HomeMy WebLinkAboutEnergy Code - JG093 (AS DESIGNED)IECC 2009 Performance Compliance
Property
1238 SKYTAG DR
CARMEL, IN 46032
Model: CUSTOM
Community: JACKSONS GRANT 93
JG093 (AS DESIGNED)
JACKSONS GRANT 93
Organization
TSI Energy Solutions
Devin Sielschott
Builder
EXECUTIVE HOMES
CONSTRUCTION, INC.
Design
Heating
Coaling
Water Heating
SubTotal - Used to determine compliance
Lights & Appliances
Onsite generation
Total
Inspection Status
Results are projected
Annual Energy Cost
IECC 2009 Performance
$2,192
$360
$214
$2,766
$1,156
$0
$3,922
Requirements
405.3 Performance -based compliance passes by D.4%
® R402.4.1.2 Air Leakage Testing
0 402.5 Area -weighted average fenestration SHGC
402.5 Area -weighted average fenestration LI-Factor
® 4032.2 Duct Testing
Mandatory Checklist Mandatory code requirements that are not
checked by Ekotrope must be met.
R4052 Duct Insulation
C",Erergy Solutions
As Designed
$2,261
$279
$214
$2,754
$1,121
$0
$3,874
Air sealing is 5.00 AC at 50 Pa. It must not exceed 7.00 AC at 50 Pa.
Design exceeds requirements for IECC 2009 Performance compliance by 0.4%.
As a 3rd party extension of the code jurisdiction utilizing these reports, I certify that this energy code compliance document has been created in accordance with the requirements of
Chapter 4 of the adopted International Energy Conservation Code based on Climate Zane 5. If rating is Projected, I certify that the building design described herein is consistent with
the building plans, specifications, and other calculations submitted with the permit application. If rating is Confirmed, I certify that the address referenced above has been
inspected/tested and that the mandatory provisions of the IECC have been installed to meet or exceed the intent of the IECC or will be verified as such by another party.
Name: Devin Sielschott
Organization: TSI Energy Solutions
Signature:
Date: 9f13119 at 9:57 AM
Ekotrope RATER - Version 3.1.1.2251
IECC 2009 Performance compliance results calculated using Ekotrope RATER's energy and code compliance algorithm.
Ekotrope RATER is a RESNET Accredited HERS Rating Tool. All results are based on data entered by Ekotrope users.
Ekotrope disclaims all liability for the information shown on this report.
1238 SKYTAG DR
CARMEL, IN 46032
Builder: EXECUTIVE HOMES CONSTRUCTION, INC.
Ceiling Attic, R-38
Above Grade Walls R-15
Foundation Walls R-10
Framed Floor R-38
Slab R-0.0 Perimeter, R-0.0 Under
Infiltration 5 ACH50
Window U-Value: 0.3, SHGC: 0.28
Building Features
Duct Supply R-20.0, Return R-20.0
Duct Leakage to Outside 250 CFM25 (4.23 / 100 s.f.)
Total Duct Leakage 472 CFM25 (Post -Construction)
Heating Furnace • Natural Gas • 92.1 AFUE
Cooling Air Conditioner • Electric • 13 SEER
Water Heating Water Heater • Natural Gas • 0.7 Energy Factor
As a 3rd party extension of the code jurisdiction utilizing these reports; I certify that this energy code compliance document has been created in accordance with the requirements of
Chapter 4 of the adopted International Energy Conservation Code based on Climate Zone 5. If rating is Projected, I certify that the building design described herein is consistent with the
building plans, specifications, and other calculations submitted with the permit application. If rating is Confirmed, I certify that the address referenced above has been inspected/tested and
that the mandatory provisions of the IECC have been installed to meet or exceed the intent of the IECC or will be verified as such by another party_
Name: Devin Sielschott
Organization: TSI Energy Solutions
Signature:
Date: 9/13/19 at 9:57 AM
Ekotrope RATER - Version 3.1.1.2251
2009 IECC compliance results calculated using Ekotrope RATER's energy and code compliance algorithm.
Ekotrope RATER is a RESNET Accredited HERS Rating Tool. All results are based on data entered by Ekotrope users.
