HomeMy WebLinkAbout(16) M3-5011 2 3 4 5 6 7 8 9 N W a: m D a L) U W M C m cD O rn a C 00 Of E U a rn a WEIGHTED BACK -DRAFT DAMP FOR AIR RELIEF GRILLE (REFER TO PL FOR SIZE AND TYPE) SHEET METAL SLEEVI AIR RELIEF DETAIL NTS SUPPLY, RETUW EXHAUST DUCT BREAK -AWAY DUCT CONNECTI GALV. STEEL SLEEVE M VALL LOUVER. SEAL ALL ,ROUND WITH SILICONE. EXTERIOR WALL ACCESS PANEL WITH LATCHES. PANEL SHALL BE RATED FOR STATIC PRESSURE OF DUCT SYSTEM. PROVIDE INSULATED ACCESS PANELS FOR INSULATED OR LINED DUCT SYSTEMS. r;[HalliHxHA4I[•91gq�a19E]i•� 165 DEGREE FUSIBLE LINK 1.5'X1.5'X1/8' STEELANGLE BOLTED TO SLEEVE. GAUGE TO MATCH DUCT FLOOR SLAB SYSTEM. 24 GAUGE MINIMUM. ULCLASSIFIED 1-1/2 HOUR 20 GAUGE GALV. STEEL FRAME FIRE DAMPER FOR STATIC SYSTEMS n HORIZONTAL FIRE/SMOKE DAMPER DETAIL U NTS OKEYED NOTES: 1. SIDEWALL EXHAUST FAN WITH GRILLE 2. STUD WALL 3. OUTLET FLANGE 4. BACKDRAFT OR MOTOR OPERATED DAMPER (SEE SCHEDULE SPECS) 5. 4' METAL EXHAUST DUCT UP INTO CEILING SPACE AND OUT SIDEWALL WITH LOUVER. SIDEWALL EXHAUST FAN NTS 0 n F-1 V DOG HOUSE FOR REFRIGERANT PIING NITS CEILING SLEEVE: MINIMU GAUGE FOR DAMPERS NI EXCEEDING 24'X24- 16 G/ FOR LARGER SIZES NOTE CONNECT SLEEVE TO DIFFU COLLAR ALL SIDES OF DEVIL AS REQUIRED BY U.L. LABEL LES 1-1/2' X 1-1/2' X 1/8- MUM; FASTENED TO SLEEVE AS UIRED BY U.L. LABEL; ANGLES TO RLAP MASONRY OPENING MINIMUM 1' )AMPER ED CEILING TION CEILING/AIR DEVICE MOUNTED FIRE DAMPER DETAIL NTS KEYED NOTES: 1. 2' x 4' TREATED NAILER 2. ANCHOR TO DECK 3. 1' LINED 4. OPENING THRU ROOF. SIZE BASED ON PIPING INSTALLATION REQUIREMENTS. 5. DOUBLE WALL V2' INSULATED CAP 6. 20 GAUGE GALV. SHEET METAL. 7. CANT REQUIRED FOR BUILT-UP ROOFING. DELETE CANT FOR ANY NON BUILT-UP ROOFING SYSTEM AND FLASH TO BELOW CURB CAP. 8. SECURE CAP TO BASE WITH 1 SCREW PER SIDE. 9. 24 GAUGE GALV. SHEET METAL THIMBLE FOR PIPE PASSAGE CAULK THIMBLE AT DOG HOUSE AND AT PIPE PENETRATION. REFER TO STR I'^T"�^' DRAWINGS FOF FASTEN WITH MASONRVANC EXHAUSTFAN FAN ENCLOSURE PREMANUFACTURED (ALUMINUM PAINTED GALVANIZED STEEL) HOOD ALUMINUM BACKDRAFT DAMPER WITH COUNTER BALANCE WALL LOUVER SIMILAR TO RUSKIN ELF3750. REFER TO SPECIFICATIONS. SHEET METAL SLEEVE EXTERIOR WALL EXHAUST FAN WITH LOUVER DETAIL NTS 14' HIGH 18 GAUGE BIRD SCREEN GALVANIZED STEEL WELDED CURB FILL GAPS WITH ~ ~��� ~ EXPANDABLE FOAM GRAVITY BACKDRAFT SEALANT DAMPER WITH BLADE SEALS, SHAFT SEALS DISCHARGE DUCT AND COUNTER BALANCE n ROOF MOUNTED EXHAUST HOOD U NTS GALVANIZED STEEL SLEEVE. METAL GAUGE TO MATCH DUCT NOTE: MECHANICAL CONTRACTOR TO COORDINATE SYSTEM. 24 GAUGE MINIMUM. VTR EXACT TRUSS LOCATION AND/OR TRUSS QUANTITY WITH TRUSS SUPPLIER. SUPPLY AIR PLENUM ON TOP OF HVAC UNIT TO EXTEND UP INTO TRUSS SPACE, NO TRUSSES TO BE LOCATED ABOVE SUPPLYAIR 1.5' X 1.5' X 1/8' STEEL ANGLE BOLTED TO SLEEVE PLENUM. 