HomeMy WebLinkAboutMechanical M1.0OUTLINE
ON ROD
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City Bf Camel (�
yVT�tanrMDA�L
DATE: \ 10/31/19
1
MECHANICAL PLAN
Mica
SCALE varmv-0"
GENERAL SHEET NOTES Is
1. EXISTIWORK. THECO TRACT RSHALL FIE DVERIFYIS BASED H LIMITEDEXISTINGSNDITIO SFORLDING DRAWINGS AND FIELD .
WORN.THECONTRACTORSHALL FIELDVERIFYTHEEXISTINGCONDITIONSFUATION THAT
CONTRACTOR SHALL NOTIFY OWNER, ARCHITECT AND ENGINEER OF ANY SITUATIONS THAT MODIFY OR
INCREASE THE SCOPE OF WORK FROM THAT IS DESCRIBED IN THE DOCUMENTS.
2. ANYTHING NOT NOTED AS EXISTING IS TO BE FURNISHED AND INSTALLED AS PART OF THIS PROJECT.
3. REFER TO DRAWINGS AND PROJECT SPECIFICATIONS OF OTHER OISCIPLINES FOR ADDITIONAL PROJECT
INFORMATION AND REQUIREMENTS. NOTIFY ENGINEER OF ANY CONFLICTS BETWEEN THE INFORMATION
PRIOR TO ANY
ISOLATION
CONDITIONS.FSYSTEMS,
C U R R A N
4. PRIORTOANV ISOLATIOU 6SYSTEMS,SHUTDOWNS OR DEMOLITION THE CONTRACTOR SHALL
PROVIDE NECESSARY INVESTIGATION AND NOTIFY THE FACULTIES ENGNEENNUMAINTENANCE
PERSONNEL OF WORK TO BE PERFORMED SO AS TO AVOID ANY DETRIMENTAL SHUTDOWN OF SYSTEMS
TO ADJACENT SPACES.
5. PROTECT EQUIPMENT, FIXTURES, PIPING, DUCTWORIC ETC. INDICATED TO REMAIN AGAINST DAMAGE A R C H I T E C T U R E
AND SOILING DURING SELECTIVE DEMOLITION. WHEN PERMITTED BY THE ARCHITECT, ITEMS MAY BE
REMOVED TO A SUITABLE, PROTECTED STORAGE LOCATION WRING SELECTIVE DEMOLITION AND THEN 5719 LAWTON LOOP E. DR. #212
CLEANED AND REINSTALLED IN THEIR ORIGINAL LOCATIONS. INDIANAPOLIS, IN 46216
6. WHERE PIPE, DUCTWORK, INSULATION, FIXTURES OR EQUIPMENT TO REMAIN IS DAMAGED OR O :: 317. 288. 0681
DISTURBED, REMOVE THE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY AND IF :: 317 . 288 . 0753
QUALITY. WHERE IDENTICAL MATERIALS ARE UNAVAILABLE OR CANNOT BE USED, USE MATERIALS
WHOSE INSTALLED PERFORMANCE EQUALS OR SURPASSES THAT OF THE EXISTING MATERIALS.
7. MAINTAIN AND RESTORE, IF INTERRUPTED BY DEMOLITION OR IN THE PATH OF NEW CONSTRUCTION,
ALL UTILITIES PASSING THROUGH AND SERVING OUTSIDE OF DEMOLITION AREA.
8. MECHANICAL SYSTEMS INSTALLATIONS MUST MAINTAIN INTEGRITY OF WALLS, PARTITIONS AND FLOORS
DESIGNATED AS EITHER FIRE RATED OR 'SMOKE TIGHT. PROVIDE CODE REQUIRED THROUGH -
PENETRATION FIRESTOP SYSTEM AT RATED OR SMOKE TIGHT ASSEMBLIES WHERE FIRE DAMPERS ARE
NOT REQUIRED. COORDINATE WIARCHITECTURAL PLANS AND GENERAL CONTRACTOR.
9. SPACE ABOVE CEILING IS INDICATED TO BE A RETURN AIR PLENUM. CONSTRUCTION MATERIALS ABOVE
CEILING SHALL BE NONCOMBUSTIBLE, OR HAVE A MAXIMUM 25 FLAME SPREAD AND 50 SMOKE
DEVELOPMENT FINISH RATING. WIRING SHALL BE LABELED PLENUM RATED PER NFPA 70.
