HomeMy WebLinkAbout(18) E2-001C R K U W J W N C C U 00] y O rn e C E C U < O a v GENERAL LIGHTING/POWER NOTES GENERAL PROJECT NOTES ABBREVIATIONS ELECTRICAL LEGEND A AMPS KW KILOWATTS AFF ABOVE FINISHED FLOOR LGTG LIGHTING 1. LIGHT FIXTURES DESIGNATED ASNIGHT LIGHTS' SHALL BEONUNSWITCHED CIRCUIT, UNLESS NOTED. 1. WORK SHALL BE DONE IN ACCORDANCE WITH LOCAL, STATE OF INDIANA, 2008 NEC AND NATIONAL CODES, RECOMMENDATIONS, REGULATIONS, AND REQUIREMENTS. AFG ABOVE FINISHED GRADE MECH MECHANICAL BKR BREAKER NIC NOT IN CONTRACT LIGHTING FIRE ALARM C CONDUIT NIL NIGHT LIGHT 2. EXIT LIGHTS SHALL BE ON UNSWITCHED CIRCUIT, UNLESS NOTED. 3. ALL RECESSED DOWNLIGHTS MOUNTED IN GRID CEILING SHALL BE CENTERED IN CEILING TILE, 2. CONTRACTORS SHALLVISIT PROJECT SITE PRIOR TO BIDDING TO ASCERTAIN AND BECOME FAMILIAR WITH EXISTING CONDITIONS AS THEY PERTAIN TO THE SCOPE OF WORK. CONTRACTOR SHALL VERIFY EXACT LOCATION AND SIZES OF ELECTRICAL CAW CABLE TELEVISION NTS NOT TO SCALE CUH CABINET UNIT HEATER PVC POLYVINYL CHLORIDE CKT CIRCUIT P PHASE (POLE) LIGHTING FIXTURE. REFER TO FIXTURE SCHEDULE. LETTER INDICATES TYPE. QF FIRE ALARM PULL STATION. 44"AFF. F UNLESS NOTED. EQUIPMENTAND ALL OTHER APPURTENANCES ASSOCIATED WITH THE WORK. Cu COPPER TTB TELEPHONE TERMINAL BOX A FIRE ALARM HORN/STROBE. 80"AFF. E EXISTING TYP TYPICAL 4. CONDUCTORS FOR BRANCH CIRCUITRY ARE #12AWG MININUM, UNLESS NOTED. DEBATE PER CODE WHERE CIRCUITS ARE COMBINED. 5. ALL N BACK TO MINIMUM, UN PER D. ALLBRA 3. PHASING SHALL UI COORDINATED AND IN COMPLIANCE WITH ALL PHASING DRAWINGS, NOTESAND ONE) WITH TELEPHONE) WITH THE OWNER AND PROVIDE NOTICE NOT LESS THAN 72 HOURS IN THE OWN COORDINATE AND TICS NOT LESS THAN HOURS IN ADVANCE. EF EXHAUSTFAN Uv UNLESS OTHERWISE NOTED ELEC ELECTRICAL UV UNITVENTILATOR EM EMERGENCY V VOLTS EMT EMERGENCY METALLIC TUBING VAT VARIABLE AIR VOLUME LAd A NL EMERGENCY LIGHTING FIXTURE WITH EMERGENCY BALLAST. MENINDICATES NIGHT LIGHT CIRCUIT. FULL LUMEN OUTPUT MINIMUM 1400 LUMENS ON LAMP. FIRE ALARM DUCT MOUNTED SMOKE DETECTOR. S = SUPPLY R = WITH DUCTWORK. MAKE SAMPLING TUBE FULL RETURN -DUCTI LENGTATE H. WIDTH OF DUCT IN LENGTH. ROVIDE GREEUN CODE ROUND CONDUCTOR IN ALL BRANCH CIRCUITRY. DEBATE PER CODE WHERE CONDUCTOR IN ALL CHCIA CIRCUITRY. PROVIDE ARE FCU FAN IT MIT VERIFY IN FIELD OB LIGHTING FIXTURE. LETTER INDICATES TYPE. (� FIRE ALARM CEILING MOUNTED SMOKE DETECTOR. COMBINED. CIRCUITS ARE COMBINED. 