HomeMy WebLinkAboutM-0.03PIPE SUPPORT
SEE NOTE 4.
PANEL POINTS,
SEE NOTE 4.
THICKNESS & REINFORCING SCHEDULE - * LOW PRESSURE DUCTWORK
GREATEST DUCT
STEEL DUCTS U.S.
ALUMINUM DUCTS B &
LONGITUDINAL
TRANSVERSE JOINT
TRANSVERSE JOINT
REINFORCING (ALL DUCTS 18" THRU 54' SHALL BE CROSSBROKEN)
DIMENSION
STANDARD GAUGE
S GAUGE
SEAM
SMALLEST DIMENSION
GREATEST DIMENSION
12" OR LESS
26
24(0.029)
PITTSBURGH OR
DRIVE SUP OR POCKET
PLAIN "S" SUP OR POCKET
NONE REQUIRED
ACME LOCK
LOCK OR BAR SLIP
LOCK OR BAR SLIP
13" THRU 18'
24
22(0.025')
PITTSBURGH OR
DRIVE SUP OR POCKET
PLAIN "S' SUP OR POCKET
NONE REQUIRED
ACME LOCK
LOCK OR BAR SLIP
LOCK OR BAR SLIP
19" THRU 30'
24
22(0.026)
PITTSBURGH OR
HEMMED "S' SUP OR BAR
HEMMED "S' SUP OR BAR
IF TRANSVERSE JOINTS ARE LOCATED 4'-0" OR LESS ON CENTER NO
ACME LOCK
SUP OR DRIVE SUP OR 1"
SUP OR 1" POCKET LOCK
REINFORCING IF ON 8'-0' CENTERS REINFORCE WITH 1'X1"X1/8"
POCKET LOCK
ANGLES AT 4 Fr. O.C. FASTENED ON 8" CENTERS
31" THRU 42'
22
20(0.032')
PITTSBURGH OR
DRIVE SUP 18' OR LESS
3AR SLIP OR REIN- FORCE
IF TRANSVERSE JOINTS ARE LOCATED 4'-0" OR LESS ON CENTER NO
ACME LOCK
BAR SUP REIN- FORCED
BAR SUP OR POCKET LOCK
REINFORCING IF ON 8'-0" CENTERS REINFORCE WITH 10X1"X1/8"
BAR SUP OR POCKET LOCK
ANGLES AT 4 Fr. O.C. FASTENED ON 8" CENTERS
43" THRU 54'
22
20(0.032')
PITTSBURGH LOCK
1 1/4" BAR SUP, OR RE-
1 1/4" BAR SUP, OR RE-
IF TRANSVERSE JOINTS ARE LOCATED 4'-0' OR LESS ON CENTER NO
INFORCED BAR SUP, OR 1
INFORCED BAR SUP, OR 1
REINFORCING IF ON 8'-0" CENTERS REINFORCE WITH 1"Xl"XI/8'
1/2' POCKET LOCK
1/2' POCKET LOCK
ANGLES AT 4 Fr. O.C. FASTENED ON B" CENTERS
ANGLES TO BE THE
SAME SIZE AS REQUIRED
REINFORCING ANGLES
ANGLE SUP
ANGLES TO BE THE
ACME LOCK
DRIVE SUP
POCKET LOG BAR SLJQ
SAME SIZE AS REQUIRED
REINFORCING ANGLES
CAULK OR GASKET
f
COMPANION LL$�CANGLESANGLES
HEMMED 'S" SLIP
REINFORCED BAR
B
!
SURCED
SL@A2 SLSL P PITTSBURGH LOG LOCK PLAIN "5" SLAP
ANGLES TO BE THE
SAME SIZE AS REQUIRED
REINFORCING ANGLES
ANGLES TO BE THE
SAME SIZE AS REQUIRED
�L
REINFORCING ANGLES
ANGLE REINFORCED POCKET LOCK
STANDING SEAM
ALTERNATE BAR
SUP ANGLE REINFORCED
STANDING SEAM
Nam:
1. LOW PRESSURE DUCTWORK SHALL BE DUCTWORK IN WHICH
THE PRESSURE DOES NOT EXCEED 2" WATER GAUGE.
