HomeMy WebLinkAbout(18) E2-4022
3
0
5
0
7
2
0
R
Panel Schedule
PANEL NAME:
PA4
VOLTAGE
208
PHASE
1
WIRE
3
NEUTRAL RATING
100%
PANELDESCRIPTION:
TYPICAL 1-BEDROOM UNIT PANEL
MAINS:
2
100A
MOUNTING:
RECESSED
MA%NO. OF CIRCUITS:
24
MANUFACTURER:
Square D
PANEL A.I.C. RATING
229000
LOCATION:
NO
BRANCH
VA
Loan
Load
VA
BRANCH
P0.E5
a(R
A
B C Type
1
BEDROOM UGHTINGARGCEPTS
BATHROOM UGHTING44ECEPTS,EF-1
1
1
2M
20
763
253
R
R
R
E
2000
1500
20
30
1
2
WASHER
CLOTHES DRYER
2
3
4
5
ENTRY LIGHTINGIRECEPTS
LIVING ROOM UGHTING/RECEPTS
1
20E
ZM
844
742
R
R
E
E
500
2000
-
15
-
1
6
]
1
RANGE
8
9
11
APPLIANCERECEPTS
APPLIANCERECEPTS
1
1
20E
ZM
360
180
R
R
E
E
10]0
1200
15
15
1
2
AHU-2
CU-2
10
12
14
13
15
MICROWAVE
GARBAGE DISPOSAL
DISHWASHER
1
1
1
20
20
20
1"
I=
830
E
E
E
E
E
38
10]0
-
-
15
-
-
1
-
GWHi
SPACE
16
18
17
19
21
SPACE
SPACE
-
-
-
-
-
-
-
-
-
-
-
SPACE
SPACE
20
22
23 ISPACE
-
NOTES:
1. a -ARC -FAULT
CIRCUIT
INTERRUPTER
-
SPACE
24
Trial
UGHTING(L)
0
0
0
0
0
RECEPTS [R]
1957
26]5
0
4 A2
31
EQUIP. tE]
5408
51W
0
10508
69
OTHER
0
0
0
0
0
ADDITION&
0
0
0
0
0
TOTAL
]3]5
W]5
0
151W
DEMAND
5163
5443
0
10E05
70
%
49
51
0
UNIT B2•A4 • ONE BEDROOM
OUHLL 114"' T0
Panel Schedule
PANEL NAME:
PAS
VOLTAGE
208
PHASE:
1
WIRE:
3
NEUTRAL RATING:
100%
PANEL DESCRIPTION:
TYPICAL 1-BEDROOM UNIT PANEL
MAINS:
100A z
MOUNTING:
RECESSED
MAX NO. OF CIRCUITS:
24
MANUFACTURER
Square D
PANEL A.I.C. RATING:
229000
VA
LOCATION:
BRANCH
NO
BRANCH
VA
Load
Lind
POLES
BKR
A
B C Type
1
3
BEDROOM UGHLNGARGCEPTS
BATHROOM UGHTINGAi CEPTS,EFA
1
1
2M
W
1303
214
R
R
R
E
2000
1500
20
30
1
2
WASHER
2
CLOTHES MYER
4
5
]
ENTRY LIGHMNGIRECEPTS
LIVING ROOM LIOH TING4RECEPTS
1
1
20E
20+
686
1102
R
R
E
E
500
2000
-
15
-
1
8
RANGE
8
9
11
APPLIANCE RECEPTS
APPLIANCE RECEPTS
1
1
2M
20+
360
iW
R
R
E
E
10]0
1200
15
15
1
2
AHU-2
CU 2
10
12
14
13
15
17
19
MICROWAVE
GARBAGEDISPOSAL
DISHWASHER
SPACE
1
1
1
-
20
20
20
-
1000
800
8?0
-
E
E
E
E
E
38
-
10]0
-
-
15
-
-
-
1
-
-
GWH1
SPACE
SPACE
18
18
20
21
23
SPACE
SPACE
-
-
-
-
-
-
SPACE
SPACE
22
24
2
NOTES:
1. a-ARGFAULT
CIRW
IT INTERRUPTER
Total
LIGHTING (L)
0
0
0
0
0
RECEPTS [R]
2349
2996
0
5345
34
EQUIP. [E]
5408
51W
0
10508
N
OTHER
0
0
0
0
0
ADDITIONAL
0
0
0
0
0
TOTAL
7757
aces
0
15853
DEMAND
5430
5667
0
11097
70
%
49
51
0
UNIT B2•A5 • ONE BEDROOM
14'=T' U
GENERALNOTES
A. ALL 120V, 15 A AND 20-A RECEPTACLES
SHALL BE TAMPER RESISTANT.
