ELECTRIC WALL HEATER SCHEDULE
TAG NO.
ARRANGEMENT
CAPACITY
ELECTRICAL
BASIS OF DESIGN
CONTROL
MFG. MODEL#
REMARKS
BNH
WATTS
VOLTAGE
PHASE
EWH-1
RECESSED WALL MOUNTED
1D,235
3000
230
1
INTEGRAL QMARK
THERMOSTAT
AWH4404F
SEE NOTES
EWH-2
RECESSED WALL MOUNTED
16,380
4800
230
1
INTEGRAL THERMOSTAT QUARK
AWH4508F
SEE NOTES
NOTES:
I ARCHITECTURAL DESIGN
2. FAN DELAY, THERMAL CUTOUT, DOUBLE POLE, SINGLE THROW ON/OFF SWITCH
3. TAMPERPROOF FRONT BAR GRILLE. 14 GAUGE
HORIZONTAL PIPING SUPPORT SCHEDULE
STEEL PIPING
COPPER PIPING
CAST RON PIPING
PVC PIPING (SCH 40)
PIPE SIZE
ROD
DIAMETER
MAXIMUM
SPACING FT.
PIPE SIZE
ROD
DVWFTER
MAXIMUM
SPACING FT.
PIPE SIZE
ROD
DIAMETER
MAXIMUM
SPACING FT.
PIPE SIZE
ROD
DIAMETER
MAMMIUM
SPACING FT.
UPT01-1/4"
3S"
8
UP TO ill
348'
5
UPTO f-t A"
313"
8
UP TO 1"
SM8'
4
1-12"T02"
3/8"
9
1-1M"T01-12"
31
8
1-12"1-02"
Sall
B
1-1/4"TO 1-12"
3/8"
5
2-12"1103"
12"
10
2"
31511
8
2-12"TOW
fall
9
2"
3/8"
5
4"TO S"
518"
12
2-12"
12"
9
4" TO S"
518"
10
2-la"
12"
6
6"
314"
12
3"TOl
12"
10
fill
W.,
12
3"TO 4"
12"
7
B"
718"
12
5"TO 6"
12"
12
8"
7M3"
12
5"TO 6"
sm.,
9
10"
1"
14
i0'
1"
14
ell
SM
10
12"
1-1/4"
14
fall
1-1 /4"
14
NOTES:
1. PROVIDE ADDITIONAL PIPE SUPPORTS AT MAGNUM I Ell FROM EACH JOINT OR FITTING ON BOTH SIDES. PROVIDE SWAY BRACING FOR PIPING SUBJECT TO MOVEMENT PERPINDICULAR TO
PIPING
2. SUPPORTALL PIPING FROM PANEL POINTS ON STRUCTURAL BAR JOISTS. PROVIDE BEMICLAMPS FOR ALL STRUCTURAL BEAMS. DO NOT SUPPORT PIPING FROM METAL ROOF DECK
3, ALL HANGERS AND SUPPORTS SHALL BE SIZED TO ACCOMMODATE THE PIPING INSULATION. PROVIDE BLOCKING AND 12" LONG SHIELDS UNDER EACH INSULATED PIPE 1-12"AND
LARGER.
4. SUPPORTALL VERTICAL PIPING AT EACH FLOOR LOCATION. SUPPORTALL VERTICAL PIPING 2" AND LESS AT EVERY4 FEET ON CENTER BACKTO STRUCTURAL MEMBER OR MASONRYWALL.
5. WHERE SEVERAL PIPES OCCUR ATTHE SAME ELEVATION, TRAPEZE TYPE HANGERS MAY BE USED. USE UNISTRUTOR EQUMALENTAPPROVED STEEL SUPPORTS. SEEIFEFOLLOW4NG:
a. UNINSULATED PIPE, USE CLAMPS. FOR COPPER TUBING, CLAMPS SHALL BE COPPER OR COPPER PLATED OR LINED. USE COMPRESSION BLOCKS ON INSULATED PIPING.
Db. INSULATED PIPING 2"AND SMALLER, USE 18 GAUGE GALVANIZED STEEL SHIELD OVER INSULATION IN 180 DEGREE SEGMENTS, MINIMUM 12" LONG WITH CLAMP
c. INSULATED PIPING 2-12" AND LARGER, USE PIPE COVERING PROTECTION SADDLE WITH ROLLER SUPPORTS.
