYESTER COVERS TO PROTECT FLUORESCENT LUMINAIRES WITH LOUVERS, BASKETS, OR LENSES DURING CONSTRUCTION. 2.11 PANELBOARDS A. MANUFACTURERS 1. CUTLER HAMMER 2. GENERAL ELECTRIC 3. SQUARE D 4. SIEMENS THE LISTING OF SPECIFIC MANUFACTURERS ABOVE DOES NOT IMPLY ACCEPTANCE OF THEIR PRODUCTS THAT DO NOT MEET THE SPECIFIED RATINGS FEATURES AND FUNCTIONS. THEIR ECMIRETYY. UPRODUCCTTSO IN COMPLIATNCE W�DTIHE OSPECIIFIICCATIONTMAND MANUFACCTURED BY Fq ERRS NOT NAMED WILL BE CONSIDERED ONLY IF PRE -APPROVED BY THE ENGINEER TEN (10 DAYS PRIOR TO BID DATE. B. RATINGS 1. PANELBOARDS RATED 240V AC OR LESS SHALL HAVE SHORT-CIRCUIT RATINGS AS SHOWN ON THE DRAWINGS OR AS HEREIN SCHEDULED, BUT NOT LESS THAN 10,000 AMPERE RMS SYMMETRICAL. 2. PANELBGARDS RATED 480V AC OR LESS SHALL HAVE SHORT-CIRCUIT RATINGS AS SHOWN ON THE DRAWINGS OR AS HEREIN SCHEDULED, BUT NOT LESS THAN 14,000 AMPERE RMS SYMMETRICAL. 3. PANEBOARDS SHALL BE LABELED WITH A UL SHORT-CIRCUIT RATING. WHEN SERIES F ANUUAL SSHHALL BE PROVIDED.INIEIT SR HOR STA E THE PCONDUT10NS OF THE ULL SERIES RATINGS INCLUDING: a. SIZE AND TYPE OF UPSTREAM DEVICE b. UL RECOGNIZED BRANCH DEVICES THAT CAN BE USED c. UL SERIES SHORT-CIRCUIT RATING. C. CONSTRUCTION 1. INTERIORS SHALL BE COMPLETELY FACTORY ASSEMBLED DEVICES. THEY SHALL BE DEIGNED SUCH THAT SWITCHING AND PROTECTIVE DEVICE CAN BE REPLACED WITHOUT DISTURBING ADJACENT UNITS AND WITHOUT REMOVING THE MAN BUS CONNECTORS. 2. TRIMS FOR BRANCH CIRCUIT PANELBOARDS SHALL BE SUPPLIED WITH A HINGED DOOR UNCOVERLANY CLUE PARRTTSS. DOORSLLSHALLHAVE A SEMI EFLUOSH CYTLINDER SEOCK AND CATCH ASSEMBLY. DOORS OVER 48 INCHES IN HEIGHT SHALL HAVE AUXILIARY FASTENERS. 3. DISTRIBUTION PANELBOARD TRIMS SHALL COVER ALL LIVE PARTS. SWITCHING DEVICE HANDLE SHALL BE ACCESSIBLE. 4. SURFACE TRIMS SHA L BE SAME HEIGHT AND WIDTH AS BOX. RUSH TIRIMS SHALL OVERLAP THE BOX BY 3 4 OF AN INCH ON ALL SIDE. 5. A DIRECTORY CARD WITH A CLEAR PLASTIC COVER SHALL BE SUPPLED AND MOUNTED ON THE INSIDE OF EACH DOOR. 6. ALL LOCKS SHALL BE KEYED ALIKE. D. BUS 1. MAN BUS BARS SRAL BE TIN-PLATED ALUMINUM SIZED IN ACCORDANCE WITH UL STANDARDS TO LIMIT TEMPERATURE RISE ON ANY CURRENT CARRYING PART TO A MAXIMUM OF 65 DEGREE C ABOVE AN AMBIENT OF 40 DEGREES C MAXIMUM. 2. A SYSTEM GROUND BUS ��S��HALL BE INCLUDED IN ALL PANELS. 