6. ALL CONDUIT CEILING. PS FOR PLENUM RATED CABLES SHALL BE PROVIDED WITH ACONDUIT BUSHING ABOVE CEILING. 4. COORDPLUMBING ATE V NEW OR RENOVATED WORK WITH THE AS O T VERIFY VOLTAGE, PHASE AND CHA ICAL CONTRACTTS ORS. MECHANICAL PLUMBING AND REQUIREMENTS, SUCH ACCESSORY REQUIREMENTS, SUCH AS MOTOR STARTERS AND DISCONNECTS. G GROUND W WATTS GROUND GFI GROUND FAULT INTERRUPTER WC WATER COOLER GRC GALVANIZED RIGID CONDUIT WP WEATHERPROOF ER HP HORSEPOWER UH UNLESS 08 WITH EMERGENCY BALLAST. OR POWERED THROUGH INVERTER THROUGH INVERTER SYSTEM. OCO COMBINATION SMOKE AND CARBON MONOXIDE DETECTOR. 0 FIRE ALARM CEILING MOUNTED HEAT DETECTOR. CUTTINGLI AND PATCHING REQUIRED FOR HIS 5. CONTRACTORKING J N ON BOX UNO UNLESS NOTED OTHERWISE � AREA CEILING FACE OF EXIT SIGN. REFER L CALUESCHEDUL LIGHTING DENOTES FACE OF UNIT. CONNECT TO LOCAL UNSWITCHED LIGHTING CIRCUIT. SD O MPER.ERCO PROVIDES OKE AS SMOVOLT POWER ON AND ORDINA0 SHOWN CTOR ONTHFORDAMPER DRAWINGS. ON THE TOR. CONNECT TO ALLCONNETIONWITM MECHANICAL ALL CONNECTIONS WITH MECHANICAL CONTRACTOR. CONNECT TO ALARM SYSTEM. ]. WHERE TERMINATED IN J-BOX, ALL SPARE CIRCUITRY SHALL BE LABELED WITH PANEL AND CIRCUIT NUMBER. 8. COORDINATE WITH MECHANICAL CONTRACTOR AND PROVIDE ALL NECESSARY AUXILLARV IN WALLS, FLOORS TO REMOVALS BE WORK. OPENINGE WALLS, FLOORS AND CD INA MANNER OATCHTHE FINISHED INAMANNERTO MATCH THE QUALITY OF FILLED LIKE ADJACENT SURFACES. THE EXISTING, LIKE ADJACENT SURFACES. KVA KILOVOLTAMPERE KILOV (S1 WALL MOUNTED EXIT SIGN. REFER TO FIXTURE SCHEDULE. SHADED AREA DENOTES FACE OF UNIT. CONNECT TO LOCAL pgCp FIRE ALARM CONTROL PANEL. CONTACTS, RELAY, ETC. IN MOTOR STARTERS FOR REQUIRED CONTROL OF MECHANICAL EQUIPMENT. 6. NEW OPENINGS IN EXISTING WALLS AND FLOORS SHALL BE CORE DRILLED OR SAW CUT. OPENINGS IN NEW WALLS AND FLOORS SHALL BE PLANNED AND COORDINATED pggp FIRE ALARM ANNUNCIATOR PANEL. 9. ALL UNDERGROUND PVC CONDUITS SHALL HAVE RIGID GALVANIZED STEEL ELBOWS. ALL WITH GENERAL CONTRACTOR FOR THE INSTALLATION OF APPROPRIATE SLEEVES. UNSWITCHED LIGHTING CIRCUIT. xSL SINGLE POLE WALL SWITCH. 120= VOLT, 20 AMP. 44" AFF. x / ❑F FIRE ALARM STROBE. 