HomeMy WebLinkAboutH5-1RELEASED FOR CONSTRl1CTI0N Su6jec� �o compliance with all regula�ims 04 S�a�e antl Local Codes City of Carmel y\0.v��i �\p;,V`iiY?A�i \ onrE: 12/02/19 FAN COIL UNIT SCHEDULE COOLWG COIL EAT LAT MIN. MIN. PIPE CIRCULATING FLUID AREA FAN E.S.P. SENSIBLE TOTAL RUNOUT ENTERING LEAVING MAX. TAG LOCATION SERVED CONFIGURATION CFM (IN. WG.) DB (°F) WB (°F) DB (°F) WB (°F) MBH MBH SIZE (IN.) FLUID GPM TEMP.(°F) TEMP. (°F) W.P.D. ;U-B133A MRIEQUIPMENTROOM MRIEQUIPMENTROOM HORIZONTALCONCEALE� 1.800 0.5 ]0.0 60.0 55.8 54A 26.5 2I.3 1" WATER 5.4 48 58 5 xores: 1. PROVIDE DIRECT DRIVE EC MOTOR CAPABLE OF REMOTE 040 VOLTSPEED CONTROL. 2. PROVI�ESINGLEPOINTPOWERCONNECTIONWITH�ISCONNECT. a. suPPoerFnNcoi�wirnsPewcnnNceas,r�srnncoeF�ecnoN. FAN MOTOR I DESIGN REFERENCE HP I RPM I VOLT IPHASE MANUFACTURER I MODEL NOTES 1 840 2]] 1 INTERNATIONALENVIRONMENTAL H�V-08 11.3 TERMINAL BOX SCHEDULE CFM UNIT AIR DATA HOT WAiER HEATING COIL DESIGN REFERENCE DUCT MAX. PIPE UNIT RUNOUT A.P.D. AT MAX. RUNOUT COOLING COOLING HEATING INLET SIZETO MAX.CFM E.AT. L.A.T. E.W.T. L.W.T. W.P.D. SIZETO MIN. TAG MAX. MIN. MAX. SIZE (IN.) UNIT (IN.) (IN.) (°F) (°F) FLUID GPM (°F) (°F) (FT. HD.) COIL (IN.) MBH MANUFACTURER MODEL NOiES TU-B130 410 410 410 8" 10" 0.4 55 &5 WATER 1.0 160 130 SA 3/4" 14.0 PRICE S�V 12.4 TU-B132 1200 1200 1200 12" 14'• - 0.4 55 &5 WATER 4.0 160 130 5.0 1" 39.1 PRICE S�V 12.3.4 NOiES: L EXISTING PIPE RUNOUT IS 314" TO REMAIN. 2. COILSHALLBEAMINIMUMOF2ROWS.HEATINGCOILPERFORMANCEISBASE�ONSCHE�ULE�TEMPERATURES.SUBMITTHISPERFORMANCEFORREVIEW,ASWELLASACON�ITIONS WITH 120°F ENGERING WATER TEMPERATIIRE AN� ]5"F LEAVING AIR TEMPERATIIRE. A�JIIST TERMINAL IINIT SIZE OR COIL ROWS AS REQl11RE� TO MEET BOTH CON�ITIONS. 3. TERMINAL UNIT SHALL HAVE 1" WSULATION AN� �OUBLE WALL SHEETMETAL CASING. G. PROVI�EACCESS�OORAN�HANGERTA6S. HUMIDIFIER SCHEDULE TAG I SYSTEM DESIGN HEATING DESIGN CONDIiIONS DUCT SIZE M� AIRFLOW ENTERINGAIR LEAVINGAIR CAPACITY WIDTH HEIGHT ABSORPTION LOCATION (CFM) DB (°F) WB (°F) DB (°F) WB (°F) (#/HR.) (IN.) (IN.) DISTANCE (IN.) DESIGN REFERENCE MODEL NOiES xores: 1. HUMI�IRERMANUFACTURERSHALLPROVI�ETHERE�UIRE�NUMBEROFMAWFOL�STOMEETTHESCHE�ULE�ABSORPTION�ISTANCE MINIMUMTWO DISPERSION MANIFOLD TUBES. 