HomeMy WebLinkAboutM501 - MECHANICAL SCHEDULES0 5 0 3 2 ELECTRIC WALL HEATER SCHEDULE TAG NO. ARRANGEMENT CAPACITY ELECTRICAL BASIS OF DESIGN CONTROL MFG. MODEL# REMARKS BNH WATTS VOLTAGE PHASE EWH-1 RECESSED WALL MOUNTED 1D,235 3000 230 1 INTEGRAL QMARK THERMOSTAT AWH4404F SEE NOTES EWH-2 RECESSED WALL MOUNTED 16,380 4800 230 1 INTEGRAL THERMOSTAT QUARK AWH4508F SEE NOTES NOTES: I ARCHITECTURAL DESIGN 2. FAN DELAY, THERMAL CUTOUT, DOUBLE POLE, SINGLE THROW ON/OFF SWITCH 3. TAMPERPROOF FRONT BAR GRILLE. 14 GAUGE HORIZONTAL PIPING SUPPORT SCHEDULE STEEL PIPING COPPER PIPING CAST RON PIPING PVC PIPING (SCH 40) PIPE SIZE ROD DIAMETER MAXIMUM SPACING FT. PIPE SIZE ROD DVWFTER MAXIMUM SPACING FT. PIPE SIZE ROD DIAMETER MAXIMUM SPACING FT. PIPE SIZE ROD DIAMETER MAMMIUM SPACING FT. UPT01-1/4" 3S" 8 UP TO ill 348' 5 UPTO f-t A" 313" 8 UP TO 1" SM8' 4 1-12"T02" 3/8" 9 1-1M"T01-12" 31 8 1-12"1-02" Sall B 1-1/4"TO 1-12" 3/8" 5 2-12"1103" 12" 10 2" 31511 8 2-12"TOW fall 9 2" 3/8" 5 4"TO S" 518" 12 2-12" 12" 9 4" TO S" 518" 10 2-la" 12" 6 6" 314" 12 3"TOl 12" 10 fill W., 12 3"TO 4" 12" 7 B" 718" 12 5"TO 6" 12" 12 8" 7M3" 12 5"TO 6" sm., 9 10" 1" 14 i0' 1" 14 ell SM 10 12" 1-1/4" 14 fall 1-1 /4" 14 NOTES: 1. PROVIDE ADDITIONAL PIPE SUPPORTS AT MAGNUM I Ell FROM EACH JOINT OR FITTING ON BOTH SIDES. PROVIDE SWAY BRACING FOR PIPING SUBJECT TO MOVEMENT PERPINDICULAR TO PIPING 2. SUPPORTALL PIPING FROM PANEL POINTS ON STRUCTURAL BAR JOISTS. PROVIDE BEMICLAMPS FOR ALL STRUCTURAL BEAMS. DO NOT SUPPORT PIPING FROM METAL ROOF DECK 3, ALL HANGERS AND SUPPORTS SHALL BE SIZED TO ACCOMMODATE THE PIPING INSULATION. PROVIDE BLOCKING AND 12" LONG SHIELDS UNDER EACH INSULATED PIPE 1-12"AND LARGER. 4. SUPPORTALL VERTICAL PIPING AT EACH FLOOR LOCATION. SUPPORTALL VERTICAL PIPING 2" AND LESS AT EVERY4 FEET ON CENTER BACKTO STRUCTURAL MEMBER OR MASONRYWALL. 5. WHERE SEVERAL PIPES OCCUR ATTHE SAME ELEVATION, TRAPEZE TYPE HANGERS MAY BE USED. USE UNISTRUTOR EQUMALENTAPPROVED STEEL SUPPORTS. SEEIFEFOLLOW4NG: a. UNINSULATED PIPE, USE CLAMPS. FOR COPPER TUBING, CLAMPS SHALL BE COPPER OR COPPER PLATED OR LINED. USE COMPRESSION BLOCKS ON INSULATED PIPING. Db. INSULATED PIPING 2"AND SMALLER, USE 18 GAUGE GALVANIZED STEEL SHIELD OVER INSULATION IN 180 DEGREE SEGMENTS, MINIMUM 12" LONG