HomeMy WebLinkAbout19015_Bharat_Patel_ElecSYMBOLS, ABBREVIATIONS, AND GENERAL SPECIFICATIONSSOME SYMBOLS AND/OR ABBREVIATIONS MAY NOT BE USED ON THIS PROJECTSTANDARD ABBREVIATIONS
A AMPERES
AC ALTERNATING CURRENT
AF AMPERE FUSE
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING
CAPACITY
AL ALUMINUM
ARCH ARCHITECT(URAL)
ATS AUTOMATIC TRANSFER
SWITCH
AUTO AUTOMATIC
AVG AVERAGE
BFC BELOW FINISHED CEILING
BFG BELOW FINISHED GRADE
BHP BRAKE HORSEPOWER
BPS BOOSTER POWER SUPPLY
BTM BOTTOM
C CONDUIT
CB CIRCUIT BREAKER
C/C CENTER TO CENTER
CCTV CLOSED CIRCUIT
TELEVISION
CF CUBIC FEET
CKT CIRCUIT
CL CENTERLINE
CLG CEILING
COMM COMMUNICATIONS
COMP COMPRESSOR
CONT CONTINUOUS
CR CRITICAL LOAD
CT CURRENT TRANSFORMER
CU COPPER
DC DIRECT CURRENT
DP DISTRIBUTION PANEL
DPST DOUBLE POLE, SINGLE
THROW
DWG DRAWING
DWH DOMESTIC WATER HEATER
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EGC EQUIPMENT GROUNDING
CONDUCTOR
EM EMERGENCY (LOAD)
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EX EXIT
EXH EXHAUST
EXP EXPLOSIONPROOF
EXT EXTERIOR
FA FIRE ALARM
FAAP FA ANNUNCIATOR PANEL
FACP FA CONTROL PANEL
FC FLAT CABLE
FCU FAN COIL UNIT
FFC FOOD FACILITY
CONTRACTOR
FFS FOOD FACILITY SUPPLIER
FHC FIRE HOSE CABINET
FIXT FIXTURE
FLUOR FLUORESCENT
FPC FIRE PROTECTION
CONTRACTOR
FSS FUSED SAFETY SWITCH
FTG FOOTING
FTL FEED THROUGH LUGS
FV FULL VOLTAGE
G, GND GROUND
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEC GROUNDING ELECTRODE
CONDUCTOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT
INTERRUPTOR
GFP GROUND FAULT
PROTECTION
GTB GENERATOR TAP BOX
H, HV HIGH VOLTAGE
HID HIGH INTENSITY
DISCHARGE
HO HAND OPERATED
HOA HAND-OFF-AUTO
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
HTR HEATER
Hz HERTZ
IC INTERCOM
ID INSIDE DIAMETER
ISG ISOLATED GROUND
J, JB JUNCTION BOX
KEC KITCHEN EQUIPMENT
CONTRACTOR
kV KILOVOLTS
kVA KILOVOLT-AMPERES
kVAR KILOVOLT-AMPERES
REACTIVE
kW KILOWATTS
L or LV LOW VOLTAGE
LB POUND
LCP LIGHTING CONTROL PANEL
LF LINEAR FEET
LP LIGHTING PANEL
LS LIFE SAFETY LOAD
LT LIGHT
LTG LIGHTING
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MCCB MOLDED CASE CIRCUIT
BREAKER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUG ONLY
MSB MAIN SWITCHBOARD
NIC NOT IN CONTRACT
OCP OVERCURRENT
PROTECTION
OD OUTSIDE DIAMETER
OF/CI OWNER FURNISHED,
CONTRACTOR INSTALLED
OF/OI OWNER FURNISHED,
OWNER INSTALLED
OR OPERATING ROOM
P POLE
PB PUSH BUTTON
PC PLUMBING CONTRACTOR
PF POWER FACTOR
PH, Φ, Ø PHASE
PIV POST INDICATOR VALVE
PL PILOT LIGHT
PNL PANELBOARD
PREFAB PREFABRICATED
PT PNEUMATIC TUBE
PTS PNEUMATIC TUBE STATION
PTZ PAN-TILT-ZOOM
PW PART WINDING
PWR POWER
RCPT RECEPTACLE
REF REFRIGERATOR
RM ROOM
RP RECEPTACLE PANEL
RPM REVOLUTIONS PER MINUTE
SCCR SHORT CIRCUIT CURRENT
RATING
SG SURGE GUARD
SN SOLID NEUTRAL
SPEC SPECIFICATIONS
SQ FT SQUARE FEET
SS SAFETY SWITCH
SSBJ SUPPLY SIDE BONDING
JUMPER
STD STANDARD
STN STATION
STR STRUCTUR(E),(AL)
SUSP SUSPENDED
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TCC TEMPERATURE CONTROL
(CONTRACTOR), (CABINET)
TELE TELECOMMUNICATION
TEMP TEMPORARY
TV TELEVISION
TYP TYPICAL
UCR UNDER COUNTER
REFRIGERATOR
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED
OTHERWISE
V VOLT
VFD VARIABLE FREQUENCY
DRIVE
VP VAPORPROOF
W/ WITH
W/O WITHOUT
WP WEATHERPROOF
WTR WATER
Z IMPEDANCE
ADA ACCESSIBLE ROOM - ALL OPERABLE DEVICES SHALL
BE MOUNTED BETWEEN 18" AFF TO BOTTOM AND 48" AFF
TO TOP OF DEVICE.
