E LEAVEA#10AWGPULLWIREORNVLONPULLSTRINGINALL
EMPTVCONDWTS.
F. SECUREALLRACEWAVSTOTHEBWLDINGSTRUCTUREINARIGID
AND SECURE MANNER, USING FASTENERS SUCH AS "CADDV CLIPS"
OR Epl1AL.
G. FLASH AND COUNTERFLASH ALL RACEWAVS W HICH PENETRATE THE
ROOF OR USE PITCH POCKETS. INSURE THAT PENETRATIONS ARE
COMPLETELV WEATHERPROOF. ALL RACEWAV SVSTEMS EXPOSED TO
THEWEATHERSHALLBEWEATHERPROOF. PRIORAPPROVALBV
LANDLORD IS REpl11RED TO ADD ADDITIONAL Epl11PMENT LOADS TO
STRUCTURE OR TO MAKE HOLES M EXISTING ROOF. NOTIFV
LANDLORD'S ROOFMG CONTRACTOR AT LEAST 12 HOURS PRIOR TO
ANV REpUIRED ROOF WORK.
i
i
ELECTRICAL SPECIFICATIONS
GENERAL CON�ITIONS:
A. THE REpUIREMENTS AS SET FORTH UN�ER GENERAL CON�ITIONS,
INSTRUCTIONS TO BIDDERS AND GENERAL REpUIREMENTS ARE A
PART OF THIS CONTRACT.
B. BIDSSHALLBEBASEDONACOMPLETEIFULLSETOFDRAWINGS.
G CONTRACTORMUSTREADTHEENTIRESPEQFICATIONSCOVERING
OTHER BRANCHES OF WORK AN� IS RESPONSIBLE FOR
COORDINATION OF THE WORK WITH WORK PERFORMED BV
OTHERTRA�ES.
SCOPE OF WORK:
A. CONTRACTOR SHALL VISIT SITE PRIOR TO BIDDING. BIDS SHALL
SERVE AS EVIDENCE OF KNOW LEDGE OF EXISTMG CONDITIONS.
ALL REpUIREMENTS MCLUDING MODIFICATIONS WHICH ARE
REQUIRE� TO MEET THE INTENT OF THE �RAWMGS AN�
SPEQFICATIONS ARE TO BE OBTAMED BV ELECTRICAL CONTRACTOR
PRIORTOANDINCLUDEDINBIDPRICE FlELDVERIFVALL
EXISTING ELECTRICAL AND TELEPHONE EpUIPMENT, LOCATIONS,
CONDITIONS ETG FAILURE TO VISITTHE SITE SHALL NOT
RELIEVE THE CONTRACTOR FROM ANV RESPONSIBILITV IN THE
PERFORMANCE OF THE ELECTRICAL WORK.
B. FURNISHALLLABOR,MATERIALS,TESTING,EpUIPMENT,
INCI�ENTALS AN� TOOLS TO PERFORM ELECTRICAL WORK SHOWN,
NOTED OR SCHEDULED FOR A COMPLETE AND FINISHED
INSTALLATION.
1. MATERIALS, PRODUCTS AND E�UIPMENT, INCLUDING ALL
COMPONENTS THEREOF, SHALL BE NEW AND AS Sl1CH APPEAR ON
THE UNDERWRITERS LABORATORIES LIST OF APPROVED ITEMS
AN� SHALL BE SIZE� IN CONFORMITV WITH REQUIREMENTS OF
THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND
OTHER APPLICABLE CO�ES, WHICHEVER ARE MORE STRMGENT.
C. THE WORK IS TO BE IN ACCORDANCE WITH THE LATEST EDITION OF
THE NEC/CEC AND ALL APPLICABLE FEDERAL, STATE AND LOCAL CODES.
D. INC W DE ANV LABOR AND MATERIALS NOT SPECIFICALLV
MENTIONED, BUT NECESSARV TO PROVIDE ACOMPLETE AND FULLV
OPERATIVE ELECTRICAL SVSTEMS.
PERMITS:
A. SECURE AND PAV FOR ALL REQUIRED PERMITS, FEES, ASSESMENTS
AND INSPECTION CERTIFICATES THAT RELATE TO THE ELECTRICAL
CONTRHCT.
B. Fl1RNISHAPPROVEDCERTIFICATEOFFINALINSPECTION,ANDTl1RN
OVER TO OWNER AT COMPLETION OF PROJECT.
DRAW INGS AND SPECIFICATIONS:
A. THIS ELECTRICAL PLANS ARE DIAGRAMMATIC, NOT SHOWMG EVERV
ITEM M EXACT LOCATION OR DETAIL. MEASUREMENTS AND
LOCATIONS M115T BE FIELD VERIFIED AND COORDINATED W ITH
ARCHITECTURAL, PLUMBING, HVAC, FlRE PROTECTION, FlREALARM,
STRUCTURAL, AN� OTHER BU IL�MG �RAW MGS.
