HomeMy WebLinkAboutNovo Spk 10-24-19Rev. 3.9.3 Date: Time In:8:30 AM Time Out:10:15 AM Inspector: Inspector:SO# Time:Time:Time:Time: Operator:Operator:Operator:Operator: A.Has there been any modifications to the system since last inspection? B.Have there been any occupant/hazard changes since last inspection? C.Was there an actuation of a device or alarm since last inspection? D.Is building completely sprinkled? E.Are all systems in service? F.Has piping been checked for stoppage? G.Do low points exist? *All answers in this section are based on the customer's knowledge of the system*All answers in this section are based on the customer's knowledge of the system*All answers in this section are based on the customer's knowledge of the system*All answers in this section are based on the customer's knowledge of the system Comments for A-G: 1)1)1)1)GeneralGeneralGeneralGeneral A. Is there proper clearance between sprinklers and storage -- 18in? B.In area protected by wet system does building appear to be properly heated? C.If required, is hydraulic nameplate in place? Plans or prints not available, unable to determine if sign is required. D.Is building occupied? E.Are there proper signs on all valves and switches? 2)2)2)2) A.Are all control valves and other valves in the open position and in good condition? B.Are all control valves locked sealed or supervised? C.Were all OS&Y valves lubricated? 3)3)3)3)Tanks, Pumps, Fire Department Connections Tanks, Pumps, Fire Department Connections Tanks, Pumps, Fire Department Connections Tanks, Pumps, Fire Department Connections A.Are fire pumps, gravity tanks, reservoirs and pressure tanks in good condition and required test performed if needed? B.Are fire department connections in good condition, couplings free and caps in place? C.Are fire department connections accessible and visible? 4)4)4)4)Antifreeze Systems Antifreeze Systems Antifreeze Systems Antifreeze Systems A.Are cold weather valves in proper position? B.This system does not have an antifreeze loop.°F Novo Panel Code:Panel Code:Panel Code:Panel Code: Owner / OccupantOwner / OccupantOwner / OccupantOwner / Occupant Inspector's Section (All responses reference current inspections)Inspector's Section (All responses reference current inspections)Inspector's Section (All responses reference current inspections)Inspector's Section (All responses reference current inspections) Control ValvesControl ValvesControl ValvesControl Valves Does Not ApplyDoes Not ApplyDoes Not ApplyDoes Not Apply L. GLOVER 3530453 System on TestSystem on TestSystem on TestSystem on Test Monitoring Company:Monitoring Company:Monitoring Company:Monitoring Company: None N.Childers Carmel, IN 46032 Inspection & Test ReportInspection & Test ReportInspection & Test ReportInspection & Test Report Inspection Type:Inspection Type:Inspection Type:Inspection Type: Wet/Dry Sprinkler Frequency:Frequency:Frequency:Frequency: Annual October 24, 2019 Novo 1215 S. Rangeline RD Yes No NoYes Yes No NoYes Yes No NoYes NoYes NoYes NoYes NoYes NoYes N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A Yes NoN/A Yes NoN/A Yes NoN/A Yes NoN/A Yes NoN/A Yes NoN/A Yes No N/A Pass Fail NoYesN/A Some areas were unable to be inspected at this time. Sprinkler Test Inspection Report Page 1 of 5 5)5)5)5)Dry Systems Dry Systems Dry Systems Dry Systems A.Are the air pressure and priming water levels normal? B.Has the air or nitrogen supply system been checked for proper operation? C.Were the low points drained? D.Did quick-opening devices operate satisfactory? E.Is dry valve in a properly heated area? 6)6)6)6)AlarmsAlarmsAlarmsAlarms A.Did water motor gong and/or electric bell test satisfactorily? B.Did electric alarm send signals to the fire alarm panel? C.Did supervisory devices work ? D.Were alarm, trouble, and supervisory signals verified with central station? 7)7)7)7)Sprinklers/Piping/GaugesSprinklers/Piping/GaugesSprinklers/Piping/GaugesSprinklers/Piping/Gauges A.Do sprinklers appear to be free from corrosion, loading, or obstruction? B.If standard sprinklers are over 50 years are they being tested? C.If quick response sprinkler are over 20 years are they being tested? D.Is stock of spare sprinklers and wrench available? E.Does the exterior condition of the sprinkler system appear to be in good condition? F.Are gauges in good condition and reading proper pressure? Manufacturers date or date last tested 2008 8)8)8)8)Stand Pipe / Hose Systems Stand Pipe / Hose Systems Stand Pipe / Hose Systems Stand Pipe / Hose Systems A.Type:Wet No.Combined No.Dry No. Water Supply: B.Are stand pipe and hose systems in good condition? 