Mechanical HVAC Piping Plan 6CALE: j
1iB�=T-o�
MECHANICAL HVAC PIPING PLAN GENERAL NOTES:
1. MECHANICAL HVAC CONTRACTOR SRALL COORDINATE ANY NECESSARY SHUTDOWNS WITH
BUILDING/MANAGEMENT.
2. MECHANICAL HVAC CONTRACTOR SHALL PERFORM A FIELD SURVEY PRIOR TO COMMENCING
WITH DEMOLITION. NOTIFY ARCHITECT/ENGINEER OF ANY DISCREPANCIES FOUND FOR
DIRECTION PRIOR TO COMMENCING WITH DEMOLITION.
3. ANY EXISTING SYSTEMS AND/OR EQUIPMENT NOTED AS EXISTING TO REMAIN SHALL BE
FIELD VERIFIED FOR DEFICIENCIES. NOTIFY ARCHITECT AND ENGINEER OF ANY DEFICIENCIES
DISCOVERED.
4. EXISTING EQUIPMENT TO BE RELOCATED SHALL BE INSPECTED PRIOR TO RELOCATION.
NOTIFY ARCHITECT AND ENGINEER OF ANY DEFICIENCIES DISCOVERED.
5. PROJECT SCOPE INVOLVES REMOVAL AND MODIFICATION TO CONDENSER WATER PIPING
SYSTEM. CONTRACTOR SHALL ISOLATE/SHUTOFF SYSTEM AND DRAIN (AND PROPERLY
DISPOSE) TO ACCOMMODATE SCOPE OF WORK.
6. MECHANICAL HVAC CONTRACTOR SHALL REFER TO ALL SHEETS CONTAINED IN DRAWING
SET FOR COMPLETE SCOPE OF WORK. TYPICAL DETAILS, INSTALLATION REQUIREMENTS
AND GENERAL BUILDING STANDARDS ARE REFERENCED AND APPUCABLE TO THESE
CONTRACT DOCUMENTS.
7. CODED NOTE NUMBERS USED/NOT USED FOR CONSISTENCY BETWEEN SHEETS
8. IT IS THE INTENT TO REUSE DUCTWORK WHERE PRACTICAL CONTRACTOR MAY REUSE
DUCT TAPS OF EQUAL SIZE. ANY EXISTING CONDITIONS THAT VARY SRALL BE BROUGHT
TO THE ATTENTION OF THE ARCHITECT/ENGINEER PRIOR TO FABRICATION OR INSTALLATION
OF NEW HVAC SYSTEMS.
RELEASED FOR CONSTRUCTION
Suhject to compliance with all regulations
of State and Local Codes
City of Carmel
MECHANICAL HVAC PIPING PLAN CODED NOTES: O
Q NEW LOCATION FOR RELOCATED HEAT PUMP. EXTEND CONDENSER WATER AND
CONDENSATE PIPING AS REQUIRED FOR NEW LOCATION.
0 CONNECT TO EXISTING CONDENSER WATER. FIELD VERIFY D(ACT LOCATION AND ROUTING.
0 CONDENSATE PIPING SHALL BE GRAVITY FED. ROUTE CONDENSATE PIPING AT 1/8- PER
FOOT SLOPE.
r=
0]
N
ARCHITECTURE
INTERIOR DESIGN
Project:
Liberty
Mutual®
INSURANCE
450 East 96th St
3rd Floor
Indianapolis IN 46240
Project No: 047.S6
Drawn by:
jH
Checked by:
Hf
H H
Approved by:
HjHH
Client Approval:
Date:
Issue For Bid:
11 /02/18
Issue For Permit: 11 /05/18
No.
Date
Revision
Scale: 1 /8" =
1'-0"
Drawing:
Mechanical
HVAC
Piping Plan
No. M-4M
DATE: 10/23/19