SHOP DRAW INGS:
A. SUBMIT ELECTRONIC COPV OF MATERIAL LISTS AND SHOP DRAWINGS FOR
MAJOR Ep WPMENT TO THE OWNER'S CONSTRl1CTION MANAGER FOR
APPROVAL PRIOR TO ORDERING EDUIPMENT. CONTRACTOR SHALL
Sl1BMIT SHOP DRAW MGS EARLV ENOl1GH IN PROJECT TO ALLOW
AMPLE TIME FOR OWNER'S REVIEW WITHOUT CAUSING TIME DELAVS
OR CONFLICTS IN THE JOB PROGRESS. SUBMITTALS SHALL BE IN
ACCORDANCE WITH GENERAL CONDITIONS AND THE MANUFACTURERS
LISTED ON THE DRAWINGS AND SHALL BEAR THE STAMP OF THE
CONTRACTOR SHOWING THAT HE HAS REVIEWED AND APPROVED THEM
AND THAT THEV ARE IN CONFORMANCE WITH THE CONTRACT
DRAW MGS LACK OF Sl1CH CONTRACTOR'S APPROVAL W ILL BE
CAUSE FOR REJECTION WITHOUT REVIEW BV THE OWNER.
B. WHERE TRHDE NAMES, BRANDS OF MANUFACTURERS OF EpUIPMENT OR
MATERIALS ARE SHOWN ON THE �RAWMGS OR SPECIFICATIONS THE
EXACT EpUIPMENT SHALL BE USED ON THE PROJECT. THE USE OF
ANV UNAUTHORIZED EQUIPMENT SHALL BE SUBJECT TO
REMOVAL/REPLACEMENT AT THE REpUEST OF THE OWNER'S
CONSTRUCTION MANAGER (AT THE ELECTRICAL CONTRACTORS
EXPENSE).
CONDUITS:
A. CONDUIT SHALL BE STANDARD STEEL RIGID, IMC OR EMT (THIN
WALL) ACCORDING TO LOCAL CODE AND LANDLORD REpl11REMENTS.
CONDUIT SHALL BE CONCEALED M FlNISHED AREAS, EXCEPT AS
OTHERWISEAPPROVEDBVARCHITECT. EMTCONNECTIONSSHALLBE
COMPRESSION OR SET SCREW TVPE.
B. FLE%BLE CONDl11T OR TVPE MC CABLE MAV BE 11SED FOR FINAL
CONNECTIONS TO LIGHT FIXTURES, MOTORS AN� VIBRATMG EpUIPMENT;
AND WHERE 50 USED TO BE GROUNDED WITH ASEPARATE FULL SIZED
GREEN GROUNDING CONDUCTOR. IN ACCESSIBLE CEILING WHERE A PIPE
AND WIRE CONDUIT SVSTEM MUST BE USED, FINAL TVPE MC/FLEX
CONNECTIONS SHALL BE LIMITED TO 6'-0" W LENGTH. IN DRVWALL OR
PLASTER CEILWGS CONTRACTOR MAV INSTALL MC CABLE FOR CIRCUIT
CONN ECTIONS AND THE HOMERUN TO THE GUTTER AT THE DISTRIBUTION
EpUIPMENT OR TO AN INTERMEDIATE JUNCTION BOX LOCATED ABOVE AN
ACCESSIBLE CEILING TO AVOID THE NEED FOR ACCESS PANELS WITHM THE
PLASTER CEILWG. FLEXBLE CONDWT OR TVPE MC CABLE MAV NOT BE 11SED
BEHIN� THE PERIMETER WALL LINEAR FIXTURES FOR CONNECTIONS FROM
JUNCTION BOX TO JUNCTION BOX.
1. MINIMUM SIZES OF CONDUITS SHALL BE 3/4" FOR STANDARD
CONDWT, AND VP' FOR FLEX CONDWT ( VP' STANDARD
CONDUIT AND 3/8" MC CABLE MAV BE USED AS SPEQFlED
ABOVE, IF ACCEPTABLE WITH LANDLORD AND LOCAL CODES,
ELECTRICAL CONTRACTOR SHALL FlELD COORDINATE WITH
LANDLORD & INSPECTION AGENCIES PRIOR TO INSTALLATION).
ELECTRIC METALLIC TUBING (EMT) SHALL BE GALVANIZED OR
ELECTRO-GALVANIZED. FlTTINGS SHALL BE SET SCREW OR
COMPRESSION TVPE, FITTING SHALL BEAS MANl1FACTl1RED BV
REGEL, STEEL QTV, RACO, T 8 B, EFCOR OR WUAL EMT
SHALL BE 115ED FOR FEEDERS AND BRANCH CIRC W TS Rl1N
ABOVE SUSPENDED CEILINGS OR CONCEALED IN INTERIOR
PARTITIONS.
2. PAINTMG OF ELECTRICAL CONDUITS, ETC., IF RWUIRED,
WILL BE BV GENERAL CONTRACTOR.
C. THE USE OF ROMEX OR BX IS NOT PERMITTED.
D. MAXIMl1M CONDl11T HANGER SPACMG SHALL BE 8'-0" FOR 3/4"
THRU 1 il4" AND 10'-0" FOR 1 il2" THRU 4" CONDUITS. DO
NOT SUPPORT CON�UIT FROM THE CEILWG SVSTEM.
RELEASED FOR CONSTRl1CTI0N
Su6jec� �o compliance with all regula�ions
of Sla�e antl Local Codes
City of Carmel
�i
`��¢m�' lamn�Ml1 �
onrE: 01 /16/20
WIRE'.
