HomeMy WebLinkAboutE001 ELECTRICAL ABBREVIATIONS SYMBOLS AND SPECIFICATIONSELECTRICAL ABBREVIATIONS
A
AMPS
AFF
ABOVE FINISHED FLOOR
CO
COMPANY
CONTR
CONTRACTOR
DIN
DOWN
DWG(S)
DRAWING(S)
EC
ELECTRIC CONTRACTOR
EDC
ELECTRICAL DISTRIBUTION CENTER
EM
EMERGENCY
EQUIP
EQUIPMENT
ETR
EXISTING TO REMAIN
EWC
ELECTRIC WATER COOLER
EX
EXISTING
FLA
FULL LOAD AMPS
FS
FLOW SWITCH
GC
GENERAL CONTRACTOR
HE
HORSEPOWER
MAX
MAXIMUM
ME
MAIN BREAKER
MC
MECHANICAL CONTRACTOR
MCA
MIMIMUM CIRCUIT AMPS
MFR
MANUFACTURER
MH
MOUNTING HEIGHT
MIN
MINIMUM
MLO
MAIN LUG ONLY
MOCP
MAXIMUM OVER CURRENT PROTECTION
MOD
MOTOR OPERATED DAMPER
MTD
MOUNTED
NIC
NOT IN CONTRACT
NTS
NOT TO SCALE
OC
ON CENTER
PC
PLUMBING CONTRACTOR
PSI
POUNDS PER SQUARE INCH
RLA
RUNNING LOAD AMPS
RPM
REVOLUTIONS PER MINUTE
V
VOLTS
UON
UNLESS OTHERWISE NOTED
PANELBOARD SCHEDULE
ABBREVIATIONS
L
LIGHTING
R
RECEPTACLE
PIN
POWER NON -SEASONAL
PW
POWER WINTER
MN
MOTOR NON -SEASONAL
MINI
MOTOR NON -SEASONAL INTERMITTENT
MS
MOTOR SUMMER
MW
MOTOR WINTER
KT
KITCHEN
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Carmel
��;W�3tIa,N
DATE: 11 /14/19
ELECTRICAL SYMBOLS
DISCONNECT
EY
EXIT SIGNAGE
e
EXIT SIGNAG E WITH EME RG ENCY HEADS
EMERGENCY LIGHTING UNIT
EMERGENCY EXIT EGRESS LIGHT
8
SUSPENDED STRIP LIGHT
SURFACE MOUNTED STRIP LIGHT
RECESSED DOWN LIGHT
O
MOTOR
LIGHT FIXTURE- ON NIGHT LIGHT CIRCUIT
LAVIN TROFFER FIXTURE
SUSPENDED LAVIN
SURFACE MOUNTED LAYIN
LIGHT FIXTURE - UNDER COUNTER
LIGHT FIXTURE - WALL SCONCE
I0
IY
LIGHT FIXTURE - PENDANT
LIGHT FIXTURE - TRACK
LIGHT FIXTURE- RECESSED DOWN LIGHT
O
LIGHT FIXTURE -VANITY LIGHT
pgp
OUTLET-4 WAY
OUTLET -DUPLEX
OUTLET- GROUND FAULT INTERRUPT
Q
OUTLET- GROUND FAULT INTERRUPT WEATHERPROOF Q Wp
OUTLET -DUPLEX WITH USE
OUTLET -220
JUNCTION BOX
O
SPECIAL EQUIPMENT COORDINATE W/SUPPLIER
FLOOR OUTLET WITH POWER, DATA AND PHONE FLR
LOW VOLTAGE ONE LINE
LOW VOLTAGE TWO LINE
-4
LOW VOLTAGE # LINES
-4 #
ANALOG PHONE LINE
WIRELESS ACCESS POINT
WAP
PUSH BUTTON
LJ
BUZZER
PHOTO CELL
p
POWER POLE
® pp
TIME CLOCK
TC
SWITCH
$
SWITCH -3 WAY
3
SWITCH -4 WAY
4
SWITCH WITH DIMMER
$D
SWITCH WITH OCCUPANCY SENSOR
Y $OS
CEILING MOUNTED OCCUPANCY SENSOR
®S
PANEL DESIGATION -i F-IT CIRCUIT BREAKER NUMBERS
X: XX,XX,XX
DOOR ALARM CONTROL PANEL
DACP
HINGE SIDE PLUNGER SWITCH
IDC
MAGNETIC LOCK WITH KEY PAD
1731
MAGNETIC LOCK WITH CARD READER
CR
ELECTRICAL SPECIFICATIONS
1. BID INSTRUCTIONS: CONTRACTORS SHALL PROVIDE BASE
BID IN STRICT ACCORDANCE WITH DESIGN BASIS
EQUIPMENT AND MATERIALS. PROJECT DOES ENCOURAGE
COMPETITIVE PRICING AND ALLOWS FOR SUBSTITUTIONS
OF EQUAL EQUIPMENT AND MATERIALS AGAINST THE BASIS
OF DESIGN. SUBSTITUTE ITEMS WILL BE COMPARED
AGAINST DESIGN BASIS DURING SUBMITTAL PROCESS.
