HomeMy WebLinkAboutM002 HVAC DETAILS AND SCHEDULES45 DEG
RECTANGULAR
DUCT
BRANCH
OCL CONNECTION J/
TAKE OFF. HAMMER
LOCKED OR FLANGED AND
FULLY SEALED
J � I
LL
o:
31Y MAX
ECCENTRIC TRANSITION MAX,
30 DEG.
ROUND SHEET METAL
DUCT TO DIFFUSER V.D.
1°
45 DEG. HIGH EFFICIENCY
TAKE OFF COMPLETELY JJ
SEALED
3W MAX
OFFSET. PROVIDE MINIMUM 2"
STRAIGHT SECTION AT EACH
END. MAX 30 DEG.
A
NOTE:
IN GENERAL, ELBOWS TO HAVE
FULL TURNING RADIUS (R=A).
WHERE "R" IS EQUAL TO OR
GREATER THAN "A" MINIMUM
RADIUS (R)-4INC HES.
U
CONCENTRIC
TRANSITION MAX, 45
DEG. DIVERGING AND
60 DEG. CONVERGING
IT
• 1YB"
NOTE:
DOUBLE THICKNESS
TURNING VANES TO BE USED
WHERE NORMAL RADIUS
ELBOW IS IMPRACTICAL
& WHERE ELBOW IS WITHIN 5
FT OF A
BRANCH TAKE -OFF.
DUCT CONSTRUCTION DETAILS
ASCALE: NONE
SECURE FLEXIBLE DUCT TO
SUPPLY DIFFUSER ELBOW
FITTING WITH DRAWBANDS.
SHEET METAL ELBOW
SEAL ALL RIBS AND
CONNECTION TO
DIFFUSER NECK
SUPPLY DIFFUSER
FLEX DUCT MAXIMUM LENGTH
SHALL NOT EXCEED T-0"
ACT CEILING
B LAY -IN DIFFUSER DETAIL
SCALE: NONE
LINED RA PLENUM BOX FULL SIZE
OF FAN COIL INLET
REFRIGERATION PIPING.
INSTALL PER
MANUFACTURES
RECOMMENDATIONS
SUPPLY AIR DUCTING
FILTER RACK
FAN COIL
INSULATED
OUTSIDE AIR DUCT
WITH MOTORIZED
AND MANUAL
DAMPER. ROUTE
TO WALL CAP
RETURN AIR DUCTING
20" MIN
WORK AREA
CAP AND PROVIDE WATER SHUT
OFF SWITCH IN DRAIN PAN.
} PVC DRAIN FROM TRAP WITH CLEAN OUT.
SLOPE AT MIN;'" PER FOOT AND SUPPORT TO
STRUCTURE MINIMUM 5' O.C.
SECONDARY DRAIN PAN, EXTEND
MINIMINUM 6" PAST ENTIRE FAN COIL
SUPPORT AT MINIMUM 16" O.C.
HORIZONAL FAN COIL DETAIL
C SCALE
CASED EVAPORATOR COIL SHALL MATCH
FURNACE WIDTH. INSTALL
MANUFACTURERS DEFLECTOR PLATE ON
HORIZONTAL APPLICATIONS.
TXV METERING DEVICE
INSTALL ALL REFRIGERATION
SPECIALTIES AS INDICATED ON
EQUIPMENT SCHEDULES.
PITCH SUCTION LINE TOWARD
COMPRESSOR. PROVIDE OIL
RETURN TRAPS PER
MANUFACTURES PIPING
RECOMMENDATIONS.
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Cannel
DATE: 11 /14/19
AIR COOLED CONDENSER INSTALL
WITH MANUFACTURERS
RECOMMENDED CLEARANCES..
REFRIGERANT PIPING SIZED AND INSTALLED PER
MANUFACTURERS. REFERENCE LONG LINE
APPLICATION REQUIREMENTS WHEN APPLICABLE
FIBERGLASS PAD BY MC UNIT SHALL
BE SET LEVEL ADJUST GRADE AS
REQUIRED.