J. COLDWATER PIPING 2-1/2" AND LARGER, USE HARD BLOCK NON -CONDUCTING TYPE SADDLES IN 90 DEGREE SEGMENTS AND MNINUM I21,LONG.
e. TRAPEZE TYPE HANGERS ARE NOTACCEPTABLE FOR PIPING 6"AND LARGER. PIPES MUST BE SUPPORTED INDIVIDUALLY.
I. THE LOAD ON THE END OFANYTRAPEZE HANGER SHALL NOT EXCEED 600 LBS WHEN SUPPORTED FROM OPEN WEB JOISTS AND 1000 LBS WHEN SUPPORTED FROM
BEAMS.
g. USE GALVANIZED STRUTAND FASTENERS OUTDOORS FOR ALL PIPE SUPPORTS. STEEL IS NOTACCEPTABLE DUE TO CORROSION OVERTIME.
6, USE PREFABRICATED PIPING SUPPORTS ON ROOFS WHERE THE BASE CAN BE PROPERLY FLASHED INTO THE ROOFING MATERIAL. SINGLE POINT PIPE STANDS PRE DIFFICULTTO FLASH.
7. PREFABRICATED PIPE SUPPORTS THAT SIT ON TOP OF THE FINISHED ROOF PRE ACCEPTABLE FOR SINGLE AND DOUBLE PIPE RUNS FOR PIPING WAND SMALLER. CLAMPATEACH
SUPPORT.
C
I
GAS FIRED FURNACE SCHEDULE
MOTOR
ELECTRICAL DATA
FULLY CASED COOLING COIL DATA
TOTAL
NAT GAS
NAT GAS
FLUE AND
TOTAL
FULL
MANUFACTURER AND
AFUE
TAG NO.
LOCATION
TYPE
CONFIGURATION
TOTAL GEM
OUTSIDE
INPUT MBH
OUTPUT MBH
COMB AIR
ESP IN
TOTAL
SENSIBLE
EAT
WGT.
REMARKS
MODELNUMBER
AIRCFM
2STAGE
2STAGE
CONN SITES
RATING
HP
DRIVE
LOAD
VOLT/PH.
DISC SW BY
RATING
TYPEE
CONTROLMBH
(L85)
WC
AMPS
MBH
DI
MTRANEODLI
MODEL
AS INDICATED
GAS
ENERGY
PROGRAMMABLE244
FURNACE-1 AND
TRANE S9V28060
UPFLOW
800
80
39.0/60.0
38.2/57.8
3'
97.0
1/2LO.5"DIRECT
7.9
120/1LES
18.1
80/67
4T%CB004
119
SEE NOTES
ON DOGS
FIREDSTAR
THERMOSTATFURNACE
AS INDICATED
GAS
ENERGY
PROGRAMMABLE
2,3,4,5
TRANE S9X2BO80
UPFLOW
1200
100
52.0/80.0
50.4/77.6
3"
97.00
3/4DIRECT
11.3
120/7
36.9
27.7
80/67
4TXCC00fi
124
SEE NOTES
ON DOGS
FIRED
STAR
THERMOSTAT
NOTES:
T. PROGRAMMABLE ELECTRIC THERMOSTATwrH TOUCH SCREEN
2_ FULLY CASED AND INSULATED EVAPORATOR COOLING COIL MATCHED WITH FURNACE_
3. PRE -CHARGED REFRIGERANT LINE SET AND THERMAL EXPANSION VALVE
4. PROVIDE ALL REFIGERATIONSPECIALTIES
SPLIT SYSTEM AIR CONDITIONER
SCHEDULE
TAG
LOCATION
BASIS OF DESIGN
MANUFACTURER
MODEL
NUMBERS
INDOOR CASSETTE
TYPE
SYSTEM
TYPE
PAIRED
CONDENSING
UNIT
f
as
W
0
8
COOLING
ELECTRICAL
PHYSICAL
NOTES
NOMINAL
CAPACITY
(MI310
ITT
CAPACITY
MIN
EER
LOW AMBIENT
VOLT
PHASE
FLA
POWER
INPUT
WATTS
OUTDOOR
UNIT
WEIGHT
LES
DESIGN
NOTES
OPTIONS
ACCESSORIES
CONTROLS
EVAP-1
IT ROOM
110A
SANYO
EVAP
KMS1272
OOND
CLM1972
WALL MOUNTED
COOLING
ONLY
COND-1
R410a
12D
11S
ISO
YES
230
1
TIE
1465
13B
1
1,2,3,4
C2
NOTES:
DESIGN NOTES
1.
