WEIGHTED BACK -DRAFT DAMP
FOR AIR RELIEF
GRILLE (REFER TO PL
FOR SIZE AND TYPE)
SHEET METAL SLEEVI
AIR RELIEF DETAIL
NTS
SUPPLY, RETUW
EXHAUST DUCT
BREAK -AWAY
DUCT CONNECTI
GALV. STEEL SLEEVE M
VALL LOUVER. SEAL ALL
,ROUND WITH SILICONE.
EXTERIOR WALL
ACCESS PANEL WITH LATCHES. PANEL
SHALL BE RATED FOR STATIC PRESSURE
OF DUCT SYSTEM. PROVIDE INSULATED
ACCESS PANELS FOR INSULATED OR LINED
DUCT SYSTEMS.
r;[HalliHxHA4I[•91gq�a19E]i•�
165 DEGREE FUSIBLE LINK
1.5'X1.5'X1/8' STEELANGLE
BOLTED TO SLEEVE.
GAUGE TO MATCH DUCT
FLOOR SLAB
SYSTEM. 24 GAUGE MINIMUM.
ULCLASSIFIED 1-1/2 HOUR
20 GAUGE GALV. STEEL FRAME
FIRE DAMPER FOR STATIC
SYSTEMS
n HORIZONTAL
FIRE/SMOKE DAMPER DETAIL
U NTS
OKEYED NOTES:
1. SIDEWALL EXHAUST FAN WITH GRILLE
2. STUD WALL
3. OUTLET FLANGE
4. BACKDRAFT OR MOTOR OPERATED DAMPER
(SEE SCHEDULE SPECS)
5. 4' METAL EXHAUST DUCT UP INTO CEILING
SPACE AND OUT SIDEWALL WITH LOUVER.
SIDEWALL EXHAUST FAN
NTS
0
n F-1
V
DOG HOUSE FOR REFRIGERANT PIING
NITS
CEILING SLEEVE: MINIMU
GAUGE FOR DAMPERS NI
EXCEEDING 24'X24- 16 G/
FOR LARGER SIZES
NOTE
CONNECT SLEEVE TO DIFFU
COLLAR ALL SIDES OF DEVIL
AS REQUIRED BY U.L. LABEL
LES 1-1/2' X 1-1/2' X 1/8-
MUM; FASTENED TO SLEEVE AS
UIRED BY U.L. LABEL; ANGLES TO
RLAP MASONRY OPENING MINIMUM 1'
)AMPER
ED CEILING
TION
CEILING/AIR DEVICE MOUNTED FIRE DAMPER DETAIL
NTS
KEYED NOTES:
1. 2' x 4' TREATED NAILER
2. ANCHOR TO DECK
3. 1' LINED
4. OPENING THRU ROOF. SIZE BASED ON PIPING
INSTALLATION REQUIREMENTS.
5. DOUBLE WALL V2' INSULATED CAP
6. 20 GAUGE GALV. SHEET METAL.
7. CANT REQUIRED FOR BUILT-UP ROOFING.
DELETE CANT FOR ANY NON BUILT-UP
ROOFING SYSTEM AND FLASH TO BELOW
CURB CAP.
8. SECURE CAP TO BASE WITH 1 SCREW PER
SIDE.
9. 24 GAUGE GALV. SHEET METAL THIMBLE FOR
PIPE PASSAGE CAULK THIMBLE AT DOG
HOUSE AND AT PIPE PENETRATION.
REFER TO STR I'^T"�^'
DRAWINGS FOF
FASTEN WITH
MASONRVANC
EXHAUSTFAN
FAN ENCLOSURE
PREMANUFACTURED
(ALUMINUM PAINTED
GALVANIZED STEEL)
HOOD
ALUMINUM BACKDRAFT DAMPER
WITH COUNTER BALANCE
WALL LOUVER SIMILAR TO RUSKIN
ELF3750. REFER TO SPECIFICATIONS.
SHEET METAL SLEEVE
EXTERIOR WALL
EXHAUST FAN WITH LOUVER DETAIL
NTS
14' HIGH 18 GAUGE
BIRD SCREEN GALVANIZED STEEL
WELDED CURB
FILL GAPS WITH ~ ~��� ~
EXPANDABLE FOAM GRAVITY BACKDRAFT
SEALANT DAMPER WITH BLADE
SEALS, SHAFT SEALS
DISCHARGE DUCT AND COUNTER BALANCE
n ROOF MOUNTED EXHAUST HOOD
U NTS
GALVANIZED STEEL SLEEVE.
METAL GAUGE TO MATCH DUCT NOTE: MECHANICAL CONTRACTOR TO COORDINATE
SYSTEM. 24 GAUGE MINIMUM. VTR EXACT TRUSS LOCATION AND/OR TRUSS QUANTITY
WITH TRUSS SUPPLIER. SUPPLY AIR PLENUM ON TOP
OF HVAC UNIT TO EXTEND UP INTO TRUSS SPACE, NO
TRUSSES TO BE LOCATED ABOVE SUPPLYAIR
1.5' X 1.5' X 1/8' STEEL ANGLE
BOLTED TO SLEEVE PLENUM.