WEBBING
STEEL BAR
JOIST
ff:3
�.,�� �,�� HANGER ROD
WASHER, SEE DETAIL -B'. \
SIDE VIEW
FRONT VIEW DETAIL A DETAIL B
NOTES; HANGER CONFIGURATION
1. ALL DETAILS SHOWN SHALL BE SUBMITTED AS SHOP DRAWINGS AND SHALL BE REVIEWED 6. THIS CONTRACTOR SHALL COORDINATE WITH ALL OTHER TRADES CONCERNED.
BY THE REGISTERED STRUCTURAL ENGINEER. 7. PROVIDE APPROVED TYPE PIPE OR CHANNEL MEMBERS TO SUPPORT DUCTWORK AND OTHER
2. WHERE POSSIBLE ALL HANGERS SHALL BE SUSPENDED FROM WF BEAMS IN UEU OF FROM JOIST. EQUIPMENT LOADS.
3. EQUIPMENT SHALL i19I BE HUNG FROM STEEL DECK OR FROM BRIDGING ANGLES. 8. ECCENTRIC BEAM CLAMPS WILL NOT BE ALLOWED.
4. HANGERS AND SUPPORTING MEMBERS SUCH AS PIPES & UNISTRUT SHALL BE LOCATED AT PANEL 9. AT FIRE RATED PARTITIONS, ADD ADDITIONAL LAYER OF ARE SAFING INSULATION
POINTS OF JOIST & SHALL BE SUPPORTED BY BAR JOISTS & NOT DIRECTLY BY WEBBING, AROUND PENETRATION SO AS TO ALL CAVITY.
COORDINATE WITH STRUCTURAL ENGINEER. TO. DUCT PENETRATIONS THRU CORRIDOR WALLS ABOVE HE CEILING ARE TO BE "FIRE STOPPED"
5. THE SUM OF ALL BUILDING TRADES HANGER LOADS SHALL NOT EXCEED 250 LBS. PER AROUND THE PENETRATION,
JOIST. WHEN THIS MAXIMUM IS EXCEEDED A DETAIL OF PROPOSED METHOD OF HANGING 11. METAL STRAPPING INSTALLED PER SMACNA CHAPTER 5 IS AN ACCEPTABLE MEANS FOR
SHALL BE SUBMITTED FOR APPROVAL. SUPPORT.
OPEN WEB JOIST DUCTWORK SUPPORT
SEE SPECS FOR SE
USING NYLON TY-W
WITH TY-WRAP TOO
S.S. DRAW HAND
INTERNALLY INSULAT
WITH INTEGRAL (NO'
FABRICATED)
ADJUSTABLE VANES
LINEAR DIFFUSER
NOTES. CONNECTING DUCT SIZE SHALL BE SAME OS
DIFFUSER NECK UNLESS SHOWN OTHERWISE.
1. OFFSETS WITH FLEXIBLE DUCT SHALL NOT EXCEED 30,
AND SHALL BE GRADUAL. OFFSETS IN EXCESS OF 30'
SHALL BE HARD DUCTED.
2. FLEXIBLE DUCT SHALL NOT HAVE MORE THAN 7a" SAG PER FOOT.
3. FOR PERIMETER DIFFUSERS LOCATE DISTANCE FROM LINEAR DIFFUSER CONNECTION
OUTSIDE WALL SHOWN ON ARCH. PLANS.
SCALE NONE
4. CONNECTION TO MAIN DUCT SHALL BE HARD DUCT
TRANSITION AND VOLUME DAMPER.
