STATEMENT OF SPECIAL INSPECTIONS CONT.:
REQUIRED VERIFICATION AND INSPECTION OF SPRAYED FIRE-RESISTANT MATERIALS:
REQUIRED
VERIFICATION AND INSPECTION
CONTINUOUS
PERIODIC
YES
NO
THE SURFACES SHALL BE PREPARED IN ACCORDANCE WITH
THE APPROVED FIRE -RESISTANCE DESIGN AND THE
ALL SURFACES TO BE
APPROVED MANUFACTURER'S WRITTEN INSTRUCTIONS. THE
INSPECTED BEFORE THE
PREPARED SURFACE OF STRUCTURAL MEMBERS TO BE
APPLICATION OF THE
X
SPRAYED SHALL BE INSPECTED BEFORE THE APPLICATION
SPRAYED FIRE-RESISTANT
OF THE SPRAYED FIRE-RESISTANT MATERIAL.
MATERIAL.
THE INSPECTOR SHALL VERIFY THAT THE MINIMUM AMBIENT
TEMPERATURE BEFORE AND AFTER APPLICATION AS
X
X
SPECIFIED IN THE APPROVED MANUFACTURER'S WRITTEN
INSTRUCTIONS IS MAINTAINED.
THE INSPECTOR SHALL VERIFY THE AREA FOR APPLICATION
IS VENTILATED DURING AND AFTER APPLICATION AS
X
X
REQUIRED BY THE APPROVED MANUFACTURER'S WRITTEN
INSTRUCTIONS
INSPECTION FOR MASTIC AND INTUMESCENT FIRE-
RESISTANT COATINGS APPLIED TO STRUCTURAL ELEMENTS
AND DECKS SHALL BE IN ACCORDANCE WITH AWCI I2-B.
X
X
INSPECTIONS SHALL BE BASED ON THE FIRE -RESISTANCE
DESIGN AS DESIGNATED IN THE APPROVED CONSTRUCTION
DOCUMENTS.
THE INSPECTOR SHALL VERIFY THE AVERAGE THICKN ESS OF THE SPRAYED FIRE-RESISTANT MATERIALS APPLIED TO
STRUCTURAL ELEMENTS IS NOT LESS THAN THE THICKNESS REQUIRED BY THE APPROVED FIRE-RESISTANT DESIGN.
THICKNESS SHALL BE DETERMINED IN ACCORDANCE WITH ASTM E605. THE THICKNESS OF THE SPRAYED FIRE-
RESISTANT MATERIAL APPLIED TO FLOOR, ROOF AND WALL ASSEMBLIES SHALL BE DETERMINED IN ACCORDANCE
WITH ASTM E605 BY TAKING THE AVERAGE OF NOT LESS THAN FOUR MEASUREMENTS FOR EACH 1,000 SQUARE FEET
OF THE SPRAYED AREA ON EACH FLOOR, ROOF, WALL OR PART THEREOF. THE THICKNESS OF SPRAYED FIRE-
RESISTANT MATERIAL APPLIED TO STRUCTURAL MEMBERS SHALL BE DETERMINED IN ACCORDANCE WITH ASTM E605.
THICKNESS TESTING SHALL BE PERFORMED ON NOT LESS THAN 25%OF THE STRUCTURAL MEMBERS ON EACH
FLOOR.
A. INDIVIDUALLY MEASURED THICKNESS, WHICH EXCEEDS THE THICKNESS SPECIFIED IN A DESIGN BY 1/4" OR
MORE SHALL BE RECORDED AS THE THICKNESS SPECIFIED IN DESIGN PLUS 1/4".
B. FOR DESIGN THICKNESSES GREATER THAN 1", THE MINIMUM ALLOWABLE INDIVIDUAL THICKNESS SHALL BE
THE DESIGN THICKNESS MIN US 25%.