WITH CLAMP c. INSULATED PIPING 2-12" AND LARGER, USE PIPE COVERING PROTECTION SADDLE WITH ROLLER SUPPORTS. J. COLDWATER PIPING 2-1/2" AND LARGER, USE HARD BLOCK NON -CONDUCTING TYPE SADDLES IN 90 DEGREE SEGMENTS AND MNINUM I21,LONG. e. TRAPEZE TYPE HANGERS ARE NOTACCEPTABLE FOR PIPING 6"AND LARGER. PIPES MUST BE SUPPORTED INDIVIDUALLY. I. THE LOAD ON THE END OFANYTRAPEZE HANGER SHALL NOT EXCEED 600 LBS WHEN SUPPORTED FROM OPEN WEB JOISTS AND 1000 LBS WHEN SUPPORTED FROM BEAMS. g. USE GALVANIZED STRUTAND FASTENERS OUTDOORS FOR ALL PIPE SUPPORTS. STEEL IS NOTACCEPTABLE DUE TO CORROSION OVERTIME. 6, USE PREFABRICATED PIPING SUPPORTS ON ROOFS WHERE THE BASE CAN BE PROPERLY FLASHED INTO THE ROOFING MATERIAL. SINGLE POINT PIPE STANDS PRE DIFFICULTTO FLASH. 7. PREFABRICATED PIPE SUPPORTS THAT SIT ON TOP OF THE FINISHED ROOF PRE ACCEPTABLE FOR SINGLE AND DOUBLE PIPE RUNS FOR PIPING WAND SMALLER. CLAMPATEACH SUPPORT. C I GAS FIRED FURNACE SCHEDULE MOTOR ELECTRICAL DATA FULLY CASED COOLING COIL DATA TOTAL NAT GAS NAT GAS FLUE AND TOTAL FULL MANUFACTURER AND AFUE TAG NO. LOCATION TYPE CONFIGURATION TOTAL GEM OUTSIDE INPUT MBH OUTPUT MBH COMB AIR ESP IN TOTAL SENSIBLE EAT WGT. REMARKS MODELNUMBER AIRCFM 2STAGE 2STAGE CONN SITES RATING HP DRIVE LOAD VOLT/PH. DISC SW BY RATING TYPEE CONTROLMBH (L85) WC AMPS MBH DI MTRANEODLI MODEL AS INDICATED GAS ENERGY PROGRAMMABLE244 FURNACE-1 AND TRANE S9V28060 UPFLOW 800 80 39.0/60.0 38.2/57.8 3' 97.0 1/2LO.5"DIRECT 7.9 120/1LES 18.1 80/67 4T%CB004 119 SEE NOTES ON DOGS FIREDSTAR THERMOSTATFURNACE AS INDICATED GAS ENERGY PROGRAMMABLE 2,3,4,5 TRANE S9X2BO80 UPFLOW 1200 100 52.0/80.0 50.4/77.6 3" 97.00 3/4DIRECT 11.3 120/7 36.9 27.7 80/67 4TXCC00fi 124 SEE NOTES ON DOGS FIRED STAR THERMOSTAT NOTES: T. PROGRAMMABLE ELECTRIC THERMOSTATwrH TOUCH SCREEN 2_ FULLY CASED AND INSULATED EVAPORATOR COOLING COIL MATCHED WITH FURNACE_ 3. PRE -CHARGED REFRIGERANT LINE SET AND THERMAL EXPANSION VALVE 4. PROVIDE ALL REFIGERATIONSPECIALTIES SPLIT SYSTEM AIR CONDITIONER SCHEDULE TAG LOCATION BASIS OF DESIGN MANUFACTURER MODEL NUMBERS INDOOR CASSETTE TYPE SYSTEM TYPE PAIRED CONDENSING UNIT f as W 0 8 COOLING ELECTRICAL PHYSICAL NOTES NOMINAL CAPACITY (MI310 ITT CAPACITY MIN EER LOW AMBIENT VOLT PHASE FLA POWER INPUT WATTS OUTDOOR