ENGINEER RESERVES THE RIGHT TO REJECT
SUBSTITUTIONS FOUND NOT TO BE EQUAL TO ITEMS
LISTED IN DESIGN BASIS..
2. PRIOR TO PROCUREMENT CONTRACTOR SHALL SUBMIT TO
ARCHITECT FULL SUBMITTALS FOR ALL ENERGY
CONSUMING OR PRODUCING ITEMS AND FOR ALL SWITCH
GEAR, LOAD CENTERS AND PANEL BOARDS. SUBMITTALS
SHALL BE DELINEATED WITH TAGS INDICATED ON PRINTS,
CONTRACTORS NAME AND PROJECT NAME. CLEARLY
INDICATE ALL MODEL NUMBERS AND ALL ACCESSORIES
AND OPTIONS BEING PROVIDED. SUBMISSIONS SHALL BE IN
PDF FORMAT. ALL EQUIPMENT AND ITEMS SHALL BE PER
DESIGN BASIS ORAPPROVED EQUAL. ENGINEER RESERVES
THE RIGHT TO REJECTANV SUBSTITUTE ITEM FOUND NOT
EQUAL TO THE SPECIFIED ITEM AS DESIGNED.
3. CONTRACTOR SHALL FURNISH A TEMPORARY SERVICE FOR
THE USE OF ALL TRADES DURING CONSTRUCTION AS
REQUIRED BY THE GENERAL CONTRACTOR. REMOVE ALL
TEMPORARY EQUIPMENT AS PERMANENT SERVICES
BECOME AVAILABLE.
4. THE DRAWINGS IN THIS SECTION ARE DIAGRAMMATIC AND
ARE NOT INTENDED TO DEFINE EXACT QUANTITIES,
LOCATIONS OR CODIFIED REQUIREMENTS. DRAWINGS
SHOW GENERAL INTENT OF SYSTEMS. MODIFICATIONS IN
ELECTRICAL SYSTEM ROUTING AND LOCATIONS AS
REQUIRED TO MEET THE INTENT, SHALL BE PERFORMED
WITHOUT ADDITIONAL COST TO OWNER. SECURE AND PAY
FOR ALL REQUIRED PERMITS.
5. THE ELECTRICAL CONTRACTOR IS TO PROVIDE ALL
REQUIRED LABOR, MATERIALS, EQUIPMENT, AND
CONTRACTOR'S SERVICES NECESSARY TO COMPLETE THE
INSTALLATION OF SYSTEMS REQUIRED IN FULL
CONFORMITY WITH APPLICABLE CODES AND ORDINANCES.
THE FINISHED JOB SHALL BE FUNCTIONAL AND COMPLETE
IN EVERY DETAIL INCLUDING ANY AND ALL SUCH ITEMS FOR
A COMPLETE SYSTEM. CONTRACTOR SHALL GUARANTEE
ALL LABOR AND MATERIALS ENTERING INTO CONTRACT
FOR A PERIOD OF ONE (1) YEAR FROM DATE OF
ACCEPTANCE.
6. ALL WORK SHALL IN BE IN FULL ACCORDANCE WITH 2O09
INDIANA ELECTRICAL CODE (2008 NFPA 70), 2010 INDIANA
ENERGY CODE (ASHRAE 90.1-2007), PERTINENT STATE,
COUNTY, CODES AND ORDINANCE AND INDIANA
AMENDMENTS. COORDINATE WORK WITH OTHER TRADES.