24GAGE
BI-ADE GALVANIZED BREAK -AWAY DUCTCONNECTION
STEEL BLADES �jl���//////
FUSIBLE LINK
20 GAUGE STEEL BLADES J �• ACCESS PANEL WITH LATCHES. PANEL
SHALL BE RATED FOR STATIC PRESSURE
ULCLASSIFIED 1-1/2 HOUR FIRE OF DUCT SYSTEM. PROVIDE INSULATED
DAMPER FOR STATIC SYSTEMS ACCESS PANELS FOR INSULATED OR
LINED DUCT SYSTEMS.
2 HOUR FIRE RATED PARTITION.
SEE ARCHITECTURAL DRAWINGS
FOR LOCATIONS.
T
YPE B VERTICAL FIRE DAMPER DETAIL
NTS
BRAMEC 4007BLK SCRE WUP FOOT AT
EA. CORNER, INVERTED AND
FASTENED TO UNIT
DIVERSITECH MP4C ANTI -VIBRATION
PADS ADHERED TO BOTTOM OF FOOT
TPO SLIP SHEET PROTECTION
LAYER AT EA. SUPPORT
.060 TPO FULLY ADHERED
MEMBRANE ROOFING OVER
1/2' FIBER BD. OVER 314' COX
PLYWOOD SHEATHING ON
ENGINEERED WOOD TRUSS
CONSTRUCTION
NOTE:'
ROOF DECK
A. CONDENSING UNITS MUST BE ANCHORED TO
ROOF TO RESIST WIND FORCES -ANCHORAGE
SHALL BE COORDINATED AND SPECIFIED BY
MECH. CONTRACTOR AND EQUIPMENT
SUPPLIER.
RELEASED FOR CONSTRUCTION UPPORT RAIL
Subject to compliance with all regulations
of State and Local Codes
City of Canned
DATE: 10/31/19
ENT OR INTAKE
ESS STEEL BAND CLAMP
ILE RUBBER OR
RENE BOOT
ILE SEALANT
LES
VENT THRU ROOF DETAIL
NTS
12' FLEX DUCT
16' SUPPLY
AIR PLENUM
2' PVC EXHAUST
IN WALL
W
W
2 CLOSET
WALL
2' PVC INTAKE,
SEE PLAN AND
SCHEDULE —
A -COIL
(SEE SCHEDUL
w 14'x21'x22'T
RINNAI
BLOWER
NO
(SEE SCHEDULE)
U
SIDE
W
FILTER
RACK
a
mJ14mx22mx34mT
z
�W oWCLOSET
WALL
w
z
2
T
m
1
o
a
}
INNAI
HEATER
(SEE SCHEDULE)
18.5"x26.4"xll.4'
I
N
12' CLEARANCE
MECHANICAL CLOSET SECTION
NTS
A
PLENUM
REFRIGERANT LINES TO
CONDENSING UNIT
RINNAI HVDRONIC
AIR HANDLER —
6.
FLOW CHECK VALVE (IFC)
BLOWER ASSEMBLY —
FLEXIBLE DUCT. MAXIMUM LENGTH T-0'.
MINIMIZE ABRUPT OR SHORT RADIUS
TURNS.(TENANT ROOMS EXEMPT FROM
MAX LENGTH REQUIREMENT)
ICI
STRAP HANGERS(TYP)
PROVIDE INSULATED ROUND PIPE WHERE
ENTIRE RUNOUT EXCEEDS 5'-0' IN LENGTH.
SEE DUCT SCHEDULE ON DRAWINGS FOR
INSULATION TYPE AND THICKNESS.
VOLUME DAMPER W ITH
LOCKING QUADRANT
AND POSITION MAIN DUCT
INDICATOR
DUCT COLLAR
SEALCON14ECTION
BETWEEN
THE DUCT COLLAR
AND THE DUCTWORK
CEILING MOUNTED ACCESSIBLE CEILING
AIR DEVICE
NOTE:
1. SEAL ENDS OF FLEXIBLE DUCT WITH TAPE AND SEAL JOINTS BETWEEN THE DUCT
COLLAR AND THE MAIN DUCT.
2. DAMPER QUADRANT SHALL PENETRATE THE INSULATION AND SUFFICIENT SPACE SHALL
BE ALLOWED FOR OPERATION.
SUPPLY OR EXHAUST RUNOUT DETAIL
NITS
EVAPORATOR COIL
HVDRONIC HEATING COIL
AIR SEPARATOR
FLOW SENSOR
CONTROLBOX
II114VA1wIalC11
VALVE STUBS FROM
TANKLESS WATER
HEATER BY P.C.
PLUMBING
EXPANSION
TANK
NOTE: ALL PIPING TO BE POTABLE GRADE COPPER
PIPING AND BRASS APPURTENANCES ONLY.
TYPICAL PIPING ARRANGEMENT FOR DIRECT SPACE HEATING
ANTS
WOOLPERT
ARCNITECTNREIENCINEERINCICEMATI1L
7635 Interactive Way
Suite 100
C Indianapolis, IN
46278
317.299.7500
FAX: 317.291.5805
F
E
V�
D
Ll
nO
W
Q
E
U
C J
J � Of y ��VVVAIIJJJ111
U
U
c
nl
OOc
0
m M
(Y]
Q my
^^,, U c
N W C �°
0C
F
L y N
U m
B �U
L Issuances:
Raw
DRIM moN
DATE
0
Issued For Building 3 Review
10/12/18
1
Issued For Building 3 Permit
06/10/19
2
ASI #10
09/11/19
Prom. No.: 074904
Date: 06/10/19
A Sheet Name:
HVAC DETAILS
M3=501