HomeMy WebLinkAboutEELECTRICAL SPECIFICATIONS AND GENERAL REQUIREMENTS: THE CONTRACT DOCUMENTS CONSIST OF THE DRAWINGS AND SPEGFICATIONS ON THE DRAWINGS. THE INTENT OF THE CONTRACT DOCUMENTS IS TO INCLUDE ITEMS NECESSARY FOR THE PROPER EXECUTION OFTHE WORK. BUILDING CODES: NEW CONSTRUCTION SHALL CONFORM TO ALL APPLICABLE GTY, STATE AND LOCAL BUILDING CODES FOR THIS CLASS OF WORK. ADA MOUNTING: MOUNTING HEIGHTS AND EQUIPMENT SHALL BE IN ACCORDANCE WITH THE AMERICANS WITH DISABILITIES ACT (ADA) WHERE REQUIRED. SEE DETAILS ON OTHER DRAWING SHEETS. UNLESS OTHERWISE NOTED ON PLANS OR CONTRACT, ELECTRICAL CONTRACTOR (EC) SHALL PROVIDE AND INSTALL TELEPHONE AND DATA WIRING BETWEEN EACH OUTLET. EC SHALL COORDINATE WITH LOCAL TELEPHONE UTILITY FOR THE CONNECTION TO THEIR SERVICE. ELECTRICAL CONTRACTOR SHALL VERIFY EXISTING CONDITIONS AND DIMENSIONS AT THE JOBSITE. IF DISCREPANCIES ARE FOUND THE GENERAL CONTRACTOR SHALL BE NOTIFIES BEFORE PROCEEDING WITH ANY WORK OR ORDERING ANY EQUIPMENT OR MATERIAL IN THE AFFECTED AREA. PRECONSTRUCTION VERIFlCATIONS ELECTRICAL CONTRACTOR SHALL VERIFY CHARACTERISTICS AND AMOUNT OF AVAILABLE ELECTRICAL SERVICE PRIOR TO PRICING AND SHALL INCLUDE REQUIRED SERVICE UPGRADES IN COST OF INSTALLATION. FIT AND QUANTIN OF THE WIRING, ELECTRICAL EQUIPMENT, THE VARIOUS NECESSARY PARTS AND MATERIALS TO MAKE A COMPLETE AND FINISHED JOB SHALL BE VERIFIED AND COORDINATED PRIOR TO START OF CONSTRUCTION AND ARE THE EXCLUSIVE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. LOCAL UTILITY COORDINATION: ELECTRICAL CONTRACTOR SHALL COORDINATE TRANSFORMERS AND SERVICE REQUIREMENTS WITH THE LOCAL UTILITY COMPANY. THE E.Q SHALL CONSULT WITH THE LOCAL UTILITY TO ESTABLISH REQUIRED kACI RATINGS. ALL FIXTURES, EQUIPMENT AND MATERIALS SHALL BE INSTALLED PER THE MANUFACTURER'S SUGGESTED INSTALLATION REQUIREMENTS IN A NEAT AND WORKMANLIKE MANNER. UL LABELING: ALL ELECTRICAL EQUIPMENT SHALL HAVE "UL" LABELS. WIRING DEVICES SHALL BE SPECIFICATION GRADE. RELEASED FOR CONSTRl1CTI0N Su6jec� �o compliance with all regula�ions 04 S�a�e antl Local Codes City of Carmel Jj¢a� ��VonV�nnw� onrE: 12/18/19 �+ _______", �+ __'____", �+ _______", A '_______",—` A '_—_""„ A _______", �+ _______", �+ _______", A a" '�' - '�'- '� -- ',�.i ',o-' '�' '�" '-0 DUPLEX RECEPTICAL ALL OUTLETS SHALL BE GFl PROTECTED WATER RESISTANT DUPLEX RECEPTICAL ALL OUTLETS SHALL BE GFI PROTECTED � ELECTRIC PANEL SEE RISER �IAGRAM BELOW � GFI � P GFI ELECTRICAL PLAN ,o AMP ANE� SCALE 1/4" = 1'-O" RANSFORM R gREAKER5A5 IF REQUIRE REQUIRED� RISER DIAGRAM NOT TO SCHLE