3. PANELBOARD51SHOWNWITH NEUTRAAL BUS UBARR TAPSS FORS PANELS WITH CSINGLLEE-POLLEE BRANCHES SHALL BE ARRANGED FOR SEQUENCE PHASING OF THE BRANCH CIRCUIT DDAIgES. NEUTRAL BUSING SHALL HAVE A SUITABLE LUG FOR EACH OUTGOING FEEDER AND/OR BRANCH CIRCUIT REQUIRING A NEUTRAL CONNECTION. E. BRANCH CIRCUIT PANEBOARDS 1. THE MINIMUM SHORT-CIRCUIT RATING FOR BRANCH CIRCUIT PANELBOARDS SHALL BE AS SPECIFIED HEREIN OR AS INDICATED ON THE DRAWINGS. PANEUKARDS SHALL BE FULLY RATED. 2. BOLT -ON TYPE HEAVY-DUTY QUICK -MAKE QUICK -BREW( SINGLE AND MULTI -POLE CIRCUIT NTH TOGGLE HANNDLES TTHATSINDICATEE WHEN EIINIT HAS TRAPPED VIDEO FOR EACH 3. CIRCUIT BREAKERS SHALL BE THERMAL-MAGNEC TYPE WITH COMMON TYPE HANDLE FOR ALL MULTIPLE POLE CIRCUIT BREKERS. CIRCUIT BREAKERS SHALL BE MINIMUM 100-AMPERE FRAME AND THROUGH 100-AMPERE TRIP SIZES SHALL TAKE, UP THE SAME POLE SPACING. CIRCUIT BREAKERS SHA(L BE UL USTED AS TYPE 'SWD FOR LIGHTING CIRCUITS AND UL LISTED AS TYPE RACR' FOR HEATING, AIR-CONDITIONING AND REFRIGERATING EQUIPMENT. a. CIRCUIT BREAKER HANDLE LOCKS SHALL BE PROVIDED FOR ALL CIRCUITS THAT SUPPLY EXT SIGNS EMERGENCY LIGHTS ENERGY MANAGEMENT, AND CONTROL SYSTEM (EMCS) PANELS AND FIRE ALARM PANELS. 4. BRANCH CIRCUIT BREAKERS SHALL HAVE A MINIMUM INTERRUPTING RATING OF 10,000 AMPERES SYMMETRICAL AT 240 VOLTS AND 14,000 AMPERE SYMMETRICAL AT 480 VOLTS. F. ENCLOSURE 1. ENCLOSURES SHALL BE AT LEST 20 INCHES WIDE MADE FROM GALVANIZED STEEL. ROVIDE MINIMUM GUTTER SPACE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. WHERE FEEDER CABLES SUPPLYING THE MAINS OF A PANEL ARE CARRIED THROUGH ITS BOX TO SUPPLY OTHER ELECTRICAL EQUIPMENT, THE BOX SHALL BE SIZED TO INCLUDE THE ADDITIONAL REQUIRED WIRING SPACE. AT LEAST FOUR INTERIOR MOUNTING STUDS WITH ADJUSTABLE NUTS SHALL BE PROVIDED. 2. ENCLOSURES SHALL BE PROVIDED WITH BLANK ENDS. 3. EXTERIOR MOUNTED PANELBOARD SHALL BE NEMA 3R AND RATED FOR EXTERIOR APPUCATIONS G. SERVICE ENTRANCE LABEL 1. EQUIPMENT WITH MAIN SERVICE DISCONNECT SWTCH(E) SHALL BE UL LABELED FOR USE AS SERVICE ENTRANCE EQUIPMENT. H. FUTURE DEVICES 1. PANELBOARDS SHALL BE FULLY PROVISIONED WITH ALL NECESSARY MOUNTING BRACKETS BUS CONNECTIONS AND APPURTENANCE REQUIRED FOR INSTALLATION OF FUTURE DEVICE. I. ACCESSORY COMPONENTS AND FEATURES 1. PROVIDE ACCESSORY SET INCLUDING TOOLS AND MISCELLANEOUS ITEMS REQUIRED FOR OVERCURRENT PROTECTIVE DEVICE TEST, INSPECTION, MAINTENANCE AND