A. WIRE SHALL BE SMGLE CONDUCTOR COPPER WITH 600 VOLT
INSULATION. MINIMUMWIRESIZESHALLBE#12AWG,ALLWIRE
AN� CABLE SHALL BE NEW AN� SHALL BE BROUGHT TO THE SITE IN
UNBROKEN PACKAGES. ALL WIRING OF ANV TVPE SHALL BE IN
CONDUIT. NOSTRANDEDWIREALLOWEDFORk10ANDk12AWG
SIZES. QNCREASECONDUCTORBVONESIZEFOREVERV150'
INCREMENT OF DISTANCE FROM THE PANEL BOARD FOR 120 VOLT
CIRCl11TS.)
1. GENERAL WIRMG SHALL BE THW OR THHN. (ALUMINUM
CONDUCTORSARENOTPERMITTED.)
B. WIRE CONNECTORS SHALL BE EQUAL TO SCOTCHLOCK FOR#BAND
SMALLER, AND EpUAL TO T& B"LOCK-TITE" FOR #6 AND LARGER.
C. THE 11SE OF SHARED NEl1TRALS IS ACCEPTABLE FOR LIGHTING AND
RECEPTACLE CIRCUITS PROVIDED THAT HANDLE TIES OR MULTIPLE POLE
CIRCl11T BREAKERS ARE 115ED PER NEC ARTICLE 200. ALL OTHER Epl11PMENT
RWUIRING A NEUTRAL CONDUCTOR SHALL HAVE A DEDICATED FULL SIZE NEUTRAL.
D. ALLWIRMGTOBECOLORCODEDASPoLLOWS:
120I208VOLTSVSTEM 2]]I480VOLTSVSTEM
NEl1TRALWHITE NEUTRAL-WHITEWITHTRACERORGRAV
PHASEAORLi-BLACK PHASEAORLi-BROWN
PHASE B OR L2-RED PHASE B OR L2-ORANGE
PHASE C OR L3-BLUE PHASE C OR L3-VELLOW
GROUND-GREEN GROl1ND-GREEN WITH TRACER
LIGHTING:
A LIGHTING FIXTURES AND LAMPS SHALL BE FURNISHED AND INSTALLED AS
SCHEDl1LEDONTHELIGHTINGFIXTl1RESCHEDl1LE. FWORESCENT
FIXTURES SHALL HAVE HPF BALLASTS WITH EFFICIENCV FACTORS IN
ACCORDANCE WITH LOCALLV ADOPTED ENERGV CODE.
B. LIGHT FIXTl1RE5 SHALL BE Sl1PPORTED FROM THE BWLDMG
STRUCTURAL VIAALL THREAD AND UNI-STRUT, AND NOT SUPPORTED BV
CEILWG SVSTEM.
WIRED GROUND SVSTEM:
A FURNISHANDINSTALLACOMPLETEWIREDGROUNDMGSVSTEMPoR
ELECTRICAL EpUIPMENT AND CIRC WTS AS SHOWN ON THE DRAWINGS
AND DESCRIBED GENERALLV BELOW.
B. ALL GROUNDING CONDUCTORS SHALL BE GREEN, WHERE EXPOSED IN
PANEL, SWITCHBOARD, Ol1TLET, BOXES, ETC.
C. ALL ENCLOSURES AN� NON-CURRENT CARRVMG METALS TO BE
GROUNDED. CONDUIT SVSTEM TO BE ELECTRICALLV CONTINUOUS.
ALL LOCK NUTS MUST CUT THROUGH ENAMELED OR PAINTED
SURFACES ON ENCLOSURES. WHERE ENCLOSURES AND NON-CURRENT
CARRVING METALS ARE ISOLATED FROM THE CONDUIT SVSTEM, USE
BONDING Jl1MPERS WITH APPROVED CLAMPS.
D. RUN A SEPARATE GROUNDMG CONDUCTOR IN EACH CONDUIT, #12
MINIMUM, OR AS SHOWN ON DRAWINGS. FOR PANEL FEEDERS BOND
THE GROUN�WG CON�UCTOR TO THE CON�UIT, W HERE ENTERMG AN�
LEAVINGTHECONDUIT. ALLGROUNDCLAMPSSHALLBEPENN-
UNION OR W UAL, SIMILAR TO "GPL" TVPE CONDUIT GROUND
BUSHINGS SHALL BE THOMAS & BETTS OR EpUAL, SIMILAR TO
k3800 SERIES W ITH NVLON INSULATED THROAT.
E ALL DEVICES SHALL BE BONDED TO THE CON DUIT SYSTEM. USE A
BONDMG Jl1MPER BETWEEN THE Ol1TLET BOX AND THE DEVICE
GROUNDINGTERMINAL. METAL-TO-METALCONTACTBETWEENTHE
�EV ICE VOKE AN� THE OUTLET BOX IS NOT ACCEPTABLE AS A BON�
FOREITHERSURFACEMOUNTEDBOXESORFLUSHTVPEBOXES. ALL
JUNCTION BOXES, OUTLET BOXES AN� PULL BOXES SHALL BE
BONDED TO THE CONDUIT SVSTEM. ALL FLEXBLE CONDUIT SHALL
BE JUMPERED WITH A GROUND CONDUCTOR.
W IRE DEVICES:
A. COLOR OF WIRING DEVICES AND COVERPLATES SHALL BE SELECTED
BV ARCHITECL (SEE PLAN NOTES FOR ADDITIONAL
INFORMATION).
1. RECEPTAQESSHALLBE20AMP,3-WIREGROUNDINGTVPE
EQUAL TO HUBBELL 5362.