10. UNITED ABOVE CEILING CLEARANCES EXIST. COORDINATE LOCATION AND ELEVATION OF MECHANICAL
WORT( WITH ALL DUCTWORK( SPRINKLERS, LIGHT FIXTURES, AND OTHER CEILING BUILT-IN FIXTURES.
CONTACT ENGINEER OR ARCHITECT IMMEDIATELY SHOULD ANY CONFLICT ARISE. DRAWN BY: STK *T/E/S
CHECKD BY: KOH
11. ALLROOF PENETRATIONS, RATTHIS C NTRAC OR'S E GSHALL 00RDINORMED BYPENETR TIONS AROVED
ROOFING CONTRACTORAT THIS HIND ANCFOU'S EXPENSE. COORDINATE ROOF A LANDLORD
AND O PENETRATIONS AND
ROOFTOP EQUIPMENT LOCATIONS WITH LANDLORD AND GENERAL CONTRACTOR.
12. NOTHINGS PERMITTEDTOBEATTACHEDTQ SUSPENDEDFROM, OR PENETRATETHE ROOF DECK.
CONTRACTOR MAY ATTACH TO OR SUSPEND FROM THE TOP CHORD OF THE JOIST ORTHE STRUCTURAL E NGINE ERING
STEEL WHICH EXISTS ABOVE THE SPACE.
13. COORDINATE FINAL ROOFTOP UNIT LOCATIONS WITH LANDLORDS STRUCTURAL ENGINEER. ROOFTOP 25760 First Street
UNITS AND MAKE-UP AIR UNIT TO BE LOCATED WITHIN STRUCTURAL BAY. PROVIDE 10' CLEARANCE FROM Cleveland, OH 44145
UNIT OUTSIDE AIR INTAKE TO ANY EXHAUSTNENTS ON ROOF. P 440 8712410
14. GENERAL CONTRACTOR TO LABEL ALL ROOFTOP EQUIPMENT WITH TENANT NAME, SPACE NUMBER AND F 440 8717954
EQUIPMENT IDENTIFICATION (RTU-1, ETC.), PER MALL SPECIFICATIONS AND STANDARDS. tesengineedng.com
15. REFER TO LL CRITERIA MANUAL FOR ADDITIONAL STANDARDS AND REQUIREMENTS.
16. COORDINATE ALL THERMOSTAT AND SENSOR LOCATIONS WITH FURNITURE LAYOUT AND
ARCHITECTURAL PLANS. DEVICES ARE TO BE INSTALLED AND WIRED BY THE HVAC CONTRACTOR
MOUNT PER ADA REQUIREMENTS.
17. ALL EXPOSED DUCTWORKTOBE PAINTED. REFER TO ARCHITECTURAL PLANS.
18. CHANGES IN DUCT SIZES SHALL BE MADE BY UNIFORM TAPER SECTION WITH A MAXIMUM INCLUDE
ANGLE OF DIVERGENCE OF 15 DEGREE.
19. DUCT SIZES INDICATED REPRESENT EXTERNAL SHEET METAL DIMENSIONS AND INCLUDE ALLOWANCE
FOR INTERNAL INSULATION.
20. SUPPLY AIR DUCTWORK NOT LOCATED IN A RETURN AIR PLENUM OR EXPOSED SHALL BE EXTERNALLY
INSULATED. ALL OUTSIDE AIR DUCTWORK NOT EXPOSED SHALL BE EXTERNALLY INSULATED.
21. BRANCH DUCTS SERVING DIFFUSERS SHALL BE SIZED TO MATCH DIFFUSER NECK SIZE INDICATED
UNLESS NOTED OTHERWISE.
22. PROVIDE ACCESS HATCHES(24"X24") FOR ALL MECHANICAL EQUIPMENT LOCATED ABOVE A HARD
CEILING COORDINATE WI ARCHITECTURAL CEILING PLANS.