PIPE INSULATION LOCATED
OUTDOORS SHALL BE PAINTED WITH
UV RESISTANT ARMAFLEX PAINT.
REFRIGERANT TUBING WITH 1/2" WALL ARMAFLEX
INSULATION. PVC SLEEVE AND SEAL WALL
PENETRATIONS WATER TIGHT AND FLUSH TO
SURROUNDING FINISH.
HEAT PUMP DETAIL
D SCALE: NONE
EXHAUST FAN SCHEDULE
TAG
MODEL#
LOCATION
TYPE FAN AND
DESCRIPTION
FAN DATA
MOTOR DATA
NOTES
CFM
ESP
SONES
HP
WATTS
VOLT
FLA
EF-3
GREENHECK SP-A90
RESTROOMS
CEIUNG
]5
.2
1.0
30
1 120
1 34
iO
iO FAN SHALL BE CONTROLLED FROM WALL SWITCH.
2O PROVIDE WITH LINE VOLTAGE COOLING ONLY THERMOSTAT.
DIFFUSERS, REGISTERS AND GRILLES
TAG
DESCRIPTION MFR MODEL
MAIL.
CFM
MOUNTNG
STYLE
INTEGRAL
DAMPER
NOTES:
S-1
9"X9" SURFACE MOUNT DIFFUSER
PRICE
BCD
STL
0-200
SURFACE
YES
0O2
S-2
24"X24" LAY414 DIFFUSER -8"NECK
PRICE
BCD
STL
130-220
LAY -IN
NO
iO O2
S-3
24'X2� LAY414 DIFFUSER - 6m NECK
PRICE
BCD
STL
0-120
LAY -IN
NO
S4
12X4 DOUBLE DEFECTION REGISTER
PRICE
520
STL
140-230
SURFACE
YES
iO O2
R-1
24X12 FIXED BLADE GRILLE
PRICE
53D
STL
0-1000
LAY -IN
NO
iO O2
R-2
BX4 FIXED BLADE GRILLE
PRICE
530
STL
0-175
SURFACE
NO
D( O3
R-3
24X12 PERFORATED GRILLE
PRICE
10
1 ALUM
1 0420
ISURFACEI
NO
iOO2 O3
O COLOR:WHITE
O2 REFER TO FLOOR PLAN FOR EXACT CFM.
O3 PROVIDE WITH LINED REGISTER BOX.
HEAT PUMP SCHEDULE
MARK
MANUFACTURER
MODEL
COOLING
HEATING
ELECTRICAL SPECIFICATIONS
NOMINALg
TONS
MBH
SEER
MBH
HSPF
ELEC.
(V-Ph-Hz)
MCA
MOCP
NOTES:
HP-1
BRVANT
214DPA060000
5.0
60.0
14
54.5
8.2
208230-34i0
21.5
30
1 2 3
HP-2
BRVANT
214DPA060000
5.0
60.0
14
54.5
8.2
208R30-34i0
21.5
30
1 2 3
O PROVIDE CYCLE PROTECTOR, OUTSIDE AIR THERMOSTAT, LOW PRESSURE SWITCH.
O ELECTRICAL CONTRACTOR TO PROVIDE AND INSTALL DISCONNECT SWITCH.
O3 ALL HVAC EQUIPMENT TO BE FIELD LABELED TO IDENTIFY WHICH AREA OF THE BUILDING THE SERVICE.
FAN COIL SCHEDULE ELECTRIC HEAT
MARK
MANUFACTURER
FCU
MODEL
HEAT KIT
MODEL
HEATING CAPACITY
COOLING
ELECTRICAL SPECIFICATIONS
TOTAL
CFM
CA
CFM
STATIC
PRESS.
NOTES:
KW
@208
MBH
@208
NOMINAL
TONS
REFG.
ELEC.