2. SWITCHES SHALL BE 20 AMP SPECIFlCATION GRADE, RATED AT
120 OR 2]] VOLT, AS REpl11RED.
3. SPECIAL �EVICES SHALL BE ASPECIFICATION GRA�E.
4. EpUAL BV ARROW-HART, GENERAL ELECTRIQ BRVANT, PASS &
SEVMOUR, OR SIERRA.
PANELBOARDS AND SAFETV SWITCHES:
A. PROVIDE BRANCH CIRCUIT PANELS WHICH SHALL BE OF THE BOLTED
CIRCUIT BREAKER TVPE WITH SOLID COPPER BUSSING FULL SIZED
NEl1TRAL, 25% GROl1ND Bl1SSING, OVERALL HINGED/LOCKABLE DOOR,
AND TVPEWRITTEN DIRECTORV INSIDE DOOR. ALL SERVICE
ENTRANCE EpUIPMENT SHALL BEAR THE MANUFACTURER'S LABEL
WHICHSHALLSTATETHATTHEEpUIPMENTISRHTED FORSERVICE
ENTRANCE APPLICATION IN ACCORDANCE WITH N E.C. #230-�0.
LOAD BALANCEALL ELECTRICAL PHASES AT PANELS AND
SWITCHBOARDS.TWOANDTHREEPOLEBREAKERSSHALLBECOMMON
TRIPTVPE. WHENUSEDASSWITCHESIN120V.AND2]]V.
LIGHTING CIRCUITS, FURNISH TVPE "SWD" BREAKERS IN
ACCORDANCE WITH N.E.Q W240-83B. Spl1ARE D OR Epl1AL BV
SIEMENS ITE, CURER-HAMMER, OR GENERAL ELECTRIC (OR
APPROVEDEpUAL)_
B. PROVIDESAFETVANDDISCONNECTSWITCHES,FUSEDORNONFUSED, AS
CALLE� FOR ON �RAW MGS AN� AS REQUIRE� BV CO�E (FUSES AS
MANUFACTUREDBVBUSSMAN,CHASESHAWMUT,ECONOMVFUSECO.,OR
LITRE FUSE CO. ARE ACCEPTABLE). DISCONNECT SW ITCHES THAT ARE
INSTALLED AT AIR CONDITION W G Epl11PMENT, HEAT Pl1MPS, ETC SHALL BE
FUSED IN ACCORDANCE WITH THE EpUIPMENT'S NAME PLATE REpUIREMENTS
PER N.EC.440-21 & 1103B. SWITCHES SHALL BE HEAW DUTV, QUICK
MAKE/DUICK BREAK TVPE, FUSIBLE OR NON-FUSIBLE, WEATHERPRW F AS
INDICATED ON THE DRAW INGS, OR AS REpUIRED BV LOCAL CODES. LOAD AND
HORSEPOWER RATED AS MANUFACTURED BV SOUARE D, SIEMENS ITE,
CUTLER HAMMER, OR GENERAL ELECTRIC (OR APPROVED EpUAL).
G MANUAL MOTOR STARTERS W ITH OVERLOAD PROTECTION MAV BE USED
FOR FRACTIONAL HORSEPOWER MOTORS THAT DO NOT REpUIRE
AUXILIARV CONTROL SINGLE PHASE STARTERS SHALL BE SOUARE
� OR EQUAL THREE PHASE STARTERS SHALL BE PROVI�E� WITH
OVERLOAD DEVICE M EACH PHASE MATCHEDTO MOTOR NAMEPLATE
RATMG. MAGNETICMOTORSTARTERS(MINIMUMSIZE#1)SHALL
BE USED FOR ALL SINGLE PHASE AND THREE PHASE MOTORS RATED
ABOVE 1/2 HP OR THAT REQUIRE AUXILIARV CONTROL. PROVIDE
CONTROL DEVICES(CONTACTS,TRANSFORMERS,ETC.)IN STARTERS
AS REpUIRED FOR INTERLOCKS, COORDINATE WITH MECHANICAL
AN�IORTEMPERATURECONTROLCONTRACTORS. COMBINATION
STARTERS, WHEN USED, SHALL CONTAIN FUSIBLE SWITCHES.
BOXES'.
A. OUTLET BOXES AND COVERS SHALL BE GALVANRED, ONEPIECE
PRESSE�STEELKNOCKOUT.
B. JUNCTION, PULL BOXES AND COVERS SHALL BE GALVANIZED STEEL,
CODE GAl1GE SIZE.
C. INSTALL BOXES RIGIDLV ON B W LDMG STRl1CTl1RE AND Sl1PPORT
INDEPENDENTLV OF THE CONDUIT SVSTEM. ALSO PROVIDE
SUITABLEIPROPER BOX EXTENSIONS TO EXTEND BOXES TO FINISHED
FACES OF WALLS ETG ALL OURET BOXES TO HAVE SUITABLE
BLOCKMG BEHIN� THEM TO MINIMIZE THE �EFLECTION THAT
OCCURS WHEN PWGGING/UNPWGGING INTO THESE DEVICES.
D. WHEREA299VOLTLIGHTSWITCHISGANGEDWITHA120VOLT
RECEPTAQE PROVIDE A SUITABLE DNIDER OR SEPARATE JUNCTION
BOXES IN ACCORDANCE W ITH NEC AND LOCAL CODES.
