Loading...
HomeMy WebLinkAboutMechanical M2.0RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and Local Codes City Bf Camel DATE: 10/31/19 ROOFTOP HVAC UNIT SCHEDULE SUPPLY FAN DATA DXCOOLINGDATA GAS HEATING DATA UNIT CHARACTERISTICS TAG SERVICE MFR MODEL Na. NOMINAL TONS EER MIN CA (CFM) NOIESIACCESSORIES AIRFLOW ESP MOTOR FAN EAT °DBIWB LAT °DBI°WR SENSIBLE TOTAL COOLING EATILAT INPUT OUTPUT HEATING VOLTAGE OPERATING (CFM) (IN WC) (BHP) (RPM) (°F) (°F) (MBH) (MBH) STAGES (°F) (MBH) (MBH) STAGES (V-q Hj UNIT MCA UNIT MOCP WEIGHT (LES) RTU-1 KITCHEN CARRIER 48HCEDOO 6.0 12.1 m0 2400 0.75 1.4 757 75.5164.3 55.1154.1 51.3 72.4 1 60,51101.5 125.0 103.0 2 208360 34.0 m.0 965 1-18 RTU-2 DINING CARRIER 48HCED07 6.0 12.0 550 2400 0.75 1.4 757 77.2'65.9 56.6155.8 51.8 74.4 1 52.BI93.8 125.0 103.0 2 208360 34.0 5).0 965 1-18 NOTESIACCESSORIES 1. 95° CONDENSING TEMPERATURE 2. REFRIGERANT -R41 OA 3. 100%REFERENCE DRYBULB EC01 4. BAROMETRIC RELIEF 5, 14" INSULATED ROOF CURB 6. UNIT MOUNTED HACR BREAKER 7. UNPOWERED GFCI RECEPTACLE WITH FDD 8. BELT DRIVE 9. SUPPLY FAN VFD WITH SINGLE ZONE VAV CONTROLLER 10. THROUGH THE BASE ELECTRICAL 11. HAIL GUARD- WITH TOOL LESS REMOVAL 12. PROGRAMMABLE SEVEN DAY ALTO CHANGE OVER THERMOSTAT WITH REMOTE SENSOR 13. HINGED ACCESS DOORS 14. MICRO -PROCESSOR CONTROLS 15. 5 YEAR PARTS AND LABOR COMPRESSOR WARRANTY 16. ALUMINIZED HEAT EXCHANGER WITH STAGED HEAT 17. 10 YEAR PARTS WARRANTY ON HEAT EXCHANGER 18. APPROVED ALTERNATES: TRANE,AAON, YORKJOHNSON CONTROLS, LENNOX, DAIKEN MAKE UP AIR UNIT SCHEDULE SUPPLY FAN DATA GAS HEATING DATA UNIT CHARACTERISTICS TAG SERVICE MFR MODEL No. NOTESIACCESSORIES AIRFLOW ESP MOTOR FAN TEMP. RISE INPUT OUTPUT HEATING VOLTAGE OPERATING (CFM) (IN WC) HP) (RPM) (°F) (MBH) (MBH) STAGES (V-(rHz) UNIT FLA UNIT MOCP WEIGHT Must MUA-1 KITCHEN CAFnVEAIRE Ai-D.250-16Z 1800 0.5 1.75 1993 69 140.0 128.8 1 208-160 6.2 15.0 617 1 NOTESIACCESSORIES 1. KITCHEN MUA IS FOR REFERENCE ONLY. KITCHEN MUA IS TO BE PROVIDED BY KITCHEN VENDOR. SEE KITCHEN VENDOR DRAWINGS FOR REQUIREMENTS. OUTSIDE AIR SCHEDULE ZONEDATA SYSTEM DATA FLOOR REQUIRED REQUIRED BREATHINGZONE ZONEAIR REQUIRED SUPPLY SYSTEM REWIRED DELIVERED ZONENAME AREA OUTSIDEAIR OCCUPANCY OUTSIDEAIR OUTSIDE AIR DISTRIBUTION OUTSIDEAIR AIR OUTDOORAIR SYSTEM NAME VENTILATION OUTSIDEAIR OUTSIDEAIR (SF) (CFMISF) (CFWPERSON) (CFM) EFFECTIVENESS (CFM) (CFM) FRACTION EFFICIENCY (CFM) (CFM) KITCHEN CORRIDOR 61 0.06 0 0 4 0.8 5 100 0.050 RTU-1 0.970 289 300 KITCHEN 664 0.18 6 7.5 165 0.8 207 1500 0.138 OFFICE 62 0.06 1 5 9 0.8 12 100 0.120 SERVING 401 0.18 4 7.5 102 0.8 128 700 0.183 RR CORRIDOR 37 0.06 0 0 2 0.8 3 100 0.030 RTU-2 0.890 530 550 DINING 855 0.18 42 7.5 469 0.8 587 2300 0.255 NOTES t. SPACE BASED ON IMC 2015 EXHAUST FAN SCHEDULE AIRFLOW ESP MOTOR FAN VOLTAGE OPERATING TAG SERVICE MFR MODEL No. (CFM) ONWC) (HR'KW) DRIVE (RPM) SONES V-�Hz) WEIGHT NOTESIACCESSORIES LBS) EF-1 KITCHEN CAPTNENRE DU85HFA 22m 1.0 1.0 HE DIRECT 1501 18.7 208.1-63 92 9 EF-2 RR 1 GREENHECK SP-&VG 100 0.25 fi W DIRECT am 2.0 1154-63 12 16 EF3 FIR GREENHECK SP-&VG 100 0.25 fiW DIRECT am 2.0 1154-63 12 16 NOTESIAOCESSOMES 1. MCA SEAL & U.L. LISTED 2.]SCONNECT SWITCH - NEMAI- FACTORY MOUNTED &N 3. BACKDRAFT DAMPER -GRAVITY 4. BIRD SCREEN - GALVANIZED 5. FAN SPEED CONTROLLER- FACTORY MOUNTED & WIRED 6. GRILLE- DECORATIVE 7. FAN CONTROLLED BY TIME CLOCK 8. APPROVED ALTERNATES: COOK, PENNBARRY 9. KITCHEN EXHAUST IS FOR REFERENCE ONLY. KITCHEN H IS TO BE PROVIDED BY KITCHEN VENDOR. SEE KITCHEN VENDOR DRAWINGS FOR REQUIREMENTS. AIR DISTRIBUTION SCHEDULE TAG SERVICE MOUNTING MFR MODEL No. MODULE DIFFUSER SIZE FRAMMORDER DAMPER NOTESIACESSORIES 51 SUPPLY CEILING TITUS OMNI 24"X24" LAY IN - 1,2 Ri RETURN CEILING TITUS mF 24"X24" LAY IN - 1 A2 RETURN CEILING TITUS mF 24"X12" LAY IN - 1 NOTESIACCESSORIES 1. FINISH -WHITE POWDER COAT 2. SECTORRING BAFFLE (SB) AS REQUIRED BY DIRECTIONAL ARROWS ON PLAN, OTHERWISE FOUR (4) WAY BLOW AIR BALANCE SCHEDULE EQUIPMENTTAG SUPPLY AIR (CFM) OUTSIDE AIR (CFM) RETURN AIR (CFM) EXHAUST AIR (CFM) TRANSFER AIR (CFM) RELIEFAIR (CFM) PRESSURE (CFM) Rl 2400 300 a300 Rl 2400 90 a90 EXH KITCHEN 2250 -2250 MUA KITCHEN 1800 1800 aIm0 EXH FIR 200 .200 NOTES: BUILDING TO BE 200 OEM POSITIVE PRESSURE TOTALBUILDINGPRESSURIZATION a200 CURRAN ARCHITECTURE 5719 LAWTON LOOP E. DR. #212 INDIANAPOLIS, IN 46216 O :: 317.288. 0681 F :: 317.288.0753 DRAWN BY: STK CHECKED BY: KDH qWT/E/S ENGINEERING 25760 First Street Cleveland, OH 44145 P 440 8712410 F 440 8717954 tesengineedng.mm B/1/19 THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOM OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCH TECTURE. © T IWG1i2019.CUsvvNA iECNR£ I:H7I_[�771�yc[+IC�7lll 10460 N MICHIGAN RD CARMEL, IN 46032 MECHANICAL SCHEDULES PROJECT NUMBER: 190197 M2.0