SHEARWALL S-1
FLOOR
SHEATHING
EDGE FASTENER
SPACING
END
STUDS
HOLD
DOWNS
SHEAR
FASTENERS
LOW ROOF
3RD FLOOR
7/16' OSB
8tl @ 6' O.C.
(2) 2x6
HDU4-SDS2.5 w/ 5/8' DIA.
THREADED ANCHOR RODS
1/2' DIA. THRU BOLTS
@32' O.C.
2ND FLOOR
7116' OSB
8d @ 4' O.C.
6x6 POST
HDUI4SDS2.5 W/ 1' DIA.
THREADED ANCHOR RODS
518' DIA. THRU BOLTS
@ 32' O.C.
13T FLOOR
7/16' OSB
8tl @ 3- O.C.
6x6 POST
HD19 w/ 1 1/4' DIA.
THREADED ANCHOR RODS
5/8' DIA. THRU BOLTS
@ 16- O.C.
NOTES:
- AT BASE OF 1ST FLOOR PROVIDE 1 1/4" ANCHOR RODS AS LISTED IN THE ABOVE SCHEDULE AND ADHESIVE
EMBED 9" INTO THE CONCRETE PODIUM.
- HOLDOWN REQUIRED AT END STUD, TYP. SEE PLAN FOR SHEARWALL TYPE.
- HOLDDOWNS REQUIRED AT EACH END OF SHEAR WALL. INSTALL HOLDOWNS USING HARDWARE RECOMMENDED
BY MANUFACTURER.
- SEE PLAN FOR SHEAR WALL TYP.
- STRUCTURAL SHEAR WALL SHEATHING SHALL BE CONTINUOUS BETWEEN FLOORS AND CONTINUE ALL THE WAY
TO THE ROOF DIAPHRAGM. DO NOT STOP SHEATHING IN THE FLOOR OR ROOF TRUSS SPACE.
SHEAR WALL S•1
scALE : 116 = r U'
SHEARWALL S-4
FLOOR
SHEATHING
EDGE FASTENER
SPACING
END
STUDS
HOLD
DOWNS
SHEAR
FASTENERS
LOW ROOF
3RD FLOOR
15132' APA
RATED EXP1
8tl @ 6' O.C.
(2) 2x6
HDU2-SDS2.5 wl 518' DIA.
THREADED ANCHOR RODS
3/8' DIA. THRU BOLTS
@ 32- O.C.
2ND FLOOR
15/32' APA
RATED EXP 1
8tl @ 6' O.C.
(3) 2x6
HDU8-SDS2.5 w/ 7ar DIA.
THREADED ANCHOR RODS
1/2' DIA. THRU BOLTS
@ 32' O.C.
1ST FLOOR
15/32' APA
RATED EXP 1
Btl @ 4- O.C.
6x6 POST
HD12 w/ 1 1/8' DIA.
THREADED ANCHOR RODS
5/8' DIA. THRU BOLTS
@ 32' O.C.
NOTES:
AT GROUND LEVEL, PROVIDE 1 1/8" ANCHOR RODS AS LISTED IN THE ABOVE SCHEDULE AND ADHESIVE
EMBED 9" INTO THE CONCRETE PODIUM.
- HOLDOWN REQUIRED AT END STUD, TYP. SEE PLAN FOR SHEARWALL TYPE.
HOLDDOWNS REQUIRED AT EACH END OF SHEAR WALL. INSTALL HOLDOWNS USING HARDWARE
RECOMMENDED BY MANUFACTURER
SEE PLAN FOR SHEAR WALL TYP.
STRUCTURAL SHEAR WALL SHEATHING SHALL BE CONTINUOUS BETWEEN FLOORS AND CONTINUE ALL
THE WAY TO THE ROOF DIAPHRAGM. DO NOT STOP SHEATHING IN THE FLOOR OR ROOF TRUSS SPACE
SHEAR WALL S•4
srmF im--vn-
SHEAR WALL S-7
FLOOR
SHEATHING
EDGE FASTENER
SPACING
END
STUDS
HOLD
DOWNS
SHEAR
FASTENERS
LOW ROOF
3RD FLOOR
15 32' APA
RATED EXP 1
Stl @ 6' O.C.
(2) 2x6
HDU2-SDS2.5 w198' DIA.