B. COORDINATE ALL KITCHEN AND
KITCHEN ISLAND RECEPTACLES WITH
ARCHITECTURAL ELEVATIONS.
C. PROVIDE FIRE RATED ELECTRICAL
BOXES IN ALL FIRE RATE WALLS,
CEILINGS, AND ASSEMBLIES. REFER TO
ARCHITECTURAL DRAWINGS FOR FIRE
RATINGS.
DRAWING NOTES
1 PROVIDE 125/250V 30A-3P, 4 WIRE DRYER
R��E�C(E,pPIT�ACTTLE, 48" M.H. NEMA 14-30R. (3) #10,
L „
2 PROVIDE 125V 20A-1P RECEPTACLE, 1811
M.H. NEMA 5-20R. (2) #12 #12 GRD., 0.75" z
3 REFER TO ROOF POWER PLAN FOR
LOCATION OF CONDENSING UNIT SERVING
THIS RESIDENTIAL UNIT. DISCONNECT TO
BE LOCATED ON ROOF, ADJACENT TO
EQUIPMENT.
4 REFER TO ARCHITECTURAL DRAWINGS
FOR RESIDENTIAL UNITS WITH FULL
BALCONIES. UNITS WITH BALCONIES
REQUIRE ONE DUPLEX WEATHERPROOF
GFI RECEPTACLE AND WALL MOUNTED
LIGHT. EXTEND NEAREST CIRCUIT IN
ASSOCIATED UNIT FOR POWER.
5 PROVIDE CEILING MOUNTED JUNCTION BOX
UL LISTED FOR FAN AND FIXTURE
SUPPORT. PRE -WIRE FOR FUTURE PADDLE
FAN AND LIGHT KIT.
6 PROVIDE RECEPTACLE AND CATV
EQUIPMENT BOX AT 18" AFF AND AT 4'-9"
AFF BETWEEN BLOCKING AT THIS
LOCATION. COORDINATE EXACT HEIGHT
AND LOCATION OF BLOCKING WITH
ARCHITECTURAL DRAWINGS.
7 PROVIDE 20A - 120V RECEPTACLE UNDER
SINK FOR GARBAGE DISPOSAL AIR SWITCH.
8 CONNECT TO RESPECTIVE CORRIDOR
LIGHTING AND RECEPTACLE CIRCUITS.
9 UDB PANEL TO BE SUTTLE SOLUTIONS 42"
SOHO ACCESS ENCLOSURE. PROVIDE
DUPLEX 12OV-20A RECEPTACLE INSIDE
PANEL FOR EQUIPMENT. ADD TO CIRCUIT
z
#5. CATALOG #SAE-42DDCNY.
10 PROVIDE RECEPTACLE IN CABINET ABOVE
G F R MI R AVE.
1ktff
WOULPERT
ARCRITEETYREjERGINEERINGIGEWATIAL
7635 Interactive Way
Suite 100
G Indianapolis, IN
46278
317.299.7500
FAX: 317.291.5805
F
E
rr.
tog
ILL
n
mlm=o
C
W
Q
0
E
U
�
J•�
.J
W
�
U
�
cn
0
0
>
M
I
N
Q
m
U o
41
W
�
c m
c a
o c
�€
U
m
= U
Q Issuances:
REV
narncMN
GATE
0
Issued For Building 2 Review
10/05/18
1
Issued For Building 2 Permit
05/01/19
2
ASI#10
09/11/19
Prom. No.: 074904
Date: 10/05/18
Sheet Name:
ELECTRICAL
ENLARGED PLANS
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Carmel
�N�1��LBw�QAs>z
DATE: 10/31/19
L*ZIA Ely