HomeMy WebLinkAboutWESTONpt-MICHIGANrd-C6.1TYPICAL SANITARY SEWER SPECIFICATIONS TO BE USED FOR PRIVATE SEWER DEVELOPMENT WITHIN CLAY TOWNSHIP REGIONAL WASTE DISTRICT REVISED 3/1/2007 1. Standard specifications of Clay Township Regional Waste District (the District) and Department of Transportation (INDOT) shall apply for all work and materials. Sanitary sewer pipe shall be installed in accordance with Section 715 of the current INDOT standard specifications handbook. 2. San nary sewer gravity pipe, unless pressure rated pipe required per IAC or directional drilled pipe, shall be Polyvinyl Chloride (PVC) in accordance with ASTM D3034-89 with a minimum wall thickness designation of SDR 35 and installed per ASTM D2321-89 specification. PVC a used shall be grooved bell spigot end and gasketed. The a shall P PP 9 P2 9 PP be made of PVC plastic having a cell classification of 12454B. 3. PVC sanitary sewer gravity fittings shall also Conform to the requirements of the ASTM D303489 specification. All fittings shall be molded in one piece with standard pipe bells, gasketed elastomeric joints, and spigot ends. Single piece molded PVC with standard pipe bells, gaskets, and spigot ends for back -tor -back tee wyes are acceptable. Wall thickness of all fittings shall have a minimum designation of SDR 26. Gaskets for elastomeric joints shall be molded with a minimum cross -sectional area of 0.20 square inches and conform to ASTM F477 specification. 4. All sanitarymanholes shall be racast concrete manholes in accordance with ASTM C478 P and Section 720 of the current f Kent standard equivalent shall hm be handbook. 0-rings shall Conform to n rise Double row of Kent Seal or equivalent shall also be applied to all joints and between riser rings and castings. Manhole step spacing shall be no more than arinches. Manholes shall be air tested for leakage in accordance with ASTM sC1 244-02,(Vacuum) Standard Test Method for Concrete Sewer Manholes the Negative Air Pressure acuum Test. by g N ) A. Installation and operation of vacuum equipment antl indicating devices must be in P9 accordance with provided ctu y the manufacturer and accepted pted by the District Engineer. Pspecifications which have been r entm b the manufacturer and aces etl b the District En ith er. P Y Pt Y 9 The vacuum equipment must be capable of testing the entire manhole, including the CBSfln and /ISBN rings. 9 9 B. With the vacuum tester set in place: 1. Connect the vacuum um to the outlet port with the valve open. pump p P 2. Draw a vacuum often (10) inches of HE. (5 psi) and close the valve. C. Accepted standards far leakage will be established from the elapsed time for a P 9 P negative pressure change from ten for f inches to nine inches mercury. The maximum allowable leakage rate for a four (4) foot diameter manhole le must be in accordance with the following: Minimum Elapsed Time for a: Manhole Depth Pressure Change of 1 Inch Hg 10 feet or less 60 seconds >10 feet but <15 feet 75 seconds >15 feet but <25 feet 90 seconds For manholes fives 5 feet in diameter, add an additional fifteen 15 seconds and for manholes six for feet in diameter, add an additional thirty (30) seconds to the time requirements forfour he foot diameter manholes. For all manholes deeper than twenty-five (25) feet, the Engineer will determine the applicable minimum elapsed time. D. If the manhole fails the test, necessary repairs must be made. The vacuum test and repairs must be repeated until the manhole passes the test. E. If manhole joint sealants are pulled out during the vacuum test, the manhole must be disassembled and the joint sealants replaced. F. Manholes will be subject to visual inspection with all visual leaks being repaired. 