ELECTRICAL CONTRACTOR SHALL BEAR ALL COSTS
RESULTING FROM ANY NON COMPLIANCE WITH CODE
REQUIREMENTS.
7. MATERIALS AND EQUIPMENT SHALL BE NEW UNLESS
INDICATED OTHERWISE. MATERIAL SHALL BEAR U.L. LABEL
WHERE SUCH STANDARDS HAVE BEEN ESTABLISHED AND
LISTED BY U.L. MATERIALS AND EQUIPMENT SHALL
CONFORM WITH THE LATEST ISSUES OF APPLICABLE
TECHNICAL STANDARDS.
8. THE ELECTRICAL CONTRACTOR IS TO PROVIDE
COMPLETE SYSTEM OF LIGHTING, RECEPTACLES, AND
POWER AS REQUIRED. VERIFY ALL VOLTAGES AND PHASE
REQUIREMENTS WITH MECHANICAL CONTRACTOR'S
EQUIPMENT PRIOR TO PERFORMING ANY WORK.
9. ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND
VERIFY ALL EXISTING CONDITIONS BEFORE SUBMITTING A
BID. NO EXTRAS WILL BE ENTERTAINED FOR
CONTRACTORS FAILURE TO IDENTIFY EXISTING
CONDITIONS AND ADJUST AS REQUIRED TO MEET DESIGN
INTENT.
10. ALL CONDUIT COUPLINGS AND CONNECTIONS SHALL BE
COMPRESSION TYPE AND MADE TO ENSURE POSITIVE
GROUNDING CONTINUITY. MAKE CONNECTIONS TO
EQUIPMENT SUBJECT TO VIBRATION WITH 18 INCHES OF
FLEXIBLE WATERTIGHT CONDUIT WITH WATERTIGHT
FITTINGS. PROVIDE FOR SUPPORT AND SECURING OF ALL
CONDUIT AND EQUIPMENT. CONNECTIONS TO LIGHTING
FIXTURES SHALL BE MADE WITH SIX (6) FEET OF FLEXIBLE
CONDUIT FROM A BOX WITHIN TWO (2) FEET OF THE
FIXTURE. SPLICE ALL WIRES ONLY IN ACCESSIBLE BOXES.
ALL FIXTURE WHIPS TO BE FLEXIBLE METAL CONDUIT 1/2"
MINIMUM SIZE WITH COMPRESSION CONNECTORS WITH
INSULATED THROATS. WHIPS SHALL NOT EXCEED 6'.
FIXTURE WHIPS TO BE SUPPORTED FROM BUILDING
STRUCTURE.
11. ALL LIGHTING AND BRANCH CIRCUITWIRING SHALL BE
SOLID COPPER MINIMUM SIZE #12 AW G. 600V INSULATION,
75 DEG. C., TYPE THW OR THW N, NOT LESS THAN #12 AW G.
ALL WIRE SERVING AS FEEDS TO DISTRIBUTION PANEL
BOARDS OR INTEGRAL HORSEPOWER MOTORS SHALL BE
EITHER STRANDED COPPER CONDUCTOR OR ASTM B800
ALUMINUM AA-8000 SERIES. THESE SHALL BE SIZED NOT
LESS THAN #10 AW G FOR COPPER AND NOT LESS THAN #8
AWG FORALUMINUM. EACH WITH MINIMUM 600V THW OR
THWN INSULATION, 75 DEG. C. ALL FEEDER SHALL BE
SIZED IN ACCORDANCE WITH NEC 310.15.
12. EXPOSED WIRING SHALL BE IN EMT RACEWAY. EXTERIOR
WIRING SHALL BE IN CONDUIT. CONCEALED WIRING SHALL
BE IN EMT OR METAL CLAD CABLE WHERE ALLOWED BY
CODE.
13. ALL LOW VOLTAGE WIRING IN PLENUM RATED CEILINGS OR
EXPOSED IN ROOMS SHALL BE PLENUM RATED CABLE.
