HomeMy WebLinkAboutA010.7CONCRETE REQUIREMENTS AND SPECIFICATIONS:
IT IS SOLELY THE CONTRACTOR'S RESPONSIBILITY TO FOLLOW ALL APPLICABLE
SAFETY CODES AND REGULATIONS DURING ALL PHASES OF CONSTRUCTION.
SHOULD ANY OF THE DETAILED INSTRUCTIONS SHOWN ON THE PLANS
CONFLICT WITH THESE STRUCTURAL NOTES, THE SPECIFICATIONS, OR WITH
EACH OTHER, THE STRICTEST PROVISIONS SHALL GOVERN.
GOVERNING CODES: INTERNATIONAL BUILDING CODE, 2008, WITH CURRENT
INDIANA AMENDMENTS.
FOUNDATIONS:
FOUNDATIONS ARE EXISTING AND NOT TO BE CHANGED.
REINFORCED CONCRETE:
ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH ACI 318-95, "BUILDING
CODE REQUIREMENTS FOR REWFORCED CONCRETE".
SPECIFlCATIONS: IN GENERAL, COMPLY WITH ACI 301-96,'STANDARD
SPEGFICATIONS FOR STRUCTURAL CONCRETE".
PLACEMENT AND CURING OF CONCRETE SHALL CONFORM TO ACI 305 "HOT
WEATHER CONCRETING" AND ACI 306 "COLD WEATHER CONCRETING".
ALL REINFORCING DETAILS SHALL CONFORM TO ACI 315-86, "MANUAL OF
STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES"
UNLESS DETAILED OTHERWISE ON THE STRUCTURAL DRAWINGS.
ALL DEFORMED REINFORCING BARS: ASTM A615, GRADE 60
ALL WELDED WIRE FABRIC: ASTM A185, DELIVERED IN FLAT SHEETS
REINFORCING SUPPLIER SHALL PROVIDE ALL BAR ACCESSORIES, CHAIRS, AND
SUPPORTS NECESSARY TO SECURE STEEL IN ACCORDANCE WITH "ACT CODE
OF STANDARD PRACTICE".
CONCRETE COVER: UNLESS OTHERWISE NOTED, DETAIL REWFORCING TO
PROVIDE MINIMUM COVER AS FOLLOWS:
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3
INCHES
CONCRETE IN THE FOLLOWING AREAS SHALL CONSIST OF NATURAL SAND FWE
AGGREGATE AND NORMAL WEIGHT COURSE AGGREGATES CONFORMING TO
ASTM C33, TYPE 1 PORTLAND CEMENT CONFORMING TO ASTM C150, AND SHALL
HAVE THE FOLLOWING COMPRESSIVE STRENGTH AT 28 DAYS:
SLABS-ON-GRADE 4,000 PSI
NO PART OF THE STRUCTURE SHALL BE PLACED ON FROZEN OR WET SOIL.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR KEEPING THE
FOUNDATION AND SOIL WITHIN THE BUILDING AREA FROM FREEZING DURING
WINTER CONSTRUCTION.
ALUMINUM GUTTERS AND DOWNSPOUTS:
1. GUTTERS SHALL BE CONTINUOUS SITE-FORMED ALUMINUM.
2. DOWNSPOUTS SHALL BE ALUMINUM.
3.ALUMINUM GUTTERS:
a. HEAVY GAUGE, MINIMUM .027 THICKNESS
b. FINISH BAKED-ON ENAMEL
c. OGEE PROFILE (REAR EDGE HIGHER THAN FRONT EDGE) AS
REQUIRED OR INDICATED ON DRAWINGS.
d. USE HIDDEN HANGERS, NO SPIKES.
4. ALUMINUM DOWNSPOUTS:
a. 3" X 4" PROFlLE
b. FINISH BAKED-ON ENAMEL
c. POP-RIVETED, MITERED.
5. INSTALL ALL MATERIALS AND ACCESSORIES WITH POSITIVE
ANCHORAGE. PROVIDE FOR THERMAL EXPANSION.
COORDINATE INSTALLATION WITH OTHER BUILDING
COMPONENTS.
ADA DIMENSIONS
INSTHLL HLL FEOUIRED BLOCKING IN WHLL FIXi
OMB BPR9, MIM0R9, PND PCCE990GE9
ROUGH FRAMING REQUIREMENTS AND SPECIFICATIONS:
IT IS SOLELY THE CONTRACTOR'S RESPONSIBILITY TO FOLLOW ALL APPLICABLE
SAFETY CODES AND REGULATIONS DURING ALL PHASES OF CONSTRUCTION.
SHOULD ANY OF THE DETAILED INSTRUCTIONS SHOWN ON THE PLANS
CONFLICT WITH THESE STRUCTURAL NOTES, THE SPECIFICATIONS, OR WITH
EACH OTHER, THE STRICTEST PROVISIONS SHALL GOVERN.
GOVERNING CODES: INTERNATIONAL BUILDING CODE, 2006, WITH CURRENT
INDIANA AMENDMENTS.
