HomeMy WebLinkAboutE600 - Electrical Specificationsi E LEAVEA#10AWGPULLWIREORNVLONPULLSTRINGINALL EMPTVCONDWTS. F. SECUREALLRACEWAVSTOTHEBWLDINGSTRUCTUREINARIGID AND SECURE MANNER, USING FASTENERS SUCH AS "CADDV CLIPS" OR Epl1AL. G. FLASH AND COUNTERFLASH ALL RACEWAVS W HICH PENETRATE THE ROOF OR USE PITCH POCKETS. INSURE THAT PENETRATIONS ARE COMPLETELV WEATHERPROOF. ALL RACEWAV SVSTEMS EXPOSED TO THEWEATHERSHALLBEWEATHERPROOF. PRIORAPPROVALBV LANDLORD IS REpl11RED TO ADD ADDITIONAL Epl11PMENT LOADS TO STRUCTURE OR TO MAKE HOLES M EXISTING ROOF. NOTIFV LANDLORD'S ROOFMG CONTRACTOR AT LEAST 12 HOURS PRIOR TO ANV REpUIRED ROOF WORK. i i ELECTRICAL SPECIFICATIONS GENERAL CON�ITIONS: A. THE REpUIREMENTS AS SET FORTH UN�ER GENERAL CON�ITIONS, INSTRUCTIONS TO BIDDERS AND GENERAL REpUIREMENTS ARE A PART OF THIS CONTRACT. B. BIDSSHALLBEBASEDONACOMPLETEIFULLSETOFDRAWINGS. G CONTRACTORMUSTREADTHEENTIRESPEQFICATIONSCOVERING OTHER BRANCHES OF WORK AN� IS RESPONSIBLE FOR COORDINATION OF THE WORK WITH WORK PERFORMED BV OTHERTRA�ES. SCOPE OF WORK: A. CONTRACTOR SHALL VISIT SITE PRIOR TO BIDDING. BIDS SHALL SERVE AS EVIDENCE OF KNOW LEDGE OF EXISTMG CONDITIONS. ALL REpUIREMENTS MCLUDING MODIFICATIONS WHICH ARE REQUIRE� TO MEET THE INTENT OF THE �RAWMGS AN� SPEQFICATIONS ARE TO BE OBTAMED BV ELECTRICAL CONTRACTOR PRIORTOANDINCLUDEDINBIDPRICE FlELDVERIFVALL EXISTING ELECTRICAL AND TELEPHONE EpUIPMENT, LOCATIONS, CONDITIONS ETG FAILURE TO VISITTHE SITE SHALL NOT RELIEVE THE CONTRACTOR FROM ANV RESPONSIBILITV IN THE PERFORMANCE OF THE ELECTRICAL WORK. B. FURNISHALLLABOR,MATERIALS,TESTING,EpUIPMENT, INCI�ENTALS AN� TOOLS TO PERFORM ELECTRICAL WORK SHOWN, NOTED OR SCHEDULED FOR A COMPLETE AND FINISHED INSTALLATION. 1. MATERIALS, PRODUCTS AND E�UIPMENT, INCLUDING ALL COMPONENTS THEREOF, SHALL BE NEW AND AS Sl1CH APPEAR ON THE UNDERWRITERS LABORATORIES LIST OF APPROVED ITEMS AN� SHALL BE SIZE� IN CONFORMITV WITH REQUIREMENTS OF THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND OTHER APPLICABLE CO�ES, WHICHEVER ARE MORE STRMGENT. C. THE WORK IS TO BE IN ACCORDANCE WITH THE LATEST EDITION OF THE NEC/CEC AND ALL APPLICABLE FEDERAL, STATE AND LOCAL CODES. D. INC W DE ANV LABOR AND MATERIALS NOT SPECIFICALLV MENTIONED, BUT NECESSARV TO PROVIDE ACOMPLETE AND FULLV OPERATIVE ELECTRICAL SVSTEMS. PERMITS: A. SECURE AND PAV FOR ALL REQUIRED PERMITS, FEES, ASSESMENTS AND INSPECTION CERTIFICATES THAT RELATE TO THE ELECTRICAL CONTRHCT. B. Fl1RNISHAPPROVEDCERTIFICATEOFFINALINSPECTION,ANDTl1RN OVER TO OWNER AT COMPLETION OF PROJECT. DRAW INGS AND SPECIFICATIONS: A. THIS ELECTRICAL PLANS ARE DIAGRAMMATIC, NOT SHOWMG EVERV ITEM M EXACT LOCATION OR DETAIL. MEASUREMENTS AND LOCATIONS M115T BE FIELD VERIFIED AND COORDINATED W ITH ARCHITECTURAL, PLUMBING, HVAC, FlRE PROTECTION, FlREALARM, STRUCTURAL, AN� OTHER BU IL�MG �RAW MGS. SHOP DRAW INGS: A. SUBMIT ELECTRONIC COPV OF MATERIAL LISTS AND SHOP DRAWINGS FOR MAJOR Ep WPMENT TO THE OWNER'S CONSTRl1CTION MANAGER FOR APPROVAL PRIOR TO ORDERING EDUIPMENT. CONTRACTOR