14. ALL CABLE SHALL BE NEW WIRE OF RECENT
ELECTRICAL SPECIFICATIONS
MANUFACTURE AND IN ACCORDANCE WITH THE LATEST
STANDARDS OF IPCEA AND NEMA AS A MINIMUM
15. PANELBOARDS SHALL BE A DEAD -LOCK SAFETY TYPE,
SURFACE OR RECESSED MOUNTED AS SHOWN, EQUIPPED
WITH THERMAL -MAGNETIC MOLDED CASE CIRCUIT
BREAKERS WITH FRAME AND TRIP RATINGS AS REQUIRED.
TERMINALS FOR FEEDER CONDUCTORS TO THE
PANELBOARD MAINS AND NEUTRAL SHALL BE U.L. LISTED
AS SUITABLE FOR THE TYPE OF CONDUCTOR SPECIFIED.
TERMINALS FOR BRANCH CIRCUIT WIRING, BOTH BREAKER
AND NEUTRAL, SHALL BE U.L. LISTED AND CONNECTORS
SHALL BE OF THE FULL COMPRESSION TVPE.THE
PANELBOARD BUS ASSEMBLY SHALL BE ENCLOSED IN A
STEEL CABINET. THE SIZE OF THE WIRING GUTTERS AND
GAUGE OF STEEL SHALL BE IN ACCORDANCE WITH NEMA
STANDARD PUBLICATION NO. PB-1971 AND U.L.
STANDARDS NO. 67 FOR PANELBOARDS. CABINET SHALL
BE FABRICATED FROM GALVANIZED STEEL OR EQUIVALENT
RUST -RESISTANT STEEL. FRONTS SHALL INCLUDE DOORS
AND HAVE FLUSH, BRUSHED STAINLESS STEEL, CYLINDER
TUMBLER -TYPE LOCKS WITH CATCHES AND SPRING
LOADED DOOR PULLS. THE FLUSH LOCK SHALL NOT
PROTRUDE BEYOND THE FRONT DOOR. ALL PANELBOARD
LOCKS SHALL BE KEYED ALIKE. FRONTS SHALL HAVE
ADJUSTABLE INDICATING TRIP CLAMPS WHICH SHALLBE
CONCEALED WHEN THE DOORS ARE CLOSED. DOORS
SHALL BE MOUNTED BY COMPLETELY CONCEALED STEEL
HINGES. FRONTS SHALL NOT BE REMOVABLE WITH DOOR
IN THE LOCATED POSITION. A CIRCUIT DIRECTORY FRAME
AND TYPEWRITTEN CARD WITH A CLEAR PLASTIC
COVERING SHALL BE PROVIDED ON THE INSIDE OF THE
DOOR. THE DIRECTORY CARD SHALL PROVIDE A SPACE AT
LEAST 114" HIGH X 3" LONG OR EQUIVALENT FOR EACH
CIRCUIT. FRONTS SHALL BE OF CODE GAUGE, FULL
FINISHED STEEL WITH RUST -INHIBITING PRIMER FACTORY
FINISHED ENAMEL PAINT.
16. LOAD CENTERS SHALL BE UL LISTED AND MANUFACTURED
IN ACCORDANCE WITH THE LATEST NEMA STANDARDS.
CABINETS SHALL USE HINGED STYLE DOORS. MOUNT AT
6'-6" TO TOP OF CABINET.
17. CIRCUIT BREAKERS SHALL BE QUICK -MAKE, QUICK -BREAK,
THERMAL -MAGNETIC, TRIP INDICATING AND HAVE COMMON
TRIP ON ALL MULTI -POLE BREAKERS. BRANCH CIRCUIT
BREAKERS FEEDING CONVENIENCE OUTLETS SHALL HAVE
SENSITIVE INSTANTANEOUS TRIP SETTINGS OF NOT MORE
THAN 10 TIMES THE TRIP RATING OF BREAKER TO PREVENT
REPEATED ARCING SHORTS RESULTING FROM FRAYED
APPLIANCE CORDS. CONNECTION TO BUS SHALL BE BOLT
ON.