HEARING IMPAIRED COMMUNICATIONS FEATURE ROOM -
VISUAL NOTIFICATION REQUIRED FOR AS SHOWN ON
PLANS.
KEYED DEMOLITION PLAN NOTE
KEYED NEW WORK PLAN NOTE
01
01
SECTION VIEW REFERENCE
VIEW REFERENCE, INCLUDING DETAILS
& ENLARGED PLANS
1
E-301
1
E-501
1 / E-301 VIEW REFERENCE TAG
GENERAL DRAWING ANNOTATIONS
15. ALL WIRING SHALL BE INSTALLED PARALLEL & PERPINDICULAR TO THE
BUILDING STRUCTURAL MEMBERS, EXCEPT WHERE INSTALLED
UNDERGROUND.
16. A DEDICATED COPPER OR ALUMINUM EGC SHALL BE INSTALLED IN ALL
RACEWAYS, EXCEPT IN SERVICE ENTRANCE CONDUITS. PARTICULAR
CARE SHALL BE TAKEN TO ELIMINATE OBJECTIONAL CURRENT, SEE
GROUNDING & BONDING DETAILS FOR SITE SPECIFIC REQUIREMENTS.
17. IT SHALL BE THE EC'S RESPONSIBILITY TO REVIEW CONDUIT SIZES AND
WIRE AMPACITY PRIOR TO INSTALLATION, TO ENSURE A
CODE-COMPLIANT INSTALLATION.
18. IT SHALL BE THE EC'S RESPONSIBILITY TO CONTACT THE DESIGNER
WITH ANY QUESTIONS, CONCERNS, OR PROPOSED CHANGES BEFORE
COMMENCING WORK.
19. CIRCUITS MAY BE COMBINED IN CONDUITS, CABLES, OR RACEWAYS,
PROVIDED THAT THE CONDUCTORS ARE PROPERLY DERATED & ALL
RACEWAYS ARE SIZED PER THE NEC.
20. CIRCUITS ARE SIZED FOR VOLTAGE DROP BASED ON ESTIMATED
ROUTING. THE EC SHALL VERIFY THAT THE ACTUAL ROUTING CHOSEN
COMPENSATES FOR VOLTAGE DROP AS FOLLOWS:
A. ALL CONDUCTORS SHALL BE SIZED TO PREVENT EXCESSIVE
VOLTAGE DROP. FEEDERS SHALL NOT EXCEED 2% VOLTAGE
DROP & BRANCH CIRCUITS SHALL NOT EXCEED 3%
VOLTAGE DROP.
B. IN GENERAL, CONDUCTORS SHALL NOT BE REQUIRED TO
INCREASE MORE THAN TWO (2) SIZES FOR THIS PURPOSE,
UNLESS NOTED OTHERWISE.
C. THE EGC SHALL INCREASE PROPORTIONALLY FROM THE SIZE
REQUIRED BY THE NEC, AS REQUIRED BY NEC 250.122(B).
21. WIRES SHALL BE COLOR CODED AS FOLLOWS, OR AS REQUIRED BY
THE AHJ:
A. 240/120V SYSTEMS = BLACK (L1), RED (L2), WHITE (N)
B. 208Y/120V SYSTEMS = BLACK (A), RED (B), BLUE (C), WHITE (N)
C. 240D/120V SYSTEMS = BLACK (A), ORANGE (B), BLUE (C),
WHITE (N)
D. 480Y/277V SYSTEMS = BROWN (A), ORANGE OR PURPLE (B),
YELLOW (C), GRAY (N)
22. ALL PANELBOARDS, SWITCHBOARDS, AND SWITCHGEAR SHALL HAVE A
PERMANENT LEGEND SHOWING THE DESIGNATED CONDUCTOR
COLORS, AS REQUIRED BY NEC 210.5(C).