ELECT
PANEL
CIRCU
WATEF
GATE
WATEF
FIEXIE
WITH
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Camiel
�Nn,�31a>A�1�A�
LATE: 10/23/19
NOTE:
INSTALL PER MANUFACTURES
RECOMMENDATIONS
SEPARATE Y'-TYPE
STRAINER WITH SLOW-
DOWN VALVE AND HOSE
THREAD CONNECTION
(TYPICAL)
TWO POSITION
ISOLATION VALVE
INTERLOCKED WITH
COMPRESSOR
I��IT-L// CIS
BALL VALVE ("ICAL)
BMA
AUTOFLOW SELF BALANCING -
VALVE, SEE HEAT PUMP
SCHEDULE FOR GPM
REQUIREMENTS
PRESSURE/TEMPERATURE
PLUGS (TYPICAL)
3/4" BALL TYPE DRAIN VAL\
WITH CAPPED HOSE THREAD
CONNECTION
HORIZONTAL HEAT PUMP DETAIL
SCALE: NONE
-UNION (TYPICAL) CONDENSATE LINE
HEAT PUMP
WATER SOURCE HEAT PUMP PIPING SCHEMATIC
SCALE: NONE
V
INSULATED FLEXIBLE
CONNECTION ONE (1) FOOT
MAX. LENGTH
CEWNG
MOTOR
PANEL
DUCT CONSTRUCTION
MINIMUM SHEET METAL THICKNESSES
RECTANGULAR DUCTS
MAXIMUM SIZE
STEEL
ALUMINUM
(INCHES)
(MINIMUM THICKNESS, NOMINAL)
(MINIMUM THICKNESS, NOMINAL)
THROUGH 12
0.022 INCH
(26 GAGE, GAGM
0.020 INCH N0. 24 B&S GAGE
13 THROUGH 30
0.028 INCH
(24 GAGE, GALV.)
0.025 INCH NO. 22 B&S GAGE
31 THROUGH 54
0.034 INCH
22 G4GE, GALV.})
0.032 INCH (NO. 20 B&S GAGE)
55 THROUGHGAGE, ROUGH 84
0.040 INCH
20 GALV.
0.040
INCH (140. 18 B&S GAGE)
OVER 84
0.052 INCH
18 GAGE, GALV.
0.051 INCH N0. 16 Bd5 GAGE)
ROUND DUCTS
SPIRAL SEAM DUCT
LONGITUDINAL SEAM DUCT
FITTINGS
MAXIMUM SIZE
STEEL
STEEL
STEEL
(INCHES)
(MINIMUM THICKNESS, NOMINAL)
(MINIMUM THICKNESS, NOMINAL)
(MINIMUM THICKNESS, NOMINAL)
THROUGH 12
0.019 INCH GAGE, CALM.26
0.022 INCH GAGE, GALM))24
0.022 INCH (26 GAGE, GALM)
13 THROUGH 18
((28
GAGE))
0.022 INCH19
0.028 INCH((26
GAGE, GAUV.)
THROUGH 28
0.028 INCH ((24 GAGE, GALV.))
0.034 INCH (22 GAGE, GALV.))
0.034 INCH 22 GAGE, GPLV.2()
22 GAGE,
(20
0.040 INCH 20
0.
37 THROUGH 52
0.040 INCH GAGE, CALM.)
0.052 INCH �18 GAGE, CALM.)
0.092 INCH18 GAGE, GALV.)
SUPPORT FROM OVERHEAD
STRUCTURE WITH THREADED RODS
HEAT PUMP AND RUBBER GROMMET VIBRATION
ISOLATION PER MANUFACTURER'S
RECOMMENDATIONS
AIR lol `- L, aR
ROW `' �� / ROW
L FILTER (MAINTAIN MINIMUM
CLEARANCE)
A/C CONDENSATE TRAP SECONDARY OVERFLOW 26 GAUGE
GALVANIZED STEEL PAN, 2" DEPTH,
AND DRAIN
HEAT PUMP DRAIN PAN
SCAIE:NONE
SEE - 1"SCA E - PLAN
OR GRILLE SCHEDULE R
METAL DUCT SIZES
HANG FROM STRUCTURE
(4)#10 GAUGE SHEET MI
HANGERS
SQUARE, RECTANGULAR OR
ROUND DISTRIBUTION DUCT
RETURN AIR BOOT
SCALE: NONE
CEILING DIFFUSER INSTALLATION DETAIL
SCALE: NONE
ACOUSTICAL LINING
AIR GRILLE
GENERAL MECHANICAL HVAC NOTES
1. ALL "BUILDING STANDARDS' AND/OR 'BUILDING SPECIFICATIONS" SHALL BE CONSIDERED AN INTEGRAL PART OF
THESE DOCUMENTS AND THE CONTRACTOR SHALL BE RESPONSIBLE TO OBTAIN A COPY OF THESE DOCUMENTS
AND COMPLY WITH ALL REQUIREMENTS, STANDARDS, AND SPECIFICATIONS CONTAINED WITHIN.
