HVAC ABBREVIATION LEGEND
PIPE SYMBOL LEGEND
SCHEMATIC SYMBOL LEGEND
A
AMPS
MC
MECHANICAL CONTRACTOR
+--CHWS4 CHILLED WATER SUPPLY PIPE
ICI PIPE DOWN
MV/AV
AIR VENT, MV-MANUALVENT;AV-
AUTOMATIC VENT
ACC
ACR
AIR COOLED CONDENSING UNIT
ACR COPPER REFRIG PIPE
MCA
MD
MINIMUM CIRCUIT AMPS
MANUAL DAMPER
!-CHWR� CHILLED WATER RETURN PIPE
,Y� PIPE UP
AFF
ABOVE FINISHED FLOOR
MFF
MATT FACED FIBERGLASS
♦-CWS� CONDENSER WATER SUPPLY PIPE
! Y ! TEE DOWN
M�
AUTOMATIC 2-WAY CONTROL VALVE
ALUM
ALUMINUM
MI
MALLEABLE IRON
!-CWR� CONDENSER WATER RETURN PIPE
�+
TEE UP
APO
AIR PRESSURE DROP
MUA
MAKE UP AIR
ASJ
ALL SERVICE INSULATION JACKET
NC
NOISE CRITERIA LEVEL
t-DCW4 DOMESTIC COLD WATER PIPE
✓ PIPE BREAK (FOR CLARITY)
AUTOMATIC 3-WAY CONTROL VALVE
B
STEAM BOILER
CA
OUTSIDE AIR
!-HWS--i HEATING HOT WATER SUPPLY PIPE
CAPPED PIPE
BAS
BUILDING AUTOMATION SYSTEM
OBD
OPPOSED BLADE DAMPER
!-HWR� HEATING HOT WATER RETURN PIPE
•r,T�' GAS SHUT-OFF VALVE
AUTOMATIC FLOW CONTROLLER
BDD
BACKDRAFT DAMPER
O.C.
ON CENTER
BHP
BRAKE HORSE POWER
ODU
OUTDOOR UNIT
♦-CLYS4 ICE WATER SUPPLY PIPE
S BALL VALVE
BOD
BOTTOM OF DUCT
PC
PLUMBING CONTRACTOR
!-GLYR4 ICE WATER RETURN PIPE
BUTTERFLY VALVE
CHECK VALVE
BOP
BOTTOM OF PIPE
PC
PRESSURE DROP
BR
BRAZED
PGGS
PAINT GRIP GALVANIZED STEEL
I-DTS� DUAL TEMPERATURE SUPPLY PIPE
L_
7 UNION
C-AL
CAL
CORRUGATED ALUMINUM
CALCIUM SILICATE INSULATION
PP
PPM
POLYPROPYLENE
PARTS PER MILLION
✓-DTR� DUAL TEMPERATURE RETURN PIPE
{; CALIBRATED BALANCE VALVE
FLEXIBLE CONNECTION
CCP
CALCIUM CARBONATE POWDER
PRESS.
PRESSURE
♦-DHWi DOMESTIC HOT WATER PIPE
7ri PRESSURE REGULATING VAVLE
CIF
CUBIC FEET
PRV
PRESSURE REGULATING VALVE
!-_VVENT PIPE
GLOBE VALVE
TR
_ F
GAUGE, T-TEMPERATURE; P-PRESSURE
CFM
CUBIC FEET PER MINUTE
PS
PRESSURE SENSOR
♦-G� NATURAL GAS PIPE
GATE VAVLE
CH
CHILLER
PVC
POLYVINYL CHLORIDE
CHP
CHILLED WATER PUMP
PVCGS
PVC COATED GALVANIZED STEEL
J-LPG� LIQUID PROPANE GAS PIPE
STRAINER WITH BLOW DOWN VALVE
�'�
MANUAL BALANCE VALVE
CHIN
CHILLED WATER
RA
RETURN AIR
!-RL� REFRIGERANT LIQUID PIPE
? Y STRAINER
CHWR
CHILLED WATER RETURN
RC
ROOM CRITERIA LEVEL
CHWS
CHILLED WATER SUPPLY
RECT
RECTANGULAR
♦-RSA REFRIGERANT SUCTION PIPE
Fi BLIND FLANGE
PIPE REDUCER/INCREASER
CI
CAST IRON
REFRIG.