24GAGE BI-ADE GALVANIZED BREAK -AWAY DUCTCONNECTION STEEL BLADES �jl���////// FUSIBLE LINK 20 GAUGE STEEL BLADES J �• ACCESS PANEL WITH LATCHES. PANEL SHALL BE RATED FOR STATIC PRESSURE ULCLASSIFIED 1-1/2 HOUR FIRE OF DUCT SYSTEM. PROVIDE INSULATED DAMPER FOR STATIC SYSTEMS ACCESS PANELS FOR INSULATED OR LINED DUCT SYSTEMS. 2 HOUR FIRE RATED PARTITION. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS. T YPE B VERTICAL FIRE DAMPER DETAIL NTS BRAMEC 4007BLK SCRE WUP FOOT AT EA. CORNER, INVERTED AND FASTENED TO UNIT DIVERSITECH MP4C ANTI -VIBRATION PADS ADHERED TO BOTTOM OF FOOT TPO SLIP SHEET PROTECTION LAYER AT EA. SUPPORT .060 TPO FULLY ADHERED MEMBRANE ROOFING OVER 1/2' FIBER BD. OVER 314' COX PLYWOOD SHEATHING ON ENGINEERED WOOD TRUSS CONSTRUCTION NOTE:' ROOF DECK A. CONDENSING UNITS MUST BE ANCHORED TO ROOF TO RESIST WIND FORCES -ANCHORAGE SHALL BE COORDINATED AND SPECIFIED BY MECH. CONTRACTOR AND EQUIPMENT SUPPLIER. RELEASED FOR CONSTRUCTION UPPORT RAIL Subject to compliance with all regulations of State and Local Codes City of Canned DATE: 10/31/19 ENT OR INTAKE ESS STEEL BAND CLAMP ILE RUBBER OR RENE BOOT ILE SEALANT LES VENT THRU ROOF DETAIL NTS 12' FLEX DUCT 16' SUPPLY AIR PLENUM 2' PVC EXHAUST IN WALL W W 2 CLOSET WALL 2' PVC INTAKE, SEE PLAN AND SCHEDULE — A -COIL (SEE SCHEDUL w 14'x21'x22'T RINNAI BLOWER NO (SEE SCHEDULE) U SIDE W FILTER RACK a mJ14mx22mx34mT z �W oWCLOSET WALL w z 2 T m 1 o a } INNAI HEATER (SEE SCHEDULE) 18.5"x26.4"xll.4' I N 12' CLEARANCE MECHANICAL CLOSET SECTION NTS A PLENUM REFRIGERANT LINES TO CONDENSING UNIT RINNAI HVDRONIC AIR HANDLER — 6. FLOW CHECK VALVE (IFC) BLOWER ASSEMBLY — FLEXIBLE DUCT. MAXIMUM LENGTH T-0'. MINIMIZE ABRUPT OR SHORT RADIUS TURNS.(TENANT ROOMS EXEMPT FROM MAX LENGTH REQUIREMENT) ICI STRAP HANGERS(TYP) PROVIDE INSULATED ROUND PIPE WHERE ENTIRE RUNOUT EXCEEDS 5'-0' IN LENGTH. SEE DUCT SCHEDULE ON DRAWINGS FOR INSULATION TYPE AND THICKNESS. VOLUME DAMPER W ITH LOCKING QUADRANT AND POSITION MAIN DUCT INDICATOR DUCT COLLAR SEALCON14ECTION BETWEEN THE DUCT COLLAR AND THE DUCTWORK CEILING MOUNTED ACCESSIBLE CEILING AIR DEVICE NOTE: 1. SEAL ENDS OF FLEXIBLE DUCT WITH TAPE AND SEAL JOINTS BETWEEN THE DUCT COLLAR AND THE MAIN DUCT. 2. DAMPER QUADRANT SHALL PENETRATE THE INSULATION AND SUFFICIENT SPACE SHALL BE ALLOWED FOR OPERATION. SUPPLY OR EXHAUST RUNOUT DETAIL NITS EVAPORATOR COIL HVDRONIC HEATING COIL AIR SEPARATOR FLOW SENSOR CONTROLBOX II114VA1wIalC11 VALVE STUBS FROM TANKLESS WATER HEATER BY P.C. PLUMBING EXPANSION TANK NOTE: ALL PIPING TO BE POTABLE GRADE COPPER PIPING AND BRASS APPURTENANCES ONLY. TYPICAL PIPING ARRANGEMENT FOR DIRECT SPACE HEATING ANTS WOOLPERT ARCNITECTNREIENCINEERINCICEMATI1L 7635 Interactive Way Suite 100 C Indianapolis, IN 46278 317.299.7500 FAX: 317.291.5805 F E V� D Ll nO W Q E U C J J � Of y ��VVVAIIJJJ111 U U c nl OOc 0 m M (Y] Q my ^^,, U c N W C �° 0C F L y N U m B �U L Issuances: Raw DRIM moN DATE 0 Issued For Building 3 Review 10/12/18 1 Issued For Building 3 Permit 06/10/19 2 ASI #10 09/11/19 Prom. No.: 074904 Date: 06/10/19 A Sheet Name: HVAC DETAILS M3=501