COOLING CAPACITIES ARE BASED ON INDOOR COIL EAT OF 80167 degF (DBANB) AND 95 del (DB) OAT.
NOTES:
OPTIONS &ACCESSORIES
1.
PROVIDE WITH LOW AMBIENT CONTROL (Oriel
2_
PROVIDE WITH INTEGRAL CONDENSATE PUMP FOR DISCHARGE TO SANITARY SYSTEM_
3.
PROVIDE ALL REFRIGERANT SPECIALTIES
4.
PROVIDE WITH 1- YEAR (FULL PARTS) WARRANTY.
NOTES:
CONTROLS
Cl
PROVIDE WITH INTEGRAL MICROPROCESSOR
PROVIDE WITH MICROPROCESSOR CONTROLLER
PROVIDE WITH WALL MOUNTED PROGRAMMABLE THERMOSTAT.
UNIT WILL BE OPERATED IN STAND ALONE MODE. NO COMMUNICATION CARD OPTION AVAILABLE.
PROVIDE FACTORY FURNISHED COMMUNICATION CARD (BACNET IP) TO INTERFACE WITH TEMPERATURE CONTROL SYSTEM.
ALL POINTS SHALL BE INTEGRATED.
C2
C3
CA
C5
DUCT INSULATION SCHEDULE
K" VALUE
STANDARD
INSULATION
VAPOR BARRIER
DENSITY
SERVICE TYPE
MATERIAL TYPE
INSULATION TYPE
AT 75
NOTES
REFERENCE
THICKNESS
JACKET
LB/CU FT
DEG F
SUPPLYAIR DUCTCONCEALED
ASTM C553
FIBERGLASS
BLANKET
1-1/2"
FSK, ALUMINUM FOI L
0.75
0.23
SUPPLYAIR DUCT EXPOSED IN
MTMC612
FIBERGLASS
RIGID BOARD
1"
FSKALUMINUMFOIL
3.09
023
OPTIONAL FINISH: CANVASJACKETUL LISTED FABRIC,60Z/SQYD, PLAIN
MECHANICALSPACES
REINFORCED
WEAVE COTTON TREATED WITH DILUTE FIRE RETARDANT LAGGING
SUPPLYAR DUCT EXPOSED IN
FINISHED SPACES
N/A
NONE REQUIRED
N/A
NIA
NIA
N/A
N/A
RETURN AIR DUCT
FSK, ALUMINUM FOIL
CONCEALEDED
ASTM C553
FIBERGLASS
BLANKET
1-1/2"
075
0.23
RETURN AIR DUCT EXPOSED IN
FSK ALUMINUM FOIL
OPTIONAL FINISH: CANVAS JACKET, ILL LISTED FABRIC, 60Z/SQ YD, PLAIN
MECHANICAL SPACES
ASTM C612
FIBERGLASS
RIGID BOARD
1"
REINFORCED
3.09
023
WEAVE COTTON TREATED WTH DILUTE FIRE RETARDANT LAGGING
RETURN AIR DUCT EXPOSED IN
FINISHED SPACES
N/A
NONE REQUIRED
NIA
N/A
N/A
N/A
N/A
OUTDOOR AIR DUCT
ASTM C553
FIBERGLASS
BLANKET
1-1/2"
FSK, ALUMINUM FOIL
0.75
0.23
CONCEALED
REINFORCED
OUTDOOR AIR D UCT EXPOSED
ASTM C612
FIBERGLASS
RIGID BOARD
1"
FSK ALUMINUM FOIL
3.09
023
OPTIONAL FINISH: CANVAS JACKET, ILL LISTED FABRIC, B OZSQYD, PLAIN
IN MECHANICAL SPACES
REINFORCED
WEAVE COTTON TREATED WTH DILUTE FIRE RETARDANT LAGGING
EXHAISTAIR DUCTWORK
ASTM CI WI
FIBERGLASS
BLAN KET LIN ER WITH
t
POLYMER COATING IN
0.85
025
INTERNALLY LINE EXHAUST DUCTWORK FROM INLET OF EXHAUST FAN
EDGE COATING
AIRSTREAM
EXTENDING A MINIMUM OF TEN FEET BACK INTO THE BUIDLING
RELIEF AIR DUCTWORK
FSK, ALUMINUM FOI L
CONCEALED
ASTM C553
FIBERGLASS
BLANKET
1-1/2"
0.75
0.23
REINFORCED
TRANSFER AIR DUCTWORK
ASTM Ci Wi
FIBERGLASS
BLAN KET LIN ER WITH
1
POLYMER COATING IN
0.65
025
EDGE COATING
AIRSTREAM
NOTES:
1. ALL INSULATION SHALL BE CONTINUOUS TIHRU WALLS, FLOORS AND CEILINGS.
2. DO NOT COMPROMISE INSULATION VAPOR BARRIER WITH THE USE OF STAPLES, PINS OR OTHER DEVICES.
3. SEAL ALL OPEN ENDS OF INSULATION WITH TAPE OR MASTIC.
4. TAPE AND SEAL ALL JOINTS.
5. INSULATE REHEAT COIL FRAMES MOUNTED ON DISCHARGE SIDE OF VAV TERMINAL UNITS.
B. LABEL ALL DUCTWOR K SERMC E AN D IN DICATE DIRECTION OF FLOW.
7. CUTAND TRIM INSULATION AROUND ALL DUCT MOUNTED DEVICES. 00 NOT COVER UP CONTROL DEVICES. CUTAROUND ALL DUCTACCESS DOORS AND SEAL AROUND DOOR FRAMES AND OTHER DEVICES.
8. ALL OUTDOOR DUCTS PENETRATING THE ROOF SHALL PENETRATE THRU A ROOF CURB AND PROPERLY FLASHED. DUCTS PENETRATING WALLS SHALL HAVE FULL PERIMETER SLEEVE, FLASHING AND SEALED.
9. PROVIDE REMOVABLE SECTIONS OF INSULATION WHERE APPLICABLE TO ACCESS DEVICES. LABEL INSULATION AS"REMOVABLE SECTION FOR SERMCE"
10. DOUBLE WALL PRE -INSULATED DUCTWORK DOES NOT NEED TO HAVE EXTERIOR INSULATION. OVERLAP TRANSITION FROM DOUBLE WALL TO SINGLE WALL BYA MINIMUM OF 6" TO MAINTAIN INSULATION
INTEGRITY
PIPE AND PIPING INSULATION SCHEDULE
SERVICE TYPE
INSULATION
"K" VALUE
STANDARD
JOINTS OR
INSULATION
VAPOR
INDOORJACKET
AND
PIPES
MATERIAL TYPE
TYPE
AT 75
NOTES
REFERENCE
CONNECTION TYPE
THICKNESS
BARRIER
TYPE
DESIGNATION
(OPTION)
DEG F
REFRIGERANT SUCTION
ALL SIZES
ACRHARDDRAWN
ASHRAESTANDARDI5
SOLDERED
ELASTOMERIC
1-12"OR LESS =la" 2"
N/A
0.28
NONE
EXTERIORJACKETSHALLBEPVCORALUMINUMWTIHOWRLAPPING
(RS)
COPPER
ASME 31.5
FOAM
OR LARGER =1"
JOINTS WITH GLUED OR BANDED SEAMS. (NO TAPE)
REFRIGERANT LIQUID
ALL SIZES
ACRHARDDRAWN
ASHRAESTMNDAtD15
SOLDERED
NONE
N/A
N/A
N/A
N/A
(RQ
COPPER
ASME 31.5
CONDENSATE FROM
ELASTOMERIC
COOLING COILS
ALL SIZES
TYPE COPPER
ANSVASTMABB
SOLDERED
FOAM
ALL SIZES=12"
N/A
0.28
NONE
NO INSULATION REQUIRED ON EXERIOR APPLICATIONS
(D)
AU -SIZES
TPEL COPPER
ANSVASTMABB
SOLDERED OR PROPRESS
ELASTOMERIC
INDOORS ALL SIZES =1"
N/A
0.28
NONE