23. WIRING SHALL BE #12 AWG COPPER, UNO. IN ALL CASES, THE EC SHALL
VERIFY THE CORRECT SIZE WIRING IS INSTALLED, FOR A
CODE-COMPLIANT INSTALLATION.
01. ALL MATERIAL & WORKMANSHIP SHALL COMPLY WITH ALL APPLICABLE
CODES, SPECIFICATIONS, LOCAL ORDINANCES, AND ACCEPTED
INDUSTRY STANDARDS.
02. THIS PROJECT CONSISTS OF TWO PARTS: THE CONTRACT DRAWINGS &
THE PROJECT SPECIFICATIONS. WHERE THESE DOCUMENTS ARE NOT
IN AGREEMENT, THE MOST STRINGENT CONDITION SHALL APPLY. IN ALL
CASES, THE EC SHALL REQUEST WRITTEN CLARIFICATION.
03. ALTHOUGH NOT ALL BRANCH WIRING & CONDUIT ARE SHOWN ON
THESE DRAWINGS, IT IS THE INTENT OF THESE DOCUMENTS THAT A
COMPLETE AND FUNCTIONING BRANCH WIRING SYSTEM BE INSTALLED.
04. ALL CONDUITS, CABINETS, CABLES, AND BOXES SHALL BE SECURELY
FASTENED AND SUPPORTED PER THE NEC.
05. ALL DIMENSIONS SHALL BE OBTAINED FROM ARCHITECTURAL AND CIVIL
SITE PLANS. IN NO CASE SHALL THE ELECTRICAL DRAWINGS BE
SCALED.
06. ALL DIMENSIONS SHOWN SHALL BE TO THE CENTERLINE OF THE
EQUIPMENT OR DEVICE BOX, UNLESS NOTED OTHERWISE.
07. VERIFY ELECTRICAL REQUIREMENTS OF ALL EQUIPMENT PROVIDED BY
OTHERS & CONNECTED BY ELECTRICAL CONTRACTOR, PRIOR TO
INSTALLATION OF WIRING, INCLUDING RECEIVING & REVIEWING
APPROVED SUBMITTALS FOR EQUIPMENT PROVIDED BY OTHER
BUILDING TRADES.
08. THE ENTIRE SET OF PROJECT DRAWINGS HAS INFORMATION
PERTAINING TO THE CONSTRUCTION OF THE BUILDING, AND THE
ELECTRICAL CONTRACTOR SHALL REVIEW ALL DRAWINGS TO
COORDINATE THE INSTALLATION OF ELECTRICAL SYSTEMS.
09. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR
COORDINATION OF LIGHTING FIXTURES & EQUIPMENT FURNISHED OR
PROVIDED BY OTHERS. EC SHALL TAKE PARTICULAR CARE TO
COORDINATE WITH THE FPC, PC, AND THE MC.
10. REFER TO ARCHITECTURAL PLANS & INTERIOR ELEVATIONS TO
COORDINATE ALL WALL MOUNTED DEVICES WITH CABINETRY &
CASEWORK. ENSURE THAT ALL DEVICE PLATES AND OTHER
EQUIPMENT WILL NOT CONFLICT WITH COUNTERTOPS, BACKSPLASHES,
WALL TILE, TRIM, ETC.
11. ALL DEVICES MOUNTED ABOVE A COUNTERTOP OR BACKSPLASH SHALL
BE INSTALLED AT THE SAME HEIGHT.
12. DEVICES INSTALLED IN BLOCK OR TILED WALLS SHALL BE INSTALLED
WITH THE BOX SET ON TOP OF NEAREST COURSE, WITH THE OPENING
FOR THE BOX CUT INTO THE COURSE ABOVE. ALL DEVICE BOXES SHALL
BE INSTALLED ON TOP OF THE COURSE NEAREST TO THE SCHEDULED
MOUNTING HEIGHT.
13. WHERE MULTIPLE DEVICES OF THE SAME VOLTAGE ARE INSTALLED IN
CLOSE PROXIMITY, THEY SHALL BE GANGED TOGETHER IN A COMMON
BOX AND COVER PLATE.
