LIFE SAFETY PLAN
1116" = 1' 0"
09 22 16.C6 - INT STEEL STUD
z
FRAMING, 3-5/8" @ 16" O.C.
092900.G1- SOUND ATTENUATION
BLANKET
z
09 51 13.A2 - CEILING FINISH, REF
ARCHITECTURAL CEILING PLANS
_
92900.B7-INT GWB, 5/8'TYPE X
A5 MC WALL TYPE
1 112" =1'-0"
i
A4 SFSW
1 112• = r-o•
07 84 46.A1 - FIRE -RESISTIVE JOINT SYSTEM
SECURE FRAMING TO DECK/STRUCTURE
ABOVE
-09 22 16.C13 - DEFLECTION TRACK
-09 29 00.137 - INT GWB, 5/8" TYPE X
09 21 16.23.131 - SHAFT LINER PANEL
09 21 16.23.C1 -SHAFT WALL NON -
LOAD -BEARING STEEL FRAMING,
24' O.C.
14HR FIRE BARRIER
UL q U415 SYSTEM A
LIFE SAFETY PLAN LEGEND
Room name
101
AREA: 150 SF
y
Ocwpanc
a
Dad. ##
w
# of Exits: 4
I
EGRESS INFORMATION TAG
LOCK BOX
ANNUNCIATOR PANEL
FIRE HOSE CABINET
FIRE EXTINGUISHER (NOT REQUIRED)
— - — - — - — 1-HOUR FB RATED WALL
{ 09 22 16.C6 - INT STEEL STUD
CI FRAMING, 3-98" @ 18" O.C.
z
f
ro
09 51 13.A2 - CEILING FINISH, REF
ARCHITECTURAL CEILING PLANS
9 29 00.137 - INT GWB, 5/8' TYPE X
A3 S4-C WALL TYPE
1 112" =1'-0"
r• re
a; u:
2'X4'INT
24" O.C.
POST BF
C.I.P. CO
FOUNDA
REF S-SI
2
CODE SUMMARY
APPLICABLE CODE:
2014 Indiana Building Code (IBC)
General Administrative Rules (GAR)
The project involves interior renovation and addition to an existing
building for The Children's TherAplay Foundation - a not -for -profit
outpatient pediatric rehabilitation clinic. The existing building includes a
therapy noting arena for one-on-one noting sessions, other therapy spaces,
and office and support functions. A previous project phase included
replacing the previously existing stable with new stable addition. The
SCOPE OF WORK:
current project phase will include an addition to office areas and a new
fund-raising banquet room surrounding the arena, dew l of existing
areas and installation of an automatic sprinkler system throughout the
building. The existing building plus addition will be approximately
31,700l including open canopies. The building is Type VB
Construction and will be classified as non -separated A-3, B and U
Occupancies.
Alterations and additions are permitted to an existing building without
requiring the entire existing building or portions of the existing building
unaffected by the proposed scope of renovation to be brought into
APPLICABILITY OF
compliance with current codes. [Rule 4, Section 12, GAR]
CODES TO THE
The current project will not involve a change of use -the existing
PROJECT:
building will remain B and U occupancies.
Maintenance and repairs are permitted of existing building elements and
systems to comply with the applicable miss of the commission that were
in effect when the building was constructed. [Rule 4, Section 9, GAR]
Variance 18-12-33 was approved to permit the addition plus existing
building to exceed allowable area. Per variance 18-12-33, a 1-hour fire
VARIANCES:
barrier with unprotected openings
with closely spaced sprinklers will be provided between the banquet
room and the rest of the building.
Therapy Riding Arena- B Occupancy (Existing) [304.1]
OCCUPANCY
Stables- U Occupancy (Existing) [312.11
CLASSIFICATION:
Offices -B Occupancy (Existing & New) [304.11
Banquet Room-A-3 Occupancy (New) [303.41
CONSTRUCTION
Type VB Construction (Existing 8 New)
TYPE
TabularArea: 5,500 of [Table 5031
Frontage Increase: 4,125 sf [506.21
Sprinkler Increase: +16,500 at [506.31
ALLOWABLE AREA:
Allowable Area: 26,125 at
Actual Area Ind. Add: 31,700 at
Variance 18-12-33 was approved to permit the addition plus existing
building to exceed allowable area.
None required. Building is classified as nonseparated ocwpncies in
OCCUPANCY
accordance with Sec. 508.3.
SEPARATIONS
. Per variance 18-12-33, a 1-hour fire border with unprotected openings
with closely spaced sprinklers will be provided between the banquet
room and the rest of the building.
INCIDENTAL USE
None applicebIs to this project. [Table 5091
SEPARATIONS:
CORRIDORS:
Corridors are not required to be rated based upon sprinkler protection
throughout. [1018.1]
2 means of egress are required from areas with an occupant load of 50 or
more or common path of travel exceeding 75 feet for Group A-3 and U,
or exceeding 100 feet for Group B. ]1015.1]
Egress travel distance is permitted to be a maximum of 250 feet for A-3
MEANS OF
occupancy, 300 feet for B occupancy, and 400 feet for U occupancy.
EGRESS:
[1016.21
Renovation will not reduce exit capacities to a level less than that
required under the current rules for new construction. Egress travel
distances will not be increased beyond what is Permitted by current rules.
[Rule 4, Section 9(f), GAR; Rule 4, Section 12(b), (BAR]
AUTOMATIC
Sprinklers am required throughout the building based upon non -separated
SPRINKLERS:
A-3 and to permit allowable area increases, and as a cenotition of variance
approval 18-12-33. [508.3. 903.2.1.31
FIRE ALARM
Fire alarm system is not required based upon less than 300 occupants in
SYSTEM:
Group A-3 occupancy and less than 500 in Group B. [907.2.1, 907.2.21
SMOKE
Smcke detectors are required in new return air systems with a design
DETECTION:
rapacity greater than 2,000 cfm. ]606, IMC]
A2 ES6S WALL TYPE
1 112" =1'-0"
6' UNFACED BATT
INSULATION
RIBBED METAL PANEL
J-CHANNEL & BRICK
FLASH
2"X4" EXTERIOR GIFTS
7/16" OSB SHEATHING W/
BUILDING WRAP
THIN -SET MASONRY
2'XS' TREATED GRADE
BOARD
REF TO FBI -BUILDER'S DRAWINGS
FOR ADDITIONAL INFORMATION
N
IC
191
w
SCHMIDT
ASSOCIATES
415 Massachusetts Avenue
Indianapolis, IN 46204
www.schmidt-arch.com
Project No. 2018-106.CTC
Project Date 03.22.2019
Produced JDRJDR
9919 Towne Road
Carmel, IN 46032
N KEY PLAN
Children's TherAplay
(±" ChildrensTherAplaS
C)N\i
Renovation and New
Construction
PROJECT SUMMARY, LIFE
SAFETY PLAN & WALL
TYPES
G-100