80"AFF. RECEPTACLE OR LOCATIONS FOR POWER TO ELECTRIC WATER COOLERS SHALL BE THE INSTALLATION LOCATIONS OF THE ELECTRIC WATER COOLERS, UNLESS COORDINATED WITHITH THE NOTED. ]. ALL CONDUIT SHALL BE 1/2"MINIMUM U.N.O. 8. CONDUIT SHALL BE CONCEALED IN CEILING OR WALLS WHEREVER POSSIBLE. �3 THREE WAY WALL SWITCH. 120120 AMP. 44"AFF 10. ALL LIGHT FIXTURES SHALL BE SEISMICALLY BRACED WITH AN INDEPENDENT WIRE (CEILING GRID TYPE WIRE) FROM TWO OPPOSITE CORNERS TO STRUCTURAL CEILING OR BAR JOIST. 9. ALL UNDERGROUND CONDUIT SHALL BE SCHEDULE 40 PVC UNLESS NOTED OTHERWISE. �4 FOUR WAY WALL SWITCH. 120/2]W, 20 AMP. 44"AFF WP F EXTERIOR FIRE ALARM BELL. WP-WEATHERPROOF $OS OCCUPANCY SENSOR WALL SWITCH.120/2]]V, 20 AMP. 44" AFF Q MAGNETIC DOOR HOLD OPEN. 11. DO NOT SUPPORT CONDUIT OFF OF CEILING GRID, CEILING GRID SUPPORTS, MECHANICAL 10. ALL BRANCH CIRCUITS AND FEEDERS SHALL CONTAIN A GREEN INSULATED GROUND SUPPORTS, OR ANY OTHER TRADE'S SUPPORTS. INSTALL CONDUITS AND BOXES ON SEPERATE SUPPORTS FROM BAR JOIST OR STRUCTURE. CONDUCTOR. GROUNDING BY MEANS OF RACEWAY IS NOT PERMITTED. �p SINGLE POLE WALL SWITCH WITH PILOT LIGHT. 120/277V, 20 AMP. 44"AFF FR­P_S1 FIRE ALARM REMOTE POWER SUPPLY 12. DO NOT SUPPORT FROM METAL ROOF DECK. PROVIDE SUPPORT FROM CONCRETE SLABS, BAR 11. REFER TO MECHANICAL, PLUMBING, AND ARCHITECTURAL PLANS FOR EXACT LOCATION OF EQUIPMENT. �L D DIMMER SYSTEM CONTROL STATION. REFER TO DWG _. ❑Z FIRE ALARM MONITOR MODULE JOIST, STRUCTURAL BEAMS, COLUMNS OR UNISTRUT BETWEEN STRUCTURAL ELEMENTS. 12. COORDINATE LOCATIONS OF LIGHTING FIXTURES IN MECHANICAL/ELECTRICAL ROOMS OS OCCUPANCY SENSOR. ® FIRE ALARM CONTROL RELAY MODULE 13. ALL SINGLE PHASE CIRCUITS SHALL HAVE A SEPERATE DEDICATED NUETRAL CONDUCTOR FOR EACH CIRCUIT. SHARING OF NUETRAL CONDUCTOR IS NOT PERMITTED. WITH EQUIPMENT, PIPING AND DUCTWORK. EXTERIOR LIGHT FIXTURE. FS FIRE SUPPRESSION FLOW SWITCH 14. PROVIDE 4" HIGH, SMOOTH FINISH CONCRETE HOUSEKEEPING PADS UNDER ALL TRANSFORMERS 13. VERIFY CEILING TYPES PER THE ARCHITECTURAL REFLECTED CEILING PLAIN. PROVIDE APPROPRIATE TYPE FIXTURE, LAY -IN FOR GRID, FLANGE FOR DRYWALL, ETC. ER- EXISTING TO REMAIN. PI-1 -NEW FIXTURE. REFER TO FIXTURE SCHEDULE. TS FIRE SUPPRESSION TAMPER SWITCH (45KVA AND LARGER) AND MAIN DISTRIBUTION SWITCHBOARDS. PAD SHALL BE 4" LARGER THAN TRANSFORMER AND SWITCHBOARD IN EACH DIRECTION. USE 3000 PSIG, 28 DAY COMPRESSIVE 14. VERIFY AND COORDINATE MOUNTING HEIGHTS AND LOCATIONS OF ALL DEVICES E,01,13.