23. PITCH POCKETS ARE NOT PERMITTED ON THE ROOF FOR CONDENSATE DRAINS, POWER OR CONTROL
WIRING. ALL CONNECTIONS ARE TO BE MADE INSIDE THE EQUIPMENT CURB OR THROUGH
FEEMANUFACTUREDPIPING CURB.
24. COORDINATE EXACT MOUNTING REQUIREMENTS AND LOCATION OF HOOD WITH HOOD SHOP DRAWINGS
AND OWNER REQUIREMENTS.
25. GREASE EXHAUST DUCT ACCESS PANEL CLEANOUT OPENINGS SHALL BE EQUIPPED WITH TIGHT FRTING
DOORS (EQUAL TO THE THICKNESS OF THE DUCT)AND SHALL HOLD TIGHTLY CLOSED.
26. CONTRACTOR MUST REPLACE ALL AIR FILTERS IN ROOFTOP UNITS WITH
AIR BALANCING AND PRIOR TO FINAL TURNOVER TO TENANT.
O SHEET KEYNOTES
1 TRANSITION LINED SUPPLY AND RETURN DUCTS IN RISE TO FULL SIZE OF RTU SUPPLYAND RETURN
OPENINGS. CONNECT TO FULL SIZE OF RTU SUPPLY AND RETURN OPENINGS WITH FLEX CONNECTION
BELOWROOFDECK. PROVIDE RECTANGULAR ELBOW WITH DOUBLE THICKNESS TURNING VANES IN
TRANSITION TO HORIZONTAL REFER TO RTU SECTION DETAIL ON SHEET M0.0 FOR ADDITIONAL
INFORMATION.
2 MOUNT THERMOSTAT BANK IN OFFICE ABOVE EQUIPMENTI FIXTURES. MOUNT THERMOSTATS AT 481
3 SMOKE DETECTOR FACTORY MOUNTED IN RETURN SECTION OF RTU.
4 UNDERCUT DOOR BY I".(TYPICAL OF ALL TOILET ROOMS)
5 2v22 OPENING IN TOP OF RE TURN DUCT.
6 ROUTE NOTED SIZE EXHAUST DUCT UP TO ROOF ABOVE AT NOTED LOCATION. PROVIDE AND INSTALL
PRE MANUFACTURED ROOF CAP WITH BACK DRAFT DAMPER FOR EXHAUST TERMINATION ABOVE ROOF.
7 WALL MOUNTED TEMPERATURE AVERAGING SENSOR. COORDINATE EXACT LOCATION WITH FURNITURE
LAYOUT AND ARCHITECTURAL PLANS. TEMPERATURE SENSOR SHALL BE WIRED BACK TO THERMOSTAT
IN OFFICE. INSTALL WITH INSULATED PAD WHERE LOCATED ON EXTERIOR WALLS.
8 BOOT TAP WITH VOLUME DAMPER FROM MAKE UP AIR DUCT MAIN TO FULL SIZE 26'X 17 MAKE UP AIR
SUPPLY OUTLETS ON HOOD. BALANCE EACH TO 900 OEM.
9 PROVIDE 1IT X 1IT GREASE EXHAUST DUCT FROM KITCHEN HOOD TO GREASE EXHAUST FAN ON ROOF
ABOVE. PROVIDE GREASE CLEANOUTS AT EVER 194-AND AT EVERY CHANGE IN DIRECTION. FOLLOW
ALL MANUFACTURER AND LOCAL CODE REQUIREMENTS FOR GREASE EXHAUST SYSTEM.
10 ROUTE NOTED SIZE MAKE UP AIR OUCTWORK FROM MUA-1, TRANSITION TO FULL SIZE OF MUA OUTLET IN
VERTICAL. PROVIDE FLEX CONNECTION AT UNIT OUTLET.
I,O�S �SS�pO
OR
5
c
^ma
PROJECT
N LOCATION `
H KEY PLAN
8/1/19
THIS DRAWING AND THE IDEAS DESIGNS
AND CONCEPTS CONTAINED HEREIN ME
THE EXCLUIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOM OR
IN PART, WITHOUTTHE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
0 C IWp172019.CLsVANNRCHIFECNR£
��*i�,lW1:1yG«Cei 11
10460 N MICHIGAN RD
CARMEL, IN 46032
MECHANICAL PLAN
PROJECT NUMBER: 190197
M 1.0