SERVICES'.
A ELECTRICALCONTRACTORSHALLPROVIDETEMPORARYSERVICEFROM
LANDLORD'S DESIGNATED LOCATION AND PROVIDE LIGHTMG, POWER
AND WIRING AS REpUIRED TO FAQLITATE APPLICABLE TEMPORARV
NEEDS, AND FURNISH EXTENSION CORDS. ANV TEMPORARV
WIRING, FUSES, ETC., SHALL BE REMOVED UPON
COMPLETIONOFTHEPROJECT. PROVIDEGROUNDFAULT
PROTECTION AS REpl11RED BV N.E.C. AND LOCAL CODES.
B. PROVIDE ELECTRICAL SERVICEAS SHOWN ON THE DRAWINGS, FlELD
VERIFV EXACT REQUIREMENTS PRIOR TO BI�S. ALL WORK NOT
SPEQFICALLV NOTED AS BEING BV THE LANDLORD OR POWER
COMPANV SHALL BE PROVIDED BV THE ELECTRICAL CONTRACTOR.
CLOSELV COORDINATE ENTIRE INSTALLATION WITH LANDLORDAND
POWERCOMPANVASREQUIRED. (PROVIDEEQUIPMENTTHATIS
COMPATBLE W ITH AVAILABLE FAU LT CURRENT LEVELS, PROVIDE
"CABLE LIMITERS" IF NECESSARV FOR SVSTEM COORDINATION).
FIELD VERIFV EXACT TVPE, SIZE, LOCATION, REQUIREMENTQ
ETG OF EXISTING POWER AND TELEPHONE FAQLITIES PRIOR TO
BI��WG PROJECT.
C. MAKE PROVISIONS FOR NEW TELEPHONE SERVICE AS REQUIRED,AND
AS INDICATED ON THE DRHWINGS.
D. CONDUIT SVSTEM FOR TELEPHONE DISTRIBUTION WITHIN TENANT'S
PREMISES SHALL BE PROVIDED AS RE�UIRED FOR A COMPLETE
TELEPHONE SVSTEM. Ol1TLET BOXES SHALL BE 4" SOl1ARE
MINIMUM WITH SINGLE DEVICE COVERAND TELEPHONE PLATE.
CLOSELV FIELD COORDINATE WITH TENANTS CONSTRl1CTION MANAGER
TO AVOID CONFLICTS.
STEP-DOWN TRANSFORMER QF APPLIGABLE)
A. PROVIDEDRV-TVPETRANSFORMERASMANUFACTUREDBVSOUARE"D",
HEAW Dl1TV, ACME, GENERAL ELECTRIQ SIEMENS ITE OR OTHER
EQUIVALENT MANUFACTURERS, OF THE ENCLOSED VENTILATED TVPE WITH
KVA AND VOLTAGE RATINGS AS CALLED FOR ON THE DRAW INGS WITH COILS
DESIGN ED FOR 150 DEGREE C RISE ABOVE A 40 DEGREE C AMBIENT W ITH
100% OF RATED LOAD CONNECTED TO THE SECONDARV, CLASS 220 DEGREE
C INSl1LATION AND A MINIMl1M OF SIX STANDARD Fl1LL CAPACITV TAPS (TWO
ABOVE AND FOUR BELOW NORMAL). SOUND LEVELIDECIBELS SHALL BE IN
ACCORDANCE WITH "NEMA" STANDARDS, AND INSTALLATION SHALL INCLUDE
"KORFOUND" OR WUAL VIBRATION-DAMPENING MOUNTS AND REXIBLE
STEEL CONDUIT FOR PRIMARV AND SECONDARV CONNECTIONS TO MINIMIZE
SOl1NDTRANSMISSION. MOl1NTTRANSFORMERONSEPARATEVIBRATION
ISOLATORS. THESE ARE ADDITIONAL VIBRATION ISOLATORS AND ARE USED IN
CONJUNCTION WITH ANV INTEGRAL FACTORV INSTALLED VIBRATION
ISOLATORS.
LIGHTING CONTACTOR AND TIMER SW ITCHES:
A. CONTACTORS FOR CONTROL OF LIGHTING AND SIGNS SHALL BE SOUARE
"D", CLASS 8903, TVPE "C', ELECTRICALLV HELD. EpWVALENT PRODl1CTS BV
OTHERMANUFACTURERSAREPERMITTE�.
B. ELECTRONICDIGITALTIMESWITCHESSHALLBEUSEDFORCONTROLOF
SHOW WINDOW LIGHTING SIGNS ANDIFRE�UIRED/DESIREDOTHER
LIGHTING. THEELECTRONICDIGITALTIMERSHALLBEATORKMODEL
DWZ100B OR EpUNALENT WITH A]-DAV FORMAT, 365 DAV ADVANCED
HOLIDAV SCHEDl1LE, CAPABLE OF DIFFERENT SETTMGS EACH DAV OF THE
W EEK, AN � HAV E AN ASTRONOM IC FEATU RE.
INSTALLATION'.
A. ALL ELECTRIC WORK SHALL BE INSTALLED SO AS TO BE READILV
ACCESSIBLE FOR OPERATMG, SERVICW G, MAINTAINMG AN�
REPAIRING. HANGERSSHALLINCLUDEALLMISCELLANEOUSSTEEL
SUCH AS CHANNELS, RODS, ETC., NECESSARV FOR THE
INSTALLATION OF WORK AND SHALL BE FASTENED TO BWLDING
STEEL, CONCRETE OR MASONRV, BUT NOT PIPING OR DUCTWORK.