REFRIGERANT
J-RHGf REFRIGERANT HOT GAS PIPE
! 4 7 MOTORIZED 2-WAYVALVE
CL
CENTERLINE
RL
REFRIGERANT LIQUID
CLP
CENTERLINE OF PIPE
RF
RETURN OR RELIEF FAN
!-LPS� LOW PRESSURE STEAM PIPE
_ p
�tl-� MOTORIZED 3-WAY VALVE
PRESSURE REDUCING VALVE
CMC
CONC.
CEILING MOUNTED CENTRIFUGAL FAN
CONCRETE
RMC
RMP
ROOF MOUNTED CENTRIFUGAL FAN
ROOF MOUNTED PROPELLER FAN
NMPS� MEDIUM PRESSURE STEAM PIPE
J-HPS� HIGH PRESSURE STEAM PIPE
I-CRCONDENSATE RETURN PIPE
l�'L PRESSURE RELIEF VALVE
SHUTOFF VALVE
CPVC
CHLORINATED PVC
RTU
ROOF TOP UNIT
CR
CRP
STEAM CONDENSATE RETURN
CONDENSATE RETURN PIPE
RV
S
RELIEF VALVE
SWITCH
♦-FWD FEED WATER PIPE
awa PRESSURE
GAGE
F THERMOMETER
COMBINATION BALANCE -SHUTOFF VALVE
CS
CARBON STEEL
SA
SUPPLY AIR
CT
COOLING TOWER
SC
SENSIBLE CAPACITY
CU
COPPER
SCH
SCHEDULE
TDV
TRIPLE DUTY VALVE;
SHUTOFF -BALANCE -CHECK
DUCTWORK SYMBOL LEGEND
CW
CONDENSER WATER
SCR
SCREWED (THREADED)
CWP
CONDENSER WATER PUMP
SF
SUPPLY FAN
SAFETY RELIEF VALVE
D
DRAIN
SO
SHUT OFF VALVE TERMINAL
a3-r�
n I SUPPLY OR OUTSIDE AIR DUCT
RADIUS RECTANGULAR ELBOW
DB
DECIBELS
SQ
SQUARE
DCW
DOMESTIC COLD WATER
SS
STAINLESS STEEL
DIRECTION OF FLOW
ICI f RETURN OR EXHAUSTAIR DUCT UP
( SUPPLY OR OUTSIDE AIR ROUND
0 W DUCTUP
CDC
DIRECT DIGITAL CONTROLS
SW
SWEAT CONNECTION
DHW
DOMESTIC HOT WATER
SWLD
SOLVENT WELD
DMPR
DAMPER
T
THERMOSTAT
SUPPLY OR OUTSIDE AIR DUCT DOWN
RETURN OR EXHAUST AIR ROUND
DUCT UP
DS
DUCT SILENCER (SOUND ATTENUATOR)
TC
TOTAL CAPACITY
DT
DUALTEMPERATURE
TEMP.