2. THESE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND ARE INTENDED TO CONVEY HE SCOPE OF WORK AND
INDICATE GENERAL ARRANGEMENT OF DUCTWORK, DIFFUSERS, GRILLES, THERMOSTATS, EQUIPMENT, DEVICES, ETC.
THE LOCATIONS OF ALL ITEMS SHOWN ON THESE DRAWINGS OR CALLED FOR IN THE SPECIFICATIONS THAT ARE
NOT DEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE. HE EXACT LOCATIONS NECESSARY TO SECURE THE
BEST CONDITIONS AND RESULTS MUST BE DETERMINED AT THE PROJECT. ALL LOCATIONS OF WORK EXPOSED TO
VIEW ARE SUBJECT TO APPROVAL OF HE ARCHITECT PRIOR TO ROUGH -INS.
3. THE MECHANICAL CONTRACTOR SHALL VERIFY EXISTING CONDITIONS TO INSURE THAT ALL NEW WORK WILL FIT INTO
THE EXISTING STRUCTURE AND CONDITIONS IN HE MANNER INTENDED AND AS SHOWN ON THE DRAWINGS. THE
CONTRACTOR SHALL NOTIFY THE CONSTRUCTION MANAGER PRIOR TO ANY ROUGH -INS, FABRICATIONS, OR
PERFORMING ANY WORK IN HE AREA INVOLVING DIFFERENCES. NOTIFICATION SHALL BE IN THE FORM OF A RE,
INCLUDING A DRAWING OR SKETCH INDICATING FIELD MEASUREMENTS AND NOTES RELATED TO THE AREA.
4. ANY DISCREPANCIES BETWEEN DRAWINGS AND SPECIFICATIONS SHALL BE PROMPTLY BROUGHT TO THE ATTENTION
OF THE ENGINEER FOR CLARIFICATION DURING THE BIDDING PERIOD. NO ALLOWANCE SHALL SUBSEQUENTLY BE
MADE TO THE CONTRACTOR BY REASON OF HIS FAILURE TO HAVE BROUGHT SAID DISCREPANCIES TO THE
ATTENTION OF HE ARCHITECT/ENGINEER DURING THE BIDDING PERIOD OR OF ANY ERROR ON THE CONTRACTOR'S
PART.
5. ALL EQUIPMENT SHALL BE INSTALLED IN A NEAT, PROFESSIONAL AND WORKMANUKE MANNER, RECTILINEAR TO
FINISHES AND BUILDING STRUCTURE.
6. GENERAL NOTES, SYMBOL LEGENDS AND DETAILS ARE APPUCABLE TO ALL DRAWINGS WITHIN CONTRACT
DOCUMENTS.
7. REFER TO ARCHITECTURAL ELEVATIONS TO DERIVE ENACT LOCATIONS OF ALL RELATED DIFFUSERS, GRILLES,
EQUIPMENT, DEVICES, ETC. DIFFUSERS, GRILLES, AND ALL LUMINAIRES AND CEILING MOUNTED EQUIPMENT SHALL
BE COORDINATED WITH THE ARCHITECTURAL RCP (REFLECTED CEILING PLANS).
8. COORDINATE WORK OF THIS SECTION WITH THAT OF ALL OTHER TRADES.
9. ALL DUCTWORK, PIPING, ETC. RUNNING THROUGH BUILDING EXPANSION JOINTS SHALL BE EQUIPPED WITH
APPROPRIATE EXPANSION FITTINGS.
10. SHEET MEFAL FITTINGS SHOWN ARE TO BE PROVIDED. NO SUBSTITUTES SHALL BE ALLOWED WITHOUT PRIOR
CONSENT FROM ENGINEER.