ALL CONDl11T SHALL BE CONCEALED WHEREVER POSSIBLE. EXPOSED
CONDUITS SHALL BE M STRAIGHT LMES PARALLEL WITH OR AT
RIGHT ANGLES TO COLUMN LINES OR BEAMS AND SEPARATED AT
LEAST 3 MCHES FROM WATER LMES WHEREVER THEV RUN
ALONGSI�E OR ACROSS SUCH LINES. ALL CON�UCTORS SHALL BE
IN CONDUIT, DUCTS OR OTHER CODEAPPROVED RACEWAVS.
B. ALL LME AND LOW VOLTAGE POWER AND CONTROL WIRING (EXCEPT
HVAC LOW VOLTAGE W IRWG) INCLUDMG CONNECTIONS TO MOTORS,
DAMPERS, INTERLOCKING, ETG, SHALL BE PROVIDED BY THE
ELECTRICAL CONTRACTOR (ALL LINE VOLTAGE WIRMG, CON�UIT,
AND FINAL CONNECTIONS FROM THE POWER SOURCE THRU THE
STARTER/DISCONNECT ETC. TO THE MOTOR OR WUIPMENT IS THE
RESPONSIBILITV OR THE ELECTRICAL CONTRACTOR. ALL HVAC
RELATED LOW VOLTAGE CONTROL WIRING, CONDUITAND FlNAL
CONNECTIONS IS THE RESPONSIBILITV OF THE
MECHANICAL/TEMPERATURECONTROLCONTRACTOR,UNLESS
OTHERWISE NOTED ON THE PLANS).
G THEELECTRICALCONTRACTORSHALL�OALLCUTTMG,CHASWGOR
CHANNELING AND PATCHING REpUIRED FOR ANV WORK UNDER THE
ELECTRICAL DIVISION, ANV CUTTING SHALL HAVE PRIORAPPROVAL
OFTHELANDLORD. SLEEVESSHALLEXTENDATLEASTTWO(Y')
INCHES ABOVE FINISHED FLOOR AND ALL SLEEVES, OPENINGS,
ETC., THROl1GH FIRE RATED WALLS AND FLOORS SHALL BE FIRE
SEALED WITH CALQUM SILICATE, SILICONE "RTV" FOAM, "3M"
FIRE RATED SEALANTS OR Epl1AL BV HILTI AFTER CONDl11TICABLES
INSTALLATION SO AS TO RETAIN THE FIRE RATING.
D. THE ELECTRICAL CONTRACTORS, INSOFARAS THE WORK IS
CONCERNED, SHALL AT ALL TIMES KEEP THE PREMISES IN A NEAT
AND ORDERLV CONDITION AND, AT THE COMPLETION OF THE WORK,
SHALL PROPERLV QEAN UP AND CART AWAV ANV DEBRIS AND
EXCESS MATERIAL.
E. THE FOLLOWMG EpUIPMENT SHALL BE IDENTIFIED WITH ENGRAVED
BAKELITE NAMEPLATES AS TO NAME ANDIOR FUNCTION;
�ISTRIBUTION PANELS, LIGHTMG PANELS, MOTOR STARTERS AN�
DISCONNECT SWITCHES. NAMEPLATES TO BE APPROXIMATELV 1"X
2" IN SIZE AND BE FASTENED WITH POP RIVETS OR SCREWS.
F. THE LOCATION OF OURETS AND EpUIPMENT SHOWN ON THE
�RAW MGS ARE APPROXIMATE AN � THE ARCHITECTITENANT
CONSTRUCTION MANAGER SHALL HAVE THE RIGHT TO RELOCATE ANV
OURETS OR FlXTURES BEFORE THEV ARE INSTALLED WITHOUT
ADDITIONAL COST.
G. ELECTRICAL CONTRACTOR SHALL RECORD ALL FIELD CHANGES IN
THE WORKAS THE JOB PROGRESSES, AND TURN THIS "AS BUILT"
INFORMATION OVER TO THE OWNER AT THE COMPLETION OF THE
PROJECT.
H. ELECTRICAL CONTRACTOR SHALL PROTECT ALL FIXTl1RES/Epl11PMENT
AGAINST DAMAGE FROM LEAKS, ABUSE, ETC., AND PAV COST OF
REPAIR OR REPLACEMENT OF FIXTURES OR EpUIPMENT MADE
NECESSARV BV FAILURE TO PROVIDE SUITABLE SAFEGUARDS OR
PROTECTION.
I. ELECTRICALCONTRACTORSHALLMAKEALLFINALELECTRICAL
CONNECTIONS AS REpUIRED FOR A COMPLETE AND OPERATING
SVSTEM. AFTER ALL EQUIPMENT HAS BEEN INSPECTED AND
APPROVED, THOROUGHLV CLEAN ALL EpUIPMENT PROVIDED UNDER
THIS WORK JUST PRIOR TO COMPLETION OF PROJECT.
J. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ANV/ALL
NECESSARV ELECTRICAL DEMOLITION WORK THAT IS REpl11REDT0
FAQLITATE THE NEW INSTALLATION, FlELD COORDINATE PRIOR TO
BIDS. REMOVE AND/OR MODIFV EQUIPMENT, ETC. AS REQUIRED
FOR A COMPLETE INSTALLATION. ANV EpUIPMENT OR DEVICE
REMAINING IN USE AFTER PART OF THE EQUIPMENT OR DEVICES
HAVE BEEN REMOVEDARE TO BE RECONNECTED TO EXISTING OR NEW
CIRCUITSANDLEFTINWORKINGORDER FEEDERSTOPANELSAND
WIRING TO OTHER EOWPMENT TO BE ROl1TED CONCEALED IN
FlNISHEDAREAS. COORDINATEANV DISRUPTION OF ELECTRICAL
OR TELEPHONE SERVICES WITH LANDLORD AND TENANT
CONSTRUCTION MANAGER TO AVOID CONFLICTS.
GUARANTEE:
A. MATERIALS, E�UIPMENTAND INSTALLATION SHALL BE GUARANTEED
FOR A PERIOD OF ON E(1) V EAR FROM DATE OF ACCEPTANCE.
DEFECTS WHICH APPEAR DURING THAT PERIOD SHALL BE CORRECTED
AT THE ELECTRICAL CONTRACTOR'S EXPENSE.
B. FOR THE SAME PERIOD, ELECTRICAL CONTRACTOR SHALL BE
RESPONSIBLE FORANV DAMAGE TO PREMISES CAUSED BV DEFECTS
IN WORKMANSHIP OR IN THE WORK OR EQUIPMENT FURNISHED
ANDIOR INSTALLED BV THE ELECTRICAL CONTRACTOR.
FlNALLV'.
A. IT IS THE INTENT THAT THE FOREGOING WORK SHALL BE COMPLETE
IN EVERV RESPECTANDTHAT ANV MATERIAL OR WORK NOT
SPEQFICALLV MENTIONED OR SHOWN ON THE DRAWINGS, BUT
NECESSARV TO FULLV COMPLETE THE WORK SHALL BE FURNISHE�.
i
TESTING (AS REpUIRED PER APPLICABLE ENERGV CODE):
A LIGHTING SVSTEMS FUNCTIONAL TESTING REpUIREMENTS FOR STORES
COMPLV W G W ITH ASHRAE 90A-2010
t LIGHTW G CONTROL �EVICES AN� CONTROL SVSTEMS SHALL BE
TESTED TO ENSURE THAT CONTROL HARDWARE AND SOFTWARE ARE
CALIBRHTED ADJUSTED PROGRAMMED AND IN PROPER WORKING
CONDITION IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS AND
MANl1FACTl1RER'S INSTALLATION INSTRl1CTIONS. WHEN OCCl1PANT
SENSORS TIMESWITCHES PROGRAMMABLESCHE�ULECONTROLS OR
PHOTOSENSORS ARE INSTALLED AT A MINIMUM THE FOLLOWING
PROCEDURES SHALL BE PERFORMED:
a. CONFIRM THAT THE PLACEMENT, SENSITNITV AND TIME-OUT
ADJl1STMENTS FOR OCCl1PANT SENSORS VIELD ACCEPTABLE
PERFORMANCE, LIGHTS TURN OFF ONLV AFTER SPACE IS VACATE�
AND DO NOT TURN ON UNLE55 SPACE IS OCCUPIED.
b. CONFIRMTHATTHETIMESWITCHESANDPROGRAMMABLESCHEDULE
CONTROLS ARE PROGRAMMED TO TURN THE LIGHTS OFF.
a CONFIRM THAT PHOTOSENSOR CONTROLS REDUCE ELECTRIC LIGHT
LEVELS BASE� ON THE AMOUNT OF USABLE �AVLIGHT IN THE SPACE
AS SPECIFlED.
THE INDNIDUAL�S) RESPONSIBLE FOR THE FUNCTIONAL TESTING SHALL
NOT BE DIRECTLV INVOLVED IN EITHER THE DESIGN OR CONSTRUCTION
OF THE PROJECTAND SHALL PROVIDE DOCl1MENTATION CERTIFVMG
THAT THE INSTALLED LIGHTMG CONTROLS MEET OR EXCEED ALL
DOCUMENTED PERFORMANCE CRITERIA.
B. LIGHTING SVSTEMS FUNCTIONAL TESTING REpUIREMENTS FOR STORES
COMPLVING WITH ASHRAE 90.b2013
L LIGHT W G CONTROL �EVICES AND CONTROL SVSTEMS SHALL BE
TESTE� TO ENSURE THAT CONTROL HAR�WARE AN� SOFTWARE ARE
CALIBRHTED, ADJUSTED, PROGRAMMED, AND IN PROPER WORKING
CONDITION IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS AND
MANUFACTURER'S INSTALLATION INSTRUCTIONS. WHEN OCCUPANT
SENSORS, TIME SWITCHES, PROGRAMMABLE SCHEDl1LE CONTROLS, OR
PHOTOSENSORS ARE INSTALLE�, AT A MINIMUM, THE FOLLOW WG
PROCEDURES SHALL BE PERFORMED:
a. OCCUPANTSENSORS
1. CERTIFV THAT THE SENSOR HAS BEEN LOCATED AND AIMED IN
ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS.
2 FOR PROJECTS WITH UP TO SEVEN (]) OCCUPANCV SENSORS, ALL
OCCUPANCV SENSORS SHALL BE TESTED.