18. CONTRACTOR TO OBTAIN MAXIMUM FAULT CURRENT
AVAILABLE FROM THE UTILITY. CALCULATE THE FAULT
CURRENT AVAILABLE AT THE PANELS. ALL
PANELS/BREAKERS/SWITCHES ARE TO BE BRACED TO
EXCEED MAXIMUM AVAILABLE FAULT CURRENT AND
CIRCUIT BREAKERS ARE TO BE CAPABLE OF INTERRUPTING
FAULT CURRENT. MANUFACTURER SHALL PROVIDE ALL
REQUIRED FAULT CURRENT AND ARC -FLASH LABELING PER
110.16 AND 110.24.
19. MAXIMUM LOADING OF 20 AMP CIRCUITS SHALL NOT
EXCEED 1750 WATTS. VOLTAGE DROP OF BRANCH
CIRCUITS SHALL NOT EXCEED 3% AND FEEDER CIRCUITS
SHALL NOT EXCEED 2%. SEAL ALL PENETRATIONS
THROUGH WALLS, CEILINGS AND FLOORS AIR AND WATER
TIGHT. FIRE STOP WHERE REQUIRED.
20. CONTRACTOR SHALL PROVIDE ENGRAVED BAKELITE
NAMEPLATES FOR ALL ELECTRICAL PANELS,
DISCONNECTS, TRANSFORMERS AND MOTORS OVER 1 HP.
FURNISH TYPEWRITTEN PANEL DIRECTORIES TO IDENTIFY
ALL ELECTRICAL CIRCUITS BOTH NEW AND EXISTING.
21. VERIFY EXACT LOCATION COLOR AND HEIGHTS OF ALL
OUTLETS, RECEPTACLES, LIGHT FIXTURES AND EQUIPMENT
WITH OWNER'S REPRESENTATIVE PRIOR TO START OF
WORK. FURNISH GENERAL SERVICE DUPLEX'S, 15 AMP
SWITCHES, 15/20 AMP GFICS, HEAVY DUTY DISCONNECTS,
HVAC SSU SWITCHES, PANEL BOARDS, LOAD CENTERS,
DISTRIBUTION PANELS ETC. AS REQUIRED.
22. DISCONNECT SWITCHES SHALL BE GENERAL DUTY, NEMA
TYPE 1 FOR INDOOR SERVICE AND NEMA TYPE 3R FOR
OUTDOOR SERVICE, SUITABLE FOR PADLOCKING, NUMBER
OF POLES, RATINGS, FUSES (IF REQUIRED) SHALL BE AS
INDICATED ON THE DRAWINGS.
23. DEVICES:
A. CONVENIENCE RECEPTACLES SHALL BE MOUNTED 18"
ABOVE FINISHED FLOOR (A.F.F.) TO BOTTOM UNLESS
NOTED OTHERWISE, SWITCHES AND PUSHBUTTONS SHALL
BE 42"A.F.F. TO BOTTOM UNLESS SPECIFIED OTHERWISE
ON THE DRAWINGS.
B. PRIOR TO ROUGH -IN E.C. SHALLVERIFY FINAL LOCATIONS
AND COLORS OF ALL DEVICES WITH OWNER.
C. INSTALL ALL DEVICES PARALLEL AND PERPENDICULAR TO
ADJACENT WALL AND CEILING, FLUSH WITH SURROUNDING
SURFACES AND FREE FROM ALL OBSTRUCTIONS.
REWORKING OF EQUIPMENT INSTALLED IMPROPERLY
SHALL BE AT THE CONTRACTOR'S EXPENSE.
D. SWITCHES, BOXES, ETC., SHALL BE NEMA TYPE 1
CONSTRUCTION FOR INDOOR APPLICATIONS AND NEMA
TYPE 3R CONSTRUCTION FOR OUTDOOR APPLICATIONS.
E. SWITCHES SHALL MEET NEMA STANDARDS, COLOR SHALL
BE BY ARCHITECT. SWITCHES SHALL BE EQUAL TO
HUBBELL COMMERCIAL SPECIFICATION GRADE 20/15
AMPERES, SINGLE POLE, 125/277V. MULTI -POLE OR
SPECIAL SWITCHING SHALL BE AS NOTED ON THE
ELECTRICAL SPECIFICATIONS
DRAWINGS.
F. RECEPTACLES SHALL BE 125 VOLT, 15/20 AMPERES,
DUPLEX, GROUNDED HUBBELL COMMERCIAL
SPECIFICATION GRADE. SPECIAL RECEPTACLES SHALL BE
AS NOTED ON THE DRAWINGS.