TEMPERATURE
DTP
DUAL TEMPERATURE PUMP
TH
THICKNESS
� RETURN OR EXHAUST AIR DUCT DOWN
ROUND DUCT DOWN
DTR
DUAL TEMPERATURE RETURN
THIRD
THREADED
DTS
DUAL TEMPERATURE SUPPLY
TOD
TOP OF DUCT
E-AL
EMBOSSED ALUMINUM
TOJ
TOP OF JOIST
�� SUPPLY/ OUTSIDE AIR DUCT OFFSET
ROUND OFFSET
EAT
ENTERING AIR TEMPERATURE
TOS
TOP OF STEEL
EC
ELECTRICAL CONTRACTOR
TS
TEMPERATURE SENSOR
EDB
ENTERING DRY BULB TEMPERATURE
T/S
PIPE TYPE OR SCHEDULE
�. RETURN AIR DUCT OFFSET
ROUND ELBOW
\ffi
EF
EXHAUST FAN
UBC
UPBLAST CENTRIFUGAL FAN
EH
ELECTRIC HEATER
UC
FLEXIBLE UNICELLULAR
EWB
ENTERING WET BULB TEMPERATURE
UH
UNIT HEATER
MANUAL BALANCING DAMPER
ROUND WYE
EWT
EXH
ENTERING WATER TEMPERATURE
EXHAUST
UV
V
UNIT VENTILATOR
VOLTS
F
FURNACE
VAV
VARIABLEAIRFLOW
MOTORIZED DAMPER
ELI
RECTANGULAR BRANCH TAKEOFF
FCU
FANCOIL UNIT
VC
VENTILATING CONTRACTOR
FD
FIRE DAMPER
WCS
WROUGHT CARBON STEEL
FIREDAMPER
Vl
RECTANGULAR DUCT TERMINATION
FFJ
FOIL FACED JACKET
WCU
WROUGHT COPPER
FG
FIBERGLASS
WILD
WELDED CONNECTION
FGB
FIBERGLASS BOARD INSULATION
WMP
WALL MOUNTED PROPELLER FAN
RECTANGULAR TO ROUND TRANSITION
�J
ROUND DUCTTERMINATION
FGW
FIBERGLASSWRAP
WPD
WATER PRESSURE DROP
FLA
FULL LOAD AMPS
WT
WEIGHT (OR DENSITY)
FLG
FLANGE
RECTANGULAR TRANSITION
•--��
FLGD
FLANGED
FMG
FOAM GLASS
FPM
FEET PER MINUTE
r,
I
STANDARD RECTANGULAR ELBOW
I 1
FPP
FAN POWERED PARALLELVAV
FPS
FAN POWERED SERIES VAV
FS
FLOW SWITCH
ANNOTATION SYMBOL LEGEND
FSD
FIRE/SMOKE DAMPER
FIN
FEED WATER
Q THERMOSTAT OR TEMP. SENSOR
QH HUMIDISTAT
SECTION SYMBOL
100
G
NATURAL GAS
GA
GAGE (GAUGE)
GALV
GALVANIZED
SWITCH
GC
GENERAL CONTRACTOR
GPH
GALLONS PER HOUR
X KEYNOTE DESIGNATION
RTU
EQUIPMENT PLAN MARK
12
GPM
GALLONS PER MINUTE
GRV
GROOVED PIPE
POINT OF NEW CONNECTION
a
GS
GALVANIZED STEEL
4 DETAIL SYMBOL
-100
H
HUMIDIFIER (HUMIDITY)
1-01 VAV TERMINAL UNIT MARK
HC
HEATING CONTRACTOR
6LW-1 EQUIPMENTMARK
HF
HI
A-8'¢ A-24x12 AIR DEVICE MARK - NECK SIZE
250 250 AIRFLOW
HG
HOTOT GAS GAS (REFRIGERANT)
HP
HORSEPOWER
8'o ROUND DUCT SIZE
HPS
HIGH PRESSURE STEAM
HRC
HEAT RECLAIM WATER
24x12 RECTANGULAR DUCT SIZE
HS
HUMIDITYSENSOR
AIR DEVICE AND DUCT ACCESS. LEGEND
HV
HEATING/VENTILATINGUNIT
HW
HEATING HOT WATER
HWB
HOT WATER BOILER
RETURN AIR GRILLE
SUPPLY AIR DIFFUSER
�� (HARD CONNECTION)
HWP
HOT WATER PUMP
HWR
HOT WATER RETURN
Imo, SUPPLYAIR DIFFUSER WITH FLEXIBLE
ICI"'� RUNOUTAND DAMPER
�: RETURN OR EXHAUST GRILLE
L�)ILJ (HARD CONNECTION)
HWS
HOT WATER SUPPLY
ILC
INLINE CENTRIFUGAL FAN
LAT
LEAVING AIR TEMPERATURE
SIDEWALL DIFFUSER
T 14X14 TRANSFER OPENING IN WALL
LDB
LEAVING DRY BULB TEMPERATURE
LP
LIQUID PROPANE
LPS
LOW PRESSURE STEAM
SUPPLY AIR DIFFUSER
�L (HARD CONNECTION)
TRANSFER OPENING IN WALL
LVR
LOUVER
LWB
LEAVING WET BULB TEMPERATURE
LWT
LEAVING WATER TEMPERATURE
RETURN OR EXH. GRILLE
(HARD CONNECTION)
M
MOTORIZED
MAT.