5. Butyl rubber coating with plastic wrap shall be applied around each manhole joint from 3- inches above to 3-inches below each joint. The appropriate primer shall be applied prior to applying the rubber coating. Inside joints to be filled with premat plug material. Entire exterior surface of sanitary sewer manholes shall be sprayed with a bituminous coating and all exterior gap exposure of riser rings shall be back plastered or grouted with nonshrink grout. 6. The manhole chimneys, including all riser rings shall be sealed using flex rib internal chimney seal manufactured by Cretex, NPC, or a District approved equal. The flex rib internal chimney seal shall extend from a minimum of 3-inches below the top of the Cone section to 3-inches over the manhole Casting frame or per manufacturers installation procedures if directed otherwise. Internal Chimney Seal shall be installed after manhole vacuum testing and prior to final acceptance. Water test may be done, per manufacturer or Districts recommendation, to provide assurance that internal chimney seal is watertight. 7. The casting elevations are set by plan, however, the castings are to be adjusted in the field by the District's representative should a discrepancy occur between plan grade and existing grade. New manhole rings) and Cover shall be installed to establish grade. Maximum height of adjusting rings shall be 12-inch on existing structure adjustment and 10-inch maximum on new construction. 8. Backfill around all installed or proposed manhole structures, sidewalks, bike paths and/or all paved areas shall be made with granular material (b-bmrow)or No. 8 stone, up to 18-inches below crosssection thickness (which shall include "Ns,. 53" stone depth). If more stringent backfill requirements are set out per city, town, county, or District specifications those standards shall be followed. Trench opening within 5-feet of the back of the curb of paved roadways, shall be backflled with granular material or No. 8 stone in accordance with Section 211 of the current INDOT standard specifcations handbook. 9. The Contractor shall be responsible for verifying that all state highways, city, and county permits have been obtained by the developer prior to start of Construction. 10. Initial asbuilts shall be presented to the inspecting engineer prior to final submittal to the District for review, otherwise Contractor shall be required to furnish the developer's Engineer with a set of prints showing actual sewer locations and inverts including lateral location, depth, and length. Such asbuiit prints must be received by the Engineer before the final contract payment can be authorized. Asbuilts shall be submitted per the Districts cu rent standard which can be fan nd at wwW.chwd.org. 11. The sanitary sewer laterals and stubs termination shall be indicated on the surface with a detectable metal post set immediately above the said termination point if full connection is not immediately made. 12. All sanitary sewer lines upon Completion will be required to pass a low pressure air test. Said test shall be conducted according to ASTM F1417-92, and shall be witnessed by a District employee or the Districts representative. The testing shall be in accordance with Table 1 as follows with 0.5 psi being added for each foot of waterabove the sewer line being tested. Sewer lines shall be subject to visual leak inspection at downstream manholes with all visual leaks being repaired and subject to televising requests by the District. 13. Prior to final deflection test (mandrel test) all mainlines shall be cleaned and free of any debris. Deflection tests shall be performed on all flexible' pipe after the final backfill has been in place at least 30 days. No pipe shall exceed a vertical deflection of 5%deflection test results. ('The fallowing are considered non -flexible pipes: concrete pipe, ductile iron pipe, and Cast iron pipe). The deflection test shall be performed with a nine -point mandrel. Proving rings shall be available at time of test otherwise no testing will be allowed. All mandrel testing shall be witnessed by a District employee or the Districts representative. 