UNIT WEIGHT LES DESIGN NOTES OPTIONS ACCESSORIES CONTROLS EVAP-1 IT ROOM 110A SANYO EVAP KMS1272 OOND CLM1972 WALL MOUNTED COOLING ONLY COND-1 R410a 12D 11S ISO YES 230 1 TIE 1465 13B 1 1,2,3,4 C2 NOTES: DESIGN NOTES 1. COOLING CAPACITIES ARE BASED ON INDOOR COIL EAT OF 80167 degF (DBANB) AND 95 del (DB) OAT. NOTES: OPTIONS &ACCESSORIES 1. PROVIDE WITH LOW AMBIENT CONTROL (Oriel 2_ PROVIDE WITH INTEGRAL CONDENSATE PUMP FOR DISCHARGE TO SANITARY SYSTEM_ 3. PROVIDE ALL REFRIGERANT SPECIALTIES 4. PROVIDE WITH 1- YEAR (FULL PARTS) WARRANTY. NOTES: CONTROLS Cl PROVIDE WITH INTEGRAL MICROPROCESSOR PROVIDE WITH MICROPROCESSOR CONTROLLER PROVIDE WITH WALL MOUNTED PROGRAMMABLE THERMOSTAT. UNIT WILL BE OPERATED IN STAND ALONE MODE. NO COMMUNICATION CARD OPTION AVAILABLE. PROVIDE FACTORY FURNISHED COMMUNICATION CARD (BACNET IP) TO INTERFACE WITH TEMPERATURE CONTROL SYSTEM. ALL POINTS SHALL BE INTEGRATED. C2 C3 CA C5 DUCT INSULATION SCHEDULE K" VALUE STANDARD INSULATION VAPOR BARRIER DENSITY SERVICE TYPE MATERIAL TYPE INSULATION TYPE AT 75 NOTES REFERENCE THICKNESS JACKET LB/CU FT DEG F SUPPLYAIR DUCTCONCEALED ASTM C553 FIBERGLASS BLANKET 1-1/2" FSK, ALUMINUM FOI L 0.75 0.23 SUPPLYAIR DUCT EXPOSED IN MTMC612 FIBERGLASS RIGID BOARD 1" FSKALUMINUMFOIL 3.09 023 OPTIONAL FINISH: CANVASJACKETUL LISTED FABRIC,60Z/SQYD, PLAIN MECHANICALSPACES REINFORCED WEAVE COTTON TREATED WITH DILUTE FIRE RETARDANT LAGGING SUPPLYAR DUCT EXPOSED IN FINISHED SPACES N/A NONE REQUIRED N/A NIA NIA N/A N/A RETURN AIR DUCT FSK, ALUMINUM FOIL CONCEALEDED ASTM C553 FIBERGLASS BLANKET 1-1/2" 075 0.23 RETURN AIR DUCT EXPOSED IN FSK ALUMINUM FOIL OPTIONAL FINISH: CANVAS JACKET, ILL LISTED FABRIC, 60Z/SQ YD, PLAIN MECHANICAL SPACES ASTM C612 FIBERGLASS RIGID BOARD 1" REINFORCED 3.09 023 WEAVE COTTON TREATED WTH DILUTE FIRE RETARDANT LAGGING RETURN AIR DUCT EXPOSED IN FINISHED SPACES N/A NONE REQUIRED NIA N/A N/A N/A N/A OUTDOOR AIR DUCT ASTM C553 FIBERGLASS BLANKET 1-1/2" FSK, ALUMINUM FOIL 0.75 0.23 CONCEALED REINFORCED OUTDOOR AIR D UCT EXPOSED ASTM C612 FIBERGLASS RIGID BOARD 1" FSK ALUMINUM FOIL 3.09 023 OPTIONAL FINISH: CANVAS JACKET, ILL LISTED FABRIC, B OZSQYD, PLAIN IN MECHANICAL SPACES REINFORCED WEAVE COTTON TREATED WTH DILUTE FIRE RETARDANT LAGGING EXHAISTAIR DUCTWORK ASTM CI