OPERATION. J. NAMEPLATE 1. PROVIDE AN ENGRAVED NAMEPLATE FOR EACH PANEL SECTION. K. WARNING LABEL 1. PROVIDE ARC -FLASH TWO WARNING LABEL FOR EACH PANEL SECTION PER NATIONAL ELECTRIC CODE N.E.C. ARTICLE 110.16. L FINISH 1. SURFACES OF THE TRIM ASSEMBLY SHALL BE PROPERLY CLEANED, PRIMED, AND A FINISH COAT OF GRAY ANSI 61 PAINT APPUED. PART 3 - EXECUTION 3.1 TESTING INSPECTION AND CLEANING A. TEST WIRING AND CONNECTIONS FOR CONTINUITY AND GROUNDS BEFORE EQUIPMENT IS CONNECTED; DEMONSTRATE INSULATION RESISTANCE BY MEGGER TEST AS REQUIRED. INSULATION RESISTANCE BETWEEN CONDUCTORS AND GROUNDS FOR SECONDARY DISTRIBUTIONS SYSTEMS SHALL MEET NEC REQUIREMENTS. B. VERIFY AND CORRECT AS NECESSARY: VOLTAGES TAP SETTINGS, TRIP SETTINGS AND PHASING ON EQUIPMENT FROM SECONDARY DISTRIBUTION SYSTEM TO POINTS OF USE. TEST SECONDARY VOLTAGES AT BUS IN MAIN SWITCHBOARD, AT PANELBOARDS, AND AT OTHER LOCATIONS ON DISTRIBUTION SYSTEMS AS NECESSARY. TEST SECONDARY VOLTAGES UNDER NO-LOAD AND FULL -LOAD CONDITIONS. C. TEST LUMINARES WITH SPECIFE LAMPS IN PLACE FOR 10 HOURS. DO NOT OPERATE LAMPS OTHER THAN FOR TESTING BEFORE FINAL INSPECTION BY ARCHITECT. REPLACE LAMPS THAT FAIL WITHIN 90 DAYS AFTER ACCEPTANCE BY ARCHITECT. D. PROVIDE NECESSARY TESTING EQUIPMENT AND TESTNG. E. FAILURE OR DEFECTS IN WORKMANSHIP OR MATERIALS REVEALED BY TESTS OR INSPECTION SHALL BE CORRECTED PROMPTLY AND RETESTED. REPLACE DEFECTIVE MATERIAL. F. CLEAN PANELS AND OTHER EQUIPMENT. PANELBOARD INTERIORS SHALL BE CLEANED AND VACUUMED, EQUIPMENT WITH DAMAGE TO PAINTED FINISH SHALL BE REPAIRED TO ARCHITECTS SATISFACTION. 3.2 NAMEPLATES A. PROVIDE NAMEPLATES ON SWTCHBOARDS, PANELBOARDS JUNCTION BOXES AND CABINETS, DA IONS STAERCTERS PORPOTHERWCONTN(AS FURNISHEDOOR INSTALLLED EUNDERMT IH S SECTRION NAMEPLATES SHALL DESIGNATE EQUIPMENT CONTROLLED AND FUNCTION. 3.3 ACCESS AND ACCESS PANELS A. PROVIDE PROPER ACCESS TO MATERIAL OR EQUIPMENT THAT REQUIRE INSPECTION REPLACEMENT REPAIR OR SERVICE AND COORDINATE THEIR DELIVERY WITH THE INSTAWNd TRADE. IF PROPER ACCESS CANNOT BE PROVIDED CONFER WITH ARCHITECT AS TO BEST METHOD OF APPROACH TO MINIMIZE EFFECTS OF REDUCED ACCESS. B. ACCESS PANELS SHALL HAVE SAME FIRE RATING CASIFICATION AS SURFACE PENETRATED. C. PANELS SHALL BE AT LEAST 12" X 12`; ACCESS PANELS AT EQUIPMENT SHALL BE 18' X 18 . 