2. SCHE�ULE�STEAMQUANTRYISTHEAMOUNTOFSTEAM�ELNERE�TOTHEAIRSTREAM.ACCOUNTFORLOSSESWHENSIZINGHUMI�IRER. 3. PROVI�ESTAINLESSSTEELSTEAMSEPARATOR,TRAP,AN�CONTROLVALVEWSTALLAN�CONRGUREHUMI�IRERSUCHTHATSTEAMCANBERETURNE�TOA LOW PRESSURE STEAM RETURN SVSTEM. PROVI�E CON�ENSATE TEMPERATURE SWITCH TO ENSURE CON�ENSATE IS FLOWING PRIOR TOALLOWING HIIMI�IFIER FROM OPENING. 4. CONRRM�UCT�IMENSIONSWITHREL�CON�ITIONSPRIORTOSUBMITTINGAN�PROWRRINGHUMI�IRER. HVAC DESIGN DATA OUTSDIE DESIGN TEMPERATURES 92 DEG. F DB SUMMER 79 DEG. F WB SUMMER -10 OEG. F OB WINTER DESIGN ALTITUDE: --- 900 FT. INTERIOR DESIGN AREA MRI EXAM ROOM MRICONTROLROOM MRI E�UIPMENT ROOM suPPORr nREns oe� �o ]2 ]2 n SUMMER RH� so 55 55 ss WINTER OB (°F) RH ( �o ao n ao �z ao n ao MISCELLANEOUS E�UIPMENT SCHEDULE ELECiRICAL REp01REMENiS �ESIGN REFERENCE rnc oescairnox VOLTAGE�V) PHASE�O) M�A MANUFACTURER MOOEL REMorEniR-coo�EocoNOENSER. cnans�EOFREdEcnNcrnEPEnKOEsicNcnancirvpNcwowc COMPRESSOR GENERATE� HEAT1AT110°F OUTSI�EAMBIENT TEMPERATURE. UNIT SHALL BE CAPABLEOF q60 3 4b FlLTRWE KCM�039 ACCU�MRI4 COOLING�OWNTOdO°FO11ID00RAM14BIENT. IINITSHALLHAVEA�JIISTABLESPEE�CONTROLSAN�FAN CVCLING TO ALLOW FOR PART LOA� CONTROL R448A REFRIG ERANT. MATCHE� TO OPERATE WRH CH- MRI 1. CLOSE� LOOPWATER CHILLE� �ESIGNE� TOOPERATE WITH REMOTE CON�ENSING UNIT. PROVI�E INTEGRAL PLATEIFRAME HEAT EXCHANGER FOR CHILLER TO OPERATE WRH B111L�ING CHILLE� WATER OR GENERATE CHILLE� WATER VIA CHILLER. MINIMUM 244,911 BTUIHR, 48°F. CHILLER SHALL HAVE COM14PLETE INTEGRAL CONTROLS WITH BACNET OR M140�BlIS COM14M1W NICATION CAR�. CHILLER SHALL UTILIZE BUIL�ING CHILLE� WATER AS THE PRIMARY MEANS OF COOLING WHEN CHILLE� WATER IS AVAILABLE. IF SUPPLY WATER SETPOINT IS NOT ACHIEVE�, CHILLER SHALL START AIITOMATICALLY. IF CH ILLE� WATER IS NOT AVAILABLE, �OMESTIC WATER BACKIIP SHALL PROVI�E TEMPORARY WOLING. LOCAL WNTROL PANEL. cN�^^Ri�i aRovmEwrECRn�zoocnuoNsrnw�EsssrEE�cniuEownrERsroRncrErnNK,oun�REouNonNr aso a sa FaTawe sMs�a000s�aaona�Nx STAINLESSSTEELCHILLE�WATERPUMPSCAPABLEOF34GPMAT58PSIG�IFFERENTIALPRESSURE PUMP SHALL 6E ARRANGE� AS A LEA�ILAG CONFIGURATION WITH LEA� PUMP ALTERNATING 6ASE� ON RUN HOIIRS. FAI W RE OF LEA� PIIMP SHALL AIITOMATICALLV START LAG Pll MP. CHILLER SHALL