WI FIBERGLASS BLAN KET LIN ER WITH t POLYMER COATING IN 0.85 025 INTERNALLY LINE EXHAUST DUCTWORK FROM INLET OF EXHAUST FAN EDGE COATING AIRSTREAM EXTENDING A MINIMUM OF TEN FEET BACK INTO THE BUIDLING RELIEF AIR DUCTWORK FSK, ALUMINUM FOI L CONCEALED ASTM C553 FIBERGLASS BLANKET 1-1/2" 0.75 0.23 REINFORCED TRANSFER AIR DUCTWORK ASTM Ci Wi FIBERGLASS BLAN KET LIN ER WITH 1 POLYMER COATING IN 0.65 025 EDGE COATING AIRSTREAM NOTES: 1. ALL INSULATION SHALL BE CONTINUOUS TIHRU WALLS, FLOORS AND CEILINGS. 2. DO NOT COMPROMISE INSULATION VAPOR BARRIER WITH THE USE OF STAPLES, PINS OR OTHER DEVICES. 3. SEAL ALL OPEN ENDS OF INSULATION WITH TAPE OR MASTIC. 4. TAPE AND SEAL ALL JOINTS. 5. INSULATE REHEAT COIL FRAMES MOUNTED ON DISCHARGE SIDE OF VAV TERMINAL UNITS. B. LABEL ALL DUCTWOR K SERMC E AN D IN DICATE DIRECTION OF FLOW. 7. CUTAND TRIM INSULATION AROUND ALL DUCT MOUNTED DEVICES. 00 NOT COVER UP CONTROL DEVICES. CUTAROUND ALL DUCTACCESS DOORS AND SEAL AROUND DOOR FRAMES AND OTHER DEVICES. 8. ALL OUTDOOR DUCTS PENETRATING THE ROOF SHALL PENETRATE THRU A ROOF CURB AND PROPERLY FLASHED. DUCTS PENETRATING WALLS SHALL HAVE FULL PERIMETER SLEEVE, FLASHING AND SEALED. 9. PROVIDE REMOVABLE SECTIONS OF INSULATION WHERE APPLICABLE TO ACCESS DEVICES. LABEL INSULATION AS"REMOVABLE SECTION FOR SERMCE" 10. DOUBLE WALL PRE -INSULATED DUCTWORK DOES NOT NEED TO HAVE EXTERIOR INSULATION. OVERLAP TRANSITION FROM DOUBLE WALL TO SINGLE WALL BYA MINIMUM OF 6" TO MAINTAIN INSULATION INTEGRITY PIPE AND PIPING INSULATION SCHEDULE SERVICE TYPE INSULATION "K" VALUE STANDARD JOINTS OR INSULATION VAPOR INDOORJACKET AND PIPES MATERIAL TYPE TYPE AT 75 NOTES REFERENCE CONNECTION TYPE THICKNESS BARRIER TYPE DESIGNATION (OPTION) DEG F REFRIGERANT SUCTION ALL SIZES ACRHARDDRAWN ASHRAESTANDARDI5 SOLDERED ELASTOMERIC 1-12"OR LESS =la" 2" N/A 0.28 NONE EXTERIORJACKETSHALLBEPVCORALUMINUMWTIHOWRLAPPING (RS) COPPER ASME 31.5 FOAM OR LARGER =1" JOINTS WITH GLUED OR BANDED SEAMS. (NO TAPE) REFRIGERANT LIQUID ALL SIZES ACRHARDDRAWN ASHRAESTMNDAtD15 SOLDERED NONE N/A N/A N/A N/A (RQ COPPER ASME 31.5 CONDENSATE FROM ELASTOMERIC COOLING COILS ALL SIZES TYPE COPPER ANSVASTMABB SOLDERED FOAM ALL SIZES=12" N/A 0.28 NONE NO INSULATION REQUIRED ON EXERIOR APPLICATIONS (D) AU -SIZES TPEL COPPER