9)9)9)9)Special Systems / Test Special Systems / Test Special Systems / Test Special Systems / Test Type:Type:Type:Type: A.If occupancy has special systems, have they been tested as required? B.Are they in good condition and were tests satisfactory? C.If testing was required, see attached form or system tags? Time to Alarm Signs 40 Drain Size Static PSI Residual PSI Static PSI 2.5 65 50 55 Although these comments are not the result of an engineering review, the following improvements are Although these comments are not the result of an engineering review, the following improvements are Although these comments are not the result of an engineering review, the following improvements are Although these comments are not the result of an engineering review, the following improvements are recommended:recommended:recommended:recommended: Time:Time:Time:Time: Operator:Operator:Operator:Operator: Novo Panel Code:Panel Code:Panel Code:Panel Code: System Back In ServiceSystem Back In ServiceSystem Back In ServiceSystem Back In Service Monitoring Company:Monitoring Company:Monitoring Company:Monitoring Company: None Explain any "No" answers:Explain any "No" answers:Explain any "No" answers:Explain any "No" answers: FDC caps are missing. Flow switch cover off Sprinkler Gauge Out Of Date. Adjustments or corrections made during this inspections:Adjustments or corrections made during this inspections:Adjustments or corrections made during this inspections:Adjustments or corrections made during this inspections: No corrections made at this time.No corrections made at this time.No corrections made at this time.No corrections made at this time. #1 s/o would not close. Recommend service. FACP without power upon arrival. Recommend service Main DrainMain DrainMain DrainMain Drain Location Result Comparable Signs Riser Yes Location Alarm Report Orifice Results Comparable Riser in back room Yes Yes Does Not ApplyDoes Not ApplyDoes Not ApplyDoes Not Apply Inspector's testInspector's testInspector's testInspector's test Smooth Bore Does Not ApplyDoes Not ApplyDoes Not ApplyDoes Not Apply Does Not ApplyDoes Not ApplyDoes Not ApplyDoes Not Apply NoYes NoYes NoYes NoYes NoYes NoYes NoYes NoYes NoYes NoYes NoYes NoYes NoYes NoYes N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A NoYesN/A NoYesN/A NoYesN/A N/A N/A N/A Multiple Inspector's Test Multiple Risers Some sprinklers are unable to be visually inspected at this time. NoYesN/A NoYesN/A NoYesN/A Sprinkler Test Inspection Report Page 2 of 5 Date: Time In:8:30 AM Time Out:10:15 AM Inspector: Inspector:Acct#Acct#Acct#Acct#01NOV1215 SO #SO #SO #SO # QuantityQuantityQuantityQuantity CircuitCircuitCircuitCircuit QuantityQuantityQuantityQuantity CircuitCircuitCircuitCircuit 1 QuantityQuantityQuantityQuantity CircuitCircuitCircuitCircuit QuantityQuantityQuantityQuantity CircuitCircuitCircuitCircuit QuantityQuantityQuantityQuantity CircuitCircuitCircuitCircuit QuantityQuantityQuantityQuantity CircuitCircuitCircuitCircuit Amps Breaker # 60 lpc 16 If FACP batteries failed, were they replaced? Qty --> Size Visual Condition Batt. #1 Batt. #2 Charger Test * See NAC inspection report for power supply battery readings Novo Battery Type Load Voltage Load Amps 120 Circuit Breaker Elec Rm FACP Battery TestFACP Battery TestFACP Battery TestFACP Battery Test Calc. Capacity in Hrs Test Results Fire Pump Controller Other Signaling Line CircuitsSignaling Line CircuitsSignaling Line CircuitsSignaling Line Circuits System Power SuppliesSystem Power SuppliesSystem Power SuppliesSystem Power Supplies No. of Alarm Initiating Circuits Primary Normal Volts Over Current Type Panel Location Fire Pump Power Switch Transfer Fire Pump Run Generator Running Fire Pump Auto Position Low Air DeviceDeviceDeviceDevice DeviceDeviceDeviceDevice Bldg Temp Generator Auto Position Site Water Temp Generator Controller Chimes Horn / Strobes Strobes No. of Indicating Circuits Are Circuits Supervised? Supervisory Signal Initiating DevicesSupervisory Signal Initiating DevicesSupervisory Signal Initiating DevicesSupervisory Signal Initiating Devices Alarm Indicating DevicesAlarm Indicating DevicesAlarm Indicating DevicesAlarm Indicating Devices DeviceDeviceDeviceDevice DeviceDeviceDeviceDevice Bells Speakers Horns Speaker / Strobes Duct Detectors Other Heat Detectors No. Of Alarm Initiating Circuits Key Switch Are Circuits Supervised? Ion Smoke Detectors Supervisory Switches Photo Smoke Detectors Beam Detectors Software Revision:Last Software Rev. : Alarm Initiating DevicesAlarm Initiating DevicesAlarm Initiating DevicesAlarm Initiating Devices DeviceDeviceDeviceDevice DeviceDeviceDeviceDevice Number of Circuits:Last Service Date: Type Transmission:Digital Panel Make: Manual Pull Stations Waterflow Switches Circuit Class:Panel Model: Operator:Panel Code: 1215 S. Rangeline RD1215 S. Rangeline RD1215 S. Rangeline RD1215 S. Rangeline RD N.Childers Carmel, IN 46032Carmel, IN 46032Carmel, IN 46032Carmel, IN 46032 L. GLOVER Monitoring Company: None Time Placed On Test: Inspection & Test ReportInspection & Test ReportInspection & Test ReportInspection & Test Report Inspection Type:Inspection Type:Inspection Type:Inspection Type:Fire Alarm Frequency:Frequency:Frequency:Frequency: October 24, 2019 NovoNovoNovoNovo Yes No Yes No Pass Fail N/A N/A N/A Yes No Fire Alarm Inspection Report Page 3 of 5 VisualVisualVisualVisual FunctionFunctionFunctionFunction Type: Qty: *See detection inspection report VisualVisualVisualVisual FunctionFunctionFunctionFunction Qty: Operator: Received Notified Technician Comments: Rev. 3.9.3 Novo Building Occupants AHJ Building Management Monitoring Agency Supervisory Signal Supervisory Restore Notified Testing CompleteNotified Testing CompleteNotified Testing CompleteNotified Testing Complete Comments Alarm Signal No Monitoring Services Alarm Restore Trouble Signal On / Off Premises MonitoringOn / Off Premises MonitoringOn / Off Premises MonitoringOn / Off Premises Monitoring Time Verified Signal Sent Comments Verified By: Fireman Phone Was dBA Meter Utilized?Average Ambient: Voice Intelligibility - Average Alarm: Phone Jack Off Hook Indicator Voice Clarity Call In Singal System Performance Phone Set Speakers Amplifiers Tone Generators Emergency Communications Equipment / Notification AppliancesEmergency Communications Equipment / Notification AppliancesEmergency Communications Equipment / Notification AppliancesEmergency Communications Equipment / Notification Appliances DeviceDeviceDeviceDevice CommentsCommentsCommentsComments Audible Visual Door Holders Were heat detectors tested with heat?If no, date on fix temperature devices: Heat detector loop resistance reading: Ground Fault Monitoring Transient Suppressors Remote Annunciators Primary Power Supply Trouble Signals Disconnect Switches Interface Equipment Lamps / LED Fuses System Test and InspectionsSystem Test and InspectionsSystem Test and InspectionsSystem Test and Inspections DeviceDeviceDeviceDevice CommentsCommentsCommentsComments Control Panel (FACP) N/A Fire Alarm Inspection Report Page 4 of 5 Page Qty:Page Qty:Page Qty:Page Qty:1111 3333 Zone or Zone or Zone or Zone or AddressAddressAddressAddress MakeMakeMakeMake ModelModelModelModel Sensitivity Sensitivity Sensitivity Sensitivity Alarm PointAlarm PointAlarm PointAlarm Point Pass / FailPass / FailPass / FailPass / Fail OSY 4"Pass OSY 4"Pass ITV Pass Carmel, IN 46032 All devices passed during this inspectionAll devices passed during this inspectionAll devices passed during this inspectionAll devices passed during this inspection DETECTION INSPECTION REPORTDETECTION INSPECTION REPORTDETECTION INSPECTION REPORTDETECTION INSPECTION REPORT October 24, 2019 SO# 0 Novo 1215 S. Rangeline RD Total devices inspectedTotal devices inspectedTotal devices inspectedTotal devices inspected Riser in back room Device LocationDevice LocationDevice LocationDevice Location TypeTypeTypeType CommentsCommentsCommentsComments Not Tampered Sensitivity RangeSensitivity RangeSensitivity RangeSensitivity Range Not Tampered WaterFlow Water Flow Riser in back room Sensitivity and Detection Inspection Report Page 5