MATERIAL
MBH
1000 BTUH
DESIGN CRITERIA
I PROJECT NOTES I
CONTROL NOTES:
1. PROVIDE PROJECT SPECIFIC CONTROL SYSTEM MANUAL FOR THE BUILDING. THE MANUAL SHALL
CONTAIN A DIAGRAM OF THE CONTROL SYSTEM ARCHITECTURE, WIRING DIAGRAMS AND A SEQUENCE
OF OPERATION. THE MANUAL SHALL ALSO INCLUDE AN 11 X 17 FLOOR PLAN INDICATING THE MAJOR
EQUIPMENT AND PANEL LOCATIONS. THE MANUAL SHALL BE BOUND IN A HARD BACK 3 RING BINDER
WITH DIVIDERS. BINDER SHALL BE LABELED'H.V.A.0 TEMPERATURE CONTROL MANUAL' AND INCLUDE
THE PROJECT NAME AS WELL AS THE BUILDING NAME, NUMBER AND ADDRESS.
2. LABEL ALL CONTROL PANELS, ACTUATORS, SENSORS, ETC WITH 118' THICK PLASTIC LAMINATE SIGNS.
SEE DRAWINGS FOR LABEL AND LETTERING REQUIREMENTS. LABEL DESIGNATIONS SHALL BE
CONSISTENT WITH THE DRAWINGS, TEMPERATURE CONTROL SYSTEM MANUAL AND DIAGRAMS.
3. MOUNT WALL MOUNTED THERMOSTATS, TEMPERATURE SENSORS AND CARBON MONOXIDE SENSORS
4'-0' ABOVE FINISH FLOOR. DO NOT MOUNT THERMOSTATS OR TEMPERATURE SENSORS IN DIRECT
SUNLIGHT OR NEAR HEAT PRODUCING EQUIPMENT.
4. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL MOTOR STARTERS AND DISCONNECT SWITCHES
FOR H.V.A.C. EQUIPMENT UNLESS THEY ARE INCLUDED WITH THE EQUIPMENT AS INDICATED ON THE
DRAWINGS AND IN THE SPECIFICATIONS. COORDINATE STARTER REQUIREMENTS WITH THE
ELECTRICAL CONTRACTOR AND THE CONTRACTOR PRIOR TO ORDERING.
5. WHERE AUXILIARY CONTACTS ARE REQUIRED IN STARTERS PROVIDED BY THE ELECTRICAL
CONTRACTOR, THE MECHANICAL CONTRACTOR SHALL COORDINATE THE QUANTITYAND TYPE OF
CONTACTS WITH THE E.C. PRIOR TO PURCHASE.
6, THE ELECTRICAL CONTRACTOR SHALL PROVIDE CIRCUIT BREAKERS IN THE ELECTRICAL PANELS THAT
ARE SPECIFICALLY DEDICATED FOR THE TEMPERATURE CONTROL SYSTEM. COORDINATE THE
QUANTITY AND SIZES WITH THE CONTRACTOR. SEE ELECTRICAL DRAWINGS FOR LOCATION.