ANSVASTMABB SOLDERED OR PROPRESS ELASTOMERIC INDOORS ALL SIZES =1" N/A 0.28 NONE DOMESTIC COLD WATER ABOVEFLOOR FOAM (CW) ALL SEES ELASTONERIC TYPE K COPPER ANSVASTMABB SOLDERED OR PROPRESS ALL SIZES =1" N/A 0.028 NONE SIZE SLEEVE AT FLOOR TO ACCOMMODATE FULL INSULATION BELOW FLOOR FOAM ELASTOMERIC DOMESTIC HOT WATER ALL SEES TYPE COPPER MNSVASTMABB SOLDERED OR PROPRESS FOAM INDOORS ALL SIZES =1" NIA 0.28 NONE (HWj ALL SIZES ELASTCul TYPE KCOPPER PNSVPSTM PHB SOLDERED OR PROPRESS pLLSIZES=1" N/A 0.028 NONE SIZE SLEEVE AT FLOOR TOACCOMMODATE FULL INSULATION BELOWFLOOR FOAM DOMESTIC HOTWATER AU -SIZES TYPE COPPER ANSV7STMABB SOLDERED OR PROPRESS ELASTOMERIC INDOORS ALL SIZES =V N/A 0.28 NONE RETURN (HWR) AU -SIZES TYPE K COPPER ANSVASTMABB SOLDERED OR PROPRESS ELASTOMERIC SIMS=1" N/A 0.028 NONE SIZE SLEEVE AT FLOOR TO ACCOMMODATE FULL INSULATION BELOW FLOIXt FOAMALL PRESSURE RELIEF( PR) ALL SIZES TYPE COPPER ANSVASTMABB SOLDERED NONE N/A NIA N/A N/A REINFORCED CRAFT ALL ABOVE GRADE FLOOR DRAIN BODIES AND HORIZONTAL PIPING ABOVE FLOOR CAST IRON CISPI301 HUBLESS NONE ALL SIMS=1" N/A 0.23 PAPER BACKTO BRANCH CONNECTION SHALL BE INSULATED. SANITARYSEWER - BUDGET OPTION TO USE SCH. 40 SANITARYABOVE OR BELOW FLOOR ISE) BELOWFLOOR CAST IRON CISPI301 HUBAWDSPIGOT NONE N/A N/A N/A N/A WITH SOLVENTWELD JOINTS. ALL PIPINGAND JOINTS ABOVE GRADE MUST BE INSULATED WITH 1"ELASTOMERIC. CAST IRON CISPI301 HUBLESS OR VICTALLIC NONE N/A N/A N/A NIA PVC VENT PIPING MIST BE FULLY INSULATED WHERE EXPOSED IN VENT PIPING M ALL SIZES SCH. 40 PVC ASTM D2665 SOLVENTWELD ELASTONERIC ALL SIZES I2" N/A 0.028 NONE RETURN AIR PLENUM. FOAM SCH. 40 BLACK 12"T02„ STEEL ASTMA53 THREADED NONE N/A N/A N/A N/A ALL GAS PIPING BELOW FLOOR OR IN CONCEALED SPACES SHALL BE GAS PIPING (G) 2-12"AND SCH.40 BLACK DOUBLE CONTAINED. PSTM/53 WELDED NONE N/A N/A N/A N/A LARGER STEEL NOTES: 1. ALL INSULATION SHALL BE CONTINUOUS THRU WALLS, FLOORS AND CEILINGS. SICE ALL PIPE SLEEVES TO ACCOMMODATE FULL THICKNESS OF INSULATION WITH THE JACKET. 2. DO NOT COMPROMISE INSULATION VAPOR BARRIER WITH THE USE OF STAPLES, PINS OR OTHER DEVICES. 3. TAPER AND SEAL ALL OPEN ENDS OF INSULATION WTH MYSTIC. 