� END OF THE LINE RESISTOR. STRENGTH CONCRETE. ROUND ALL EDGES AND CORNERS OF CONCRETE PAD. MOUNTED IN CASEWORK OR ABOVE COUNTERS WITH SPECIFIC EQUIPMENT POWER M1 KNOX BOX WITH ALARM CONTACT. FURNISHED. 15. NO MORE THAN 3 PHASE CONDUCTORS SHALL BE INSTALLED IN ANY ONE CIRCUIT, TAMPER RESISTANT DUPLEX RECEPTACLE. 120 VOLT, 20 AMP. 16" AFF UNO. DUCT MOUNTED SMOKE DAMPER BY MECHANICAL CONTRACTOR. PROVIDE A DUCT UNLESS NOTED OTHERWISE. EACH BRANCH CIRCUIT SHALL CONTAIN THEIR OWN MOUNTED SMOKE DETECTOR, WITH RELAY BASE, MOUNTED WITHIN 5'-0"OF THE I NEUTRAL CONDUCTOR. NO SHARED NEUTRALS. SD DAMPER WITH NO AIR OUTLETS OR INLETS BETWEEN THE DETECTOR AND THE TAMPER RESISTANT DUPLEX RECEPTACLE MOUNTED AT 44" OR ABOVE DAMPER. 16. FURNISH ALL ELECTRICAL ACCESS FLOORS TO GENERAL CONTRACTOR FOR HIS BACKSPLASH. 120 VOLT, 20 AMP. INSTALLATION. REFER TO SPECIFICATIONS FOR ACCESS DOOR REQUIREMENTS. /�/� DOOR ACCESS 18. CONTRACTOR SHALL PROVIDE ALL FIRESTOPPING FOR CONDUIT OR CABLE TRAY Air TAMPER RESISTANT DOUBLE DUPLEX RECEPTACLE. 120 VOLT, 20 O ELECTRIC DOOR STRIKE. PENETRATIONS THAT PENETRATE ACOUSTICAL RATED OR SMOKE AND FIRE RATED ASSEMBLIES. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF ALL RATED TT AMP. 16" AFF UNO. ASSEMBLIES. ALL RATED PENETRATIONS SHALL BE FIRESTOPPED TO ORIGINAL ASSEMBLY RATING. ALL NON -RATED FLOOR PENETRATIONS SHALL BE SEALED WATER TAMPER RESISTANT 120 VOLT DOUBLE DUPLEX, 20 AMP RECEPTACLE © DOOR SWITCH/CONTACT. TIGHT WITH A FLEXIBLE SEALANT. MOUNTED AT 44" AFF OR 4" ABOVE BACKSPLASH. 19. BRANCH BE UTILIZED AS GUIDELINE FOR VOLTAGE DROP ❑K IN TAMPER PROOF ENCLOSURE. KEY OR KEYCARD WEATHERPROOF. WP -WEATHERPROOF. COMPENSATION, SIZE.(A COMPENSATION, INCREASE CONDUIT SIZING PER WIRE SIZE. (APPLIES TO ALL SHEETS) SATIO , WWIRINGRING E CONDUIT 0d''NI� DUPLEX RECEPTACLE WITH GROUND FAULT PROTECTION. 120 VOLT, 20 AMP. A. 20A-120 VOLT CIRCUITS 2 i'i WP 18"AFF UNO. JUNCTION BOX Ip DUPLEX RECEPTACLE WITH INTEGRAL USB OUTLETS. 