14. The ends of all laterals are to be plugged watertight with a gasketed cap capable of withstanding a law pressure air test without leakage. Laterals shall be subject to visual leak inspection at downstream manholes with all visual leaks being repaired 15. Bedding for flexible pipe and rigid pipe shall be No. 8 Crushed stone from 6-inches below RELEASED FOR CONSTRUCTION .)a placed on no leas than 6-inches of No. B Subject to compliance with all regulations of State and Local Codes City of Camel ((�� �vmlUAIILTr1�nDAaL DATE: \ 08/19/19 16. Water line, utility, and legal drain crossings and separations shall be in accordance with the mare stringent of the two: 327 IAC 3-6-9 or the Districts standard drawings. 17. The trench shall be opened sufficiently ahead of pipe laying to reveal obstruction, and shall be properly protected and/or barricaded when left unattended. 18. No water shall be permifled to flow into the sanitary sewer system during Construction. Contractor shall utilize a pump to keep the water level below the pipe. Pump discharge shall be directed to a storm outlet in accordance with state and federal laws and regulations 327 IAC 3-6-20 . An a entering existing sewers shall be plugged with 9 ( ) YPP 9 9 P 99 screw type mechanical, braced plug until such time as all tests on the sewers and all punch list items are complete. 19. All sewer laterals installed shall be bedded the same as the main line sewer. 20. Forty-eight (48) hours notice shall be given to the District prior to the start of sewer construction. Also, 48 hours notice shall be given prior to doing any testing on the sewer. 21. Manhole Castings shall be stamped SANITARY SEWER (Neenah Casting R-1772 or East Jordan 1022Z1GS) and be sel(sealing type. The casting flange shall be 34 inches and the clear opening shall be min. 20-13116 inches. Watertight castings shall be bolt - down East Jordan 1022Z1 PT and also stamped SANITARY SEWER. 22. The minimum slope of the sewer shall be Size of Pipe Minimum Constructed Sid 8-inch 0.40 % 10-inch 0.28 % 12-inch 0.22 % 15-inch 0.15 % 18-inch 0.12 % 23. The Contractor shall provide measurements of the slope of the sewer for each manhole P P section r Constructionprogresses. Such measurements shall be certified b a Registered Y 9 Land Surveyoro than beavailable oon-site for aonstrute by the District's Inspector. en mare than three manhole sections can be constructed in advance of such measurements. 24. In the event the Contractor does not meet the minimum slopes, the sewer section and any other affected sewer sections shall be reconstructed to meet such minimum slopes. 25. Laterals are to be installed with a minimum 14 gauge tracer wire tram the wye to the terminus. Upon lateral completion the contractor for the building or home will extend the wire from this temlinus to the building cleanout adjacent to the building. SUMMARY OF LATERAL INSTALLATION REQUIREMENTS 1. Only one building may connect to the sewer main per lateral mleaS otharv4Se approved by TRON. 2. Foundation drains, sump drains, downspouts and otharstamwaterdmins Mall Never be mnNeded tothesanitary Sewer. site devwtering Systems Shall Never be discharged to Me sanitary server, 3. The existing sewer lire tram the beh irg to Me sepfic tank may Only be mused N it 6 located under a buildimaddilion, patio, pereM1«paved driveway, and Me line passes an air tesflhet is obrervetl by TriGY C rut TrC We more idom:afion about air telling requirements. The properly martens responsible for testing casts. A TriC Mail