THE INSPECTOR SHALL VERIFY THE DENSITY OF THE SPRAYED FIRE-RESISTANT MATERIAL IS NOT LESS THAN THE
DENSITY REQUIRED IN THE APPROVED FIRE-RESISTANT DESIGN. THE DENSITY OF SPRAYED FIRE-RESISTANT
MATERIAL SHALL BE DETERMINED IN ACCORDANCE WITH ASTM A605.
THE INSPECTOR SHALL VERIFY THE COHESIVE/ADHESIVE BOND STRENGTH OF THE CURED SPRAYED FIRE-RESISTANT
MATERIAL APPLIED TO STRUCTURAL ELEMENTS IS NOT LESS THAN 150 POUNDS PER SQUARE FOOT. THE
COHESIVE/ADHESIVE BOND STRENGTH SHALL BE DETERMINED IN ACCORDANCE TO ASTM A736 BY TESTING IN -PLACE
SAMPLES OF SPRAYED FIRE-RESISTANT MATERIAL. THE TEST SAMPLES SHALL BE SELECTED FROM EACH FLOOR,
ROOF AN D WALL ASSEMBLY AT A RATE OF ONE SAMPLE FOR EVERY 10,000 SQUARE FOOT OF SPRAYED AREA IN EACH
STORY. THE TEST SAMPLES SELECTED FROM BEAMS, GIRDERS, JOISTS, TRUSSES AND COLUMNS SHALL BE AT RATE
OF NOT LESS THAN ONE SAMPLE FOR EACH TYPE OF STRUCTURAL FRAMING MEMBER FOR EVERY 10,000 SQUARE
FOOT OF FLOOR AREA OR PART THEREOF.
THE INSPECTOR SHALL PROVIDE A FINAL INSPECTION REPORT AFTER PATCHING AND REPAIR OF DAMAGED OR NOW
COMPLIANT SPRAYED FIRED -RESISTANT MATERIALS.
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Camel
',PAG11
SPECIAL INSPECTION AND TESTS FOR MASONRY CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE QUALITY
ASSURANCE PROGRAM REQUIREMENTS OF THE MASONRY SOCIETY (TMS) 402/ACI 530/ASCE 5 AND TMS 602JACI
530.1/ASCE 6.
TABLE 3.1.1- LEVEL A QUALITY ASSURANCE
MINIMUM VERIFICATION
PRIOR TO CONSTRUCTION, VERIFY CERTIFICATES OF COMPLIANCE USED IN MASONRY CONSTRUCTION
TABLE 3.1.2- LEVEL B QUALITY ASSURANCE
MINIMUM TESTS
VERIFICATION OF SLUMP FLOW AND VISUAL STABILITY INDEX (VSI) AS DELIVERED TO THE PROJECT SITE
IN ACCORDANCE WITH SPECIFICATION ARTICLE 1.5B.1.b.3 FOR SELF -CONSOLIDATING GROUT
VERIFICATION OF fMAND f� IN ACCORDANCE WITH SPECIFICATION ARTICLE 1AB PRIORTO
CONSTRUCTION, EXCEPT WHEN SPECIFICALLY EXEMPTED BY THIS CODE
MINIMUM SPECIAL INSPECTION
INSPECTION TASK
FREQUENCYI°I
REFERENCE FOR CRITERIA
TMS 402/
TM$602/
CONTINUOUS
PERIODIC
ACI530/
ACI 530.1/
ASCE 6
ASCE 6
1. VERIFY COMPLIANCE WITH THE
X
Art 1.5
APPROVED SUBMITTALS