TW031/2"CONDUITS = GROUN�PER W/4-500 MCM - NEC IF REQUIRED PROVIDE ALL DISCONNECTS REQUIRED PER NATIONAL AND LOCAL ELECTRICAL CODES RATED TO UTILITY SUPPLIED kAIC LIMITS, OR, IF NOT SUPPLIED, TO NEC MINIMUMS. ELECTRICAL SHOWN IS DIAGRAMMATIC AND MUST BE FlELD VERIFlED FOR EXACT ROUTING AND ADDITIONAL EQUIPMENT OR DEVICES NECESSARY FOR COMPLETEJOB. ALL EXPOSED WIRE AND WIRING BELOW CONCRETE SLABS SHALL BE IN CONDUIT. TEMPERATURE CONTROL WIRING SHALL BE COMPLETED BY THE MECHANICAL CONTRACTOR. GFIC FOR HVAC UNITS: ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL A GFIC OUTLET IN AN APPROPRIATE LOCATION FOR USE FOR THE HVAC UNIT(S). OUTLET SHALL BE WEATHERPROOF WHILE IN USE. DISCONNECT FOR ROOFTOP EQUIPMENT: PROVIDE A PERMANENT DISCONNECT WITHIN SIGHT FOR ALL ROOFTOP EQUIPMENT, INCLUDED BUT NOT NECESSARILY LIMITED TO: WALK-IN COOLER CONDENSING UNITS, RANGE HOOD EXHAUST AND MAKE-UP AIR FANS, AND ROOFTOP HVAC UNIT(S). DISCONNECT FOR WATER HEATER: ELECTRICAL CONTRACTOR SHALL INSTALL A LOCAL DISCONNECT WITHIN LINE OF SIGNT OF PERMANENTLY CONNECTED WATER HEATER. WIRE: ALL WIRE SHALL BE COPPER, MINIMUM SIZE #12 AWG. ALL CONDUCTORS SHALL HAVE TYPE "THHN" INSULATION. CONDUCTORS #10 AND SMALLER MAY BE SOLID. GROUNDING CABLES SHALL BE NO SMALLER THAN 4 COPPER. BREAKER PANELS: FURNISH AND INSTALL A BREAKER PANEL AS MANUFACTURED BY SQUARE D OR ITE. INSTALL PANEL SO TOP BREAKER IS NO HIGHER THAN 6'-0". FURNISH AND INSTALL TYPEWRITTEN DIRECTORY. IDENTIFY AND LABEL ALL ELECTRICAL SERVICE EQUIPMENT. CONDUIT: CONDUIT IN FINISHED AREAS TO BE CONCEALED AND AS PERMITTED BY CODES. GROUNDING: GROUNDING SHALL BE DONE STRICTLY ACCORDING TO SECTION 250.52 OF THE NATIONAL ELECTRIC CODE USING ACCEPTABLE ELECTRODES AND CONNECTIONS. FOLLOW THE GROUNDING DIAGRAM INSIDE THE PLANS UNLESS NEC 250.30- 250.66 REQUIRES SOMETHING DIFFERENT. FOR THIS INSTALLATION THE FOLLOWING SVSTEMS ARE ACCEPTABLE: 1. ROD ELECTRODES (GROUND ROD) IF INSTALLED CORRECTLY 2 CONCRETE ENCASED ELECTRODE ATTACHED TO A STEEL REINFORCING BAR NOT LESS THAN 20 FEET IN LENGTH AND %" DIAMETER. A SINGLE 20 FOOT RE-BAR IS NOT REQUIRED AS LONG AS THE RE-BARS ARE CONNECTED CORRECTLY. THE PREFERRED METHOD IS TO ATTACH TO THE RE-BAR CAGE, EFFECTIVELY MAKING THE ENTIRE FOUNDATION A CONCRETE- ENCASED ELECTRODE. ADDITIONALLY, IF ANCHOR BOLTS IN A FOOTER ARE AVAILABLE, ATTACHMENT SHALL BE MADE TO THEM. ALARMS: ALL ALARMS SHALL BE VISIBLE AS WELL AS AUDIBLE. ALL UNDERFLOOR CONDUITS SHALL BE P.V.C. SWITCHES: ALL SWITCHES SHALL BE RATED 20 AMP, 125 VOLT AND SHALL BE MOUNTED 4'-6" AFF, UNLESS NOTED OTHERWISE. RECEPTICALS: ALL RECEPTACLES TO BE 15 AMP, 125 VOLT, GROUNDING TYPE AND SHALL BE MOUNTED 18" AFF, UNLESS NOTED OTHERWISE. PROVIDE TEMPORARY POWER REQUIRED BY THE GENERAL CONTRACTOR AND OTHER TRADES. COORDINATE POWER REQUIREMENTS WITH GC PRIOR TO INSTALLATION. LIGHTING FIXTURES: LIGHTING FIXTURES TO BE FURNISHED AND INSTALLED COMPLETE WITH LAMPS AS DETAILED ON THE PLANS OR AS INTENDED. SEE REFLECTED CEILING PLAN AND/OR LIGHTING PLAN FOR THE EXACT LOCATION OF THE CEILING GRID, LIGHT FIXTURES, OR THE GENERAL INTENT OF THE DRAWINGS. SEE THE ELECTRICAL DRAWING(5) FOR THE FIXTURE SCHEDULE, NOTES AND OTHER SPECIFICATION REQUIREMENTS. THE ARCHITECT SHALL HAVE ACCESS TO THE CONSTRUCTION SITE AND HAVE THE RIGHT TO REJECT ANY WORK (AFfER CONSULTATION WITH THE GENERAL CONTRACTOR) THAT DOES NOT CONFORM TO THE DRAWINGS, SPECIFICATIONS, CODES OR WORK THAT HAS NOT BEEN EXECUTED IN A WORKMANLIKE MANNER. CONTRACTOR SHALL BE RESPONSIBLE FOR NOTICE TO THE INSPECTING AUTHORITIES, ARCHITECT, OR GENERAL CONTRACTOR, SO THAT WORK CAN BE INSPECTED OR APPROVED BEFORE COVERING. THIS PROCEDURE SHALL OCCUR WITHOUT AFFECTING CONSTRUCTION PROGRESS AND COMPLETION. THE INTENTION OF THESE DOCUMENTS IS TO PROVIDE THE OWNER WITH A BUILDING COMPLETE IN ITS ENTIREN AT THE TIME OF OCCUPANCY. IT IS THE SUB-CONTRACTOR'S RESPONSIBILIN TO CONTRACT THE GENERAL CONTRACTOR DURING THE BIDDINGIPRICING PHASE OF ANY DETAILS MISSING, VAGUE, ORE INCOMPLETE SO THAT AN APPROPRIATE ADDENDUM OR CLARIFICATION CAN BE ISSUED. THE SELECTED CONTRACTOR SHALL PROVIDE ALL MATERIALS, LABOR, TOOLS, EQUIPMENT, AND SERVICES NECESSARY FOR A COMPLETE, FUNCTIONAL, AND OPERATIONAL FAGLITY. OPERATION AND MAINTENANCE MANUALS: TWO COPIES OF OPERATION AND MAINTENANCE MANUALS FOR MATERIALS INSTALLED PER WORK OF THIS SECTION SHALL BE DELNERED TO OWNER PRIOR TO ACCEPTANCE OF THESE SPACESFOR OCCUPANCY. OXES NEAR MAIN 9EP END, ONE NEAR SYMBOLS OA � OC D � LED RECESSED EXTERIOR RATED CEILING LIGHT - 6" PLUS TRIM KIT 4LAMP24"x48"SURFACE MOUNT LED CHEMICAL RESISTANT LED RECESSED CEILING FIXTU RE - 6" PLUS TRIM KIT EMERGENCV WALLPACK � EXHAUSTFAN WIRE WITH LIGHT FIXTURE 120 CFM GREENHECKOR EQUAL VENT TO DAVLIGHT WITH RAIN HOODAND INSECT SCREEN (jj o O o y rc ° ■���■ ti N N N � yt0 N N_ � a N N 0 U� � N N � � � � r W 3 � M M � C i' � N � K � m N s � U� o�a N � V C Q a � U W � _ U � Q Y � Q J U Z O 0 � Q/� V ■ � � � J � O d 0 Z Q � c� Z � J � m � WN L.I_ � � � Z � � � U /�n V W J W I � Q Z Q � Z } � z � � Z � � J � Q _ 'TEMBER 12, 201 � winnun. � EDVARD "'�. .�°°d' c <, j�p9 �G\STEqf (yp, u � No. � F e AR00032537 e STATE OF E1.1