SHALL Sl1BMIT SHOP DRAW MGS EARLV ENOl1GH IN PROJECT TO ALLOW AMPLE TIME FOR OWNER'S REVIEW WITHOUT CAUSING TIME DELAVS OR CONFLICTS IN THE JOB PROGRESS. SUBMITTALS SHALL BE IN ACCORDANCE WITH GENERAL CONDITIONS AND THE MANUFACTURERS LISTED ON THE DRAWINGS AND SHALL BEAR THE STAMP OF THE CONTRACTOR SHOWING THAT HE HAS REVIEWED AND APPROVED THEM AND THAT THEV ARE IN CONFORMANCE WITH THE CONTRACT DRAW MGS LACK OF Sl1CH CONTRACTOR'S APPROVAL W ILL BE CAUSE FOR REJECTION WITHOUT REVIEW BV THE OWNER. B. WHERE TRHDE NAMES, BRANDS OF MANUFACTURERS OF EpUIPMENT OR MATERIALS ARE SHOWN ON THE �RAWMGS OR SPECIFICATIONS THE EXACT EpUIPMENT SHALL BE USED ON THE PROJECT. THE USE OF ANV UNAUTHORIZED EQUIPMENT SHALL BE SUBJECT TO REMOVAL/REPLACEMENT AT THE REpUEST OF THE OWNER'S CONSTRUCTION MANAGER (AT THE ELECTRICAL CONTRACTORS EXPENSE). CONDUITS: A. CONDUIT SHALL BE STANDARD STEEL RIGID, IMC OR EMT (THIN WALL) ACCORDING TO LOCAL CODE AND LANDLORD REpl11REMENTS. CONDUIT SHALL BE CONCEALED M FlNISHED AREAS, EXCEPT AS OTHERWISEAPPROVEDBVARCHITECT. EMTCONNECTIONSSHALLBE COMPRESSION OR SET SCREW TVPE. B. FLE%BLE CONDl11T OR TVPE MC CABLE MAV BE 11SED FOR FINAL CONNECTIONS TO LIGHT FIXTURES, MOTORS AN� VIBRATMG EpUIPMENT; AND WHERE 50 USED TO BE GROUNDED WITH ASEPARATE FULL SIZED GREEN GROUNDING CONDUCTOR. IN ACCESSIBLE CEILING WHERE A PIPE AND WIRE CONDUIT SVSTEM MUST BE USED, FINAL TVPE MC/FLEX CONNECTIONS SHALL BE LIMITED TO 6'-0" W LENGTH. IN DRVWALL OR PLASTER CEILWGS CONTRACTOR MAV INSTALL MC CABLE FOR CIRCUIT CONN ECTIONS AND THE HOMERUN TO THE GUTTER AT THE DISTRIBUTION EpUIPMENT OR TO AN INTERMEDIATE JUNCTION BOX LOCATED ABOVE AN ACCESSIBLE CEILING TO AVOID THE NEED FOR ACCESS PANELS WITHM THE PLASTER CEILWG. FLEXBLE CONDWT OR TVPE MC CABLE MAV NOT BE 11SED BEHIN� THE PERIMETER WALL LINEAR FIXTURES FOR CONNECTIONS FROM JUNCTION BOX TO JUNCTION BOX. 1. MINIMUM SIZES OF CONDUITS SHALL BE 3/4" FOR STANDARD CONDWT, AND VP' FOR FLEX CONDWT ( VP' STANDARD CONDUIT AND 3/8" MC CABLE MAV BE USED AS SPEQFlED ABOVE, IF ACCEPTABLE WITH LANDLORD AND LOCAL CODES, ELECTRICAL CONTRACTOR SHALL FlELD COORDINATE WITH LANDLORD & INSPECTION AGENCIES PRIOR TO INSTALLATION). ELECTRIC METALLIC TUBING (EMT) SHALL BE GALVANIZED OR ELECTRO-GALVANIZED. FlTTINGS SHALL BE SET SCREW OR COMPRESSION TVPE, FITTING SHALL BEAS MANl1FACTl1RED BV REGEL, STEEL QTV, RACO, T 8 B, EFCOR OR WUAL EMT SHALL BE 115ED FOR FEEDERS AND BRANCH CIRC W TS Rl1N ABOVE SUSPENDED CEILINGS OR CONCEALED IN INTERIOR PARTITIONS. 2. PAINTMG OF ELECTRICAL CONDUITS, ETC., IF RWUIRED, WILL BE BV GENERAL CONTRACTOR. C. THE USE OF ROMEX OR BX IS NOT PERMITTED. D. MAXIMl1M CONDl11T HANGER SPACMG SHALL BE 8'-0" FOR 3/4" THRU 1 il4" AND 10'-0" FOR 1 il2" THRU 4" CONDUITS. DO NOT SUPPORT CON�UIT FROM THE CEILWG SVSTEM. RELEASED FOR CONSTRl1CTI0N Su6jec� �o compliance with all regula�ions of Sla�e antl Local Codes City of Carmel �i `��¢m�' lamn�Ml1 � onrE: 01 /16/20 WIRE'. A. WIRE SHALL BE SMGLE CONDUCTOR COPPER WITH 600 VOLT