2. AS MASONRY CONSTRUCTION
BEGINS, VERIFY THAT THE
FOLLOWING ARE IN COMPLIANCE:
a. PROPORTIONS OF SITE-
X
Ad. 2.1, 2.6 A
PREPARED MORTAR
b. CONSTRUCTION OF MORTAR
X
AN. 3.3 B
JOINTS
c. GRADE AND SIZE OF
PRESTRESSING TENDONS
X
AN. 2.4 B, 2.4 H
AND ANCHORAGES
d. LOCATION OF REINF,
CONNECTORS, AND
X
Ad. 3.4.3.6 A
PRESTRESSING TENDONS
AND ANCHORAGES
e. PRESTRESSING TECHNIQUE
X
AN. 3.6B
I. PROPERTIES OF THIN -BED
XI^I
XI°I
AN. 2.1C
MORTAR FOR AAC MASONRY
3. PRIOR TO GROUTING, VERIFY THAT
THE FOLLOWING ARE IN COMPLIANCE:
a. GROUTSPACE
X
Ad. 3.2 D. 3.2F
b. GRADE, TYPE, AND SIZE OF
REINF. AND ANCHOR BOLTS,
X
AND PRESTRESSING
Sect. 6.1
Ad. 2.4. 3.4
TENDONS AND ANCHORAGES
c. PLACEMENT OF REINF.,
Sect. 6.1,
CONNECTORS, AND
X
6.2.1, 6.2.6,
Ad. 3.2 E, 3.41
PRESTRESSING TENDONS
627
3.6A
AND ANCHORAGES
d. PROPORTIONS OF SITE -
PREPARED GROUT AND
Art 2.6 B, 2.4
PRESTRESSING GROUT FOR
X
G.1.b
BONDEDTENDONS
e. CONSTRUCTION OF MORTAR
X
M. 3.3 B
JOINTS
4. VE RIFY D U R IN G CON STRU CTION:
a. SIZE AND LOCATION OF
X
M. 3.3 F
STRUCTURAL ELEMENTS
b. TYPE, SIZE, AND LOCATION OF
ANCHORS, INCLUDING OTHER
DETAILS OR ANCHORAGE OF
X
Sect. 1.2.1(e),
MASONRY TO STRUCTURAL
6.1.4.3. 6.2.1
MEMBERS, FRAMES, OR
OTHER CONSTRUCTION
Sect 8.1.6.7.2,
C. WELDING OF REINF.
X
9.3.3.4(c),
11.3.3.4(b)
d. PREPARATION,
CONSTRUCTION, AND
PROTECTION OF MASONRY
DURING COLD WEATHER
X
Ad. 1.8 C, 1.8 D
(TEMPERATURE BELOW 40°F)
OR HOT WEATHER
(TEMPERATURE ABOVE 90°F)
e. APPLICATIONAND
MEASUREMENTOF
X
Ad. 3.68
PRESTRESSING FORCE
f. PIACEMENTOF GROUTAND
PRESTRESSING GROUT FOR
Ad. 3.5. 3.6 C
BONDED TENDONS IS IN
X
COMPLIANCE
g. PLACEMENT OF AAC
MASONRY UNITS AND
XI^I
X(C)
Ad. 3.38.9,
CONSTRUCTION OF THIN -BED
3.3 FAb
MORTAR JOINTS
An. 1.4
5. OBSERVE PREPARATION OF GROUT
B.2.a.a.3, 1.4
SPECIMENS, MORTAR SPECIMENS,
X
8.2.b.3, 1.4
AND/OR PRISMS
8.2.c.3, 1.4
8.3, 1.48.4
(a) FREQUENCY REFERS TO THE FREQUENCY OF SPECIAL INSPECTION, WHICH MAY BE CONTINUOUS
DURING THE TASK LISTED OR PERIODIC DURING THE LISTED TASK, AS DEFINED IN THE TABLE.
(b) REQUIRED FOR THE FIRST 5000 SQUARE FEET OF AAC MASONRY.
(c) REQUIRED AFTER THE FIRST 5000 SQUARE FEET OF AAC MASONRY.