3.4 WIRINGWIRING MW�DSODS A. AL RACEWAYS CABLE ASSEMBUES BOXES CABINETS FITTINGS ETC. SHALL BE SECURED AND SUPPORTED IN ALL ASSEMBUEB AS REQUIRED PER N.E.C. ARTICLE 300.11. B. INSTALL WIRE AND CABLE AS SPECIFIED AND AS APPROVED BY AUTHORITIES HAVING JURISDICTION. ALL CONDUITS OR RACEWAYS SHALL BE CONCEALED WHERE POSSIBLE EXCEPT FOR UNFINISHED AREAS, SUCH AS EQUIPMENT ROOMS. PROVIDE STAND-OFF CUPS WHERE CONDUITS ARE INSTALLED ON MASONRY WALLS. C. RUN CONCEALED CONDUIT IN AS DIRECT LINES AS POSSIBLE WITH MINIMUM NUMBER OF BENDS OF LONGEST POSSIBLE RADIUS. RUN CONDUIT PARALLEL TO OR AT RIGHT ANGLES TO BUILDING LINES TIGHT TO BUILDING STRUCTURE. D. CONDUIT RUNS SHALL BE MECHANICALLY AND ELECTRICALLY CONTINUOUS EOM SERVICE ENTRANCE TO OUTLETS. CONDUIT SHALL ENTER AND BE SECURED TO CABINET JUNCTION BOX, PULL BOX OR OUTLET BOX WITH LOCKNUT OUTSIDE AND BUSHING INSIDE. E. ALL RACEWAY SHALL BE 374' TRADE SIZE MINIMUM AS INDICATED ON THE DRAWINGS OR AS REQUIRED BY THE NEC( AND SHALL CONTAIN AA EQUIPMENT GROUNDING CONDUCTOR. PROVIDE INSERTS, HANGERS, ANCHORS AND STEEL SUPPORTS AS NECESSARY. • Integrated I(1 Engineering Consultants, Inc. 9700 ROCKSIDE RD. SUITE #290 CLEVELAND, OH 44125 (P): 216.901.6711 IF): 216.901.6712 vmv.ieoinQ.R:R: PE11800575 •'. o % STATEOF F. INSTALL CONDUIT SYSTEMS COMPLETE BEFORE DRAWING IN CONDUCTORS. BLOW THROUGH AND SWAB AFTER PATER IS FINISHED AND DRY, AND BEFORE CONDUCTORS ARE INSTALLED. G. WIRE FROM POINT OF SERVICE CONNECTION TO RECEPTACLES LUMINAIRES, DEVICES EQUIPMENT, AND OTHER ELECTRICAL APPARATUS AS SHOWN ON DRAWINGS. PROVIDE SLACK WIRRE FOR CONNECTIONS. H. CONDUCTORS 10-AWG AND SMALLER IN BRANCH CIGUN PANELBOARDS SIGNAL CABINETS SIGNAL CONTROL BOARDS SWITCHBOARDS AND MOTOR CONTROL CENTERS SHALL BH CENTTERS, ANDNPULL BOXES�SHALL BEE CABLED AIN GINDIIVVIDUALALI CIRCUITS. MOTOR CONTROL I. FOLLOW HOMERUN CIRCUIT NUMBERS SHOWN ON DRAWINGS TO CONNECT CIRCUITS TO PANELBOARDS. CONNECT EACH BRANCH CIRCUIT HOMERUN WITH TWO OR MORE CIRCUITS AND COMMON NEUTRAL TO CIRCUT BREAKER OR SWITCH IN THREE -WIRE OR FOUR -WIRE BRANCH CIRCUT PANELBOARD SO THAT NO TWO CIRCUITS ARE FED FROM SAME BUS. WHERE PANELBOARD CABINETS ARE RECESSED PROVIDE CONDUITS WITH SUFFICIENT CAPACITY FOR FUTURE CONDUCTORS FOR SPARE ARANCH CIRCUIT PROTECTIVE DEVICE AND SPACES IN PANELBOARD; STUB UP CONCEALED TO JUNCTION BOX. PROVIDE EXTENSIONS ABOVE CEILING. J. ELECTRICAL METALLIC