11. RUN DUCTS PIPING, ETC. CONCEALED, UNLESS SPECIFIED OTHERWISE, AND CLEAR OF CEILING INSERTS. ALL
DUCTWORK SHALL BE INSTALLED AS CLOSE AS POSSIBLE TO WALL AND UNDERSIDE OF BEAMS AND JOISTS..
12. THE MECHANICAL HVAC CONTRACTOR SHALL REFER TO THE ELECTRICAL SPECIFICATIONS FOR ACCEPTABLE CONDUIT
TYPES/LOCATIONS.
13. IT IS NOT INTENDED THAT THE PUNS INDICATE ALL OBSTRUCTIONS, NECESSARY BENDS, AND OFFSETS. IT SHALL
BE THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL HIS WORK TO CONFORM AND SMACNA TO CODE
REQUIREMENTS, HE STRUCTURE, MAINTAIN HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR. REFER TO
THE ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS AS REQUIRED.
14. REFER TO SPECIFICATIONS FOR DUCTWORK, CONSTRUCTION CLASSES, SEAL, AND LEAKAGE CUSSES.
15. INSTALL THERMOSTAT AT ADA 4'-D" ABOVE FINISHED FLOOR OR AS DIRECTED OTHERWISE BY ARCHITECT.
16. ALL WORK SHALL BE COORDINATED WITH ALL JOB TRADES. OFFSETS IN DUCTS (INCLUDING DIVIDED DUCTS)
TRANSITIONS AROUND OBSTRUCTIONS PIPING, ETC. SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
17. FIELD VERIFY HE EXACT LOCATION OF MECHANICAL HVAC EQUIPMENT THAT REQUIRES ELECTRICAL CONNECTIONS
WITH RESPECTIVE CONTRACTORS.
18. VERIFY ALL EQUIPMENT CONNECTIONS WITH MANUFACTURER'S SPECIFICATIONS AND INSTALLATION DRAWINGS.
VERIFY AND PROVIDE DUCT TRANSITIONS TO EQUIPMENT AS REQUIRED. FIELD VERIFY AND COORDINATE ALL
DIMENSIONS BEFORE FABRICATION.
19. ACCESS PANELS SHALL BE PROVIDED TO CLEAN AND SERVICE COILS AND DAMPERS, HEATERS, VALVES, ETC., AND
ALL CONCEALED MECHANICAL EQUIPMENT THAT REQUIRES ACCESS.
20. SUPPORT ALL EQUIPMENT, DUCTWORK, PIPING, ETC. FROM BUILDING STRUCTURE TO PROVIDE A VIBRATION FREE
INSTALLATION. NOTIFY ARCHITECT AND STRUCTURAL ENGINEER OF ALL WEIGHTS AND METHODS OF SUPPORT PRIOR
TO ANY ROUGH -INS OR INSTALLATIONS.
21. ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH N.E.C. REQUIREMENTS AND ELECTRICAL SPECIFICATIONS.
22. ALL MATERIALS AND EQUIPMENT SHALL BE NEW, UNLESS NOTED OTHERWISE.
23. DIFFUSER SIZES SHOWN ARE NECK SIZES; REGISTER AND GRILLE SIZE ARE NOMINAL. SUPPLY DUCT TO
DIFFUSERS/GRILLES SHALL EQUAL NECK SIZE UNLESS SHOWN OTHERWISE.
24. THE INSIDE OF ALL UNLINED DUCTWORK VISIBLE THROUGH A GRILLE OR DIFFUSER SHALL BE PAINTED FLAT BLACK.
25. INSULATE ALL SUPPLY AIR DUCTWORK IN CONCEALED AND RETURN AIR PLENUMS WITH MINIMUM R-3.5 (VERIFY
WITH ASHRAE CLIMATE ZONE) ALL SERVICE FIBER GLASS DUCT WRAP WITH FRK VAPOR RETARDING FACING. DUCT
WRAP IN RETURN AIR PLENUM SHALL COMPLY WITH ASTM E 84 (FLAME SPREAD - 25, SMOKE DEVELOPED - 50).