14. COORDINATE ALL FASTENERS USED WITH WALL, CEILING, AND
STRUCTURAL SYSTEMS. EC SHALL TAKE PARTICULAR CARE NOT TO
USE FASTENERS IN A METHOD WHICH VIOLATES MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
GENERAL PROJECT NOTES / SPECIFICATIONS
THE LETTER "X" EQUALS THE DEVICE TYPES LISTED BELOW, UNO:
BLANK = NORMAL POWER / STANDARD RECEPTACLE
IG = NORMAL POWER / ISOLATED GROUND RECEPTACLE
TR = NORMAL POWER / TAMPERPROOF RECEPTACLE
WP = NORMAL POWER / WEATHER RESISTANT RECEPTACLE WITH
WEATHERPROOF IN-USE COVER
EM = EMERGENCY POWER / STANDARD RECEPTACLE WITH RED
BODY
USB = NORMAL POWER / STANDARD RECEPTACLE WITH (2)
INTEGRAL USB CHARGING PORTS AND 5V POWER SUPPLY
OC = INSTALL AT 8" ABOVE COUNTERTOP HEIGHT - COORDINATE
WITH ANY BACKSPLASH OR TILED FINISHES
RECEPTACLES / ELECTRICAL DEVICES
SIMPLEX RECEPTACLE, WALL MOUNTED. X
X
DUPLEX RECEPTACLE, WALL MOUNTED
SOLID CENTER INDICATES DEDICATED CIRCUIT.X
SPLIT WIRED DUPLEX RECEPTACLE, WALL
MOUNTED.
DOUBLE DUPLEX (QUAD) RECEPTACLES, WALL
MOUNTED. SOLID CENTER INDICATES DUAL
DEDICATED CIRCUITS.
X
GFCI RATED RECEPTACLE, WALL MOUNTED
SOLID CENTER INDICATES DEDICATED CIRCUIT.
X
SPECIAL PURPOSE RECEPTACLE, NEMA
CONFIGURATION AS NOTED ON PLANS, WALL
MOUNTED.
X
DESCRIPTIONSYMBOL MOUNTING
HEIGHT
+18" AFF
+18" AFF
+18" AFF
+18" AFF
+18" AFF
+18" AFF
DUPLEX RECEPTACLE, CEILING MOUNTED. X N/A
JUNCTION BOX
X
SEE PLANS
MULTI-SERVICE CEILING OUTLET,
CONFIGURATION AS NOTED ON PLANS,
CEILING MOUNTED.
X N/A
FLOOR MOUNTED RECEPTACLE. N/A
J
JUNCTION BOX WITH FLEXIBLE EQUIPMENT
CONNECTION, (6) FEET MAX LENGTH.SEE PLANSJ
DOUBLE DUPLEX (QUAD) RECEPTACLES,
CEILING MOUNTED.N/A
MULTI-SERVICE POWER POLE, CONFIGURATION
NOTED ON PLANS.N/A
PUSHBUTTON, TYPE AND QUANTITY OF
BUTTONS AS NOTED ON PLANS.SEE PLANS
X
X
X TTHERMOSTAT, FURNISHED BY OTHERS UNO.
SEE MECHANICAL SCHEDULES FOR DETAILS.+44" AFF
SMOKE DETECTOR CEILING
X
POWER DISTRIBUTION
MAIN SWITCHBOARD, MAY BE SWITCHBOARD OR
SWITCHGEAR CONSTRUCTION, SEE PLANS FOR
DETAILS. FLOOR MOUNTED, FREE STANDING.
DASHED LINES REPRESENT CODE REQUIRED
CLEARANCES.
DESCRIPTIONSYMBOL
MSB-A
SURFACE MOUNTED DISTRIBUTION
PANELBOARD. DASHED LINES REPRESENT
CODE REQUIRED CLEARANCES.
SURFACE MOUNTED BRANCH PANELBOARD.
DASHED LINES REPRESENT CODE
REQUIRED CLEARANCES.
FLUSH MOUNTED BRANCH PANELBOARD.
DASHED LINES REPRESENT CODE
REQUIRED CLEARANCES.
HV-1
HV-1
T-1 DRY TYPE TRANSFORMER, 15kVA OR LARGER.
T DRY TYPE TRANSFORMER, LESS THAN 15kVA.
SEE PLANS FOR DETAILS.
MGB MAIN GROUNDING BUS. SEE PLANS FOR
DETAILS.
NF DISCONNECT SWITCH, NON -FUSED. MOUNT AT
48" AFF.