inspect allnew lateralsor lateral repairs in their Andres. Final connection to the Sanitary Sewer must the observed byl-rim The property owner or contractor mustmtify TWo Fria to heckflliFg.lnspectiwNnust beaMeduled m least 24 Hours in advance. N an inspection fails and Subsequent inspectionsare required, or Nthe contractor is Feet on site for the scheduled inspection, a $100fee will he assessed and From be k rlorto whadulung the reins 5. se -ra stem COMeMs or shall never be dsche etl to sanNa sewer. aeatlVisetl that put healthce mmeMre uktesx c IW r m ry ro r pa q ati systems. Upon camactiOn toaanitarysew«, a septictank mumypirally be abandoned,pumped clean,and filled competaly wind earthen material. Comas your county health departr mnfor more intolmmimm SRI system am abandonment requirements, am to natty Me depanmant of anyabandonment. 6 Th PVC pipe SDR3lor8DR SASToruseingnavilyserver lale21ins1allaliOn orrepair: PVCpipe sOR 3s «sOR 2s, ASTM D3o3a, s' stammer PVC pipe, pressure rated SDR 21, ASTM D2241, 6" diameter PVC restrained joint pipe far directional drilling: Cartago GrAmIireSDR 21,ASTM D2241, W diameter All gasketed joints Shell meat ASTM D3212 All finings Shall be SDR26 or baiter Ductile Goon meManical jant fangs ANY proper be river n BEAR 26 gasketed repair Sleeves or Indiana Beal shear gwN Fence, and similar flexible couplings re only aoce table in and shell Trot be used without Order oval tram TWo a Y P P PP Gkareuls: 6" threaded PVC caps Bedding. Use 98CNsided more or tortured face aggregate The Following materials an amepubk for use in low rea mwer aterainstallatlon or mPr HOPE pipe f«diredmalruling: ORn In Lzs"diaaterPEwic Conneaene stall he made via eleaMusiOn or using polypmpyene or stainless steel compression fittings Eedrauaw high Mduma tapping tee,raed 200 psi, M4710 1251PB full Part1/4tum fusible PEb II valve,rateel 200 psi Tibrearded 9chede valve 316 stainless sterelinited 200 per Caused T Cofaac ble u setiOnmaterials,mend u antl other r requirements repro a s,P P cops ], F it and b systems, the I I th building Mallnot exceetl 3 'n length before a tleanoul must he atltletl and the line g y pressure y rg g gl istrensitionedt 8"diameter SOR35 WC Glued' Man rid allayed after No addaaal load flM a narrowed heMeen Ma building PPa g g a 9 and the lransMbNcbamM For all gravity lines aeaomS shall net bee acad more than 0(YaParthewethe bNH' gand Ma sewer man Sea Tiros standard castings RYr more intwmww tiaeanan m inallatim. 8. BeddingmaterialShellhe laced Water bimheS below l2 include the i ewrtace.The trench Shallbea minimum of l8'4AdewiM at P PP least 6" of clearance On both sides of the pipe.Mmer6lShall be placed over the pipe and tracerwire aNerinspectiOn.Boq unstable or unsuitable material found belcev and near the lateralIncluding any fill or foundation backfill maternal must be removed and roplaosel w8 alone The Contractor 6 wely responsible for esWbl6lirg stable pipe bcdd' gConditions, 9, w101 sdtl Copper tracerwireshall Word On top of and Fun the Mire length of the lateral. AN Elkirg of timerwire shall use3M splice kit model DBRIYEY RUNS Innwa homer conn Direct Bury Lug Aqua Ww03 N9622oor TrKo approved equal. 10. Laterals Shell ter installed at least2C tared water wells unless PVC pressure grade pipe is used. My pmposad'nstallation requiring pressure pipe Shellherev awed by TnCo pnorM nmallm w Wren a transition is made between BEAR 35 pipe and pressure grade BEAR 21 pipe, a ductile Iran gasketedmechanical couplings must be used. 11, Laterals less than 5 deep shall be st least 24" ham the property line. Laterals more than 5 deep all be at least Sol Man the property lire. WTere the lateral more in dope proximity to the property line the prcpMy cMl«s must be accurately maMtl by a professional land surveyor pilot to Inspection. 