26. INTERNAL AIR FLOW DIMENSIONS ARE SHOWN FOR DUCTS. CONTRACTOR SHALL INCREASE SIZE FOR LINER IF
APPLICABLE.
27. MECHANICAL WAG CONTRACTOR SHALL FIELD VERIFY ALL EXISTING ITEMS, SIZES, AND MATERIALS BEFORE
FABRICATION OR PURCHASE OF ALL NEW ITEMS.
28. CONTRACTOR SHALL PROVIDED ALL NECESSARY INCREASERS/DEGREASERS TO ADAPT NEW DUCTWORK TO EXISTING
DUCTWORK.
29. REPAIR FIREPROOFING AFTER INSTALLATION OF HANGERS AND SUPPORTS TO ORIGINAL CONDITIONS.
30. PROVIDE FIRE DAMPERS AND ASSOCIATED ACCESS PANELS WHERE SHOWN ON DRAWINGS AND WHERE REQUIRED BY
CODE FOR DUCTS THAT PENETRATE ARE WALLS, FLOORS AND PARTITIONS PROVIDE SLEEVES WHERE PENETRATIONS
ARE NOT PERPENDICULAR TO SURFACE PENETRATED, ENCLOSE DAMPERS IN 10 GAUGE STEEL SLEEVE.
31. MAINTAIN CODE AND MANUFACTURER'S RECOMMENDED SERVICE CLEARANCES FOR EQUIPMENT.
32. EXHAUST FANS/DUCTS AND ROOF VENTS SHALL TERMINATE A MINIMUM OF 10'-0 FROM OUTSIDE AIR INTAKES.
33. ALL MATERIALS IN CEILING SPACE SHALL BE PLENUM RATED PER CODE.
34. PROVDE SECONDARY/AUXIUUARY DRAIN PAN PER SPECIFICATIONS FOR ALL CEILING MOUNTED EQUIPMENT WITH
CONDENSATE OR WATER PIPING CONNECTIONS.
MECHANICAL DEMOLITION NOTES
1. IN EVERY INSTANCE OF DEMOLITION AND/OR REMODELING, THE MECHANICAL CONTRACTOR SHALL FIGURE A COMPLETE
JOB AS NONE OTHER SHALL BE ACCEPTED.
2. THESE NOTES ARE TO BE USED ONLY AS A GUIDELINE FOR DEMOLITION. THE MECHANICAL CONTRACTOR MUST
VISIT THE SITE PRIOR TO BIDDING TO VERIFY ALL WORK REQUIRED FOR A COMPLETE JOB AND INCLUDE THE COST
OF SUCH WORK IN HIS BID.
3. THE MECHANICAL CONTRACTOR SHALL MAINTAIN EXISTING SERVICES TO AND IN THE EXISTING AREA AS REQUIRED
ARRANGEMENTS SHALL BE MADE WITH THE OWNER PRIOR TO THE INTERRUPTION OF ANY SERVICE WITHIN THE
BUILDING.
4. THE MECHANICAL HVAC CONTRACTOR SHALL PROVIDE TEMPORARY SERVICES IN THE EXISTING AREA.
5. THE MECHANICAL WAG CONTRACTOR SHALL CAP ALL DUCTWORK TO REMAIN AND CAP OR PROVIDE FILTERS FOR ALL
RETURN AIR OPENINGS TO SPACE.
6. THE MECHANICAL HVAC CONTRACTOR SHALL PROVIDE PROTECTION FOR ALL DUCT SMOKE DETECTION DEVICES, AND
COORDINATE SHUT -DOWNS WHEN NECESSARY.
7. ALL MECHANICAL HVAC EQUIPMENT AND DEVICES SHALL BE REMOVED COMPLETE AND TURNED OVER TO OWNER.
8. ANY EXISTING DUCTWORK, PIPING AND/OR ELECTRICAL AND MECHANICAL DEVICES BEING DISTURBED BY THE WORK
SHALL BE REWORKED BY THIS CONTRACTOR AS REQUIRED TO RETURN TO ITS FORMER EXISTING OPERATING
CONDITION.