THREADED ANCHOR RODS
3/8' DIA. THRU BOLTS
@ 32' O.C.
2ND FLOOR
15/32' APA
RATED EXP 1
8tl @ 6' O.C.
(2) 2x6
HDU2-SDS2.5 w/ 5/8' DIA.
THREADED ANCHOR RODS
318' DIA. THRU BOLTS
I @ 32' O.C.
1ST FLOOR
15132' APA
RATED EXP 1
8tl @ 6' O.C.
(2) 2x6
i
HDU5-SDS2.5 wl 518' DIA.
THREADED ANCHOR RODS
3/8' DIA. THRU BOLTS
I @ 32' O.C.
NOTES:
- AT GROUND LEVEL, PROVIDE 5/6" ANCHOR RODS AS LISTED IN THE ABOVE SCHEDULE AND ADHESIVE
EMBED 5" INTO THE CONCRETE PODIUM.
- HOLDOWN REQUIRED AT END STUD, TYP. SEE PLAN FOR SHEARWALL TYPE.
- HOLDDOWNS REQUIRED AT EACH END OF SHEAR WALL. INSTALL HOLDOWNS USING HARDWARE
RECOMMENDED BY MANUFACTURER
- SEE PLAN FOR SHEAR WALL TYP.
- STRUCTURAL SHEARWALL SHEATHING SHALL BE CONTINUOUS BETWEEN FLOORS AND CONTINUE
ALL THE WAY TO THE ROOF DIAPHRAGM. DO NOT STOP SHEATHING IN THE FLOOR OR ROOF TRUSS SPACE.
SHEAR WALL S•7
OGALL : 110 = I--U
SHEARWALL S-10
FLOOR
SHEATHING
EDGE FASTENER
SPACING
END
STUDS
HOLD
DOWNS
SHEAR
FASTENERS
HIGH ROOF
4TM FLOOR
7116' OSB
8d @ 6- O.C.
(2) 2x6
HDU2-SDS2.5 w/ 5/8' DIA.
THREADED ANCHOR RODS
112' DIA. THRU BOLTS
0 32- O.C.
3RD FLOOR
7/16' OSB
8d @ 6' O.C.
(3) 2x6
HDU8SDS2.5 w/ 7/8' DIA.
THREADED ANCHOR RODS
112' DIA. THRU BOLTS
@ 32- O.C.
2ND FLOOR
7116' OSB
8d @ 6- O.C.
6x6 POST
HOW 4-SDUS2.5 w/ 1' DIA.
THREADED ANCHOR RODS
518' DIA. THRU BOLTS
A 32' O.C.
1ST FLOOR
NOTES:
- AT GROUND LEVEL, PROVIDE I" ANCHOR RODS AS LISTED IN THE ABOVE SCHEDULE AND ADHESIVE
EMBED 71/2" INTO THE CONCRETE PODIUM.
- HOLDOWN REQUIRED AT END STUD, TYP. SEE PLAN FOR SHEARWALL TYPE.
HOLDDOWNS REQUIRED AT EACH END OF SHEAR WALL. INSTALL HOLDOWNS USING HARDWARE
RECOMMENDED BY MANUFACTURER
- SEE PLAN FOR SHEAR WALL TYP.
- STRUCTURAL SHEAR WALL SHEATHING SHALL BE CONTINUOUS BETWEEN FLOORS AND CONTINUE ALL THE
WAY TO THE ROOF DIAPHRAGM. DO NOT STOP SHEATHING IN THE FLOOR OR ROOF TRUSS SPACE
RELEASED FOR CONSTRUCTION IlEAR WALL SW10
Subject to compliance with all regulations E: 118'=T-6'
of State and meal Codes
City of Carried
SHEAR WALL S-2
FLOOR
SHEATHING
EDGE FASTENER
SPACING
END
STUDS
HOLD
DOWNS
SHEAR
FASTENERS
LOW ROOF
3RD FLOOR
15/32- APA
RATED EXP1
8tl @ 6- O.C.
(2) 2x6
HDU2-SDS25 w/ 5/8' DIA.
THREADED ANCHOR RODS
3/8' DIA. THRU BOLTS
@ 32.O.C.
2ND FLOOR
15/32' APA
RATED EXP 1
8tl @ 6' O.C.
(2) 2x6
HDU5-SDS2.5 wl 518' DIA.