ROUGH CARPENTRY SPECIFICATIONS: SECTION 06100
ALL WOOD CONNECTIONS, JOIST HANGERS, POST CAPS, BASES, HOLD-DOWNS,
ETC. SHALL BE MANUFACTURED BY SIMPSON STRONG-TIE CO. INC. OR AN
APPROVED EQUAL. UNLESS OTHERWISE NOTED, CONNECTIONS SHALL BE
INSTALLED STRICTLY IN ACCORDANCE WITH MANUFACTURER'S WRITTEN
INSTRUCTIONS FOR CONDITIONS SIMILAR TO THESE APPLICATIONS.
ALL MEMBER SIZES GIVEN IN THE DRAWINGS ARE NOMINAL DIMENSIONS.
ALL FLOOR JOISTS (IF USED AND OF ANY SIZE) AND ROOF JOISTS (GREATER
THAN 2X8'S) SHALL BE LATERALLY SUPPORTED BY SOLID BLOCKING EXCEPT
WHERE ENDS OF JOIST ARE NAILED TO A HEADER OR RIM JOIST OR TO AN
ADJOINING STUD. S90LID BLOCKING SHALL NOT BE LESS THAN TWO INCHES IN
THICKNESS AND THE FULL DEPTH OF THE JOIST. SOLID 2X BRIDGING AT
CENTER OF SPAN FOR ALL FLOOR JOISTS.
COORDINATE ALL DIMENSION LUMBER SIZES BETWEEN ARCHITECTURAL AND
STRUCTURAL DRAWINGS. BRING ANY DISCREPANCIES TO THE ATTENTION OF
THE ARCHITECT.
WHERE POSTS ARE SHOWN, HEADERS SHALL BEAR FULLY ON POSTS.
ALL WOOD JOISTS SHALL BEAR ON THE FULL WIDTH OF SUPPORTING MEMBERS.
ALL BEAMS AND JOISTS NOT BEARING ON SUPPORTING MEMBERS SHALL BE
FRAMED WITH SIMPSON JOIST HANGERS OR EQUAL USE TYPE LU-210 (OR
EQUAL) FOR SINGLE 2X'S AND NPE HUS-210-2 (OR EQUAL) FOR DOUBLE 2X'S.
PROVIDE MINIMUM 2-2X12 HEADERS WITH MIN. V2 INCH PLYWOOD FLITCH
PLATE AT ALL OPENINGS IN BEARING WALLS WHERE NO HEADERS ARE CALLED
OUT. MAXIMUM SPAN FOR 2-2X12 HEADERS SHALL BE 4'-0" UNLESS NOTED.
WOOD HEADERS OR POSTS MADE UP OF 2X'S SHALL BE SPIKED TOGETHER.
BOTTOM PLATES OF ALL BEARING INTERIOR AND EXTERIOR FIRST FLOOR STUD
WALLS SHALL BE ANCHORED WITH 1l2 INCH RED HEAD ANCHOR BOLTS WITH
MIN. 6 WCH EMBEDMENT AT 4'-0" ON CENTER, OR WITH EQUIVALENT ANCHORS
AS APPROVED BY THE ARCHITECT. ANCHORS SHALL BE A MAXIMUM OF 1'-0"
FROM CORNERS.
BOTTOM PLATES OF NON-BEARING FIRST FLOOR STUD WALLS IN CONTACT
WITH SLAB SHALL BE ANCHORED USING #16D CONCRETE NAILS 32" ON CENTER
OR EQUAL.
BOTTOM PLATES IN CONTACT WITH MASONRY OR CONCRETE SLAB, AND
LUMBER USED FOR BATTEN BOARDS, SHALL BE PRESSURE TREATED
IMPREGNATED WITH WATERBORNE PRESERVATION IN ACCORDANCE WITH THE
AMERICAN WOOD PRESERVATION BUREAU (AWPB) STANDARD LP-2, CURRENT
EDITION.
ROOF SHEATHING SHALL BE MIN. 1l2 INCH 321164-PLY C-D INT-APA. H-CLIPS
SHALL BE USED TO SUPPORT EDGES OF THE PLYWOOD SHEATHING BETWEEN
THE TRUSSES OR ROOF RAFTERS.
WALL SHEATHING AT CORNERS SHALL BE 1I2 INCH CDX PLYWOOD, GLUED WITH
EXTERIOR GLUE AND NAILED AT PERIMETER CORNERS. NAILED-ONLY ALONG
STRAIGHT RUNS.
ALL LUMBER USED FOR LOAD SUPPORTING PURPOSES, INCLUDING END-
JOINTING OR EDGE GLUED LUMBER SHALL BE IDENTIFIED BY THE GRADE MARK
OF AN INSPECTION AGENCY CERTIFlED BY THE AMERICAN LUMBER STANDARDS
COMMITTEE" (ALSCj. IN LIEU OF A GRADE MARK, A CERTIFICATE OF INSPECTION
AS TO SPECIES AND GRADE ISSUED BY A LUMBER GRADING OR INSPECTION
AGENCY APPROVED BY THE ALSC MAY BE ACCEPTED.