INSULATION. MINIMUMWIRESIZESHALLBE#12AWG,ALLWIRE AN� CABLE SHALL BE NEW AN� SHALL BE BROUGHT TO THE SITE IN UNBROKEN PACKAGES. ALL WIRING OF ANV TVPE SHALL BE IN CONDUIT. NOSTRANDEDWIREALLOWEDFORk10ANDk12AWG SIZES. QNCREASECONDUCTORBVONESIZEFOREVERV150' INCREMENT OF DISTANCE FROM THE PANEL BOARD FOR 120 VOLT CIRCl11TS.) 1. GENERAL WIRMG SHALL BE THW OR THHN. (ALUMINUM CONDUCTORSARENOTPERMITTED.) B. WIRE CONNECTORS SHALL BE EQUAL TO SCOTCHLOCK FOR#BAND SMALLER, AND EpUAL TO T& B"LOCK-TITE" FOR #6 AND LARGER. C. THE 11SE OF SHARED NEl1TRALS IS ACCEPTABLE FOR LIGHTING AND RECEPTACLE CIRCUITS PROVIDED THAT HANDLE TIES OR MULTIPLE POLE CIRCl11T BREAKERS ARE 115ED PER NEC ARTICLE 200. ALL OTHER Epl11PMENT RWUIRING A NEUTRAL CONDUCTOR SHALL HAVE A DEDICATED FULL SIZE NEUTRAL. D. ALLWIRMGTOBECOLORCODEDASPoLLOWS: 120I208VOLTSVSTEM 2]]I480VOLTSVSTEM NEl1TRALWHITE NEUTRAL-WHITEWITHTRACERORGRAV PHASEAORLi-BLACK PHASEAORLi-BROWN PHASE B OR L2-RED PHASE B OR L2-ORANGE PHASE C OR L3-BLUE PHASE C OR L3-VELLOW GROUND-GREEN GROl1ND-GREEN WITH TRACER LIGHTING: A LIGHTING FIXTURES AND LAMPS SHALL BE FURNISHED AND INSTALLED AS SCHEDl1LEDONTHELIGHTINGFIXTl1RESCHEDl1LE. FWORESCENT FIXTURES SHALL HAVE HPF BALLASTS WITH EFFICIENCV FACTORS IN ACCORDANCE WITH LOCALLV ADOPTED ENERGV CODE. B. LIGHT FIXTl1RE5 SHALL BE Sl1PPORTED FROM THE BWLDMG STRUCTURAL VIAALL THREAD AND UNI-STRUT, AND NOT SUPPORTED BV CEILWG SVSTEM. WIRED GROUND SVSTEM: A FURNISHANDINSTALLACOMPLETEWIREDGROUNDMGSVSTEMPoR ELECTRICAL EpUIPMENT AND CIRC WTS AS SHOWN ON THE DRAWINGS AND DESCRIBED GENERALLV BELOW. B. ALL GROUNDING CONDUCTORS SHALL BE GREEN, WHERE EXPOSED IN PANEL, SWITCHBOARD, Ol1TLET, BOXES, ETC. C. ALL ENCLOSURES AN� NON-CURRENT CARRVMG METALS TO BE GROUNDED. CONDUIT SVSTEM TO BE ELECTRICALLV CONTINUOUS. ALL LOCK NUTS MUST CUT THROUGH ENAMELED OR PAINTED SURFACES ON ENCLOSURES. WHERE ENCLOSURES AND NON-CURRENT CARRVING METALS ARE ISOLATED FROM THE CONDUIT SVSTEM, USE BONDING Jl1MPERS WITH APPROVED CLAMPS. D. RUN A SEPARATE GROUNDMG CONDUCTOR IN EACH CONDUIT, #12 MINIMUM, OR AS SHOWN ON DRAWINGS. FOR PANEL FEEDERS BOND THE GROUN�WG CON�UCTOR TO THE CON�UIT, W HERE ENTERMG AN� LEAVINGTHECONDUIT. ALLGROUNDCLAMPSSHALLBEPENN- UNION OR W UAL, SIMILAR TO "GPL" TVPE CONDUIT GROUND BUSHINGS SHALL BE THOMAS & BETTS OR EpUAL, SIMILAR TO k3800 SERIES W ITH NVLON INSULATED THROAT. E ALL DEVICES SHALL BE BONDED TO THE CON DUIT SYSTEM. USE A BONDMG Jl1MPER BETWEEN THE Ol1TLET BOX AND THE DEVICE GROUNDINGTERMINAL. METAL-TO-METALCONTACTBETWEENTHE �EV ICE VOKE AN� THE OUTLET BOX IS NOT ACCEPTABLE AS A BON� FOREITHERSURFACEMOUNTEDBOXESORFLUSHTVPEBOXES. ALL JUNCTION BOXES, OUTLET BOXES AN� PULL BOXES SHALL BE BONDED TO THE CONDUIT SVSTEM. ALL FLEXBLE CONDUIT SHALL BE JUMPERED WITH A GROUND CONDUCTOR. W IRE DEVICES: A. COLOR OF WIRING DEVICES AND COVERPLATES SHALL BE SELECTED BV ARCHITECL (SEE PLAN NOTES FOR ADDITIONAL INFORMATION). 1. RECEPTAQESSHALLBE20AMP,3-WIREGROUNDINGTVPE EQUAL TO HUBBELL 5362. 