THREADED ANCHOR RODS
318' DIA. THRU BOLTS
@ 32' O.C.
1ST FLOOR
15/32- APA
RATED EXP 1
Btl @ 6' O.C.
6t6 POST
HDW1 SDS2.5 w/ 1' DIA.
THREADED ANCHOR RODS
1/2- DIA. THRU BOLTS
@ 32- O.C.
NOTES:
AT BASE OF 1ST FLOOR, PROVIDE 1"ANCHOR RODS AS LISTED IN THE ABOVE SCHEDULE AND ADHESIVE
EMBED 7112" INTO THE CONCRETE PODIUM.
- HOLDOWN REQUIRED AT END STUD, TYP. SEE PLAN FOR SHEARWALLTYPE.
HOLDDOWNS REQUIRED AT EACH END OF SHEAR WALL INSTALL HOLDOWNS USING HARDWARE
RECOMMENDED BY MANUFACTURER
SEE PLAN FOR SHEAR WALL TYP.
STRUCTURAL SHEAR WALL SHEATHING SHALL BE CONTINUOUS BETWEEN FLOORS AND CONTINUE ALL
THE WAY TO THE ROOF DIAPHRAGM. DO NOT STOP SHEATHING IN THE FLOOR OR ROOF TRUSS SPACE.
SHEAR WALL S•2
SCALE : 116 = lU'
SHEAR WALL S-5
FLOOR
SHEATHING
EDGE FASTENER
SPACING
END
STUDS
HOLD
DOWNS
SHEAR
FASTENERS
HIGH ROOF
47H FLOOR/LOW ROOF
15132' APA
RATED EXP 1
Btl @ 6- O.C.
(2) 2x6
HDU2-SDS2.5 wl 518' DIA.
THREADED ANCHOR RODS
WB' DIA. THRU BOLTS
@ 32- O.C.
3RDFLOOR
15/32- APA
RATED EXP 1
8tl@6.O.C.
(2)2x6
HDU5-SDS25 w/5/8'DIA.
THREADED ANCHOR RODS
1/2' DIA. THRU BOLTS
@ 32- O.C.
2ND FLOOR
15132' APA
RATED EXP 1
8tl @ 6' O.C.
6x6 POST
HOW 1-SDS2.5 wl V DIA.
THREADED ANCHOR RODS
1/2' DIA. THRU BOLTS
@ 32- O.C.
1STFLOOR
15132- APA
RATED EXP 1
Btl @ 6- O.C.
6x6 POST
HDUI SDS25 w/ 1- DIA.
I THREADED ANCHOR RODS
1 112' DIA. THRU BOLTS
I @ 32- O.C.
NOTES:
AT GROUND LEVEL, PROVIDE I"ANCHOR RODS AS LISTED IN THE ABOVE SCHEDULE AND ADHESIVE
EMBED 7112" INTO THE CONCRETE PODIUM.
HOLDOWN REQUIRED AT END STUD, TYP. SEE PLAN FOR SHEARWALL TYPE.
- HOLDDOWNS REQUIRED AT EACH END OF SHEAR WALL. INSTALL HOLDOWNS USING HARDWARE
RECOMMENDED BY MANUFACTURER
SEE PLAN FOR SHEAR WALL TYP.
SHEAR WALLS MARKED WITH THE TAG "SIM." ON THE PLANS ARE THE SAME EXCEPT THAT THEY ARE
ONLY BETWEEN THE 1 ST FLOOR AND ROOF.
STRUCTURAL SHEAR WALL SHEATHING SHALL BE CONTINUOUS BETWEEN FLOORS AND CONTINUE
ALL THE WAY TO THE ROOF DIAPHRAGM. DO NOT STOP SHEATHING IN THE FLOOR OR ROOF TRUSS SPACE.
SHEAR WALL S•5
scAi P vR^ = rn-
SHEAR WALL S-8
FLOOR
SHEATHING
EDGE FASTENER
SPACING
END
STUDS
HOLD
DOWNS
SHEAR
FASTENERS
LOW ROOF
3RD FLOOR
7/16- OSB
8tl @ 6' O.C.
(2) 2x6
HDU2-SDS2.5 w/ 518' DIA.
THREADED ANCHOR RODS
318' DIA. THRU BOLTS
@ 32' O.C.