120 VOLT, 20 AMP. 18" pJ HANDICAP DOOR ACCESS BUTTON IN FLUSH WALL BOX. a. #12 WIRE -]5' LENGTH MAX. 412 GRID. b. #10 WIRE -125' LENGTH MAX. - #10 GRD. AFT UNO. c. #8 WIRE -200' LENGTH MAX. -#8 GRID. d. #6 WIRE - 300' LENGTH MAX. 46 GRID. USB GROUNDING FLUSH FLOOR DUPLEX RECEPTACLE IN FLOOR BOX. 20. PROVIDE ALL PULL BOXES, IN ACCESSIBLE AREA, THAT EXCEED NEC NUMBER OF BENDS LENGTH IN FEEDER AND BRANCH CIRCUITS. INSTALL BOXES WHERE 120 VOLT SINGLE 20 AMP RECEPTACLE. QG GROUND ROD 3l4" DIA. x 10' LONG REQUIRED PER CODE LOCATED IN COMMON AREAS AND EXTERIOR AREAS. 21. ALL WIRING DEVICES SHALL BE OF COMMERCIAL GRADE CONSTRUCTION. REFER TO ARCHITECTURAL SHEETS AND CODE SHEET FOR ALL FIRE -RATED PARTITION ® SPECIAL PURPOSE RECEPTACE. REFER TO FLOOR PLANS FOR NEMA CONFIGURATION. F GROUND CABLE EXOTHERMIC WELD CONNECTION TO REBAR ROD IN CONCRETE FOOTER. LOCATIONS AND RATINGS. �M FRACTIONAL HP MOTOR STARTER WITH THERMAL OVERLOADS. S GROUND CABLE EXOTHERMIC WELD CONNECTION TO BUILDING STEEL. 22. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL CORE -DRILLS REQUIRED FOR INSTALLATION OF ELECTRICAL WORK. .a ELECTRICAL MOTOR. 23. ROUTING OF CIRCUITRY INSTALLED IN CASEWORK, CABINETRIES, ETC. SHALL BE COORDINATED FOR PROPER CONCEALMENT AND FUNCTION OF CASEWORK, ti INDICATES FINAL CONNECTION REQUIRED. - UNDERGROUND COPPER CABLE. CABINETRIES, ETC. 24. VERIFY THE LOCATION OF ALL UTILITIES PRIOR TO EXCAVATION, TRENCHING, OR PPII-21 �� HOMERUN TO PANELBOARD. NOTION INDICATES PANELAND CIRCUIT NUMBER. (ALL CONDUCTORS SHALL BE #10 UNLESS NOTED OTHERWISE.) GENERAL DRILLING. 25. ALL ROOF PENETRATIONS OR PATCHES SHALL BE MADE PER ROOFING o ELECTRICAL PANELBOARD. DETAIL # REFERENCE TAG MANUFACTURER WARRANTY REQUIREMENTS. O JUNCTION BOX. E-406 _DETAIL DRAWING# REFER TO DETAIL SHEETS 26. ALL EXPOSED METAL CONDUITS ARE TO BE PAINTED TO MATCH THE ADJACENT SURFACE. COORDINATION OF PAINTING OF CONDUIT IS TO BE BY THE ELECTRICAL CONTRACTOR, WITH PAINTING BY OTHERS. WCJy IlL 120 VOLT 20 AMP DUPLEX, GFI RECEPTACLE FOR ELECTRIC WATER COOLER. COORDINATE INSTALLATION WITH PLUMBING CONTRACTOR. O KEYNOTE FOR DRAWING 1 27. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL REQUIRED JUNCTION BOXES, PULL BOXES. ETC FOR A COMPLETE INSTALLATION PER THE N.E.C. DETAIL REFERENCE TAG (SECTION) BAS BUILDING AUTOMATION CONTROL PANEL. E-0O6 AND LOCAL CODES. ALL CONDUCTORS SHALL BE RATED FOR 90 DEGREE CELSIUS. 28. COORDINATE WORK WITH OTHER TRADES. COORDINATION OR SCHEDULING SHALL BE 7 CONDUIT STUB -OUT AND CAP BELOW GRADE. MARK STUB -OUT AT GRADE LEVEL. 