TABLE 3.1.3. LEVEL C QUALITY ASSURANCE
MINIMUM TESTS
VERIFICATION OF NAND fAR IN ACCORDANCE WITH SPECIFICATION ARTICLE 1.4 B PRIOR TO
CONSTRUCTION AND FOR EVERY 5000 SO, FT. DURING CONSTRUCTION
VERIFICATION OF PROPORTIONS OF MATERIALS IN PREMIXED OR PREBLENDED MORTAR, PRESTRESSING
GROUT, AND GROUT OTHER THAN SELF -CONSOLIDATING GROUT, AS DELIVERED TO THE PROJECT SITE
VERIFICATION OF SLUMP FLOW AND VISUAL STABILITY INDEX (VSI) A$ DELIVERED TO THE PROJECT SITE IN
ACCORDANCE WITH SPECIFICATION ARTICLE 1.5B.i.b.3 FOR SELF -CONSOLIDATING GROUT
MINIMUM SPECIAL INSPECTION
INSPECTION TASK
FREQUENCYN
REFERENCE FOR CRITERIA
TMS Q21
TMS 602/
CONTINUOUS
PERIODIC
ACI5301
ACI 530.1/
ASCE 6
ASCE 6
1. VERIFY COMPUANCE WITH THE
X
Ad. 1.5
APPROVED SUBMITTALS
2. VERIFY THAT THE FOLLOWING ARE IN
COMPLIANCE:
a. PROPORTIONS OF SITE -
MIXED MORTAR, GROUTAND
Ad. 2.1. 2.6
PRESTRESSING GROUT FOR
X
A, 2.6 B, 2.6
BONDED TENDONS
C. 2.4 G.1.b
It. GRADE, TYPE, AND SIZE OF
REINF. AND ANCHOR BOLTS,
AND PRESTRESSING
X
Sect. 6.1
Ad. 2.4, 3.4
TENDONS AND ANCHORAGES
c. PLACEMENT OF MASONRY
UNITS AND CONSTRUCTION
X
Ad. 3.3B
OF MORTAR JOINTS
d. PLACEMENT OF REINF.,
Sect . 6.1,
CONNECTORS, AND
X
6.2.1.6.2.6.
Ad. 3.2 E, 3.4,
PRESTRESSING TENDONS
627
3.6A
AND ANCHORAGES
e. GROUT SPACE PRIOR TO
Ad. 3.2 D,
GROUTING
X
3.2 F
f. PLACEMENT OF GROUT AND
PRESTRESSING GROUT FOR
X
Art. 3.5, 3.6 C
BONDED TENDONS
g. SIZE AND LOCATION OF
X
Art. 3.3F
STRUCTURAL ELEMENTS
6. TYPE, SIZE, AND LOCATION OF
ANCHORS, INCLUDING OTHER
DETAILS OR ANCHORAGE OF
X
Sect 1.2.1(e),
MASONRY TO STRUCTURAL
6.1.4.3. 6.2.1
MEMBERS, FRAMES, OR
OTHER CONSTRUCTION
Sect. 8.1.6.7.2,
I. WELDING OF REINF.
X
9.3.3.4(c),
11.3.3.4(b)
j. PREPARATION,
CONSTRUCTION, AND
PROTECTION OF MASONRY
DURING COLD WEATHER
Ad. 1.8 C. 1.8 D
(TEMPERATURE BELOW 40°F)
OR HOT WEATHER
X
(TEMPERATURE ABOVE 90°F)
K. APPLICATION AND
MEASUREMENTOF
X
AN. 3.6B
PRESTRESSING FORCE
I. PLACEMENTOF AAC
MASONRY UNITSAND
X
AN. 3.3 B.9,
CONSTRUCTION OF THIN -BED
3.3 F.1.b
MORTAR JOINTS
M. PROPERTIES OF THIN -BED
X
Art 2.1 CA
MORTAR FOR AAC MASONRY
Art. 1.4
3. OBSERVE PREPARATION OF GROUT
B.2.a.3,1 1.4
SPECIMENS, MORTAR SPECIMENS,
X
8.2.b.3, 1.4
AND/OR PRISMS
8.2.c.3, 1.4
8.3, 1.4 B.4
(a) FREQUENCY REFERS TO THE FREQUENCY OF SPECIAL INSPECTION, WHICH MAY BE CONTINUOUS
DURING THE TASK LISTED OR PERIODIC DURING THE LISTED TASK, AS DEFINED IN THE TABLE.