2ND FLOOR
7/16- OSB
Btl @ 6- O.C.
(2) 2x6
HDU4-SDS2.5 w/ 518' DIA.
THREADED ANCHOR RODS
3/8' DIA. THRU BOLTS
I @ 32' O.C.
167 FLOOR
7116- OSB
So @ 6' O.C.
(3) 2x6
HDU8-SDS2.5 w/ 7/8' DIA.
THREADED ANCHOR RODS
I 3/8' DIA. THRU BOLTS
I @32'O.C.
NOTES:
AT GROUND LEVEL, PROVIDE 718" ANCHOR RODS AS LISTED IN THE ABOVE SCHEDULE AND ADHESIVE
EMBED 5" INTO THE CONCRETE PODIUM.
HOLDOWN REQUIRED AT END STUD, TYP. SEE PLAN FOR SHEARWALL TYPE.
- HOLDDOWNS REQUIRED AT EACH END OF SHEAR WALL. INSTALL HOLDOWNS USING HARDWARE
RECOMMENDED BY MANUFACTURER
- SEE PLAN FOR SHEAR WALL TYP.
STRUCTURAL SHEAR WALL SHEATHING SHALL BE CONTINUOUS BETWEEN FLOORS AND CONTINUE
ALL THE WAY TO THE ROOF DIAPHRAGM. DO NOT STOP SHEATHING IN THE FLOOR OR ROOF TRUSS SPACE.
SHEAR WALL S•8
OGALL: 110 = 1--U
SHEAR WALL S-3
FLOOR
SHEATHING
EDGE FASTENER
END
HOLD
SHEAR
SPACING
STUDS
DOWNS
FASTENERS
LOW ROOF
3RD FLOOR
15132- APA
Btl @ 6- O.C.
(2) 2x6
HDU2-SDS25 w/ 5/8' DIA.
3/8' DIA. THRU BOLTS
RATED EXP 1
THREADED ANCHOR RODS
@ 32- O.C.
2ND FLOOR
15/32' APA
ad @ 6' O.C.
(2) 2x6
HDU4-SDS2.5 w/5/8' DIA.
3/8' DIA. THRU BOLTS
RATED EXP 1
THREADED ANCHOR RODS
@ 32' O.C.
isT FLOOR
15132-APA
Sol @6.O.C.
6x6 POST
HDU11-SDS25 w/1-DIA.
1/2' DIA. THRU BOLTS
RATED EXP 1
THREADED ANCHOR RODS
@ 32- O.C.
NOTES:
- AT BASE OF 1ST FLOOR, PROVIDE 1"ANCHOR RODS AS LISTED IN THE ABOVE SCHEDULE AND ADHESIVE
EMBED 71/2" INTO THE CONCRETE PODIUM.
HOLDOWN REQUIRED AT END STUD, TYP. SEE PLAN FOR SHEARWALL TYPE.
HOLDDOWNS REQUIRED AT EACH END OF SHEAR WALL. INSTALL HOLDOWNS USING HARDWARE
RECOMMENDED BY MANUFACTURER
- SEE PLAN FOR SHEAR WALL TYP.
STRUCTURAL SHEAR WALL SHEATHING SHALL BE CONTINUOUS BETWEEN FLOORS AND CONTINUE ALL THE
WAY TO THE ROOF DIAPHRAGM. DO NOT STOP SHEATHING IN THE FLOOR OR ROOF TRUSS SPACE
SHEAR WALL S=3
SCALE : 116" = l'-U
SHEAR WALL S-6
FLOOR
SHEATHING
EDGE FASTENER
SPACING
END
STUDS
HOLD
DOWNS
SHEAR
FASTENERS
ROOF
4TH FLOOR/LOW ROOF
15132' APA
RATED EXP 1
8tl @ 6' O.C.
(2) 2x6
HDU4-SDS2.5 w/ 5/8' DIA.
THREADED ANCHOR RODS
3/8' DIA. THRU BOLTS
@ 16' O.C.
3RD FLOOR
15132' APA
RATED EXP 1
8tl @ 4- O.C.
6X6 POST
HDW1 SDS2.5 wl 1' DIA.
THREADED ANCHOR RODS
1/2' DIA. THRU BOLTS
@ 16' O.C.
2ND FLOOR
15/32' APA
RATED EXP 1
8tl @ 3' O.C.