2. SWITCHES SHALL BE 20 AMP SPECIFlCATION GRADE, RATED AT 120 OR 2]] VOLT, AS REpl11RED. 3. SPECIAL �EVICES SHALL BE ASPECIFICATION GRA�E. 4. EpUAL BV ARROW-HART, GENERAL ELECTRIQ BRVANT, PASS & SEVMOUR, OR SIERRA. PANELBOARDS AND SAFETV SWITCHES: A. PROVIDE BRANCH CIRCUIT PANELS WHICH SHALL BE OF THE BOLTED CIRCUIT BREAKER TVPE WITH SOLID COPPER BUSSING FULL SIZED NEl1TRAL, 25% GROl1ND Bl1SSING, OVERALL HINGED/LOCKABLE DOOR, AND TVPEWRITTEN DIRECTORV INSIDE DOOR. ALL SERVICE ENTRANCE EpUIPMENT SHALL BEAR THE MANUFACTURER'S LABEL WHICHSHALLSTATETHATTHEEpUIPMENTISRHTED FORSERVICE ENTRANCE APPLICATION IN ACCORDANCE WITH N E.C. #230-�0. LOAD BALANCEALL ELECTRICAL PHASES AT PANELS AND SWITCHBOARDS.TWOANDTHREEPOLEBREAKERSSHALLBECOMMON TRIPTVPE. WHENUSEDASSWITCHESIN120V.AND2]]V. LIGHTING CIRCUITS, FURNISH TVPE "SWD" BREAKERS IN ACCORDANCE WITH N.E.Q W240-83B. Spl1ARE D OR Epl1AL BV SIEMENS ITE, CURER-HAMMER, OR GENERAL ELECTRIC (OR APPROVEDEpUAL)_ B. PROVIDESAFETVANDDISCONNECTSWITCHES,FUSEDORNONFUSED, AS CALLE� FOR ON �RAW MGS AN� AS REQUIRE� BV CO�E (FUSES AS MANUFACTUREDBVBUSSMAN,CHASESHAWMUT,ECONOMVFUSECO.,OR LITRE FUSE CO. ARE ACCEPTABLE). DISCONNECT SW ITCHES THAT ARE INSTALLED AT AIR CONDITION W G Epl11PMENT, HEAT Pl1MPS, ETC SHALL BE FUSED IN ACCORDANCE WITH THE EpUIPMENT'S NAME PLATE REpUIREMENTS PER N.EC.440-21 & 1103B. SWITCHES SHALL BE HEAW DUTV, QUICK MAKE/DUICK BREAK TVPE, FUSIBLE OR NON-FUSIBLE, WEATHERPRW F AS INDICATED ON THE DRAW INGS, OR AS REpUIRED BV LOCAL CODES. LOAD AND HORSEPOWER RATED AS MANUFACTURED BV SOUARE D, SIEMENS ITE, CUTLER HAMMER, OR GENERAL ELECTRIC (OR APPROVED EpUAL). G MANUAL MOTOR STARTERS W ITH OVERLOAD PROTECTION MAV BE USED FOR FRACTIONAL HORSEPOWER MOTORS THAT DO NOT REpUIRE AUXILIARV CONTROL SINGLE PHASE STARTERS SHALL BE SOUARE � OR EQUAL THREE PHASE STARTERS SHALL BE PROVI�E� WITH OVERLOAD DEVICE M EACH PHASE MATCHEDTO MOTOR NAMEPLATE RATMG. MAGNETICMOTORSTARTERS(MINIMUMSIZE#1)SHALL BE USED FOR ALL SINGLE PHASE AND THREE PHASE MOTORS RATED ABOVE 1/2 HP OR THAT REQUIRE AUXILIARV CONTROL. PROVIDE CONTROL DEVICES(CONTACTS,TRANSFORMERS,ETC.)IN STARTERS AS REpUIRED FOR INTERLOCKS, COORDINATE WITH MECHANICAL AN�IORTEMPERATURECONTROLCONTRACTORS. COMBINATION STARTERS, WHEN USED, SHALL CONTAIN FUSIBLE SWITCHES. BOXES'. A. OUTLET BOXES AND COVERS SHALL BE GALVANRED, ONEPIECE PRESSE�STEELKNOCKOUT. B. JUNCTION, PULL BOXES AND COVERS SHALL BE GALVANIZED STEEL, CODE GAl1GE SIZE. C. INSTALL BOXES RIGIDLV ON B W LDMG STRl1CTl1RE AND Sl1PPORT INDEPENDENTLV OF THE CONDUIT SVSTEM. ALSO PROVIDE SUITABLEIPROPER BOX EXTENSIONS TO EXTEND BOXES TO FINISHED FACES OF WALLS ETG ALL OURET BOXES TO HAVE SUITABLE BLOCKMG BEHIN� THEM TO MINIMIZE THE �EFLECTION THAT OCCURS WHEN PWGGING/UNPWGGING INTO THESE DEVICES. D. WHEREA299VOLTLIGHTSWITCHISGANGEDWITHA120VOLT RECEPTAQE PROVIDE A SUITABLE DNIDER OR SEPARATE JUNCTION BOXES IN ACCORDANCE W ITH NEC AND LOCAL CODES. SERVICES'. A ELECTRICALCONTRACTORSHALLPROVIDETEMPORARYSERVICEFROM LANDLORD'S DESIGNATED LOCATION AND PROVIDE LIGHTMG, POWER AND WIRING AS REpUIRED