HomeMy WebLinkAboutM0.3 Mechanical PlanROOFTOP HVAC UNIT SCHEDULE SUPPLY FAN DATA DX COOLING DATA GAS HEATING DATA UNIT CHARACTERISTICS TAG SERVICE MEN MODEL No, NOMINAL EEO/SEER MIN OA NOTES/ OPERATING TONS (CFM) p[R FLOW ESP MOTOR FAN EAT EAT SENSIBLE TOTAL COMING EAT1 T INPUT OUTPUT HEATING VOLTAGE ACCESSORIES (CFM) (IN WC) (HP) (RPM) °DB/°RB °DU/°REP (MBH) (MBH) STAGES °F (III (Ml STAGES (V-0-Hz) UNIT MCA UNIT MOCP WEIGHT (LESS) RTU-1 RESTAURANT TENANT TRANS YHD180 15.0 12.0115.0 150D 600D 1.0 3.CO 1740 78.9166.7 57.1156.4 142.2 180.5 2 51.8182.5 250.0 1 200.0 1 2 200-3-60 68.0 90.0 2663 1-18 NOTES/ACCESSORIES 1. 95° CONDENSING TEMPERATURE 2. REFRIGERANT - R410A 3. 100% ECONOMIZER WITH FIXED DRYBULB CONTROL 4. PONEBED RELIEF S. 14° INSULATED ROOF CURB 6. HACH CIRCUIT BREAKER 7. UN -POWERED CONVENIENCE OUTLET 8. DIRECT DRIVE 9. SINGLE ZONE VAV 10. THROUGH THE BASE ELECTRICAL 11. HAIL GUARD - WITH TOOL LESS REMOVAL 12. PROGRAMMABLE SEVEN DAY AUTO CHANGE OVER THERMOSTAT WITH REMOTE TEMPERATURE SENSOR 13. HINGED ACCESS DOORS 14. 2° PLEATED FILTERS MERV 8 15. MICRO -PROCESSOR CONTROLS 16. 5 YEAR COMPRESSOR WARRANTY 17. STAINLESS STEEL HEAT EXCHANGER 18. 10 YEAR WARRANTY ON HEAT EXCHANGER 1 SHELL MECHANICAL PLAN M-0.3 SCALE: 118-iii RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and Local Codes City of Camel (� �VTl�ilonPfiDAAL DATE: \\ 08/19/19 GENERAL SHEET NOTES 1. ANYTHING NOT NOTED AS EXISTING IS TO BE FURNISHED AND INSTALLED AS PART OF THIS PROJECT. 2. REFER TO DRAWINGS AND PROJECT SPECIFICATIONS OF OTHER DISCIPLINES FOR ADDITIONAL PROJECT INFORMATION AND REQUIREMENTS. NOTIFY ENGINEER OF MY CONFLICTS BETWEEN THE INFORMATION PRESENTED AND FIELD CONDITIONS. 3. MECHANICAL SYSTEMS INSTALLATION MUST MAINTAIN INTEGRITY OF WALLS, PARTITIONS AND FLOORS DESIGNATED AS EITHER FIRE RATED OR °SMOKE TIGHT•. SEAL AROUND ALL PENETRATIONS THROUGH RATED OR SMOKE TIGHT ASSEMBLIES. CCORDINATE W/ARCHITECTURAL PLANS AND GENERAL CONTRACTOR. 4. ALL ROOF PENETRATIONS, PATCHING AND FLASHING SHALL BE PERFORMED BY AN APPROVED ROOFING CONTRACTOR AT THIS CONTRACTOR'S EXPENSE. COORDINATE HOOF PENETRATIONS AND ROOFTOP EQUIPMENT LOCATIONS WITH LANDLORD AND GENERAL CONTRACTOR. 5. NOTHING IS PERMITTED TO BE ATTACHED TO, SUSPENDED FROM, OR PENETRATE THE ROOF DECK, CONTRACTOR MAY ATTACH TO OR SUSPEND FROM THE TOP CHORD OF THE JOIST OR THE STRUCTURAL STEEL MACH EXISTS ABOVE THE SPACE. 6. COORDINATE FINAL ROOFTOP UNIT LOCATIONS WITH STRUCTURAL ENGINEER. PROVIDE 10' CLEARANCE FROM UNIT OUTSIDE AIR INTAKE TO MY EXHAUST/VENTS ON ROOF. 7. GENERAL CONTRACTOR TO LABEL ALL ROOFTOP EQUIPMENT WITH TENANT NAME, SPACE NUMBER AND EQUIPMENT IDENTIFICATION ETU-1, ETC.), PER MALL SPECIFICATIONS AND STANDARDS. 8. PITCH POCKETS ARE NOT PERMITTED ON THE ROOF FOR CONDENSATE DRAINS, POWER OR CONTROL WIRING. ALL CONNECTIONS ARE TO BE MADE INSIDE THE EQUIPMENT CURB OR THROUGH PRE -MANUFACTURED PIPING CURB. O SHEET KEYNOTES 1 PROVIDE SUPPLY AND RETURN DUCT DROPS FULL SIZE WITH FLEX CONNECTION AT UNIT CORN THRU ROOF TO 1'-0° BELOW JOIST FOR FUTURE TENANT CONNECTION. 2 PROVIDE 7-DAY PROGRAMMABLE THERMOSTAT. THERMOSTAT SHALL BE SUSPENDED IN JOIST SPACE WITH 50' OF COILED WIRE FOR FUTURE TENANT RELOCATION. 3 RETURN AIR MOUNTED SLAKE DETECTOR PROVIDED AND WIRED BY ELECTRICAL CONTRACTOR, MOUNTED BY MECHANICAL CONTRACTOR. CURRAN ARCHITECTURE 5719 LAWTON LOOP E. DR. #212 INDIANAPOLIS, IN 46216 O c 317.288 .0681 IF :: 317.288.0753 DRAM BY: JES CHECKED BY: KDH OTIE/S ENGINEERING 25760 First Street Cleveland, OH 44145 P 440 8712410 F 440 871 7954 tesengineering.com NGEM T ED 767.�_ STATE OF :•4i� /W0R NIAilln�ON � THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE E%CLUNVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOM OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. COPRICHr 20'6, CLRMN nHNgFCTI1HF WESTON POINTE RESTAURANT WESTON POINTE DRIVE NORTH MICHIGAN ROAD CARMEL, INDIANA MECHANICAL PLAN CARMEL RESUBI - PERMIT SET 07,17, ADDENDUM 1 09,22,17 ADDENDUM 2 10,12,17 PERMIT SET 05,21,19 170026 M=0.3