ALL LUMBER SHALL BE SEASONED TO A MOISTURE CONTENT OF 19 PERCENT.
LUMBER SHALL BE PROTECTED FROM THE ELEMENTS UNTIL SUCH TIME IT IS
USED IN CONSTRUCTION STORED OFF THE GROUND.
ACCESSIBILITY REQUIREMENTS:
MIRRORS:
MIRRORS SHALL BE FLAT AGAINST THE WALL, WITH THE BOTTOM
OF THE MIRROR SURFACE NO MORE THAN 40 INCHES ABOVE
FINISH FLOOR. THE TOP EDGE OF THE MIRROR SURFACE SHALL
BE A MINIMUM OF 741NCHE5 ABOVE FINISH FLOOR.
LAVATORIES AND SINKS:
WATER SUPPLY AND DRAINPIPES UNDER LAVATOPoES AND SINKS
SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
AGAINST CONTACT. THERE SHALL BE NO SHARP OR ABRASNE
SURFACES UNDER LAVATORIES AND SINKS.
ACCESSIBLE TOILET WATER CLOSETS:
CENTERLWE OF WATER CLOSET SHALL BE 16" MINIMUM TO 18"
MAXIMUM FROM THE SIDEWALL OR PARTITION.
CONTRACTOR SHALL CONFIRM IN THE FIELD THAT THE
CLEARANCES IN A WATER CLOSET STALL SHALL BE 60 INCHES
MINIMUM MEASURED PERPENDICULAR FROM THE SIDEWALL AND
REAR WALL. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BE
LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
NOTIFY ARCHITECT IMMEDIATELY IF AN OBSTRUCTION
CONFLICTS WITH THE ABOVE REQUIREMENTS.
HEIGHT: THE HEIGHT OF ACCESSIBLE WATER CLOSETS SHALL BE
17 INCHES MINIMUM TO 19 INCHES MAXIMUM MEASURED TO THE
TOP OF THE TOILET SEAT. SEATS SHALL NOT BE SPRUNG TO
RETURN TO A LIFTED POSITION.
FLUSH CONTROLS SHALL BE LOCATED ON THE TRANSFER SIDE
OFTHE WATERCLOSET.
ACCESSIBLE URINALS:
URINALS SHALL BE WALL-HUNGTYPE WITH THE RIM 171NCHES
MAXIMUM ABOVE FINISH FLOOR. URINALS SHALL PROVIDE A
MINIMUM DEPTH OF 13 1/3 INCHES MEASURED FROM THE OUTER
FACE OF THE URINAL RIM TO THE BACK OF THE FIXTURE.
CONFIRM THAT THERE IS CLEAR FLOOR SPACE OF 48 INCHES
PERPENDICULAR FROM REAR WALL OF URINAL, AND 30 INCHES
CENTERED ON ACCESSIBLE URINAL. IF A CONFLICT IS PRESENT,
NOTIFY ARCHITECT.
GRAB BARS:
GRAB BARS SHALL BE INSTALLED STRICTLY ACCORDING TO
ARCHITECT'S DRAWING SHOWING ACCESSIBILITY DIMENSIONS
OR THE LATEST ADA REQUIREMENTS, WHICHEVER IS STRICTER.
WHERE WALL SPACE PERMITS, A 36 LONG GRAB BAR SHALL BE
INSTALLED ON THE REAR WALL OF THE WATER CLOSET AREA,
WITH THE ADDITIONAL LENGTH ON THE TRANSFER SIDE OF THE
WATER CLOSET.
GENERAL TOILET ROOM ELEMENTS:
IF SOAP AND TOWEL DISPENSERS ARE PROVIDED, THEY MUST BE
LOCATED WITHIN THE REACH RANGES IN ADA STANDARDS.
�
w
�
z
0
�
U m
� o
O ry
K �
N Y
O 'U
■���■
� N i�(l u'1 U
y(0 N �1_
N � i(l N �
U�
� N N �
o � � ^ o
3 � M M �
� . Y
a!��X`m
�Qo�U
m NaLLC7
0
�
m �
7 c
Q
Q
F
U
W
�
2
U
�
Q
Y
�
Q
J
U
Z
�
O
�
�
�
�
�
LL
�
J
�
O
d
0
z
�
z
�
J
�/�
W
Q
WN
L.L
�
�
�
Z
CW
G
�
�
U
Q
W
J
w
�
Q
Z
Q
�
Z
�
�
z
�
0
z
0
J
C
Q
JULY 1 L 2019
� e' No.
e AR0003i
SiAiE
A5.1
,,.,,�a, ,,,,.v���y��v��.c n�,�� o�� � cy.�v,����v
04 S�a�e antl Local Codes
City of Carmel
`�j sv�� �\'��v�N�nl.� �
�
onrE: 12/18/19