TO FAQLITATE APPLICABLE TEMPORARV NEEDS, AND FURNISH EXTENSION CORDS. ANV TEMPORARV WIRING, FUSES, ETC., SHALL BE REMOVED UPON COMPLETIONOFTHEPROJECT. PROVIDEGROUNDFAULT PROTECTION AS REpl11RED BV N.E.C. AND LOCAL CODES. B. PROVIDE ELECTRICAL SERVICEAS SHOWN ON THE DRAWINGS, FlELD VERIFV EXACT REQUIREMENTS PRIOR TO BI�S. ALL WORK NOT SPEQFICALLV NOTED AS BEING BV THE LANDLORD OR POWER COMPANV SHALL BE PROVIDED BV THE ELECTRICAL CONTRACTOR. CLOSELV COORDINATE ENTIRE INSTALLATION WITH LANDLORDAND POWERCOMPANVASREQUIRED. (PROVIDEEQUIPMENTTHATIS COMPATBLE W ITH AVAILABLE FAU LT CURRENT LEVELS, PROVIDE "CABLE LIMITERS" IF NECESSARV FOR SVSTEM COORDINATION). FIELD VERIFV EXACT TVPE, SIZE, LOCATION, REQUIREMENTQ ETG OF EXISTING POWER AND TELEPHONE FAQLITIES PRIOR TO BI��WG PROJECT. C. MAKE PROVISIONS FOR NEW TELEPHONE SERVICE AS REQUIRED,AND AS INDICATED ON THE DRHWINGS. D. CONDUIT SVSTEM FOR TELEPHONE DISTRIBUTION WITHIN TENANT'S PREMISES SHALL BE PROVIDED AS RE�UIRED FOR A COMPLETE TELEPHONE SVSTEM. Ol1TLET BOXES SHALL BE 4" SOl1ARE MINIMUM WITH SINGLE DEVICE COVERAND TELEPHONE PLATE. CLOSELV FIELD COORDINATE WITH TENANTS CONSTRl1CTION MANAGER TO AVOID CONFLICTS. STEP-DOWN TRANSFORMER QF APPLIGABLE) A. PROVIDEDRV-TVPETRANSFORMERASMANUFACTUREDBVSOUARE"D", HEAW Dl1TV, ACME, GENERAL ELECTRIQ SIEMENS ITE OR OTHER EQUIVALENT MANUFACTURERS, OF THE ENCLOSED VENTILATED TVPE WITH KVA AND VOLTAGE RATINGS AS CALLED FOR ON THE DRAW INGS WITH COILS DESIGN ED FOR 150 DEGREE C RISE ABOVE A 40 DEGREE C AMBIENT W ITH 100% OF RATED LOAD CONNECTED TO THE SECONDARV, CLASS 220 DEGREE C INSl1LATION AND A MINIMl1M OF SIX STANDARD Fl1LL CAPACITV TAPS (TWO ABOVE AND FOUR BELOW NORMAL). SOUND LEVELIDECIBELS SHALL BE IN ACCORDANCE WITH "NEMA" STANDARDS, AND INSTALLATION SHALL INCLUDE "KORFOUND" OR WUAL VIBRATION-DAMPENING MOUNTS AND REXIBLE STEEL CONDUIT FOR PRIMARV AND SECONDARV CONNECTIONS TO MINIMIZE SOl1NDTRANSMISSION. MOl1NTTRANSFORMERONSEPARATEVIBRATION ISOLATORS. THESE ARE ADDITIONAL VIBRATION ISOLATORS AND ARE USED IN CONJUNCTION WITH ANV INTEGRAL FACTORV INSTALLED VIBRATION ISOLATORS. LIGHTING CONTACTOR AND TIMER SW ITCHES: A. CONTACTORS FOR CONTROL OF LIGHTING AND SIGNS SHALL BE SOUARE "D", CLASS 8903, TVPE "C', ELECTRICALLV HELD. EpWVALENT PRODl1CTS BV OTHERMANUFACTURERSAREPERMITTE�. B. ELECTRONICDIGITALTIMESWITCHESSHALLBEUSEDFORCONTROLOF SHOW WINDOW LIGHTING SIGNS ANDIFRE�UIRED/DESIREDOTHER LIGHTING. THEELECTRONICDIGITALTIMERSHALLBEATORKMODEL DWZ100B OR EpUNALENT WITH A]-DAV FORMAT, 365 DAV ADVANCED HOLIDAV SCHEDl1LE, CAPABLE OF DIFFERENT SETTMGS EACH DAV OF THE W EEK, AN � HAV E AN ASTRONOM IC FEATU RE. INSTALLATION'. A. ALL ELECTRIC WORK SHALL BE INSTALLED SO AS TO BE READILV ACCESSIBLE FOR OPERATMG, SERVICW G, MAINTAINMG AN� REPAIRING. HANGERSSHALLINCLUDEALLMISCELLANEOUSSTEEL SUCH AS CHANNELS, RODS, ETC., NECESSARV FOR THE INSTALLATION OF WORK AND SHALL BE FASTENED TO BWLDING STEEL, CONCRETE OR MASONRV, BUT NOT PIPING OR DUCTWORK. ALL CONDl11T SHALL BE CONCEALED WHEREVER POSSIBLE. EXPOSED