Fa
BUILDING CODES REFERENCED
2014 INDIANA BUILDING CODE (20121BC, 1ST PRINTING)
2012 INDIANA PLUMBING CODE
2014 INDIANA MECHANICAL CODE (20121MC, 1ST PRINTING)
20141NDIANA FIRE CODE (20121FC, 1ST PRINTING)
2009 INDIANA ELECTRICAL CODE (NFPA 70-2008)
ASHRAE 90.1-2007 EDITION
ANSI At 17.1-2009
DESCRIPTION
WOOD FRAMED CONSTRUCTION WITH A COMBINATION OF
MASONRY, CEMENT FIBER BOARD AND EXTERIOR
INSULATED FINISH SYSTEM. STEEL FRAMED
CONSTRUCTION WITH SPRAY -APPLIED FIRE -PROOFING ON
FIRST FLOOR.
TYPE R-2 PRIMARY OCCUPANCY
TYPE V-A CONSTRUCTION
FOUR STORY APARTMENT BUILDING
BUILDING AREA
BUILDING 3
FIRST FLOOR -
SECOND FLOOR -
THIRD FLOOR -
FOURTH FLOOR-
TOTAL -
RELEASED FOR CONSTRUCTION
AUTOMATIC FIRE SUPPRESSION SYSTEM
BUILDING IS REQUIRED TO HAVE AND IS PROVIDED
THROUGHOUT W ITH AUTOMATIC SPRINKLER SYSTEM IN
ACCORDANCE WITH NFPA 13R AND IBC 903.3.1.2.
FIRE EXTINGUISHERS
FIRE EXTINGUISHER CABINETS AT 75' MAX TRAVEL.
FIRE ALARM SYSTEM
COMPLETE FIRE ALARM SYSTEM REQUIRED AND
PROVIDED IN ACCORDANCE WITH NFPA 72 AND IBC.
PROVIDE VISUAL NOTIFICATION (STROBES) IN ACCESSIBLE
UNITS IN ACCORDANCE WITH NFPA 72.
[d•] 9 i �7_\ /_71: Y I q:1: GV [O:Id E139 R �] I: [•IdO �] i
OCCUPANCYGROUP
SECTION 310.3 OCCUPANCY
R2 OCCUPANCY: (RESIDENTIAL, APARTMENT)
M MERCANTILE RETAIL
B BUSINESS (OFFICES)
SEPARATED MIXED USE PER IBC 508:
OCCUPANCY SEPARATIONS INDICATED ON FLOOR PLAN
12,039
GSF
SECTION 510- SPECIAL PROVISIONS
12,523
GSF
HORIZONTAL SEPARATIONS MUSTCOMPLY WITH THE
12,523
GSF
FOLLOWING:
• 3-HR FIRE RESISTANCE RATING
12,523
GSF
THE BUILDING BELOW IS NOT GREATER THAN ONE
49,608
GSF
STORYABOVE GRADE
• THE BUILDING BELOW IS OF TYPE 1A CONSTRUCTION
• ANY SHAFT, STAIRWAYS, RAMP, OR ESCALATOR MUST
BE IN A 2-HOUR RATED ENCLOSURE
• THE BUILDING BELOW IS PROTECTED BY AN
AUTOMATIC FIRE SPRINKLER SYSTEM, PER NFPA 13
SECTION 510.9 MULTIPLE BUILDINGS ABOVE A
HORIZONTAL ASSEMBLY SHALL BE REGARDED AS
SEPARATE BUILDINGS.
BUILDING 3
EQUIPPED WITH NFPA 13 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1
TABLE601 CONSTRUCTION TYPE: V-A
SECTION 708 FIRE BLOCKING REQUIRED
SECTION 718.3.2 DRAFTSTOPPING REQUIRED IN FLOORS, AT EVERY SLEEPING UNIT
SECTION 718.4.2 DRAFTSTOPPING IN ATTICS: REQUIRED, EVERY 3,000 SF
SECTION 903.2.8 GROUP R- AUTOMATIC SPRINKLER SYSTEM NFPA I3R REQUIRED.
SECTION 1023 STAIRWAYS- ENCLOSURE MINIMUM OF 2HR RATING
SECTION SMOKEPROOF ENCLOSURES- NOT RED. WHERE TOP FLOOR IS
1023.11 LESS THAN 75 FT ABOVE FIRE DEPARTMENT ACCESS. (FLOOR
LEVEL OF FOURTH FLOOR IS 37'-0"
CONCEALED SPACES
IBC 718 AND NFPA 13
A. FIREBLOCKING: REQUIRED, BOTH VERTICAL AND HORIZONTAL
10' INTERVALS BEHIND TRIM FINISHES.
FIRE BLOCKING SHALL CONSIST OF ONE OF THE FOLLOWING: APPROVED
NONCOMBUSTIBLE MAT 2" OR (2) 1" LUMBER WIBROKEN LAP JOINTS, 1 23/32" WOOD
STRUCTURAL PANEL W/JOINTS BACKED BY 23/32" STRUCTURAL PANEL OR 2X LUMBER.
B. DRAFTSTOPPING IN FLOORS: PER IBC 718.3.
C. DRAFTSTOPPING IN ATTIC: PER IBC 718.4.2.
PENETRATIONS THROUGH FIRE RATED ASSEMBLIES
A. REFER TO SECTION 714
EXIT SIGNS S EMERGENCY LIGHTING
EXIT SIGNS PROVIDED PER IBC 1013, INTERNAL BATTERY BACKUP. FLOOR -LEVEL EXITS
SIGNS PROVIDED PER IBC 1013.2.