G. MATCHING COVER PLATES SHALL BE PROVIDED FORALL
RECEPTACLES AND SWITCHES.
23. LIGHTING FIXTURES:
A. CONTRACTOR SHALL BE RESPONSIBLE FORVERIFVING
FIXTURES- MODEL NUMBERS, QUANTITY AND DISTANCE
BETWEEN LIGHTING FIXTURE PER FLOOR PLANS.
B. PRIOR TO ROUGH -IN E.C. SHALL VERIFY FIXTURE
QUANTITY, MODELS, STYLE, TRIM, LENS, ETC. WITH OWNER
FOR ALL FIXTURES.
C. PROVIDE LIGHTING FIXTURES COMPLETE WITH, BUT NOT
NECESSARILY LIMITED TO, HOUSINGS, LAMPS, LAMP
HOLDERS, REFLECTORS, BALLASTS, STARTERS AND
WIRING.
24. INSTALLATION OF LIGHTING FIXTURES:
A. INSTALL LIGHTING FIXTURES AT LOCATIONS AND HEIGHTS
AS INDICATED, IN ACCORDANCE WITH FIXTURE
MANUFACTURER'S WRITTEN INSTRUCTIONS, APPLICABLE
REQUIREMENTS OF NEC, NECA'S "STANDARD OF
INSTALLATION", NEMA STANDARDS, AND WITH RECOGNIZED
INDUSTRY PRACTICES TO ENSURE THAT LIGHTING
FIXTURES FULFILL REQUIREMENTS.
B. COORDINATE WITH OTHER ELECTRICAL WORK AS
APPROPRIATE TO PROPERLY INTERFACE INSTALLATION OF
INTERIOR LIGHTING FIXTURES WITH OTHER WORK.
C. E.C. TO FASTEN FIXTURES SECURELY DIRECTLY TO
BUILDING STRUCTURAL SYSTEM. LIGHT TROFFERS SHALL
BE SUPPORTED AT EACH CORNER OF FIXTURE BY WIRES
OF SAME GAUGE AS HANGER WIRE FOR CEILING GRID.
ATTACH EARTHQUAKE CLIPS TO GRID AS RECOMMENDED
BY LIGHT MANUFACTURER. USE SCREWS IF REQUIRED BY
MANUFACTURER. ATTACH THE WIRE TO THE STRUCTURE
ABOVE. LIGHTS SHALL NOT BE SUPPORTED IN ANYWAY BY
LAY -IN CEILING.
D. FIXTURE LOCATIONS SHALL BE AT APPROXIMATE
LOCATIONS AS SHOWN ON THE DRAWINGS FREE FROM ALL
OBSTRUCTIONS. CLEAN ALL LIGHTING EQUIPMENT AFTER
LIGHTING INSTALLATION AND GENERAL CONSTRUCTION IS
COMPLETE. REPAIR ANY FIXTURES DAMAGED DURING
CONSTRUCTIONS.
E. PROVIDE NECESSARY MOUNTING FRAMES, SUPPORTS AND
RELATED ITEMS REQUIRED TO PROPERLY INSTALL
FIXTURES. SUPPORT FIXTURES INDEPENDENTLY OF PIPING
AND DUCTWORK. MAKE MODIFICATIONS TO THE
STRUCTURE AS REQUIRED TO INSTALL FIXTURES. ANY
MODIFICATIONS TO THE STRUCTURE SHALL NOT IMPAIR
THE STRUCTURAL INTEGRITY OF THE BUILDING.
25. EQUIPMENT CONNECTIONS
A. ALL DEVICES AND EQUIPMENT SHALL BE SOLIDLY
GROUNDED IN ACCORDANCE WITH NEC REQUIREMENTS.
B. ALL SOLID CONDUCTOR WIRES MAY BE TERMINATED
UNDER SCREW HEADS. STRANDED WIRES MAY BE
TERMINATED BY USING PUSH -IN CLAMP TYPE
CONNECTORS FURNISHED WITH DEVICES OR TERMINATED
WITH COMPRESSION TYPE TERMINAL LUGS. SETSCREW
TYPE TERMINATIONS ARE NOT PERMITTED.