12. Laterals running parallel to a building or stmaunahell he at least 36" tram Me farm da crawl Space or SET on grade founaton and 6P fain the face of a basement foundation wall. Spacing requirements also apply whh respect to Me anallary unt dura's fouMa4on depth. Ancillary structures (e g. window wells) and other utili es shell net he placed over or Near Me lateral. TriCo may adjust retwernems ARM fMun access to the lateral mayheobstmaedbydherutiftie.TheamtraaasheuMFalltodiswssfdrt rNhe/shebelievesthiswuMheanissue. 13, All intrastructure ConNeaed to TaCo's Reversysternm betened in ed atelevised at TaCcEdimretiOn and mum remain accsssibleand a p PmP Y tl maintained. 14. Call 811 «1-ec0a825.544bef«e you rig. For rtwn information go to www.indiana811.oFg.1f you have any queatbnaoM you waMM request an exception M standards and spreaffirations, pease contain TriCadming mural bu®Ness hours at 317A44-9200 prior to mnpleing the voh and scheduling aninspaction. Go tosomatrooecmo view standard drawings and specifications. Revised NIBGO19 1 1 ra r r-rr r (11PIC4) TOP VIEW WE: SS ROWTOF aN pEO ( SE SEADED RENT 3 Ns, flu MAEMRM mnLMRE MM RSN CONCRETE xaawT 6MM FMINC To ASTM 990 WE: MrptVRY CONCRETE PFCgUCTi, INC APPROXIMATE KOM BASE SECTOR 9375 be MAR SEtDw 7659 be TOP SUB non Itu STRUCTURE MIGHT MT& MM Fa DFfAt 1 44�' - {,1, III` �✓Il�ll'J'.RR��s1Nj5 yy .y MM a � _ Y�.�i .• It Ica � IP Y H �_ �� �mNN IEI NNNW�Ia: ' I•I ��•� 1� _ r r r rrMiYri; Ip• r W�� li I I TT-r-�o_✓ I L_ C rrr rrrrrr rr rrY rrrrrr'}rrrrrr'r IF Zee;t - rr r'It; ift r rrrrrr i-rrrrrr: i, MUM, �i!RiMi01iirifli fi • r •1 (4) 3/bC x J" AANIE55 STEEL 1'-5" IN. ANCNR Sam (APICAL) 1P Ron NRR MNMiau' pjs(ima.) UANl AIR aIRfFN NL avR a0 ALL KUM SiVL ME SEALED By A FlFInBE B111L REM D EE YAUHT (ROPE) CNFOWNG TD AM C Ws, D]PB M AND NMNMS OF NATEP.IAL SHALL Cf DEPENDENT M SEASR OF WT.ND M AND AS pFEDTED BY ENGNEG. CONTRACTOR SHALL GROUT NL INTERNAL MANNRE AMIR We WN-SBRVN CNWT. EACH MANHOLE SECWW SHALL BE SAVED won M EYTERNAL Kew Sand OF INRl GAUGE MAP a MMmACR.wED Br YNNO M1EN5, Mc. ME (9) INCH MN TG UNIRBItWED EARTH ge 'CLENC Ras a M TO I1nL NOW: 1)E meo S PER CODE OR LOCALL 9 I RaEmB. ra MM ALL ME APIVtlh➢ W MOM 2) ME FOR ORiENTATON NU BE DE MOM UPON THE 3) P SHOP GRANTED MUST BE SUBMITTED nl TRILo FOR RE4EM AND APPROVAL. EXTERIOR INTERCEPTOR/SEPARATOR DETAIL INIS MANHOLE CASTING TABLE wGWw MCOD. COVER m xa ream 6.6 ra.-„ro ® cam 4y RAN IF MTL pm MAN OF our m l�n Never,wIY smF UD MERWP IE1Tmmo RTAL # DISTANCE MAY BE IXOEA4D BASED ON THE m nUMM OF THE WASTE mu ROK C WLT rare Hamm BIM MAN%SL U& # # NNIWM UQUO WITH MAY BE RDIMYD OR A CASE -BY -CASE Miss a IFFP BY TIME NOTE, 1) INWMPrw/ MARNI SMI tllliwY To ASTW core unuj 4,000 Pm WHx IxsTAUAnw w r z WNMT OR CAST MIN.. SRIl WTm S/ MARNS &WL ONLY BE INSTALLED 1119w A mmm N" FOR MED CORE RIM OPENING SP NNNw NM RSUENT CwMCTUB jIOR W OJBT N ROUGE AiOC m� llnroICK RNL4 R RIIEIRARXS� �rp CpH 1,1L BF p_ MM Rrc¢T UE Y O N ll"Ci UI IEWAALRIA7 G" STNXLtss CBS- SMART MWM FOR B PVC PIPE flu INnutm Br mHEes (Ica) SE ART DETAIL WANMIM aMF1E IY MINIMUM Mar WASHED 08 SEE MAT FOR ILIflIXG AND SUPPORT TMCO mR - won To Mum SEAL` No4 PREMIUM _ PRECAST @E1EEE MADE 9JM RUBBER SEALANT NM UNG ME e';jIPF�n n OUNT BALL CON WNMEIE CR FLANS fi COUNT (RmE) cMFASIM Tc :::"P cMRN ASTM R90 `,:i : •� , TRICO DETAILS )p •PEGIS Rf0 %IS a -, PEBBQ932 STATE OF :.�Q S /st II do we do we S a4 O Br m tl Mar w 4 u z w ad V Per NW W ry ao ON Ca Ce C4 F W O wI a F U � I O � E N a F w 5 q, a M 'N � e E 41 �a S d Z o ry W Z w0 z - ofNif O n ,f1 W N Ed W WI 0 IYI Ci a cad n a 5 d zD `o is 0- 1� L.La i 3 w 5 E w _ m th S � O Is O 9 � c ad �I p A�1QA�A o +N z z V m U vl F W O r,✓t Z C G W F z r O Z I+y a - z re 2 DO � U DRAWN BY: TEN CHECKED BY: ALD PROJECT No. 1610-024 SHEET No. C6e]