Ekotrope disclaims all liability for the information shown on this report.
Energy Code Inspection Checklist
Property Organization
1238 SKYTAG DR TSI Energy Solutions
CARMEL, IN 46032 Devin Sielschott
Model: CUSTOM
Community: JACKSONS GRANT 93 Builder
EXECUTIVE HOMES
JG093 (AS DESIGNED) CONSTRUCTION, INC.
JACKSDNS GRANT 93
General Building Information
Conditioned Area (sq ft) 5,915
Conditioned Volume (cubic ft) 56,395
Insulated Shell Area (sq ft) 11,475
Inspection Status
Results are projected
C",
Energy Solutions
The building energy model in Ekotrope reflects the building assemblies and energy features listed below. Sometimes energy
features will change in the field from what has been modeled. The inspection process should identify any changes and ensure
that the home continues to meet the applicable energy code.
Slab
] Name: BSMT(1,822 s.f., 213 ft. exterior perimeter)
R-0 perimeter insulation, R-0 under slab insulation.
Framed Floor
] Name: GARAGE (450 s.f.)
R-0 continuous insulation, R-38 cavity insulation
Insulation Grade: I
Foundation Wall
1� Name: CGNDIAMB (Exterior Perimeter [ft]: 142, Height Above Grade [ft]: 2.5, Depth Below Grade [ft]: 6.5)
1--I R:9.696
Fully insulated (top to bottom)
] Name: COND/AMB UNFIN (Exterior Perimeter [ft]: 33, Height Above Grade [ft]: 2.5, Depth Below Grade [ft]: 6.5)
R: 0.00
Fully insulated (top to bottom)
] Name: CON DIGARAGE UN FIN (Exterior Perimeter [ft]: 38, Height Above Grade [ft]: 2.5, Depth Below Grade [ft]: 6.5)
R: 0.00
Fully insulated (top to bottom)
Above Grade Wall
Energy Code Inspection Checklist
Property Organization
1238 SKYTAG DR TSI Energy Solutions
CARMEL, IN 46032 Devin Sielschott
Model: CUSTOM
Community: JACKSONS GRANT 93 Builder
EXECUTIVE HOMES
JG093 (AS DESIGNED) CONSTRUCTION, INC.
JACKSDNS GRANT 93
Name: CONDIAMB (3,270 s.f.)
R-0 continuous insulation, R-15 cavity insulation
Insulation Grade: I
Name: CON DIGAR (380 s.f.)
R-0 continuous insulation, R-15 cavity insulation
Insulation Grade: I
Name: CONDIATTIC (831 s.f.)
R-0 continuous insulation, R-15 cavity insulation
Insulation Grade: I
Rim Joist
1� Name: CONDIAM6 (299 s.f.)
1--1 R: 15.414
Roof
Name: CON DIGARAGE (38 s.f.)
R: 15.414
Name: CONDIATTIC (119 s.f.)
R: 15.414
Name: MAIN (1,989 s.f.)
R-27.55 continuous insulation, R-10.15 cavity insulation
Insulation Grade: I
Name: BONUS ROOM (360 s.f.)
R-0 continuous insulation, R-38 cavity insulation
Insulation Grade: I
❑paque Door
El Name: FRONT (48 s.f.)
U: 0.476
Inspection Status
Results are projected
C",
Energy Solutions
2
Energy Code Inspection Checklist
Property
1238 SKYTAG DR
CARMEL, IN 46032
Model: CUSTOM
Community: JACKSONS GRANT 93
JG093 (AS DESIGNED)
JACKSONS GRANT 93
Name: GARAGE (20 s.f.)
U: 0.182
Glazing
Organization
TSI Energy Solutions
Devin Sielschott
Builder
EXECUTIVE HOMES
CONSTRUCTION, INC.