DOMESTIC COLD WATER
ABOVEFLOOR
FOAM
(CW)
ALL SEES
ELASTONERIC
TYPE K COPPER
ANSVASTMABB
SOLDERED OR PROPRESS
ALL SIZES =1"
N/A
0.028
NONE
SIZE SLEEVE AT FLOOR TO ACCOMMODATE FULL INSULATION
BELOW FLOOR
FOAM
ELASTOMERIC
DOMESTIC HOT WATER
ALL SEES
TYPE COPPER
MNSVASTMABB
SOLDERED OR PROPRESS
FOAM
INDOORS ALL SIZES =1"
NIA
0.28
NONE
(HWj
ALL SIZES
ELASTCul
TYPE KCOPPER
PNSVPSTM PHB
SOLDERED OR PROPRESS
pLLSIZES=1"
N/A
0.028
NONE
SIZE SLEEVE AT FLOOR TOACCOMMODATE FULL INSULATION
BELOWFLOOR
FOAM
DOMESTIC HOTWATER
AU -SIZES
TYPE COPPER
ANSV7STMABB
SOLDERED OR PROPRESS
ELASTOMERIC
INDOORS ALL SIZES =V
N/A
0.28
NONE
RETURN
(HWR)
AU -SIZES
TYPE K COPPER
ANSVASTMABB
SOLDERED OR PROPRESS
ELASTOMERIC
SIMS=1"
N/A
0.028
NONE
SIZE SLEEVE AT FLOOR TO ACCOMMODATE FULL INSULATION
BELOW FLOIXt
FOAMALL
PRESSURE RELIEF( PR)
ALL SIZES
TYPE COPPER
ANSVASTMABB
SOLDERED
NONE
N/A
NIA
N/A
N/A
REINFORCED CRAFT
ALL ABOVE GRADE FLOOR DRAIN BODIES AND HORIZONTAL PIPING
ABOVE FLOOR
CAST IRON
CISPI301
HUBLESS
NONE
ALL SIMS=1"
N/A
0.23
PAPER
BACKTO BRANCH CONNECTION SHALL BE INSULATED.
SANITARYSEWER
- BUDGET OPTION TO USE SCH. 40 SANITARYABOVE OR BELOW FLOOR
ISE)
BELOWFLOOR
CAST IRON
CISPI301
HUBAWDSPIGOT
NONE
N/A
N/A
N/A
N/A
WITH SOLVENTWELD JOINTS. ALL PIPINGAND JOINTS ABOVE GRADE
MUST BE INSULATED WITH 1"ELASTOMERIC.
CAST IRON
CISPI301
HUBLESS OR VICTALLIC
NONE
N/A
N/A
N/A
NIA
PVC VENT PIPING MIST BE FULLY INSULATED WHERE EXPOSED IN
VENT PIPING M
ALL SIZES
SCH. 40 PVC
ASTM D2665
SOLVENTWELD
ELASTONERIC
ALL SIZES I2"
N/A
0.028
NONE
RETURN AIR PLENUM.
FOAM
SCH. 40 BLACK
12"T02„
STEEL
ASTMA53
THREADED
NONE
N/A
N/A
N/A
N/A
ALL GAS PIPING BELOW FLOOR OR IN CONCEALED SPACES SHALL BE
GAS PIPING (G)
2-12"AND
SCH.40 BLACK
DOUBLE CONTAINED.
PSTM/53
WELDED
NONE
N/A
N/A
N/A
N/A
LARGER
STEEL
NOTES:
1. ALL INSULATION SHALL BE CONTINUOUS THRU WALLS, FLOORS AND CEILINGS. SICE ALL PIPE SLEEVES TO ACCOMMODATE FULL THICKNESS OF INSULATION WITH THE JACKET.