TUBING ((EMT MAY BE USED FOR INTERIOR APPLICATIONS ABOVE GRADE WHERE PERMITTED BY CODE FOR LUMINAIRE AND RECEPTACLE CIRCUITS TELEPHONE INTER -COMMUNICATIONS SIGNAL AND INSTRUMENTATION CIRCUITS, AND FOR MECHHANIICALLIR AND ELECTRICAL BCHASES ANNDVI CLOSETS EIIINNGb(POSED UILOCATIONSO ACTING CEILINGS OR WALE ABOVE NORMAL TRAFFIC LEVEL AND WHERE NOT SUBJECT TO ACCIDENTAL DAMAGE OR ABUSE. K. INSTALL CONNECTORS AND COUPLINGS AS RECOMMENDED BY MANUFACTURERS. COMPRESSION FITTINGS SHALL BE USED IN AREAS SUBJECT TO MOISTURE. L METAL CUD CABLE (MCI AS APPROVED BY LOCAL CODE FOR RECEPTACLE CIRCUTS IN SUSPENDED CEUNGS ANO STUD -WALL PARTITIONS. N. FLEXIBLE METAL CONDUIT 94C SHALL BE USED FOR CONNECTIONS TO ELECTRICAL EQUIPMENT AND TO EQUIP E FURNISHED UNDER DIVISIONS 14 AND 15 THAT ARE SUBJECT TO MOVEMENT AND VIBRATION. FMC SHALL BE UNITED TO LENGTHS OF 6 FEET AND SHALL CONTAIN GROUNDING CONDUCTOR. 0. ALL LOW VOLTAGE CABLE NOT IN CONDUT AND INSTALLED IN RETURN AIR PLENUM SHALL BE U.L. LISTED PLENUM TYPE CABLE. P. OPENINGS AROUND ELECTRICAL PENETRATIONS THROUGH FIRE RESISTANT RATED WALLS PARTITIONS FLOORS OR CEILINGS HALL BE FIRESTOPPED USING U.L. APPROVED METHODS PER MAN FACTURES GUIDELINES ($HILT] FIRE STOP SYSTEMS OR 3M FIRE PROTECTION PRODUCTSI}' TO MAINTAIN THE FIRE RESISTANCE RATING OF STRUCTURE. REFER TO ARCHITECTURAL DRAWINGS FOR FIRE RATINGS REQUIREMENTS TO BE MAINTAINED. 3.5 INSTALLATION OF LUMINAIRES A THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL CEILING CONSTRUCTION TYPES HEIGHTS CEILING SPACE CLEARANCES, ETC. NTH THE ARCHITECTUftpL PECHANIC& PLUMBING ANTS FIRE PROTECTION PLANS ELEVATIONS AND DETAILS. PROVIDE ROPER FRAMES, ROUGH -IN KITS TRIM RINGS, MOUNTING HARDWARE N.E.C. REQUIRED ACCESS, ANCILLARY AMANUFFSSNREESR'S FC' F R ANTSOMPLETE N.E.C. AND U.L LISTED INSTALLATION PER AIL B. COORDINATE INSTALLATION OF ALL LUMINAIRES WITH ALL TRADE AND THE INSTALLATION OF CEILING MATERIALS AND SUSPENSION SYSTEMS PRIOR TO ANY ROUGH -INS. C. DO NOT INSTALL LUMINAIRES UNTIL WORK OF OTHER TRADES THAT MAY DAMAGE LUMINAIRES IS COMPLETED. D. INVESTIGATE LUMINAIRE LOCATIONS AND SUPPORTS TO ENSURE THAT NO INTERFERENCE EXISTS WITH HANGERS, DUCTS, SPRINKLERS, PIPE AND ALL OTHER EQUIPMENT. E. PROVIDE PROPER PLASTER FRAME FOR LUMINAIRES RECESSED IN GYPSUM BOARD OR PLASTER CEUNG. F. DO NOT SUSPEND OR SUPPORT LUMINAIRES OR SAFETY CHAINS