Inspection Status
Results are projected
El Name: FRONT (176 s.f.), U: 0.300, SHGC: 0.28, Orientation: SOUTH
[] Name: BACK (214 s.f.), U: 0.300, SHGC: 0.28, Orientation: NORTH
El Name: LEFT (76 s.f.), U: 0.300, SHGC: 0.28, Orientation: WEST
El Name: RIGHT (96 s.f.), U: 0.300, SHGC: 0.28, Orientation: EAST
Name: SLIDER (48 s.f.), U: 0.300, SHGC: 0.28, Orientation: EAST
El Name: BACK BSMT (30 s.f.), U: 0.300, SHGC: 0.28, Orientation: NORTH
Name: LEFT BSMT (16 s.f.), U: 0.300, SHGC: 0.28, Orientation: WEST
Skylight
None Present
Mechanical Ventilation
Mechanical ventilation system rated for, and capable of, providing continuous ventilation.
System shall include automatic timing controls.
System type: Exhaust Only, 24 hrslday, 6 Watts.
Mechanical Equipment
FURNACE 1 • Natural Gas • 100% Heating Load @ 92.1 AFUE
El AC 1 • Electric • 100% Cooling Load @ 13 SEER
E] Water Heating • Natural Gas • 100% Hot Water Load @ 0.7 Energy Factor
CTMEriergy Solutions
3
Energy Code Inspection Checklist
Property Organization
1238 SKYTAG DR TSI Energy Solutions
CARMEL, IN 46032 Devin Sielschott
Model: CUSTOM
Community: JACKSONS GRANT 93 Builder
EXECUTIVE HOMES
JG093 (AS DESIGNED) CONSTRUCTION, INC.
JACKSDNS GRANT 93
Air Leakage Control
inspection Status
Results are projected
Test Status: Blower -door tested
House is air -sealed as to achieve 4,700 CFM50 (5.00 ACH50) or less at final blower -door test.
Infiltration Requirements for IECC in Climate Zone 5
2009 IECC Infiltration limit for the design home is 7 ACH50.
2012 IECC Infiltration limit for the design home is 3 ACH50.
2015 IECC Infiltration limit for the design home is 3 ACH50.
Duct Leakage
Duct System 1
NOT entirely within conditioned space, testing required
Leakage to ❑utside specified as: 250 CFM25 (4.23 / 100 s.f.)
Total Leakage specified as: 472 CFM25 (Post -Construction)
Duct Leakage Code Requirements for IECC
2009 IECC:
Postconstruction Leakage Test: Duct Leakage to Outdoors <= 8 CFM25 / 100 sq ft CFA.
Rough in Test with AHU: Total Duct Leakage <= 6 CFM25 / 100 sq ft CFA.
Rough in Test without AHU: Total Duct Leakage <= 4 CFM25 / 100 sq ft CFA.
2012 IECC and 2015 IECC Prescriptive Path:
Postconstruction Leakage Test: Total Duct Leakage <= 4 CFM251 100 sq ft CFA.
Rough in Test with AHU: Total Duct Leakage <= 4 CFM25 / 100 sq ft CFA.
Rough in Test without AHU: Total Duct Leakage <= 3 CFM25 / 100 sq ft CFA.
2015 Performance Path (Cost Compliance):
C",
Energy Solutions
Leakage testing is required UNLESS all ducts and air handlers are located entirely within the thermal envelope.
There is no pass/fail threshold for duct leakage on the performance path.
Project Notes
4
Building Summary
Property
Organization
Inspection Status
*Sl
Energy Solutions
1238 SKY -FAG DR
TSI Energy Solutions
Results are projected
CARMEL, IN 46032
Devin Sielschott
Model: CUSTOM
Community: JACKSONS GRANT 93
Builder
EXECUTIVE HOMES
JG093 (AS DESIGNED)
CONSTRUCTION, INC.
JACKSONS GRANT 93
Number Of Bedrooms
5
Number Of Floors
2
Conditioned Floor Area [sq. ft.]