DISCONNECT SWITCH, FUSIBLE. FUSE RATING
SHOWN. MOUNT AT 48" AFF.
COMBINATION MOTOR STARTER / FUSIBLE
DISCONNECT. NEMA STARTER SIZE AND FUSE
RATING SHOWN. MOUNT AT 48" AFF.
60A
N1/60A
ELECTRIC MOTOR, NUMBER INDICATES
HORSEPOWER. NOT DRAWN TO SCALE.500
25,769 A AVAILABLE BOLTED FAULT CURRENT
SF4000N-AL FEEDER TAG, SEE SCHEDULE FOR DETAILS.
LIGHTING FIXTURES / DEVICES
FIXTURE TYPES AND/OR SWITCHING ARE INDICATED AS LISTED BELOW, UNO:
# = FIXTURE TYPE MARK, REFER TO FIXTURE SCHEDULES.
NL = "NIGHT LIGHT" FIXTURE, WIRED FOR 24 HOUR OPERATION.
a,b = INDICATES SWITCH GROUP WITHIN ROOM OR AREA
SHADING INDICATES FIXTURE EITHER CONTAINS AN INTEGRAL BATTERY
OPERATED EMERGENCY INVERTER OR IS CONNECTED TO AN EMERGENCY
POWER SUPPLY SYSTEM. REFER TO PLANS FOR DETAILS.
DESCRIPTIONSYMBOL MOUNTING
HEIGHT
RECESSED FIXTURE
NL
# a,b
a,b # SURFACE MOUNTED FIXTURE
# a,b LINEAR FIXTURE, SUSPENDED.
RECESSED DOWNLIGHT. ARROW INDICATES
DIRECTION OF WALL WASH LENS, WHERE USED.
# a,b
# a,b WALL MOUNTED FIXTURES
#
NL
a,b SURFACE MOUNTED STRIP FIXTURES
#
#
# #
EMERGENCY EXIT SIGN. SHADING INDICATES
FACES USED, ARROWS INDICATE EGRESS PATH.
MAY BE CEILING MOUNTED, NOT EXCEEDING
+12'-0" AFF.
WALL MOUNTED EMERGENCY LIGHTING UNIT
SEE
SCHEDULES
SEE
SCHEDULES
SEE
SCHEDULES
SEE
SCHEDULES
SEE
SCHEDULES
SEE
SCHEDULES
+8'-0" AFF
+8'-0" AFFEMERGENCY LIGHTING REMOTE HEAD, MOUNT
+12" ABOVE DOOR FRAMES OR AS NOTED.
WALL =
+8'-0" AFF
X
a
THE LETTER "X" EQUALS THE DEVICE TYPES
LISTED BELOW, UNO:
BLANK = SINGLE POLE TOGGLE SWITCH
2 = DOUBLE POLE TOGGLE SWITCH
3 = THREE WAY TOGGLE SWITCH
4 = FOUR WAY TOGGLE SWITCH
M = MOTOR RATED SWITCH
LV = DIGITAL LOW VOLTAGE SWITCH
D = DIMMING SWITCH
T = TIMER SWITCH
WP = WEATHERPROOF SWITCH
K = KEY OPERATED SWITCH
OS = OCCUPANCY SENSOR SWITCH
+48" AFF
OS a
SEE
SCHEDULES
OCCUPANCY SENSOR, TYPE AS INDICATED IN
SCHEDULES.
PC a
SEE
SCHEDULES
PHOTOCELL, TYPE AS INDICATED
IN SCHEDULES.
PP a
SEE
SCHEDULES
LIGHTING CONTROL RELAY, TYPE AS INDICATED
IN SCHEDULES.
SINGLE-LINE DIAGRAM
DESCRIPTIONSYMBOL
400AT
400AF
LSI
CIRCUIT BREAKER - TRIP RATING / FRAME SIZE,
AND/OR NUMBER OF POLES. SETTINGS AND
OTHER ACCESSORIES AS NOTED ON PLANS.
400AT
400AF
LSIG
EB
DRAWOUT CIRCUIT BREAKER - TRIP RATING /
FRAME SIZE, AND/OR NUMBER OF POLES.
SETTINGS AND OTHER ACCESSORIES AS NOTED
ON PLANS.
TRANSFORMER - VOLTAGE CONFIGURATION,
KVA RATING, WIRING CONFIGURATION. SEE
PLANS FOR OTHER DETAILS AND
REQUIREMENTS.
T-1
2,500 kVA
480D-208Y/120V
3000-5 CURRENT TRANSFORMER - RATIO OF PRIMARY
TO SECONDARY WINDINGS.