MEANS OF EGRESS ILLUMINATION AND EMERGENCY LIGHTING PROVIDED PER IBC 1008.
ELEVATOR
REQUIRED TO MEET ASME At 7.1
EXIT 8
0.2" 32
7n IA"
z SECOND FLOOR LIFE SAFETY PLAN
A8-201 SCALE: 3/32" = 1'-0"
STAIR B
32
mn
AW
MEANS OF EGRESS BUILDING 3
REQUIREMENT
REQUIRED
PROVIDED
NUMBER OF EXITS
2 PER FLOOR
2 PER FLOOR
STAIR WIDTH
44"MIN
48"WIDTH PROVIDED
CORRIDOR WIDTH
44" MIN
60" MIN
EGRESS DOOR SIZE
32" MIN
32" MIN PROVIDED
TABULAR OCCUPANT LOAD, BUILDING 3 (IBC 1004.1.2)
FLOOR
OCC. TYPE
AREA (SF)
FACTOR
(SF/PERSON)
OCC. LOAD
(PERSONS)
FIRST
MERCANTILE
12,039 SF
1/60 GROSS
201
SECOND
RESIDENTIAL
12,435 SF
1/200 GROSS
63
MECHANICAL
88 SF
1/300 GROSS
1
THIRD
RESIDENTIAL
12,435 SF
1/200 GROSS
63
MECHANICAL
88 SF
1/300 GROSS
1
FOURTH
RESIDENTIAL
12,435 SF
1/200 GROSS
63
MECHANICAL
88 SF
1/300 GROSS
1
BUILDING TOTAL
I
I
1
1 393
10
EXIT 7
0.2"
32
l70
T 34"
FIRE RESISTIVE RATINGS ( TABLE 601 )
STRUCTURAL ELEMENT
F.R. RATING
F.R. RATING
DESIGN NUMBER
PER CODE
PER DESIGN
BEARING WALLS (V-A)
EXT. WALLS (112)
1 HOUR
1 HOUR
U.L. #U356
INT. WALLS
1 HOUR
1 HOUR
U.L. #U305
CORRIDOR WALLS (112)
30 MIN
1 HOUR
U.L. #U311
OPENING PROTECTION
20 MIN
20 MIN
GUESTROOM SEPARATION
1 HOUR
1 HOUR
U.L #U311
OPENING PROTECTION
45MIN
60 MIN
STAIR (INT. WALLS)
2 HOUR
2 HOUR
U.L #U301
STAIR (EXT. WALLS)
1 HOUR
1 HOUR
U.L #U356
OPENING PROTECTION
90 MIN
90 MIN
ELEVATORS
2 HOUR
2 HOUR
U.L.#U906
OPENING PROTECTION
90 MIN
90 MIN
---
CEILING
-
-
---
STORAGE,TIECH
1 HOUR
1 HOUR
U.L#U305
FLOOR -ABOVE RETAIL
1 HOUR
1 HOUR
U.L. #G801
FLOOR - CEILING
1HOUR
1HOUR
U.L.#L521
ROOF - CEIUNG cQ STAIR
ROOF - CEIUNG
1HOUR
1HOUR
U.L.#P522
SHAFT
1 HOUR
1 HOUR
U.L. #U305
STAIR
A
0.3"
32
160
48"
11
EGRESS ELEMENT
OCCUPANTS SERVED
(REQUIRED)
EGRESS WIDTH
(PROVIDED)
OCCUPANTS SERVEC
(PROVIDED)
REQUIRED ELEMENT
WIDTH
1 HOUR RATED
w w FIRE BARRIER
2 HOUR RATED
w w w FIRE BARRIER
EXIT
EXIT SIGN - SEE
ELECTRICAL
SPACE AREA
FUNCTION OF SPACE
BUSINESS
6000 SF
B
OCCUPANCY
1 / 100 60
2
CLASSIFICATION
NUMBER OF REQUIRED
EXITS
NUMBER OF OCCUPANTS
REQUIRED S.F. PER
OCCUPANT
TRAVEL DENOTES EXIT
DISTANCE ROUTE
100' - 6"
♦��GEEDGEND 4
L START DENOTES EXIT
POINT DISCHARGE
SEMI -RECESSED PORTABLE FIRE
EEL
EEL
EXTINGUISHER CABINETWITH
PORTABLE FIRE EXTINGUISHER PER
NFPA 72 AS SELECTED BY LOCAL FIRE
MARSHALL. REFER TO DETAIL 10/A-602.
FE
WALL MOUNTED PORTABLE FIRE
EXTINGUISHER PER NFPA 72 AS
SELECTED BY LOCAL FIRE MARSHALL.
W®®LPERT
ARCXIIELTUREj1eNGINEEWNGjGEGSPATILL
7635 Interactive Way
Suite 100
G
Indianapolis, IN
46278
317.299.7500
FAX: 317.291.5805
U
J
J
Q
0
0
sE
CID
Q Issuances:
NEW
Mcm"M
DATE
0
Issued For Building 3 Reviea
10/12/18
1
Issued For Building 3Permit
06/10/19
Prom. No.: 074904
Date: 10/12/18
Sheet Name:
FIRST AND SECOND
FLOOR LIFE SAFETY
PLANS
Subject to compliance with all regulations
of State and Local Codes
City of Cannel /�
�N�1 10300:aUMASL
DATE: 10/31/19
FIRST FLOOR LIFE SAFETY PLAN
SCALE: 3/32" = 1'-0"
LS3=101