5,915
Unconditioned; attached garage?
Yes
Conditioned Volume [cu. ft.]
56,395
Total Units in Building
1
Residence Type
Single family detached
Floor Number
Model
CUSTOM
Community
JACKSONS GRANT 93
Climate Zone
5A
rFoundation Wall
Name Library type
Height Above Grade Depth Below Grade Perimeter Location
Enclosing
CONDIAMB R-11 Finished, G1
2.5
6.5
142 Exposed Exterior
Conditioned Space
CONDIAMB UNFIN Uninsulated
2.5
6.5
33 Exposed Exterior
Conditioned Space
CONDIGARAGE Uninsulated
2.5
6.5
38 Exposed Exterior
Conditioned Space
UNFIN
Foundation Wall Library List
Name Feet From Wall Top To
Feet From Wall Tap To Is Fully Insulated Continuous R-value Cavity R-value
Effective Insulation R-
Continuous Insulation
Continuous Insulatian
value
Top
Bottom
R-11 Finished, G1 NIA
NIA
Yes
NIA NIA
9.696
Uninsulated NIA
NIA
Yes
NIA NIA
0.00
lab
Name Library type
Perimeter Floor Grade
Carpet R Exposed
Surface Area Location Enclosing
Masonry Area
BSMT Uninsulated
213 Below Grade
❑ ❑
1,822.0ft' Exposed Exterior Conditioned
Space
1
Building Summary
Property Organization Inspection Status
1238 SKY -FAG DR TSI Energy Solutions Results are projected
CARMEL, IN 46032 Devin Sielschott
Model: CUSTOM
Community: JACKSONS GRANT 93 Builder
EXECUTIVE HOMES
JG093 (AS DESIGNED) CONSTRUCTION, INC.
JACKSONS GRANT 93
Slab Library List
Name Wall Construction Slab Completel�r Underslab Perimeter Perimeter
Type Insulated. Insulation Width [ft] Insulation Depth [ft] Insulation R Value
Uninsulated Woad Frame 1 Other No ❑ 0 ❑
C"IEnergy Solutions
No 0.00
Framed Floor
Name Library Type Carpet R Floor Grade Surface Area Location
I GARAGE R-38. GR1 1 Above Grade 450.0 ft' Unconditioned. attached
garage
Framed Floor Library List
Name Effective R-value
G 33.825
Rim Joist
Name Library Type Surface Area Location
CONDIAMB G1 R-19. OSB 299.0 ft' Exposed Exterior
CONDIATTIC G1 R-19. OSB 119.0 ft1 Attic
CONDIGARAGE G1 R-19. OSB 38.0 ft1 Unconditioned, attached garage
Rim Joist Library List
Name Effective Insulation R-value
G1 R-19. OSB 15.414
Building Summary
Property
Organization
1238 SKY -FAG DR
TSI Energy Solutions
CARMEL, IN 46032
Devin Sielschott
Model: CUSTOM
Community: JACKSONS GRANT 93
Builder
EXECUTIVE HOMES
JG093 (AS DESIGNED)
CONSTRUCTION, INC.