480-120
75 VA
POTENTIAL TRANSFORMER - RATIO OF PRIMARY
VOLTAGE TO SECONDARY VOLTAGE, HEAT
RATING.
1000A
BPS
DISCONNECT SWITCH - FRAME SIZE.
"BPS" INDICATES BOLTED PRESSURE SWITCH.
1000A
CLASS J FUSE - TRIP RATING, FUSE CLASS.
ELECTRONIC BREAKER OPERATORS:
EB = MOTOR OPERATED CLOSE / OPEN
GF = GROUND FAULT TRIP UNIT
ST = SHUNT TRIP OPEN
UV = UNDERVOLTAGE RELEASE
400AT
400AF
LSIG
GF
GROUND CONNECTION
N E
TRANSFER SWITCH, SEE PLANS FOR TYPE AND
OTHER DETAILS. ARC INDICATES CLOSED
TRANSITION.
SPD SURGE PROTECTIVE DEVICE, SEE PLANS.
ELECTRONIC METER, SEE PLANS FOR TYPE.
KEYED INTERLOCK, SEE PLANS FOR DETAILS.
PROTECTIVE RELAY, SEE PLANS FOR DETAILS.
M
K1
R1
ELECTRICAL CONNECTION, BOLT / LUG / SCREW.
CIRCUITS
PHASE CONDUCTORS
GROUND CONDUCTOR (IF TWO ARE SHOWN,
THE SECOND SHALL BE AN ISOLATED GROUND)
NEUTRAL CONDUCTOR
DRAWING No. :
DRAWN BY :
DATE :
SCALE :
PROJECT No. :PROJECT NAME :DRAWING TITLE :CERTIFIED BY :
ORIGINAL DRAWING IS : 24"x36"
DEEM MECHANICAL & ELECTRICAL, LLC.
RESERVES THE RIGHT TO REVISE THE
DESIGN OF THE ELECTRICAL AND/OR
MECHANICAL SYSTEMS PROVIDING THE
CHANGES MEET THE DESIGN/BUILD
SPECIFICATIONS FOR THIS PROJECT.6831 East 32nd Street, Suite 200Indianapolis, IN 46226Office: 317.860.2990Fax: 317.860.2964www.deemfirst.com
A Mechanical and Electrical Company
THIS DRAWING AND ALL INFORMATION ONIT IS THE PROPERTY OF DEEMMECHANICAL & ELECTRICAL, LLC. IT ISCONFIDENTIAL AND IT'S SUBMISSION ORDISTRIBUTION TO MEET OFFICIAL REGULATORYREQUIREMENTS, OR FOR OTHER PURPOSES INCONNECTION WITH THIS PROJECT, IS NOT TO BECONSTRUED AS PUBLICATION IN DEROGATION OFDEEM MECHANICAL & ELECTRICAL, LLC., COMMONLAW COPYRIGHT, OR OTHER RESERVED RIGHTS.NEITHER THIS DRAWING NOR ANY PART OF IT MAYBE REPRODUCED, COPIED, EXHIBITED, ORDISTRIBUTED TO OTHERS, NOR MAY ANY ARTICLEOR ITEM BE FABRICATED OR ASSEMBLED FROMTHIS DRAWING, WITHOUT WRITTEN CONSENTFROM DEEM MECHANICAL & ELECTRICAL, LLC.A
1
B
C
D
A
B
C
D
2 3 4 5
1 2 3 4 5
1/8" = 1'-0"8/19/2019 9:42:03 AMAuthor
05/28/2019
19015
10209 DITCH ROAD,CARMEL INDIANASYMBOLS & ABBREVIATIONS
BHARAT PATEL HOUSEE-01
ELECTRICAL SHEET INDEX-D
SHEET No. SHEET NAME REV No. REV DATE
E-01 SYMBOLS & ABBREVIATIONS
E-10 SITE ELECTRICAL PLAN
E-20 LOWER LEVEL POWER PLAN
E-21 CLERESTORY POWER PLAN
E-23 UPPER LEVEL POWER PLAN
E-24 UPPER ROOF POWER PLAN
E-30 LOWER LEVEL LIGHTING PLAN
E-31 CLERESTORY LIGHTING PLAN
E-32 MAIN LEVEL LIGHTING PLAN
E-33 UPPER LEVEL LIHTING PLAN
E-50 ONE LINE DIAGRAM
E-60 PANEL SCHEDULE REVISION SCHEDULENo. DESCRIPTION DATE08/23/19
David Rutti
GYM
008
POW.