3. FOR PROJECTS WITH MORE THAN SEVEN Q)OCCUPANCV
SENSORS, TESTING SHALL BE DONE FOR EACH UNIpUE
COMBINATION OF SENSOR TYPE AND SPACE GEOMETRV.
(a)FOR EACH SENSOR TO BE TESTE�, VERIFV THE
FOLLOW ING'.
(1) STATUSINDICATOR(ASAPPLIGABLE)OPERATES
CORRECTLV
(2) CONTROLLEDLIGHTSTURNOFFORDOWNTOTHE
PERMITTE� LEVEL WITHIN THE REQUIRE� TIME
(3) FORAUTO-ON OCCUPANT SENSORS, THE LIGHTS
TURN ON TO THE PERMITTED LEVEL WHEN SOMEONE
ENTERS THE SPACE
(4) FOR MANUALON SENSORQ THE LIGHTS TURN ON
ONLV WHEN MANUALLV ACTIVATED
(5) THE LIGHTS ARE NOT INCORRECTLV TURNED ON BV
MOVEMENT IN NEARBV AREAS OR BV HVAC
OPERATION
b. Al1TOMATICTIMESWITCHES
1. CONFIRMTHATTHEAUTOMATICTIME-SWITCHCONTROLIS
PROGRAMMED WITH APPROPRIATE WEEKDAV, WEEKEND,AND
HOLIDAY (AS APPLICABLE) SCHEDULES.
2. DOCl1MENTFORTHEOWNERAl1TOMATICTIME-SWITCH
PROGRAMMMG, INCW DMG WEEKDAV, WEEKEND, AND HOLIDAV
SCHEDULES, AS WELL AS ALL SETUP AND REFERENCE PROGRAM
SETTINGS.
3. VERIFV THAT CORRECT TIMEAND DATE ARE PROPERLV SET M THE
TIME SW ITCH.
4. VERIFV THATANV BATTERV BACKl1P (AS APPLICABLE) IS INSTALLED
AND ENERGIZED.
5. VERIFVTHATTHEOVERRIDETIMELIMITISSETTONOMORETHAN
TWO (2) HOURS.
6. SIMULATEOCCUPIEDCONDITION.VERIFVANDDOCUMENTTHE
FOLLOW MG:
(a)ALL LIGHTS CAN BE TURNED ON AND OFF BV THEIR
RESPECTNEAREACONTROLSWITCH.
(b)THE SWITCH ONLV OPERATES LIGHTING M THE ENCLOSED
SPACE IN WHICH THE SWITCH IS LOCATED.
�. SIMULATEUNOCCUPIE�CON�ITION.VERIFVAN��OCUMENTTHE
FOLLOW MG:
(a)ALL NONEXEMPT LIGHTING TURNS OFF
(b)MANUAL OVERRIDE SWITCH ALLOWS ONLV THE LIGHTS IN
THE ENCLOSED SPACE W HERE THE OVERRIDE SW ITCH IS
LOCATED TO TURN ON OR REMAIN ON UNTIL THE NEXT
SCHE�ULE�SHUTOFFOCCURS
c. DAYLIGHT CONTROLS
1. ALL CONTROL DEVICES(PHOTOCONTROLS)HAVE BEEN PROPERLV
LOCATED, FIELD-CALIBRATED, AND SET FOR APPROPRIATE
SETPOINTS AND THRESHOLD LIGHT LEVELS.
2. DAVLIGHT CONTROLLED LIGHTING LOADS ADJUST TO
APPROPRIATE LIGHT LEVELS IN RESPONSE TO AVAILABLE
DAVLIGHT.
3. THE LOCATION WHERE CALIBRATION ADJUSTMENTS ARE MADE IS
READILV ACCESSIBLE ONLV TO AUTHORIZED PERSONNEL.
THE INDNIDUAL(5) RESPONSIBLE FOR THE FUNCTIONAL TESTING SHALL
NOT BE DIRECTLV INVOLVED M EITHER THE DESIGN OR CONSTRUCTION
OF THE PROJECTAND SHALL PROVIDE DOCUMENTATION CERTIFVING
THAT THE INSTALLED LIGHTMG CONTROLS MEET OR EXCEED ALL
DOCUMENTED PERFORMANCE CRITERIA.
I
I
I
I
i
SEPHORA
525 MARKET STREET, 32ND FLOOR
SAN FRANCISCO, CA 94105
Ber me er
g
Y
_
/ /
11
M-Engineering
]50 Brooksedge Blvd.
Westervllle, Ohlo 43081
phone: 614.839.4639
lar: 6f4.8392222
www meigineering.us.com
STAMP
��,4-19
,...... ...
GEA.M� •
� ,... ... -.
�T� ���srER��O�
nissoasas
STATE OF
Q I DATE I ISSUEDESCRIPTION I BV I CHECK
10.01.19 I DESIGNDEVELOPMENT
i1.0A]9 I ISSUE FOR PERMIT
PROJECTLOCATION:
CLAY TERRACE
14390 CLAY TERRACE BLVD
SPACE D13
CARMEL, IN 46032
AREA: 4,129 SF
SHEET TITLE:
ELECTRICAL
SPECIFICATIONS
PROJECT N0. 19122
STORE N0. 1326
SCALE: AS NOTED
DATE: 11.04.2019
DRAWN BY: NH
REVIEWED BY: DFG
SHEET N0.
E-600