4. LABEL ALL PIPING SERVICEAND INDICATE DIRECTION OF FLOW 5. INSULATION ON REFRIGERANT PIPING SHALL BE CONTINUOUS. UTILIZE PIPE CLAMPS OCCUR SO THERE IS NO BREW IN OVERALL INSULATING VALUE. USING CLAMPS TO BARE PIPE IS UNACCEPTABLE. THE USE OF PRE-MDDED ELASOMERIC FOAM ON FITTINGS WHERE FIBERGLASS IS USED FOR INSULATING STRAIGHT RUNS IS ACCEPTABLE AS LONG AS ALL JOINTS ARE SEALED AND THERE IS NO COMPROMISE IN THE VAPOR BARRIER. RELEASED FOR CONSTRUCTION POSITION SEAMS ON INSULATION ON THE BOTTOMOFTHEPIPING INTHE 6OCLOCKPOSRION. Subject to compliance with all regulations of State and meal Codes City of Carmel \ (� `llumoW\IatrM'X1gAAL DATE: 10/30/19 INSULATION SHALL ALLOW FULL MOVEMENT OF VALVE STEMS AND HANDLES WITHOUT INTERFERING WITH THE INSULATION. PROVIDE EXTENDED STEMS ON ALL PIPING TO ACCOUNT FOR INSULATION THICKNESS. REFIGERANT PIPING SHALL BE INSULATED CONTINUOUS UP TO COIL CONNECTIONS. MAINTAIN ACCESS TOALL PIPING ACCESSORIES SUCH AS DEANS, VENTS, PIPING WELLS, PIPE MOUNTED SENSORS, FLOW METERS, PRESSURE/TEMPERATURE PORTS, ETC ON ALL PIPING SYSTEMS. PADKANYVOIDS IN FITTINGS WTH LOOSE FIBERGLASS INSULATION TO FILL IN AR GAPS AS NEEDED. ALL FIRINGS SHALL FT TIGHTLYTO PIPING AND NOT LEAVE ANYAR GAPS TO ALLOW PIPING TO CONDENSE WITHIN THE ENCLOSED FIRING. 5 0 FAN SCHEDULE FAN IF MOTOR DISCONNECT BASIS OF DESIGN TAG NO_ AREA SERVED CONTROL WEIGHT LES. NOTES FAN TYPE CFM STATIC PRESSURE (IN. W. C.) SPEED (RPM) DRIVE HP VOLTS PHASE EM POWER PROVIDED BY LOCATIOIJ MFG. MODEL# EF-1 SINGLE TOILET ROOMS CEILING EXHAUST FAN 110 0.25 WA DIRECT 30AMPS 120 1 NO LIGHT SW. IN CEILING M 12 BROAN X3110 1 EF-1 MERS 105 AND WOMENS 106 CENTRIFUGAL ROOF MTD 375 0.25 1550 DIRECT 1I100 120 1 NO MEN ROOF T 65 GREENHECK G-080.0GEX-OD 2, 3,4 NOTES: CONTROL: 1. BACKDRAFT DAMPER AND INTEGRAL EXHAUST GRILLE C- CONTINUOUS NIGHT AND DAY OPERATION 2. PROVIDE BACKDRAFT DAMPER 16" CURB AND BIRD SCREEN. M- MANUALLY OPERATED WHEN LIGHT SWITCH IS TURNED ON. 3. PROVIDE DISCONNECT_ N - ON NIGHT SETBACK, CONTINUOUS OPERATION DURING ZONE OCCUPIED SCHEDULE 4. PROVIDE 16" HIGH INSULATED ROOF CURB WITH CANT TO MATCH SLOPE OF ROOF TO LEVEL FAI T-CONTROLLED BY SPACE TEMPERATURE SENSOR MT- MANUALLY STARTED WITH INTERLOCK TO DOC PROGRAMMABLE TIMER MIT- MANUALLY STARTED WITH MECHANICAL 1 HOUR TIMER IL- INTERLOCK WITH ASSOCIATED INTAKE DAMPER. AIR COOLED CONDENSING UNIT SCHEDULE COOLING