010
CHANGE
012
STEAM RM
013
MECH / STORAGE
015
COVERED PATIO
005
PARTY LOUNGE
006
BAR
007
MECH / WATER
016
STEAM MECH
014
BATH
002A
BEDROOM
002
BEDROOM
001
MECH.
003
HALL
004
ELEV MECH
009
BATH
001A
CLOSET
001B
CLOSET
002B
HALL
011TVTVTV
WP
WP
WP
3
3
ELEVATOR
CONTROLLER
ELEVATOR CAB
LIGHTS
INSTALLED IN
ELEV. PIT
200A PANEL
200A PANELS
BREAKER
DISCONNECT
LOCATION
DRAWING No. :
DRAWN BY :
DATE :
SCALE :
PROJECT No. :PROJECT NAME :DRAWING TITLE :CERTIFIED BY :
ORIGINAL DRAWING IS : 24"x36"
DEEM MECHANICAL & ELECTRICAL, LLC.
RESERVES THE RIGHT TO REVISE THE
DESIGN OF THE ELECTRICAL AND/OR
MECHANICAL SYSTEMS PROVIDING THE
CHANGES MEET THE DESIGN/BUILD
SPECIFICATIONS FOR THIS PROJECT.6831 East 32nd Street, Suite 200Indianapolis, IN 46226Office: 317.860.2990Fax: 317.860.2964www.deemfirst.com
A Mechanical and Electrical Company
THIS DRAWING AND ALL INFORMATION ONIT IS THE PROPERTY OF DEEMMECHANICAL & ELECTRICAL, LLC. IT ISCONFIDENTIAL AND IT'S SUBMISSION ORDISTRIBUTION TO MEET OFFICIAL REGULATORYREQUIREMENTS, OR FOR OTHER PURPOSES INCONNECTION WITH THIS PROJECT, IS NOT TO BECONSTRUED AS PUBLICATION IN DEROGATION OFDEEM MECHANICAL & ELECTRICAL, LLC., COMMONLAW COPYRIGHT, OR OTHER RESERVED RIGHTS.NEITHER THIS DRAWING NOR ANY PART OF IT MAYBE REPRODUCED, COPIED, EXHIBITED, ORDISTRIBUTED TO OTHERS, NOR MAY ANY ARTICLEOR ITEM BE FABRICATED OR ASSEMBLED FROMTHIS DRAWING, WITHOUT WRITTEN CONSENTFROM DEEM MECHANICAL & ELECTRICAL, LLC.A
1
B
C
D
A
B
C
D
2 3 4 5
1 2 3 4 5
1/8" = 1'-0"8/19/2019 9:42:03 AMWV
05/28/2019
19015
10209 DITCH ROAD,CARMEL INDIANALOWER LEVEL POWER PLANBHARAT PATEL HOUSEE-20REVISION SCHEDULENo. DESCRIPTION DATE1/8" = 1'-0" 1 LOWER LEVEL POWER PLAN
200A,
120V/240V,1P
PANELBOARD
UTILITY
METERING
CABINET
UTILITY FEED
(4) 3/0, (1)#6G, 4"C.
ONE LINE DIAGRAM
200A BREAKER
DISCONNECTS
200A,
120V/240V,1P
PANELBOARD
200A,
120V/240V,1P
PANELBOARD
08/23/19
David Rutti
ENTRY
109
POW.
110
CLOSET
100B
TEMPLE
103
MASTER BEDROOM 1
100 MASTER BEDROOM 2
101
LIVING ROOM
104
DINING ROOM
108
KITCHEN
112
PANTRY 1
113
LAUNDRY
115
MAIN ROOF PATIO
107
STORAGE
117
PANTRY 2
111
BATH
101A
LOUNGE
106
MUDROOM /
CLOSET
101B
GARAGE
116
BATH
100A
HALL
102
HALL
114
MASTER ROOF PATIO
118
BENCH BENCH
J
3 3
33
3
3
33
WPWP
WP
DRAWING No. :
DRAWN BY :
DATE :
SCALE :
PROJECT No. :PROJECT NAME :DRAWING TITLE :CERTIFIED BY :
ORIGINAL DRAWING IS : 24"x36"
DEEM MECHANICAL & ELECTRICAL, LLC.