1 DOOR OR CONFIGURATION DETAIL REFERENCE TAG NEXT LETTER NEXT TO TAGAG REFERS TO SPECIFIC DOOR OR CABLETRAV RESPONSIBILITY OF THE INVOLVED CONTRACTORS. -UE- UNDERGROUND HIGH VOLTAGE OR SECONDARY SERVICE FEED. _ E-002 B LAYOUT. CONFIGURATION INDICATIED IN DETAIL. EJ SAFETY DISCONNECT SWITCH (NON -FUSED). EF-1 MECHANICAL EQUIPMENT TAG. REFER TO EQUIPMENT DATA SAFETY DISCONNECT SWITCH (FUSED). SCHEDULE. ®J COMBINATON MOTOR STARTER/DISCONNECT. WITH HOA SWITCH AT UNIT (FUSIBLE). OR (CIRCUIT BREAKER FOR ELEVATOR). UDB UNIT DISTRIBUTION BOX-FURNISHEDANDINSTALLEDBVE.C.- -Q SOHO 28"H x 14.25"W x 3.75"D FOR TELEPHONE/CAW DISTRIBUTION DATA AND COMMUNICATION v DATA/COMMUNICATION OUTLET. TWO PORTS REFER TO DETAIL FOR MOUNTING REQUIREMENTS. Tim WALL PHONE. 54" AFF. V DATA OUTLET. 16" AFF. Q4 DATA/COMMUNTICATION. FOUR PORT DATA, 16"AFF. Q6 DATA/COMMUNTICATION. SIX PORT DATA, 16" AFF. 1717A[A CABLE TRAY ABOVE CEILING. vWAP WIRELESS ACCESS CONNECTION POINT WITH CEILING MOUNTED CISCO WIRELESS DEVICE. -COM- UNDERGROUND COMMUNICATION DUCT. RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and meal Codes City of Cannel 'PAGIUI DATE: 10/31/19 ELECTRICAL SHEET LIST SHEET NUMBER SHEET NAME E24101 ELECTRICAL LEGEND, GENERAL NOTESAND ABBREVIATATIONS E2-101 LIGHTING PLAN- PARKING AND FIRST FLOOR E2-1W LIGHTING PLAN- SECOND AND THIRD FLOOR E2-103 LIGHTING PLAN- FOURTH FLOOR E2-111 POWER AND SYSTEMS PLAN- PARKING AND FIRST FLOOR E2-112 POWER AND SYSTEMS PLAN- SECOND AND THIRD FLOOR E2-113 POWER AND SYSTEMS PLAN- FOURTH FLOOR AND ROOF E2401 ELECTRICAL ENLARGED PLANS E24@ ELECTRICAL ENLARGED PLANS E2403 ELECTRICAL ENLARGED PLANS E24N ELECTRICAL ENLARGED PLANS E2-501 ELECTRICAL DETAILS E2.601 SINGLE LINE DIAGRAM - SOUTH E2-602 SINGLE LINE DIAGRAM -NORTH E2-701 PANELBOARD SCHEDULES E24I01 EQUIPMENT AND LIGHT FIXTURE SCHEDULES 1kii �- ITT-- WOULPERT MCRITEETUREj N61NEERIN6l6EMATIIL 7635 Interactive Way Suite 100 G Indianapolis, IN 46278 317.299.7500 FAX: 317.291.5805 F E D E OL (_0`J W - W E U C J '- J W K U U O O c r� �I% N M Q nt � 0 W s= om co o c L UI U G€ B m GE) Q Issuances: Rev DEsMMM MTE 0 Issued For Building 2 Review 10/05/18 1 Issued For Building 2 Permit 05/01/19 2 ASI #10 09/11/19 Prom. No.: 074904 Date: 10/05/18 A Sheet Name: ELECTRICAL LEGEND, GENERAL NOTES AND ABBREV IATATIONS E2=001