9. ALL WALLS, CEILINGS, FLOORS, ETC. BEING DISTURBED BY THE WORK SHALL BE RETURNED TO FINISHED CONDITIONS
THE MECHANICAL WAG CONTRACTOR SHALL DO HIS OWN CUTTING AND PATCHING AS NECESSARY UNDER HIS
CONTRACT.
10. EXISTING MATERIAL SHALL BE TURNED OVER TO THE OWNER. IF NOT REQUIRED BY OWNER, THE MECHANICAL
CONTRACTOR SHALL REMOVE THESE MATERIALS FROM THE PREMISES.
• Integrated
/'� Engineering
Consultants, Inc.
9700 ROCKSIDE RD. SUITE #290
CLEVELAND, OH 44125
(P): 216.901.6711
fl: 216.901.6712
www.ieoinc.Qc
PE118006T5
•'.
s •, STATE OF
MECHANICAL HVAC SYMBOL LEGEND
SUPPLY OR OUTDOOR AIR DUCT UP
SUPPLY OR OUTDOOR AIR DOWN
RETURN, OR RELIEF AIR DUCT UP
RETURN, OR RELIEF AIR DUCT DOWN
EXHAUST DUCT UP
EXHAUST DUCT DOWN
MITERED DUCT ELBOW WITH TURNING
VANES
SQUARE TO ROUND TRANSITION
INTERNAL DUCT INSULATION
I--��
BALANCING (VOLUME) DAMPER
- X- X-
EXISTING ITEM TO BE REMOVED
NEW DUCTWORK
EXISTING DUCTWORK/EQUIPMENT TO REMAIN
ARE
ABOVE FINISHED FLOOR
NIS
NOT TO SCALE
TYR
TYPICAL
EA
EXHAUST AIR
w
RA
RETURN AIR
SA
SUPPLY AIR
EC
ELECTRICAL CONTRACTOR
CC
GENERAL CONTRACTOR
o
MC
MECHANICAL CONTRACTOR
PC
PLUMBING CONTRACTOR
o
TOO
TEMPERATURE CONTROL CONTRACTOR
z
CU
CONDENSING UNIT
FE
EXHAUST FAN
QT THERMOSTAT
Q TEMPERATURE SENSOR
KK M�K DIFFUSER OR GRILLE DESIGNATION
- CD C CONDENSATE DRAIN UNE
DEMOLITION ANNOTATION LEGEND
"X"
DENOTES EXISTING EQUIPMENT AND DEVICES TO BE REMOVED IN ITS ENTIRETY INCLUDING
BRANCH DUCTWORK, PIPING, CONTROL WIRING, BACK TO SOURCE OR NEXT ACTIVE REM BEING
MAINTAINED.
"XR"
DENOTES EXISTING EQUIPMENT AND DEVICES TO BE RELOCATED IN ITS ENTIRETY. RELOCATION
TO NEW LOCATION ("1M") IS INDICATED ON 'NEW WORK" DRAWINGS.
"XN"
DENOTES NEW LOCATION OF EXISTING RELOCATED ('XR' EQUIPMENT AND DEVICES. REWORK
OR PROVIDE NEW BRANCH DUCTWORK, PIPING, CONTROL WIRING, ETC. TO NEW LOCATION AS
REQUIRED/INDICATED.
"XM"
DENOTES EXISTING EQUIPMENT TO BE MAINTAINED.
H
E
L L
Y
E R
LEWIS=
ARCHITECTURE
INTERIOR
DESIGN
Project:
10
Liberty
Mutual.
INSURANCE
450 East 96th St
3rd Floor
Indianapolis IN 46240
Project No: 047.S6
Drawn by:
JH
Checked by:
HJHH
Approved by:
HJHH
Client Approval:
ur.r
Issue For Bid:
11 /02/18
Issue For Permit: 11 /OS / 1 8
No.
Date
Revision
Scale:
Drawing:
Mechanical HVAC
Details,
Legends and
Notes
No. M-0.03