HAVE SEM14I�HERMETIC AN� SCROLLCOMPRESSOR(S).A�JUSTABLETHERMOSTAT,EXPANSION vn�ves, nicn��ow Paessuae srnr, auMa-oowN so�eNoio vn�ves, aeFeiceanNr sicnr c�nss, oEnroanToa nNo nEno nNo sucTioN PaEssuaE cnucEs. nu co�o PnaTs snnu eE iNsu�nTEo wiTn c�oseo ce�uNsu�nnoN. REFERTO�IAGRAMONTHISPAGEFOROTHEROPERATIONALRE�UIREMENT. PROVI�EALLACCESSOPoES REpUIRE� TO ACHIEVE SEpUENCE �ESCRIBE�. FACTORV PACKAGE� VAWE PANEL CONTAINING TEMPERATURE GUAGES, PRESSURE GAUGES, FLOW METER, 5� MICRON RLTER,BALLVALVES,CONTROLVALVES,AN� SENSORS REQUIRE� TO PROVI�E AN AUTOMATIC �OMESTIC WATER BACNUP SYSTEM FOR MRI. QCP�MRI4 FROMPANELSHALLBEHINGE�FORACCESSTOVALVES. WSTALLTEMPERATUREGUAGES,PRESSURE �,�-,. �.��'�.� .'�'�. FlLTRINE QCP GAUGES, AN� FLOW METER ON FRONT PANEL. .. .. ... ALL INTERNAL COL� PIPING SHALL BE FACTORY WSULATE�. PROVI�EALLINTERLOCKWIRINGREpUIRE�TOCONNECTTOCHILLERCONTROLLER. PROVI�ECONTACTS FOR REMOTE MONRORWG OF STATUS OF �OMESTIC WATER OPERATION. NOiES 1. POWERE�BYINTERLOCNINGCONTROLWIREWITHCHILLER. COOR�INATEALLWIRINGRE(lUIREMENTSWITHCHILLERMANUFACTURER. DIFFUSER / GRILLE SCHEDULE TAG I SIZE I SIZE I MATERIAL I FINISH RG1 8"0 24"H24" ALUMINUM WHITE RGS Y2"%22" 24"%24" ALUMINUM WHITE SD1 B"0 2a"%2a" ALUMINUM WHITE MAX MAX TOTAL CFM MAX THROW ADP RANGE NC (FT) (IN WG) 0-200 15 N/A 0.05 0-1,200 15 NlA 0.03 0� 200 15 6 0.05 MANUFACTURER MODEL NOiES PRICE P�R-MRI 12.3.4 PRICE P�R 12.3.4 PRICE P�S 12.3A NOiES: 1. BRANCH DUCT RUNOUT TOTHE DIFFUSER SHALL BE THE SAME SIZE AS THE DIFFUSER NECK UNLESS NOTED OTHERWISE ON THE DRAWINGS. 2 ALLSIIPPLV�IFFIISERBACKPLATESSHALLBEINSIILATE�WITHAMINIMIIMOFi"INSIILATION.INSIILATIONMAVBEFACTORVORFIEL�APPLIE�. a. PaovmeFanMesTnenPPaoPainTeFoaceaiNCTVPe�i.e.�nv-iN,suaFnceMouNT,smewnu,eTc�.aeFeaTooanwiNcsnNonacniTecTuan� aEF�ECTEo cEawc P�nNs Foa �ocnnoNs. 4. ALL�IFFIISERSIREGISTERSIGRILLESINSTALLE�WITHINTHEMRIE%AMROOMSHALLBECONSTRIICTE�COMPLETELVOIITOFAWMINIIMSl11TABLEFORMRI APPLICATION. a�= o Q Y pU � N m o o � u 0 a� N a � N � U N co - 3 ?? - (O R (i O N o�noao� PE10606131 � - STAiE OF „ �, � � Z wC C w U a J d W � � Z W � d � � W N M � m H _ a � N � 0 H 2 � Z� Qa�+� � O � = O � � J= W Z r � _ w¢zW 2 W o � = A � � � � U 0 0 � � L p d E=;m `/ `ma_� Y � � _ W 5 � �. � Q HVAC SCHEDULES H 5-1