CONDUITS SHALL BE M STRAIGHT LMES PARALLEL WITH OR AT RIGHT ANGLES TO COLUMN LINES OR BEAMS AND SEPARATED AT LEAST 3 MCHES FROM WATER LMES WHEREVER THEV RUN ALONGSI�E OR ACROSS SUCH LINES. ALL CON�UCTORS SHALL BE IN CONDUIT, DUCTS OR OTHER CODEAPPROVED RACEWAVS. B. ALL LME AND LOW VOLTAGE POWER AND CONTROL WIRING (EXCEPT HVAC LOW VOLTAGE W IRWG) INCLUDMG CONNECTIONS TO MOTORS, DAMPERS, INTERLOCKING, ETG, SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR (ALL LINE VOLTAGE WIRMG, CON�UIT, AND FINAL CONNECTIONS FROM THE POWER SOURCE THRU THE STARTER/DISCONNECT ETC. TO THE MOTOR OR WUIPMENT IS THE RESPONSIBILITV OR THE ELECTRICAL CONTRACTOR. ALL HVAC RELATED LOW VOLTAGE CONTROL WIRING, CONDUITAND FlNAL CONNECTIONS IS THE RESPONSIBILITV OF THE MECHANICAL/TEMPERATURECONTROLCONTRACTOR,UNLESS OTHERWISE NOTED ON THE PLANS). G THEELECTRICALCONTRACTORSHALL�OALLCUTTMG,CHASWGOR CHANNELING AND PATCHING REpUIRED FOR ANV WORK UNDER THE ELECTRICAL DIVISION, ANV CUTTING SHALL HAVE PRIORAPPROVAL OFTHELANDLORD. SLEEVESSHALLEXTENDATLEASTTWO(Y') INCHES ABOVE FINISHED FLOOR AND ALL SLEEVES, OPENINGS, ETC., THROl1GH FIRE RATED WALLS AND FLOORS SHALL BE FIRE SEALED WITH CALQUM SILICATE, SILICONE "RTV" FOAM, "3M" FIRE RATED SEALANTS OR Epl1AL BV HILTI AFTER CONDl11TICABLES INSTALLATION SO AS TO RETAIN THE FIRE RATING. D. THE ELECTRICAL CONTRACTORS, INSOFARAS THE WORK IS CONCERNED, SHALL AT ALL TIMES KEEP THE PREMISES IN A NEAT AND ORDERLV CONDITION AND, AT THE COMPLETION OF THE WORK, SHALL PROPERLV QEAN UP AND CART AWAV ANV DEBRIS AND EXCESS MATERIAL. E. THE FOLLOWMG EpUIPMENT SHALL BE IDENTIFIED WITH ENGRAVED BAKELITE NAMEPLATES AS TO NAME ANDIOR FUNCTION; �ISTRIBUTION PANELS, LIGHTMG PANELS, MOTOR STARTERS AN� DISCONNECT SWITCHES. NAMEPLATES TO BE APPROXIMATELV 1"X 2" IN SIZE AND BE FASTENED WITH POP RIVETS OR SCREWS. F. THE LOCATION OF OURETS AND EpUIPMENT SHOWN ON THE �RAW MGS ARE APPROXIMATE AN � THE ARCHITECTITENANT CONSTRUCTION MANAGER SHALL HAVE THE RIGHT TO RELOCATE ANV OURETS OR FlXTURES BEFORE THEV ARE INSTALLED WITHOUT ADDITIONAL COST. G. ELECTRICAL CONTRACTOR SHALL RECORD ALL FIELD CHANGES IN THE WORKAS THE JOB PROGRESSES, AND TURN THIS "AS BUILT" INFORMATION OVER TO THE OWNER AT THE COMPLETION OF THE PROJECT. H. ELECTRICAL CONTRACTOR SHALL PROTECT ALL FIXTl1RES/Epl11PMENT AGAINST DAMAGE FROM LEAKS, ABUSE, ETC., AND PAV COST OF REPAIR OR REPLACEMENT OF FIXTURES OR EpUIPMENT MADE NECESSARV BV FAILURE TO PROVIDE SUITABLE SAFEGUARDS OR PROTECTION. I. ELECTRICALCONTRACTORSHALLMAKEALLFINALELECTRICAL CONNECTIONS AS REpUIRED FOR A COMPLETE AND OPERATING SVSTEM. AFTER ALL EQUIPMENT HAS BEEN INSPECTED AND APPROVED, THOROUGHLV CLEAN ALL EpUIPMENT PROVIDED UNDER THIS WORK JUST PRIOR TO COMPLETION OF PROJECT. J. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ANV/ALL NECESSARV ELECTRICAL DEMOLITION WORK THAT IS REpl11REDT0 FAQLITATE THE NEW INSTALLATION, FlELD COORDINATE PRIOR TO BIDS. REMOVE AND/OR MODIFV EQUIPMENT, ETC. AS REQUIRED FOR A COMPLETE INSTALLATION. ANV EpUIPMENT OR DEVICE REMAINING IN USE AFTER PART OF THE EQUIPMENT OR DEVICES HAVE BEEN REMOVEDARE TO BE RECONNECTED TO EXISTING OR NEW CIRCUITSANDLEFTINWORKINGORDER FEEDERSTOPANELSAND WIRING TO OTHER EOWPMENT TO BE ROl1TED CONCEALED IN FlNISHEDAREAS. COORDINATEANV DISRUPTION OF ELECTRICAL OR TELEPHONE SERVICES WITH LANDLORD AND TENANT CONSTRUCTION MANAGER TO AVOID CONFLICTS. GUARANTEE: A. MATERIALS, E�UIPMENTAND INSTALLATION SHALL BE GUARANTEED FOR A PERIOD OF ON E(1) V EAR FROM DATE OF ACCEPTANCE. DEFECTS WHICH APPEAR DURING THAT PERIOD SHALL BE CORRECTED AT THE ELECTRICAL CONTRACTOR'S EXPENSE. B. FOR THE SAME PERIOD, ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FORANV DAMAGE TO PREMISES CAUSED BV DEFECTS IN WORKMANSHIP OR IN THE WORK OR EQUIPMENT FURNISHED ANDIOR INSTALLED BV THE ELECTRICAL CONTRACTOR. FlNALLV'. A. IT IS THE INTENT THAT THE FOREGOING WORK SHALL BE COMPLETE IN EVERV RESPECTANDTHAT ANV MATERIAL OR WORK NOT SPEQFICALLV MENTIONED OR SHOWN ON THE DRAWINGS, BUT NECESSARV TO FULLV COMPLETE THE WORK SHALL BE FURNISHE�. i TESTING (AS REpUIRED PER APPLICABLE ENERGV CODE): A LIGHTING SVSTEMS FUNCTIONAL TESTING REpUIREMENTS FOR STORES COMPLV W G W ITH ASHRAE 90A-2010 t LIGHTW G CONTROL �EVICES AN� CONTROL SVSTEMS SHALL BE TESTED TO ENSURE THAT CONTROL HARDWARE AND SOFTWARE ARE CALIBRHTED ADJUSTED PROGRAMMED AND IN PROPER WORKING CONDITION IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS AND MANl1FACTl1RER'S INSTALLATION INSTRl1CTIONS. WHEN OCCl1PANT SENSORS TIMESWITCHES PROGRAMMABLESCHE�ULECONTROLS OR PHOTOSENSORS ARE INSTALLED AT A MINIMUM THE FOLLOWING PROCEDURES SHALL BE PERFORMED: a. CONFIRM THAT THE PLACEMENT, SENSITNITV AND TIME-OUT ADJl1STMENTS FOR OCCl1PANT SENSORS VIELD ACCEPTABLE PERFORMANCE, LIGHTS TURN OFF ONLV AFTER SPACE IS VACATE� AND DO NOT TURN ON UNLE55 SPACE IS OCCUPIED. b. CONFIRMTHATTHETIMESWITCHESANDPROGRAMMABLESCHEDULE CONTROLS ARE PROGRAMMED TO TURN THE LIGHTS OFF. a CONFIRM THAT PHOTOSENSOR CONTROLS REDUCE ELECTRIC LIGHT LEVELS BASE� ON THE AMOUNT OF USABLE �AVLIGHT IN THE SPACE AS SPECIFlED. THE INDNIDUAL�S) RESPONSIBLE FOR THE FUNCTIONAL TESTING SHALL NOT BE DIRECTLV INVOLVED IN EITHER THE DESIGN OR CONSTRUCTION OF THE PROJECTAND SHALL PROVIDE DOCl1MENTATION CERTIFVMG THAT THE INSTALLED LIGHTMG CONTROLS MEET OR EXCEED ALL DOCUMENTED PERFORMANCE CRITERIA. B. LIGHTING SVSTEMS FUNCTIONAL TESTING REpUIREMENTS FOR STORES COMPLVING WITH ASHRAE 90.b2013 L LIGHT W G CONTROL �EVICES AND CONTROL SVSTEMS SHALL BE TESTE� TO ENSURE THAT CONTROL HAR�WARE AN� SOFTWARE ARE CALIBRHTED, ADJUSTED, PROGRAMMED, AND IN PROPER WORKING CONDITION IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS AND MANUFACTURER'S INSTALLATION INSTRUCTIONS. WHEN OCCUPANT SENSORS, TIME SWITCHES, PROGRAMMABLE SCHEDl1LE CONTROLS, OR PHOTOSENSORS ARE INSTALLE�, AT A MINIMUM, THE FOLLOW WG PROCEDURES SHALL BE PERFORMED: a. OCCUPANTSENSORS 1. CERTIFV THAT THE SENSOR HAS BEEN LOCATED AND AIMED IN ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS. 2 FOR PROJECTS WITH UP TO SEVEN (]) OCCUPANCV SENSORS, ALL OCCUPANCV SENSORS SHALL BE TESTED. 