7. THE MECHANICAL CONTRACTOR SHALL PROVIDE ALLTEMPERATURE CONTROL SYSTEM WIRING AND
CONDUIT REGARDLESS OF VOLTAGE AS REQUIRED TO PROVIDE THE SPECIFIED SEQUENCE OF
OPERATION OR SATISFYANY MANUFACTURER REQUIREMENTS. POWER AND CONTROL WIRING AND
CONDUIT FOR VALVE ACTUATORS, DAMPER ACTUATORS, CARBON MONOXIDE SENSORS,
TEMPERATURE CONTROL PANELS, RELAYS, INDICATOR LIGHTS, REMOTE CONTROL PANELS, SOLENOID
VALVES AND OTHER SIMILAR DEVICES THAT ARE PART OF THE H.V.A.0 SYSTEM SHALL BE PROVIDED
BV THE MECHANICAL CONTRACTOR. SEE ELECTRICAL DRAWINGS FOR THE LOCATION OF CIRCUIT
BREAKERS SPECIFICALLY DEDICATED FOR TEMPERATURE CONTROL SYSTEM COMPONENTS. ALL 120 V
CONTROL WIRING SHALL BE INSTALLED IN CONDUIT. CONCEALED ABOVE CEILING PLENUM RATED LOW
VOLTAGE (24 VOLTS OR LESS) CONTROL WIRING DOES NOT REQUIRE TO BE INSTALLED IN CONDUIT.
B. THE MECHANICAL CONTRACTOR SHALL PROVIDE ALL CONTROLS, RELAYS, SENSORS, CONTROLLERS,
CONTROL TRANSFORMERS, CONTROL INTERFACE COMPONENTS, SOFTWARE, HARDWARE,
ACTUATORS, SWITCHES AND ANY OTHER CONTROL COMPONENTS REQUIRED TO PROVIDE THE
SPECIFIED SEQUENCE OF OPERATIONS ON PLANS, TO INTEGRATE PROJECT CONTROLS AND SYSTEM,
AND TO MEET EQUIPMENT MANUFACTURER'S INSTALLATION AND OPERATION REQUIREMENTS,
UNLESS NOTED OTHERWISE ON PLANS.
9. IT SHALL BE THE MECHANICAL CONTRACTORS RESPONSIBILITY TO COORDINATE ALL TEMPERATURE
CONTROL SYSTEM REQUIREMENTS WITH THE ELECTRICAL CONTRACTOR PRIOR TO THE PURCHASE
OR INSTALLATION OF ANY OF THE ELECTRICAL POWER OR TEMPERATURE CONTROL SYSTEM
COMPONENT.
10. ALL DAMPERS ON THE INLET OR OUTLET OF THE FAN SHALL BE OPEN PRIOR TO STARTING THE FAN.
PROVIDE ANY TIME DELAYS OR END SWITCHES AS REQUIRED.
11. IN PUBLIC AREAS PROVIDE CLEAR PLASTIC VENTED IMPACT RESISTANT LOCKABLE GUARDS ON ALL
WALL MOUNTED THERMOSTATS OR SENSORS WITH ADJUSTABLE SET -POINTS.
IDENTIFICATION:
1. PROVIDE PLASTIC LAMINATE IDENTIFICATION LABELS ON ALL EQUIPMENT SCHEDULED ON THE
DRAWINGS. THE IDENTIFICATION SHALL BE CONSISTENT WITH THE PLANMARKS SHOWN ON THE
DRAWINGS AND THE BAS SYSTEM USER INTERFACE. SEE DETAILS ON DRAWINGS REGARDING COLOR,
SIZE, TEXT HEIGHT, ETC.
2. PROVIDE PLASTIC LAMINATE IDENTIFICATION LABELS ON ALL TEMPERATURE CONTROL COMPONENTS
SUCH AS CONTROL PANELS, TEMPERATURE SENSORS, HUMIDITY SENSORS, ETC. THE IDENTIFICATION
SHALL BE CONSISTENT WITH THE PLANMARKS SHOWN ON THE DRAWINGS WHERE AVAILABLE AND
THE BAS SYSTEM USER INTERFACE. SEE DETAILS ON DRAWINGS REGARDING COLOR, SIZE, TEXT
HEIGHT, ETC.
3. PLASTIC LAMINATE SIGNS AND LABELS ON OUTDOOR EQUIPMENT SHALL BE FIXED TO EQUIPMENT
WITH STAINLESS STEEL OR ALUMINUM RIVETS OR STAINLESS STEEL OR PLATED SCREWS.