C. NO MOTORS ARE TO BE SUPPLIED UNDER THIS CONTRACT
UNLESS ITEMS REQUIRING A MOTOR ARE FURNISHED BY
THIS CONTRACTOR. THE CONTRACTOR SHALL FURNISH
ALL STARTERS FOR ALL MOTORS REQUIRING A STARTER.
THE CONTRACTOR SHALL CONNECT ALL POWER
EQUIPMENT IF & WHERE SHOWN ON PLANS UNLESS
OTHER -WISE SPECIFIED & ASSURE OWNER THE MOTORS
ARE IN GOOD RUNNING ORDER.
D. E.C. SHALL PROVIDE ALL COMPONENTS NEEDED TO MEET
MEANS OF DISCONNECT PER N.E.C. FOR ALL HARD WIRED
EQUIPMENT.
26. LOW VOLTAGE
A. ALL LOW VOLTAGE CABLE WHERE CONCEALED IN
CONSTRUCTION OR IN EXPOSED OPEN AREAS SHALL BE
RUN IN MINIMUM 3/4"EMT CONDUIT. CONTRACTORSHALL
INSTALL 3/4" CONDUIT (MINIMUM) FROM EACH LOW
VOLTAGE ROUGH -IN LOCATION TO ACCESSIBLE CEILING
SPACE, LOW VOLTAGE WIRE TRAY OR HANGERS AND THEN
TO MDF, HEAD -IN, PBX PUNCH DOWN, CONTROLLER ETC.
B. E.C. SHALL COORDINATE WITH LOCAL PHONE AND CABLE
PROVIDER AS CHOSEN BY OWNER AND PROVIDE
RACEWAYS FOR BRINGING IN SERVICES AS REQUIRED.
C. ALL LOW VOLTAGE CABLE SHALL BE PLENUM RATED IN
PLENUMS.
D. ALL DATA CABLE SHALL BE CAT 6 UNLESS OTHER WISE
NOTED. TERMINATE, LABEL AND TEST ALL WIRING.
E. ALL TV CABLE SHALL BE HIGH DEFINITION COAX RG6 OR AS
REQUIRED BY PROVIDER, VERIFY PRIOR TO ROUGH IN.
27. CLOSE OUT
A. PROVIDE MANUFACTURERS OPERATION AND
MAINTENANCE MANUALS AND PROVIDE AS BUILT
DRAWINGS. PROVIDE (1) TRAINING SESSION TO OWNER
SELECTED PERSONNEL AS REQUESTED AND PROVIDE
WARRANTY INFORMATION FOR ALL MANUFACTURERS
WARRANTED EQUIPMENT
MITSCH
D E S I G N
200 S. Rangeline Rd. I Suite 226
Carmel, Indiana 46032
317.573.2222
WwW.mgachdeaign.com
GOODERUM & ASSOCIATES ENGINEERING
MEP Consulting Engineers
874 Cheltenham Way
Avon, IN 46123
P: 317.506.8151
F: 317.745.5761
E: dave@gnaengineering.mm
P
LLJ
LLJ
N
0Y
NO
F--
Q
(n
ED
LLJ
F--
Nt
U
LLJ
LL
�z
U
o
z
'LLJ
VJ
_J
LLJ
LLJ
LLJ
_z
C:)
:2L
N�N
1_
Q
DO
Q
LLJ
U
`V
(-)
EL
No.
02003'
STATE OF
•.,rUNAL„
DATE: 09-19-2019
O
r
n_
No
�
rc
O
w
ancs
`
mo m
w
x
O
f
o
ca
N
z
O
w
N
N
TE
w
F-
O
U
an
NorJ
O
O
NTmo
zNRa
QZY
2_F
UOf
z
0Of2
WELD
�
O
moo
a_O.LL
U
A L DEM, DESIGNS AND EMS GRGMALMASS OF
AUTHORSHIP FIXED IN ATANGIBIE MEDIUM OF EXPRESSION)
INDICATED OR PRESENTED BYTHESE DRAWINGS AND
DOCUMENTS ME OWNED BY, AND ARE ME PROPERTY OF
MUTSGU DESIGN. ALLRIGHTSRESERN D.Ei FOR LEES
EXPRESSLYFPRMITTED IN WAmNG.
ELECTRICAL
ABBREVIATIONS,
SYMBOLS,&
SPECIFICATIONS