2. DO NOT COMPROMISE INSULATION VAPOR BARRIER WITH THE USE OF STAPLES, PINS OR OTHER DEVICES.
3. TAPER AND SEAL ALL OPEN ENDS OF INSULATION WTH MYSTIC.
4. LABEL ALL PIPING SERVICEAND INDICATE DIRECTION OF FLOW
5. INSULATION ON REFRIGERANT PIPING SHALL BE CONTINUOUS. UTILIZE
PIPE CLAMPS OCCUR SO THERE IS NO BREW IN OVERALL INSULATING VALUE. USING CLAMPS TO BARE PIPE IS UNACCEPTABLE.
THE USE OF PRE-MDDED ELASOMERIC FOAM ON FITTINGS WHERE FIBERGLASS IS USED FOR INSULATING STRAIGHT RUNS IS ACCEPTABLE AS LONG AS ALL JOINTS ARE SEALED AND THERE IS NO COMPROMISE IN THE VAPOR BARRIER.
RELEASED FOR CONSTRUCTION POSITION SEAMS ON INSULATION ON THE BOTTOMOFTHEPIPING INTHE 6OCLOCKPOSRION.
Subject to compliance with all regulations
of State and meal Codes
City of Carmel \ (�
`llumoW\IatrM'X1gAAL
DATE: 10/30/19
INSULATION SHALL ALLOW FULL MOVEMENT OF VALVE STEMS AND HANDLES WITHOUT INTERFERING WITH THE INSULATION. PROVIDE EXTENDED STEMS ON ALL PIPING TO ACCOUNT FOR INSULATION THICKNESS.
REFIGERANT PIPING SHALL BE INSULATED CONTINUOUS UP TO COIL CONNECTIONS.
MAINTAIN ACCESS TOALL PIPING ACCESSORIES SUCH AS DEANS, VENTS, PIPING WELLS, PIPE MOUNTED SENSORS, FLOW METERS, PRESSURE/TEMPERATURE PORTS, ETC ON ALL PIPING SYSTEMS.
PADKANYVOIDS IN FITTINGS WTH LOOSE FIBERGLASS INSULATION TO FILL IN AR GAPS AS NEEDED. ALL FIRINGS SHALL FT TIGHTLYTO PIPING AND NOT LEAVE ANYAR GAPS TO ALLOW PIPING TO CONDENSE WITHIN THE ENCLOSED FIRING.
5
0
FAN SCHEDULE
FAN
IF MOTOR
DISCONNECT
BASIS OF DESIGN
TAG NO_
AREA SERVED
CONTROL
WEIGHT
LES.
NOTES
FAN TYPE
CFM
STATIC
PRESSURE
(IN. W. C.)
SPEED
(RPM)
DRIVE
HP
VOLTS
PHASE
EM
POWER
PROVIDED
BY
LOCATIOIJ
MFG.
MODEL#
EF-1
SINGLE TOILET ROOMS
CEILING
EXHAUST FAN
110
0.25
WA
DIRECT
30AMPS
120
1
NO
LIGHT SW.
IN CEILING
M
12
BROAN
X3110
1
EF-1
MERS 105 AND WOMENS
106
CENTRIFUGAL
ROOF MTD
375
0.25
1550
DIRECT
1I100
120
1
NO
MEN
ROOF
T
65
GREENHECK
G-080.0GEX-OD
2, 3,4
NOTES:
CONTROL:
1. BACKDRAFT DAMPER AND INTEGRAL EXHAUST GRILLE
C- CONTINUOUS NIGHT AND DAY OPERATION
2. PROVIDE BACKDRAFT DAMPER 16" CURB AND BIRD SCREEN.
M- MANUALLY OPERATED WHEN LIGHT SWITCH IS TURNED ON.
3. PROVIDE DISCONNECT_
N - ON NIGHT SETBACK, CONTINUOUS OPERATION DURING ZONE OCCUPIED SCHEDULE
4. PROVIDE 16" HIGH INSULATED ROOF CURB WITH CANT TO MATCH SLOPE OF ROOF TO LEVEL FAI
T-CONTROLLED BY SPACE TEMPERATURE SENSOR
MT- MANUALLY STARTED WITH INTERLOCK TO DOC PROGRAMMABLE TIMER
MIT- MANUALLY STARTED WITH MECHANICAL 1 HOUR TIMER
IL- INTERLOCK WITH ASSOCIATED INTAKE DAMPER.