4. CLEAN EQUIPMENT AND PIPING PRIOR TO AFFIXING ADHESIVE TYPE LABELS AND SIGNS.
I PROJECT NOTES I
GENERAL:
1. INSTALL THE H.V.A.C. SYSTEM AS INDICATED IN ACCORDANCE WITH ALL STATE AND LOCAL
CODES.
2. COORDINATE ALL WORK WITH OTHER TRADES. REWORK OF PIPING, DUCTWORK, EQUIPMENT
LOCATION, CONDUIT, ETC. AS A RESULT OF POOR PLANNING. COORDINATION OR SCHEDULING
SHALL BE THE RESPONSIBILITY OF THE INVOLVED CONTRACTORS. NOTIFY THE
ARCHITECT/ENGINEER OF ANY CONFLICTS PRIOR TO START OF WORK.
3. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF ANY
FRAMING REVISIONS, EQUIPMENT LOCATIONS, ADDITION OF CONTROLS, ELECTRICAL CIRCUITING
REVISIONS, ETC. THAT RESULT FROM USING EQUIPMENT OTHER THAN THOSE INDICATED ON
THE DRAWINGS. APPROVAL OF THE SHOP DRAWINGS BYTHE ARCHITECT/ENGINEER WILL NOT
WAIVE THE CONTRACTOR OF THIS RESPONSIBILITY.
4. THE MECHANICAL CONTRACTOR SHALL HAVE THE FINAL RESPONSIBILITY FOR SYSTEM START
UP, TRAINING, WARRANTY AND TURN OVER TO THE OWNER. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR INSTRUCTING THE OWNER ON ANY ROUTINE MAINTENANCE REQUIRED
DURING THE WARRANTY PERIOD.
5. ALL ITEMS INCLUDED ON THESE DRAWINGS AND THE SPECIFICATIONS SHALL BE INCLUDED IN
THE CONTRACTORS BID. ANY ITEMS THAT ARE UNCLEAR OR FOUND TO BE INCORRECT BY THE
CONTRACTOR SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER PRIOR TO
THE BID DUE DATE. EXCLUSIONS OF WORK FROM THE BID ARE NOT ACCEPTABLE.
6. ALL WORK INDICATED ON THE MECHANICAL DRAWINGS SHALL BE PROVIDED BY THE
MECHANICAL CONTRACTOR UNLESS SPECIFICALLY NOTED OTHERWISE.
7. THE MECHANICAL CONTRACTOR SHALL PROVIDE ALL FIRESTOPPING FOR DUCT AND PIPE
PENETRATIONS THAT PENETRATE FIRE RATED ASSEMBLIES. SEE ARCHITECTURAL DRAWINGS
OR REFER TO THE OWNERS RECORD DRAWINGS FOR LOCATIONS OF FIRE RATED ASSEMBLIES.
ALL FLOOR PENETRATIONS SHALL BE FIRESTOPPED AND SEALED WATER TIGHT WITH A FLEXIBLE
SEALANT. INSTALL PER MFG. RECOMMENDATIONS.
B. THE MECHANICAL CONTRACTOR SHALL COORDINATE ANY ROOF PATCHING FOR ANY
MECHANICALROOF PENETRATIONSNOTSPECIFICALLYIDENTIFIED THEARCHITECTURAL
DRAWINGS. ALL PATCHING SHALL BE PROVIDED BY GENERAL CONTRACTOR AND BE
PERFORMED IN A MANNER CONSISTENT WITH THE ROOF SYSTEMS CURRENT WARRANTY
REQUIREMENTS AND MANUFACTURERS RECOMMENDATIONS.
9. THE MECHANICAL CONTRACTOR SHALL NOT PERFORM ANY WELDING OR TORCH CUTTING
OPERATIONS WITHIN THE OCCUPIED BUILDING WITHOUT OBTAINING PERMISSION OR A BURN
PERMIT FROM THE OWNER.