6k6 POST
HD19 w/ 1 1/4' DIA.
THREADED ANCHOR RODS
5l8' DIA. THRU BOLTS
16, O.C.
isT FLOOR
15132' APA
RATED EXP 1
8tl @ 3- O.C.
6X6 POST
i
HD19 wl 1 1W DIA.
THREADED ANCHOR RODS
5l8' DIA. THRU BOLTS
@ 16' O.C.
NOTES:
AT GROUND LEVEL, PROVIDE 1 1/4" ANCHOR RODS AS LISTED IN THE ABOVE SCHEDULE AND ADHESIVE
EMBED 9" INTO THE CONCRETE PODIUM.
HOLDOWN REQUIRED AT END STUD, TYP. SEE PLAN FOR SHEARWALL TYPE.
- HOLDDOWNS REQUIRED AT EACH END OF SHEARWALL INSTALL HOLDOWNS USING HARDWARE
RECOMMENDED BY MANUFACTURER
SEE PLAN FOR SHEAR WALL TYP.
SHEAR WALLS MARKED WITH THE TAG RSIM.R ON THE PLANS ARE THE SAME EXCEPT THAT THEY ARE ONLY
BETWEEN THE 1ST FLOOR AND ROOF.
STRUCTURAL SHEAR WALL SHEATHING SHALL BE CONTINUOUS BETWEEN FLOORS AND CONTINUE ALL THE
WAY TO THE ROOF DIAPHRAGM. DO NOT STOP SHEATHING IN THE FLOOR OR ROOF TRUSS SPACE
SHEAR WALL S=6
scAi P vR^ = rn-
SHEAR WALL S-9
FLOOR
SHEATHING
EDGE FASTENER
SPACING
END
STUDS
HOLD
DOWNS
SHEAR
FASTENERS
HIGH ROOF
4TH FLOOR
15/32- APA
RATED EXP1
8tl @ 6- O.C.
(2) 2x6
HDU2-SDS25 w/ 5/8' DIA.
THREADED ANCHOR RODS
1/2' DIA. THRU BOLTS
@ 32.O.C.
3RD FLOOR
15/32' APA
RATED EXP 1
ad @ 6- O.C.
(3) 2x6
HDU8-SDS2.5 w/ 7/8' DIA.
THREADED ANCHOR RODS
1/2' DIA. THRU BOLTS
@ 32' O.C.
2ND FLOOR
15/32- APA
RATED EXP 1
8tl @ 6- O.C.
6x6 POST
HDU14-SDS25 W/ 1- DIA.
THREADED ANCHOR RODS
1/2' DIA. THRU BOLTS
A 32' O C.
1ST FLOOR
NOTES:
HOLDOWN REQUIRED AT END STUD, TYP. SEE PLAN FOR SHEARWALL TYPE.
- HOLDDOWNS REQUIRED AT EACH END OF SHEAR WALL. INSTALL HOLDOWNS USING HARDWARE
RECOMMENDED BY MANUFACTURER
- SEE PLAN FOR SHEAR WALL TYP.
SHEAR WALLS MARKED WITH THE TAG "SIM." ON THE PLANS ARE THE SAME EXCEPT THAT THEY ARE ONLY
BETWEEN THE 1ST FLOOR AND ROOF.
- STRUCTURAL SHEAR WALL SHEATHING SHALL BE CONTINUOUS BETWEEN FLOORS AND CONTINUE ALL THE
WAY TO THE ROOF DIAPHRAGM. DO NOT STOP SHEATHING IN THE FLOOR OR ROOF TRUSS SPACE
SHEAR WALL S=9
OGALL: 110 = I--U
74SIF
�V
W O U L R E PT
ARCHITECTURENGiNEmiNG GEOsvcTiu
7635 Interactive Way
Suite 100
G Indianapolis, IN
46278
317.2997500
FAX: 317.291.5805
F
E
LN]
Mf�j
E
cam
U
�
J•�
H--�
W
U
K
O
CL
Y
0
c
�
L
N
cam
€W
H
Q
�
U �
C
o m
C
O C
E
�€
U
m
So
Issuances:
oeswenax
Prom. No.: 074904
Date: 05/01/19
A Sheet Name:
SHEARWALL
SCHEDULES
S2=201
DATE: 10/31/19