MANUFACTU ER PAIRED COMPR CONE)MINIMU REFRIG MAX WEIGHT MARK CAPACITY VOLTAGE PHASE MCA MODEL NO. EQUIPMENT RLA FAN FLA MSEER TYPE FUSE LBS. ACCU-1 AND 6 TRANE 4TTR6024.11 FURNACE 1 AND 6 24.0 10.9 0.64 17 R41 CA 230 1 14C 25.0 162 ACCU-2,3,4,5 TRANE 417Iffi036J1 FURNACE 2,3,4,5 MO 116 0.64 1635 R41 GA 230 1 18C 30.0 212 NOTES; 1. DISCONNECT SWITCH BY ELECTRICAL CONTRACTOR. GRILLE AND DIFFUSER SCHEDULE MAX MAX OVERALL SIZE MAX MANUFACTURERAND MARK TYPE NECK SIZE NOISE FRAME/MOUNPNG COLOR REMARKS Ux W„ VEL VEL (FECK (FPM) GEM CRITERIA MODEL NUMBER SRA SQUARE PANEL 4"0 12"X12" 700 40 20 REFER TO REFLECTED CEILING TITUS TMS WHITE ALL STEEL CEILING DIFFUSER PLANS SQUARE PANEL REFER TO REFLECTED CEILING BOB fill 0 24"x24" 700 140 20 TRUS TMS WHITE ALL STEEL CEILING DIFFUSER PLANS SOU SQUARE PANEL 8" 0 24"x24" 650 225 20 REFER TO REFLECTED CEILING TITUS TMS WHITE ALL STEEL CEILING DIFFUSER PLANS SQUARE PANEL REFER TO REFLECTED CEILING SOU 10' 0 24"x24" 685 375 20 TINS TMS WHITE ALL STEEL CEILING DIFFUSER PLANS RGA EGGCRATE GRILLE - 12'%12" 6DO 525 20 REFER TO REFLECTED CEILING TITUS 5OF ALUM PLANS REFER TO REFLECTED CEILING RIGS EGGCRATE GRILLE - 181 600 1100 20 TTUS 5OF ALUM PLANS RGC EGGCRATE GRILLE - 24"x24" 500 1800 20 REFER TO REFLECTED CEILING TITUS 5OF ALUM PLANS DUCT OR SIDEWALL REFER TO WIFE UNLESS DOUBLE DEFLECTION, FRONT BARS PARALLEL BOA SUPPLY GRILLE - 81 400 50 20 TITUS 30ORL FLOOR PLAN NOTED OTHERWISE TO LONG DIMENSION, NO DAMPER EGA EXHAUSTGRILLE - 8"XB" 500 80 20 DUCT OR SIDEWALL REFER TO TITUS 350FL WHITE FIXED 35" DEFLECTION BLADES FLOOR PLAN DUCT MOUNTED REFER TO EG2 EXHAUST GRILLE - 12"X12' 500 150 13 TAUS 350FL WHITE FIXED 35" DEFLECTION BLADES FLOOR PLAN 3 2 E 10 C 10 0 SCHMIDT ASSOCIATES 415 Massachusetts Avenue Indianapolis, IN 46204 www.schmidt-arch.com Project No. 2018-101 Project Date 03.22.2019 Produced Designer Author 3/22/19 Applied Engineering Services TAW wnra,p.Ano,M..s�am.�wsmiw,aweao Td LI8N1111 • r¢3118N11q •Hup{Yiamo These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this Project and are not to be used on any other Project or Wodc without prior written permission from the Architect. 9919 Towne Road Carmel, IN 46032 N KEY PLAN Children's Theraplay Renovation and New Construction MECHANICAL SCHEDULES M501