RESERVES THE RIGHT TO REVISE THE
DESIGN OF THE ELECTRICAL AND/OR
MECHANICAL SYSTEMS PROVIDING THE
CHANGES MEET THE DESIGN/BUILD
SPECIFICATIONS FOR THIS PROJECT.6831 East 32nd Street, Suite 200Indianapolis, IN 46226Office: 317.860.2990Fax: 317.860.2964www.deemfirst.com
A Mechanical and Electrical Company
THIS DRAWING AND ALL INFORMATION ONIT IS THE PROPERTY OF DEEMMECHANICAL & ELECTRICAL, LLC. IT ISCONFIDENTIAL AND IT'S SUBMISSION ORDISTRIBUTION TO MEET OFFICIAL REGULATORYREQUIREMENTS, OR FOR OTHER PURPOSES INCONNECTION WITH THIS PROJECT, IS NOT TO BECONSTRUED AS PUBLICATION IN DEROGATION OFDEEM MECHANICAL & ELECTRICAL, LLC., COMMONLAW COPYRIGHT, OR OTHER RESERVED RIGHTS.NEITHER THIS DRAWING NOR ANY PART OF IT MAYBE REPRODUCED, COPIED, EXHIBITED, ORDISTRIBUTED TO OTHERS, NOR MAY ANY ARTICLEOR ITEM BE FABRICATED OR ASSEMBLED FROMTHIS DRAWING, WITHOUT WRITTEN CONSENTFROM DEEM MECHANICAL & ELECTRICAL, LLC.A
1
B
C
D
A
B
C
D
2 3 4 5
1 2 3 4 5
1/8" = 1'-0"8/19/2019 9:42:04 AMWV
05/28/2019
19015
10209 DITCH ROAD,CARMEL INDIANAMAIN LEVEL POWER PLANBHARAT PATEL HOUSEE-22REVISION SCHEDULENo. DESCRIPTION DATE1/8" = 1'-0"1 MAIN LEVEL POWER PLAN
08/23/19
David Rutti
PARTY ROOM
201
GAME ROOM
202
UPPER ROOF PATIO
209
GUEST ROOF PATIO
208
BEDROOM
206
BEDROOM
207
CLOSET
207A
HALL
205
BATH
207B
POWDER
204
BAR
203
BATH
206B
CLOSET
206A
FIREPIT / TABLE
TV
TVJ
WP
WP
DRAWING No. :
DRAWN BY :
DATE :
SCALE :
PROJECT No. :PROJECT NAME :DRAWING TITLE :CERTIFIED BY :
ORIGINAL DRAWING IS : 24"x36"
DEEM MECHANICAL & ELECTRICAL, LLC.
RESERVES THE RIGHT TO REVISE THE
DESIGN OF THE ELECTRICAL AND/OR
MECHANICAL SYSTEMS PROVIDING THE
CHANGES MEET THE DESIGN/BUILD
SPECIFICATIONS FOR THIS PROJECT.6831 East 32nd Street, Suite 200Indianapolis, IN 46226Office: 317.860.2990Fax: 317.860.2964www.deemfirst.com
A Mechanical and Electrical Company
THIS DRAWING AND ALL INFORMATION ONIT IS THE PROPERTY OF DEEMMECHANICAL & ELECTRICAL, LLC. IT ISCONFIDENTIAL AND IT'S SUBMISSION ORDISTRIBUTION TO MEET OFFICIAL REGULATORYREQUIREMENTS, OR FOR OTHER PURPOSES INCONNECTION WITH THIS PROJECT, IS NOT TO BECONSTRUED AS PUBLICATION IN DEROGATION OFDEEM MECHANICAL & ELECTRICAL, LLC., COMMONLAW COPYRIGHT, OR OTHER RESERVED RIGHTS.NEITHER THIS DRAWING NOR ANY PART OF IT MAYBE REPRODUCED, COPIED, EXHIBITED, ORDISTRIBUTED TO OTHERS, NOR MAY ANY ARTICLEOR ITEM BE FABRICATED OR ASSEMBLED FROMTHIS DRAWING, WITHOUT WRITTEN CONSENTFROM DEEM MECHANICAL & ELECTRICAL, LLC.A
1
B
C
D
A
B
C
D
2 3 4 5
1 2 3 4 5
1/8" = 1'-0"8/19/2019 9:42:04 AMWV
05/28/2019
19015
10209 DITCH ROAD,CARMEL INDIANAUPPER LEVEL POWER PLANBHARAT PATEL HOUSEE-23REVISION SCHEDULENo. DESCRIPTION DATE1/8" = 1'-0"1 UPPER LEVEL POWER PLAN
08/23/19
David Rutti