DUCTWORK -GENERAL:
1. ALL DUCTWORK SHALL BE CONSTRUCTED, INSTALLED AND SUPPORTED PER THE LATEST
VERSION OF THE S.M.A.C.N.A. H.V.A.C. DUCT CONSTRUCTION STANDARDS. UNLESS SPECIFIED
MORE STRINGENTLY IN THESE CONSTRUCTION DOCUMENTS.
2. COORDINATION OF DUCT SYSTEM INSTALLATION WITH OTHER TRADES SHALL BE PERFORMED
PRIOR TO THE FABRICATION OF ANY DUCTWORK. VERIFY DUCT CLEARANCES PRIOR TO
FABRICATION. NOTIFY THE ARCHITECT/ENGINEER OF ANY CONFLICTS THAT REQUIRE
DIMENSIONAL CHANGES OR REQUIRE MAJOR RELOCATION OF DUCTWORK.
3. ALL DUCTWORK SHALL BE SUPPORTED FROM ROOF OR FLOOR STRUCTURE ABOVE. DUCTWORK
SHALL NOT LAY ON TOP OF CEILING OR LIGHT FIXTURES.
4. ALL DUCTWORK SIZES SHOWN ARE EXTERNAL DIMENSIONS. ALLOWANCE HAS BEEN MADE FOR
1' DUCTLINER WHERE AND IF REQUIRED.
5. RECTANGULAR DUCTWORK SHALL BE SUPPORTED PER THE S.M.A.C.N.A. STANDARDS AND AT
EACH CHANGE IN DIRECTION.
EQUIPMENT - GENERAL
1. THE H.V.A.C. EQUIPMENT AND SYSTEM SHALL NOT BE USED TO DURING CONSTRUCTION. THE
WARRANTY PERIOD SHALL NOT BEGIN UNTIL SUBSTANTIAL COMPLETION. THE CONTRACTOR
SHALL EXTEND THE EQUIPMENT WARRANTY PERIOD AS NECESSARY WHEN EQUIPMENT IS USED
AFTER INITIAL START UP AND PRIOR TO SUBSTANTIAL COMPLETION.
74,E
WOOLG EUT
MCNITECTNE IENOINEw11N0I0ECWATIAL
7635 Interactive Way
Suite 100
G Indianapolis, IN
46278
317.299.7500
FAX: 317.291.5805
No PEIINU247
STATE OF
F
E
U
�
C J
'-
J
K
W
U
rn
V I
�
c
m
O
O
c
O
N V
U
W
O
c 5
o c
L
� _
d
�E
U
m
= U
B
Dlssuances:
GENERAL DESIGN INFORMATION INDOOR DESIGN CONDITIONS
BUILDING STAIRWELL WINTER DRY BULB: 60.0°F
LOCATION: CARMEL, INDIANA
LATITUDE: 39.97 CORRIDORS AND TENANT ROOMS
LONGITUDE: 86.13
ELEVATION: 853 WINTER DRY BULB: 70.0°F
OUTDOOR DESIGN CONDITIONS WINTER RH%: AMBIENT
SUMMER DRY BULB: 75.0°F
SUMMERDRY 91.3-F (0.4%ASHRAE DESIGN SUMMERRHh: 60% MAX
Prom. No.: 074904
BULB: CONDITION)
SUMMER WET 75.0-F (0.4% ASHRAE DESIGN
Date: 04126119
BULB: CONDITION)
WINTER DRY 2.6°F (99.6% ASHRAE DESIGN
BULB: CONDITION)
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Camel
'1"19,
MECHANICAL SHEET LIST
SHEET NUMBER
SHEET NAME
M2-001
WAC LEGEND AND NOTES
M2-101
WAC FIRST AND SECOND FLOOR PLAN
M2-102
WAC THIRD AND FOURTH FLOOR PLAN
M2-103
WAC ROOF PLAN
M2401
WAC TYPICAL ENLARGED PLANS
M2402
WAC TYPICAL ENLARGED PLANS
M2501
WAC DETAILS
M2-601
MAC SCHEDULES
A Sheet Name:
HVAC LEGEND AND
NOTES
M2=001
DATE: 10/31/19