AIR COOLED CONDENSING UNIT SCHEDULE
COOLING
MANUFACTU ER
PAIRED
COMPR
CONE)MINIMU
REFRIG
MAX
WEIGHT
MARK
CAPACITY
VOLTAGE
PHASE
MCA
MODEL NO.
EQUIPMENT
RLA
FAN FLA
MSEER
TYPE
FUSE
LBS.
ACCU-1 AND 6
TRANE 4TTR6024.11
FURNACE 1 AND 6
24.0
10.9
0.64
17
R41 CA
230
1
14C
25.0
162
ACCU-2,3,4,5
TRANE 417Iffi036J1
FURNACE 2,3,4,5
MO
116
0.64
1635
R41 GA
230
1
18C
30.0
212
NOTES;
1. DISCONNECT SWITCH BY ELECTRICAL CONTRACTOR.
GRILLE AND DIFFUSER SCHEDULE
MAX
MAX
OVERALL SIZE
MAX
MANUFACTURERAND
MARK
TYPE
NECK SIZE
NOISE
FRAME/MOUNPNG
COLOR
REMARKS
Ux W„
VEL VEL (FECK
(FPM)
GEM
CRITERIA
MODEL NUMBER
SRA
SQUARE PANEL
4"0
12"X12"
700
40
20
REFER TO REFLECTED CEILING
TITUS TMS
WHITE
ALL STEEL
CEILING DIFFUSER
PLANS
SQUARE PANEL
REFER TO REFLECTED CEILING
BOB
fill 0
24"x24"
700
140
20
TRUS TMS
WHITE
ALL STEEL
CEILING DIFFUSER
PLANS
SOU
SQUARE PANEL
8" 0
24"x24"
650
225
20
REFER TO REFLECTED CEILING
TITUS TMS
WHITE
ALL STEEL
CEILING DIFFUSER
PLANS
SQUARE PANEL
REFER TO REFLECTED CEILING
SOU
10' 0
24"x24"
685
375
20
TINS TMS
WHITE
ALL STEEL
CEILING DIFFUSER
PLANS
RGA
EGGCRATE GRILLE
-
12'%12"
6DO
525
20
REFER TO REFLECTED CEILING
TITUS 5OF
ALUM
PLANS
REFER TO REFLECTED CEILING
RIGS
EGGCRATE GRILLE
-
181
600
1100
20
TTUS 5OF
ALUM
PLANS
RGC
EGGCRATE GRILLE
-
24"x24"
500
1800
20
REFER TO REFLECTED CEILING
TITUS 5OF
ALUM
PLANS
DUCT OR SIDEWALL REFER TO
WIFE UNLESS
DOUBLE DEFLECTION, FRONT BARS PARALLEL
BOA
SUPPLY GRILLE
-
81
400
50
20
TITUS 30ORL
FLOOR PLAN
NOTED OTHERWISE
TO LONG DIMENSION, NO DAMPER
EGA
EXHAUSTGRILLE
-
8"XB"
500
80
20
DUCT OR SIDEWALL REFER TO
TITUS 350FL
WHITE
FIXED 35" DEFLECTION BLADES
FLOOR PLAN
DUCT MOUNTED REFER TO
EG2
EXHAUST GRILLE
-
12"X12'
500
150
13
TAUS 350FL
WHITE
FIXED 35" DEFLECTION BLADES
FLOOR PLAN
3
2
E
10
C
10
0
SCHMIDT
ASSOCIATES
415 Massachusetts Avenue
Indianapolis, IN 46204
www.schmidt-arch.com
Project No. 2018-101
Project Date 03.22.2019
Produced Designer Author
3/22/19
Applied
Engineering Services
TAW wnra,p.Ano,M..s�am.�wsmiw,aweao
Td LI8N1111 • r¢3118N11q •Hup{Yiamo
These Drawings and Specifications, and all copies
thereof are and shall remain the property and copyright
of the Architect. They shall be used only with respect to
this Project and are not to be used on any other Project
or Wodc without prior written permission from the
Architect.
9919 Towne Road
Carmel, IN 46032
N
KEY PLAN
Children's Theraplay
Renovation and New
Construction
MECHANICAL SCHEDULES
M501