JACKSONS GRANT 93
Inspection Status
Results are projected
C"IEnergy Solutions
1-111C LIYIGIr 1311ju
JY1-w
YY1Vl
LYL L-11
CONDIAMB G1 R-15 BATT, OSB
Medium
3,270.0 ft'
Exposed Exterior
CONDIATTIC G1 R-15 BATT, OSB
Medium
831.0 ft,
Attic
CONDIGAR G1 R-15 Gar Walls
Medium
380.0 ft2
Unconditioned, attached garage
Wall Library List
Name Effective R-value
G1 R-15 BATT. OSB
13.423
G1 R-15 Gar Walls
11.972
Glazing
Name Library type Wall Assignment
Foundation Wall Overhang
Depth
Overhang Ft To Overhan-0
Ft To
Orientation
Surface Area
Assignment
Tap
Ejottom
BACK U-.30. SHGC-.28 CONDIAMB
0
0
0
North
214.0 ft'
BACK BSMT U-.30, SHGC-.28
CONDIAMB
0
0
0
North
30.0 ft'
FRONT U-.30, SHGC-28 CONDIAMB
0
0
0
South
176.0 ft2
LEFT U-.30. SHGC-28 CONDIAMB
0
0
0
West
76.0 ft2
LEFT BSMT U-.30, SHGC-28
CONDIAMB
0
0
0
West
16.0 ft2
RIGHT U-.30. SHGC-28 CONDIAMB
0
0
0
East
96.0 ft2
SLIDER U-.30. SHGC-.28 CONDIAMB
0
0
0
East
48.0 ft2
Glazing Library List
Name
Shg c
U-facto r
U-.30, SHGC-.28
028
0.300
3
Building Summary
Property
1238 SKY -FAG DR
CARMEL, IN 46032
Model: CUSTOM
Community: JACKSONS GRANT 93
JG093(AS DESIGNED)
JAGKSONS GRANT 93
Skylight fW I
Skylight Library List
Opaque Door
Organization
TSI Energy Solutions
Devin Sielschott
Builder
EXECUTIVE HOMES
CONSTRUCTION, INC.
i
None Present
Inspection Status
Results are projected
C"IEnergy Solutions
Name Library Type Wall Assignment Foundatian Wall Emittance Solar Surface Color Surface Area Location
Assignment Absorptance
FRONT Wood Door CONDIAMB 0.9 0.75 Medium 48.0 fIl Exposed Exterior
GARAGE Steel Door CONDIGAR 0.9 0.75 Medium 20.0 fI2 Exposed Exterior
Opaque Door Library List
Name Effective U-factor
Steel Door 0.182
Wood Door 0.476
Roof Insulation
Name
BONUS ROOM R-38 Vaulted, GR1
MAIN R-38 Blown, GR1
360
No
Medium
360.0 fl'
Attic
1,989
No
Medium
1,989.0 rtz
Attic
4
Building Summary
Property
1238 SKY -FAG DR
CARMEL, IN 46032
Model: CUSTOM
Community: JACKSONS GRANT 93
JG093(AS DESIGNED)
JAGKSONS GRANT 93
Roof Insulation Library List
Name Has
R-38 Blown, GR1
R-38 Vaulted, GR1
Organization Inspection Status
TSI Energy Solutions Results are projected
Devin Sielschott
Builder
EXECUTIVE HOMES
CONSTRUCTION, INC.
No 38.268
No
32.263
Whole House Infiltration
Infiltration Measurement type Shelter Class
5ACH at 50 Pa
Blower -door tested
MW
Mechanical Ventilation
Ventilation Type Ventilation Rate [ft' l Operational hours per day
Minute]
Exhaust Only 20 24
Lighting
% Interior Fluorescent % Interior LED Lighting % Exterior Fluorescent
Lighting Lighting
0 80 a
Onsite Generation
one
Onsite Generation Library List
None Present
4
C"IEnergy Solutions
Fan Watts Runs once every three Energy Recovery Percent
hours
6 Yes
ing % Garage Fluorescent % Garage LED Lighting
Lighting
80 0 8C
5
Building Summary
Property
1238 SKY -FAG DR
CARMEL, IN 46032
Model: CUSTOM
Community: JACKSONS GRANT 93
JG093(AS DESIGNED)
JAGKSONS GRANT 93
Solar Generation
Organization
TSI Energy Solutions
Devin Sielschott
Builder
EXECUTIVE HOMES
CONSTRUCTION, INC.