74ALi
WOOLG ERT
ARCHITECTURE �NOINEEINOmOEOWATIAL
7635 Interactive Way
Suite 100
Indianapolis, IN
46278
317.299.7500
FAX: 317.291.5805
E
U �
C
J '-
K
U
Q)
V r^
I
�
c
m
O
a
c
�
m
�
i
Cam(DN
o
€ ro
my
W
o m
C 9
O C
ABBREVIATIONS:
(0
y E
CL
CENTERLINE
MAX
MAXIMUM
m
d
So
°F
DEGREES FAHRENHEIT
MIN
MINIMUM
B
"
INCH
MPII
MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS
(E)
EXISTING
NTS
NOT TO SCALE
(N)
NEW
OC
ON CENTER
ACI
AMERICAN CONCRETE INSTITUTE
OF
OPPOSITE HAND (MIRRORED)
ISSUBnCeS:
ASCE
AMERICAN SOCIETYOF CIVIL ENGINEERS
PL
PLATE
ASTM
AMERICAN SOCIETYFOR TESTING AND MATERIALS
PSI
POUNDS PER SQUARE INCH
z
Descmencn
MT
0
Issued For Building 2 Remew
10/05/1
BOT
BOTTOM
PJP
PARTIAL JOINT PENETRATION WELD
1
Issued For Building Permit
05/01/1
C
CHANNEL
RBS
REDUCED BEAM SECTION
CET CRITICAL EXPOSURE TEMPERATURE REF REFERENCE
CJ
CONTROL JOINT
REINF
REINFORCING
CJP
COMPLETE JOINT PENETRATION WELD
READ
REQUIRED
CL
CENTERLINE
REV
REVISION
CLR
CLEAR, CLEARANCE
SC
SLIP CRITICAL
COL
COLUMN
SH
SHEET
CONC
CONCRETE
SIM
SIMILAR
DIA DIAMETER SME SUBJECT MATTER EXPERT
DO
DITTO
SQ
SQUARE
DWG
DRAWING
STD
STANDARD
Prom. No.: 074904
EF
EACH FACE
SYM
SYMMETRICAL
EJ
EXPANSION JOINT
T&B
TOP AND BOTTOM
Date: 05/01/19
EL
ELEVATION
TOO
TOP OF CONCRETE
EQ
EQUAL, EQUALLY
TOS
TOP OF STEEL
EW
EACH WAY
TYP
TYPICAL
FDN
FOUNDATION
UNO
UNLESS NOTED OTHERWISE
FT
FULLY TENSIONED
VERT
VERTICAL
fN
SPECIFIED COMPRESSIVE STRENGTH OF CLAY MASONRY OR CONCRETE MASONRY, PSI
W
WIDE FLANGE ROLLED STEEL BEAM
Sheet Name:
fA
SPECIFIED COMPRESSIVE STRENGTH OF AAC MASONRY, PSI
WP
WORKING POINT
A
SPECIAL INSPECTION
GA
GAUGE
WT
STRUCTURALTEE
HORIZ
HORIZONTAL
WWF
WELDED WIRE FABRIC
CONT.
HSS
HOLLOW STRUCTURAL SECTION (TUBE STEEL)
XS
EXTRA -STRONG
ICC-ES
INTERNATIONAL CODE COUNCIL EVALUATION SERVICE
IBC
INDIANA BUILDING CODE
KIP
THOUSAND POUNDS FORCE
KSI
THOUSAND POUNDS PER SQUARE INCH
L
STEELANGLE
LLH
LONG LEG HORIZONTAL
LLV
LONG LEG VERTICAL
S2=003
DATE: 10/31/19