3. FOR PROJECTS WITH MORE THAN SEVEN Q)OCCUPANCV SENSORS, TESTING SHALL BE DONE FOR EACH UNIpUE COMBINATION OF SENSOR TYPE AND SPACE GEOMETRV. (a)FOR EACH SENSOR TO BE TESTE�, VERIFV THE FOLLOW ING'. (1) STATUSINDICATOR(ASAPPLIGABLE)OPERATES CORRECTLV (2) CONTROLLEDLIGHTSTURNOFFORDOWNTOTHE PERMITTE� LEVEL WITHIN THE REQUIRE� TIME (3) FORAUTO-ON OCCUPANT SENSORS, THE LIGHTS TURN ON TO THE PERMITTED LEVEL WHEN SOMEONE ENTERS THE SPACE (4) FOR MANUALON SENSORQ THE LIGHTS TURN ON ONLV WHEN MANUALLV ACTIVATED (5) THE LIGHTS ARE NOT INCORRECTLV TURNED ON BV MOVEMENT IN NEARBV AREAS OR BV HVAC OPERATION b. Al1TOMATICTIMESWITCHES 1. CONFIRMTHATTHEAUTOMATICTIME-SWITCHCONTROLIS PROGRAMMED WITH APPROPRIATE WEEKDAV, WEEKEND,AND HOLIDAY (AS APPLICABLE) SCHEDULES. 2. DOCl1MENTFORTHEOWNERAl1TOMATICTIME-SWITCH PROGRAMMMG, INCW DMG WEEKDAV, WEEKEND, AND HOLIDAV SCHEDULES, AS WELL AS ALL SETUP AND REFERENCE PROGRAM SETTINGS. 3. VERIFV THAT CORRECT TIMEAND DATE ARE PROPERLV SET M THE TIME SW ITCH. 4. VERIFV THATANV BATTERV BACKl1P (AS APPLICABLE) IS INSTALLED AND ENERGIZED. 5. VERIFVTHATTHEOVERRIDETIMELIMITISSETTONOMORETHAN TWO (2) HOURS. 6. SIMULATEOCCUPIEDCONDITION.VERIFVANDDOCUMENTTHE FOLLOW MG: (a)ALL LIGHTS CAN BE TURNED ON AND OFF BV THEIR RESPECTNEAREACONTROLSWITCH. (b)THE SWITCH ONLV OPERATES LIGHTING M THE ENCLOSED SPACE IN WHICH THE SWITCH IS LOCATED. �. SIMULATEUNOCCUPIE�CON�ITION.VERIFVAN��OCUMENTTHE FOLLOW MG: (a)ALL NONEXEMPT LIGHTING TURNS OFF (b)MANUAL OVERRIDE SWITCH ALLOWS ONLV THE LIGHTS IN THE ENCLOSED SPACE W HERE THE OVERRIDE SW ITCH IS LOCATED TO TURN ON OR REMAIN ON UNTIL THE NEXT SCHE�ULE�SHUTOFFOCCURS c. DAYLIGHT CONTROLS 1. ALL CONTROL DEVICES(PHOTOCONTROLS)HAVE BEEN PROPERLV LOCATED, FIELD-CALIBRATED, AND SET FOR APPROPRIATE SETPOINTS AND THRESHOLD LIGHT LEVELS. 2. DAVLIGHT CONTROLLED LIGHTING LOADS ADJUST TO APPROPRIATE LIGHT LEVELS IN RESPONSE TO AVAILABLE DAVLIGHT. 3. THE LOCATION WHERE CALIBRATION ADJUSTMENTS ARE MADE IS READILV ACCESSIBLE ONLV TO AUTHORIZED PERSONNEL. THE INDNIDUAL(5) RESPONSIBLE FOR THE FUNCTIONAL TESTING SHALL NOT BE DIRECTLV INVOLVED M EITHER THE DESIGN OR CONSTRUCTION OF THE PROJECTAND SHALL PROVIDE DOCUMENTATION CERTIFVING THAT THE INSTALLED LIGHTMG CONTROLS MEET OR EXCEED ALL DOCUMENTED PERFORMANCE CRITERIA. I I I I i SEPHORA 525 MARKET STREET, 32ND FLOOR SAN FRANCISCO, CA 94105 Ber me er g Y _ / / 11 M-Engineering ]50 Brooksedge Blvd. Westervllle, Ohlo 43081 phone: 614.839.4639 lar: 6f4.8392222 www meigineering.us.com STAMP ��,4-19 ,...... ... GEA.M� • � ,... ... -. �T� ���srER��O� nissoasas STATE OF Q I DATE I ISSUEDESCRIPTION I BV I CHECK 10.01.19 I DESIGNDEVELOPMENT i1.0A]9 I ISSUE FOR PERMIT PROJECTLOCATION: CLAY TERRACE 14390 CLAY TERRACE BLVD SPACE D13 CARMEL, IN 46032 AREA: 4,129 SF SHEET TITLE: ELECTRICAL SPECIFICATIONS PROJECT N0. 19122 STORE N0. 1326 SCALE: AS NOTED DATE: 11.04.2019 DRAWN BY: NH REVIEWED BY: DFG SHEET N0. E-600 � �za�s(az��srza�e� �_