(V-Ph-Hz)
MCA
MOCP
FGi
BRVANT
FB4CNP061L00
KFCEH3401F24
18
61.4
5.0
R410A
20MO-3
77.8
80
1990
.5
OO
FC-2
BRVANT
FB4CNP061L00
KFCEH3401F24
18
61.4
5.0
R410A
20"0-3
77.8
80
1990
.5
1 O2
O PROVIDE PROGRAMABLE DIGITAL DISPLAY THERMOSTAT.
O2 PROVIDE MANUFACTURER FILTER KIT AND SINGLE POINT CONNECTION KIT FOR HEATER.
VENTILATION AIR CALCULATIONS
SYSTEM
AREA TYPE
TOTAL
NET
AREA
OCCUPAN
TSPER
1000 FT
CALCULATED
OCCUPANTS
CFM/PERSON
REQUIRMENT
PEOPLE CFM
REQUIRED
AREA CFM
RQUIRME
CFMIFT2
AREA CFM
REQUIRED
TOTAL CFM
REQUIRED
CONFERENCE ROOM
453
50
23
5
115
0.06
28
143
FC-1
CORRIDOR
1165
0
0
0
0
0.06
70
70
OFFICE
534
5
3
5
15
0.06
33
48
TOTAL
2152
261
OFFICE
1177
5
6
5
30
0.06
71
101
FC-2
CORRIDOR
175
0
0
1 0
1 0
1 0.06
59
59
TOTAL
2152
160
REFRIGERATION LINE SET
INSTALLED PER
MANUFACTURERS
RECOMMENDATIONS.
PROVIDE OPEN SITE TEE
WITH MOISTURE SWITCH
ON SECONDARY DRAIN
CONNECTION. INTERLOCK
WITH ACCU.
3/4" PVC DRAIN LINE
INDIRECTION CONNECTION
TO MOP SINK OR FLOOR
DRAIN IN MECH ROOM
FAN
COIL
UNIT
18" MIN.
PROVIDE LINED SHEET METAL
RETURN AIR BOX UNDER FCU.
NO SIDE CONNECTIONS
ALLOWED.
E FAN COIL DETAIL
SCALE: NONE
FRESH AIR DUCT WITH
MOTORIZED SHUT OFF
AND MANUAL BALANCING
DAMPER.
LINED RETURN AIR RISER.
FILTER BOX
MITSCH
D E S I G N
200 S. Rangeline Rd. I Suite 226
Carmel, Indiana 46032
317,573,2222
w .milschdesign.com
GOODERUM & ASSOCIATES ENGINEERING
MEP Consulting Engineers
874 Cheltenham Way
Avon, IN 46123
P: 317.506.8151
F: 317.745.5761
E: dave@gnaengineering.com
Q
WLLI
w
N
z
0
LL
CD
O
W
�
w
LL-
Q
Q
Q
0
o
LU
(q
Jwz
W
Z
O
:5
_J
WEll
cH
LL
(Y
NGN
Q
CO
Q
U^J
No.
02003'
SWE OF
"'MuUrrvlx�iS�l�nma"°m..
DATE: 09-19-2019
O
rL
m m
w
Y
m
$$
j
N
N
wo
d
W
m
h
5
o
696
U
m
N
>O>
W
�
O
U
W
m
W
ZUm
K
U
o
4
qax
rcrcw
�
O
is
U
U
LL M1 LL
U
ALL IDEAS. DESIGNS AND PLANS IORIGIML WORKS OF
AUTHORSHIP FIXED IN ATANGINLE MEDIUM of EXPRESSIOID
INDICATED OR PRESENTED BY THREE DMWINGS AND
DOCUMENTS ARE OWNED By. AND ME THE PROPEM OF
MRSGIDESIGN. ALL RIGHTS RESERVED, EXCEPT FOR L6E8
EXPRESSLY FERMHTED IN WRRING.
HVAC DETAILS &
SCHEDULES
M 002