Solar Generation Library List
None
Conditioning Equipment
Name Library Type
AC " CA13MA042-A
FURNACE 1 912SA481o0S17
Water Heating GPVX-75L-210
Equipment Type: 912SA4810OS17
9
*Sl Energy Solutions
Inspection Status
Results are projected
ng Yercen . LoaG MOT water YercenT Loao LOCaTIOn
0% 100% 0% Conditioned Space
100% 0%
0% 0%
Fuel Type
Natural Gas
Distribution Type
Forced Air
Motor Type
PSG (Single Speed)
Heating Efficiency
92.1 AFUE
Heating Capacity [kBtulh]
93
Use default EAE
No
EAE [kWh]
756
Equipment Type:
CA13NA042-A
Fuel Type
Electric
Distribution Type
Forced Air
Motor Type
PSG (Single Speed)
Cooling Efficiency
13 SEER
Cooling Capacity [kBtulh]
40
0% Conditioned Space
100% Conditioned Space
Building Summary
Property
Organization
1238 SKY -FAG DR
TSI Energy Solutions
CARMEL, IN 46032
Devin Sielschott
Model: CUSTOM
Community: JACKSONS GRANT 93
Builder
EXECUTIVE HOMES
JG093 (AS DESIGNED)
CONSTRUCTION, INC.
JACKSONS GRANT 93
quipment Type: GPVX-75L-210
Fuel Type
Natural Gas
Distribution Type
Hydronic Delivery
Hot Water Efficiency
0.7 Energy Factor
Tank Capacity (gal.)
75
Hot Water Capacity [kBtulhl
40
Recovery Efficiency
0.79
r Distribution System
Distribution Type
Forced Air
Heating Equipment
FURNACE 1
Cooling Equipment
AC 1
Sq. Feet Served
5915
# Return Grilles
4
Supply Duct R Value
20
Return Dud R Value
20
Supply Duct Area [ftq
1597.05
Return Dud Area [ftJ
1183
Leakage to Outdoors
250 CFM25 (4.231 100 s.f.)
Total Leakage
472 CFM25
Total Leakage Duct Test Conditions
Post -Construction
Use Default Flow Rate
Yes
Duct 1
Duct Location
Conditioned Space
Percent Supply Area
50
Percent Return Area
50
Duct 2
Duct Location
Attic (well vented, under insulation)
Percent Supply Area
50
Percent Return Area
50
Duct 3
Duct Location
Conditioned Space
Percent Supply Area
❑
Percent Return Area
❑
Duct 4
Duct Location
Conditioned Space
Percent Supply Area
❑
Percent Return Area
0
Duct 5
Duct Location
Conditioned Space
Percent Supply Area
❑
Percent Return Area
❑
Duct 6
Duct Location
Conditioned Space
Percent Supply Area
0
Percent Return Area
❑
rCeiling Fan
Has Ceiling Fan No
Cfm Per Watt 100
Inspection Status
Results are projected
C"IEnergy Solutions
Building Summary
Property
Organization
1238 SKY -FAG DR
TSI Energy Solutions
CARMEL, IN 46032
Devin Sielschott
Model: CUSTOM
Community: JACKSONS GRANT 93
Builder
EXECUTIVE HOMES
JG093 (AS DESIGNED)
CONSTRUCTION, INC.
JACKSONS GRANT 93
Water Distribution
Water Fixture Type
Standard
Use Default Hot Water Pipe Length
No
Hot Water Pipe Length [ft]
75
At Least R3 Pipe Insulation?
No
Hot Water Recirculation System?
No
Recirculation System Pipe Loop Length [ft]
20
Drain Water Heat Recovery?
No
Clothes Dryer
Fuel Type Electric
Cef 2.617
Field Utilization Timer Controls
INA
Label Energy Rating
704 kWh1Year
Electric Rate
$0.081kWh
Annual Gas Cost
$23.00
Gas Rate
$0.581Therm
Capacity
2.874
Imet
❑.331
ppliances and Controls
rogrammable thermostat?
Yes
ishwasher Size
Standard
ishwasher Efficiency
ID
270 kWhangefOven
Fuel
Electric
onvection Oven?
N❑
duction Range?
N❑
efrigerator Consumption
709 kVVhfYear
Inspection Status
Results are projected
C"IEnergy Solutions