FROM HUNG CEILING, CONDUIT OR DUCT. SUPPORT LUMINAIRES FROM STRUCTURAL BUILDING MEMBERS ONLY. G. FRAMING MEMBERS OF SUSPENDED CEIUNG SYSTEMS USED TO SUPPORT LUMINAIRES SHALL BE SECURELY FASTENED TO EACH OTHER AND SHALL BE SECURELY ATTACHED TO THE BUILDING STRUCTURE AT APPROPRIATE INTERVALS. LUMINAIRES SHALL BE SECURELY FASIENED TO THE CEILING FRAMING MEMBER BY MECHANICAL MEANS SUCH AS BOLTS SCREWS pR RIVETS. LISTED CAPS IDENTIFIED FOR USE WITH THE TYPE OF CEILING FRAMING MEMBE6gJ77j ANO LUMINARE(S) SHALL ALSO BE PERMITTED PER N.E.C. 2008 ARTICLE 410.36(8). H. PROVIDE STRUT BELOW DUCTS WHERE LUMINAIRE LOCATIONS COINCIDE WITH DUCT RUNS. PROVIDE A COMPLETE THREADED ROD SYSTEM TO SUPPORT STRUT. I. PATCH ALL EXISTING SPRAY -ON FIREPROOFING DAMAGED DURING INSTALLATION. J. SUPPORT SURFACE -MOUNTED LUMINAIRES AT LEAST TWO CONCEALED POINTS TO PREVENT ROTATION. K. LOCATE CEIUNG AND WALL MOUNTED LUMINAIRES AS SHOWN ON ARCHITECTURAL REJECTED CEILING PLANS AND ELEVATIONS. 3.6 GROUNDING A PROVIDE EQUIPMENT GROUNDING SYSTEM AS SHOWN ON DRAWINGS. EQUIPMENT GROUNDING SYSTEM SHALL BE DEIGNED SO METALLIC STRUCTURE, ENCLOSURES RACEWAYS, JUNCTION BOXES OUTLET BOXES CABINETS MACHINE FRAMES PORTABLE EQUIPMENT AND OTHER CONDUCTIVE ITEMS IN CLOSE PROAIMITY WITH ELECTRICAL CIRCUITS OPERATE CONTINUOUSLY AT GROUND POTENTIAL AND PROVIDE LOW IMPEDANCE PATH FOR POSSIBLE GROUND FAULT CURRENTS. B. SYSTEM SHAIl MEET NEC REQUIREMENTS, MODIFIED AS SHOWN ON DRAWINGS AND AS SPECIFIED. C. PROVIDE SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR FOR EACH BRANCH CIRCUT. INSTALL GROUNDING CONDUCTOR IN COMMON CONDUIT WITH RELATED ONNEE RAEAYU S7HALL HAEC INDWIIDDALBNEL SIZE GREENEINSULATTED EQUIPMENT RGROU D CONDUCTORS. D. INETPNIOBOARDS AND OTHER SELOECTRICALW EQUIPMENT, EPROVIDEIPSCREWGTTEERMINALS FOR ACTIVE CIRCUITS, SPARES AND SPACE. E. PROVIDE GREEN INSULATED GROUNDING CONDUCTOR IN NONMETAWC CONDUITS OR DUCTS UNLESS SPECIFIED OTHERWISE. 3.7 TELECOMMUNICATIONS CONDUIT SYSTEM A PROVIDE SYSTEM OF EMPTY CONDUIT, OUTLETS AND MOUNTING BOARDS, AS SPECIFIED AND AS SHOWN ON DRAWINGS. B. NYLON PULL -IN WIRE SHALL BE INSTALLED IN TELECOMMUNICATIONS CONDUITS FOR USE BY WNER. HELLYER LEWIS= ARCHITECTURE INTERIOR DESIGN Project: Liberty Mutual INSURANCE 450 East 96th St 3rd Floor Indianapolis IN 46240 Drawing: Electrical Specifications No. E-9.03 DATE: 10/23/19