HomeMy WebLinkAboutM200 - Mechanical Schematicsi
i
SUPPLV AND/OF
RETURN AIR DU
RETURN TUBE
SMOKEDETECI
AND INSTALLEO
CONTRACTORt
M G EXPENSE)
SAMPLING TUBE
_�-
/ SCALE:NTS
9 SMOKE DETECTOR SCHEMATIC
SCALE:NTS vErvrvzEVHvaoaeFMusHaooM
TYPE FLHT ROOF CHP. PHINT TO
MHTCH ftOOF
TIE BHN�
SEAL ALL OPENINGS W ITH
rvorv-Hnaoervwc cnu�K.
ExTENo aoociNc
urvoERcourvTER �
FLASHiNG
8" HIGH CURB
CUTS�UARE
ROOF OPENING HN�
FRHMEOPENING —
E
�ooc
EXHHUST �UCT � SEE PLHN
NOTE- MAINTAIN A MINIMUM OF 10'-0" SEPARATION
BETWEEN ALL EXHAUST AND INTAKE LOCATIONS
,� ROOF CAP EXHAUST SCHEMATIC
�� SCALE:NTS
LAV-I N
� �
/ SCALE:NTS
NOTE'. ROUGH-IN OPENING SIZES'.
NOM INAL 1 Y'x 1 Y' = 12 VY'x 12 VY'
NOM INAL 24"x 24" = 24 1/Yk 24 VY'
NOM INAL 24"x 1 Y' = 24 VY'x 12 VY'
NOMINAL 18"x 18" = 181/2"x 181/2•'
NOM INAL 20"x 20" = 20 VYk 20 VP'
25 1/4".21 1/4",
191/4" OR 131/4•'
1 VY'
24". 20". 18" OR 1Y'
1 1/8'
� �
J SCALE:NTS
SCALE:NTS
VOUNG REGULATORDAMPER
WITH CABLE TO FACE OF
REGISTER
8" OR 10"0 FLEX
(S MAX. LENGTH)
VOUNG REGULATOR BOWDEN PLENUM PROVI�E�
BVMECH.CONTR.
CABLE CONTROLS W20CC
DAMPER WITH 210I215
DRNECONTROLKIT.OR o 0
WUAL
TRANSITION AS REpUIRED .,� �'� ��SCREW DRIVER
LINEARDIFFUSER � , ADJUSTMENTATFACE
OF DIFFUSER
FIELD COORDINATE INSTALLATION
WITH GENERAL CONTRACTOR.
NOTES
1. DIFFUSER SHALL APPEAR CONTINUOUS.
2. ALL CORNERS SHALL BE MITERED.
RELEASED FOR CONSTRl1CTI0N
Su6jec� �o compliance with all regula�ions
of Sla�e antl Local Codes
City of Carmel
��
`��¢m�' lamn�Mn?>�
onrE: 01 /16/20
_�-
J SCALE:NTS
225°
BLADEANGLE
SPIRAL ROUND
AIR DUCT
ALL DUCT LIN ER TRANSVERSE
EDGES TO BE COATED W/
ADHESIVE IN ACCORDANCE
WISMACNASTANDARDS
(TVP.) �
FLANGED AND GASKETED JOI NT
OR DUCT CONNECTION AND RE
INFORCEMENTINACCORDANCE
WI SMACNA 2" W.G. CLASS,
SEALNON-GASKETEDTRANS-
VERSE JOINTS IN ACCORDANCE
W/ SMACNA CLASS "C" (TVP_)
AIR
�
i
�� � � MAIN DUCT J
PROVIDE INTERNAL l
OR EXTERNAL WRAP
INSULATION AS
SPECIFlE�
DUCT MOUNTED DIFFUSER SCHEMATIC
SCALE:NTS
DUCT FROM MAIN
FLAG DAMPER SO IT IS
EASILV IDENTIFIABLE
DURWG INSPECTIONS�
RIGID S A. DUCT SEE
PLAN FOR SIZE—
DUCT HANGER (iYPIG
i
BANDCLAMP�
6"MW �
�i�
VOLUME DAMPER LOCATION WHERE
DAMPER WOULD BE INACCESSIBLEAT
TAKE-OFF, PROVIDE WB" EXTENDED
SHAFT, HANDLE AND COLLAR.
HAR�ELBOW
BAND CLAMP
FLEXIBLE DUCT SAME SIZE AS DIFFUSER
NECK.S'-0" MAX. LENGTH
MIN. OF 6" HIGH STRAIGHT VERTICAL
DUCT AT DIFFUSER CONNECTION
PROVIDE FACE OPERATED OPPOSED BLADE
DAMPER IN GVP. BOARD CLG. ONLV
� / SCALE:NTS
ALLDUCTLINERTRANSVERSE FLANGEDANDGASKETEDJOINT
EDGES TO BE WATED WI OR DUCT WNNECTION AND RE
ADHESIVEINACCORDANCE INFORCEMENTINACCORDANCE
W/SMACNASTANDARDS WISMACNA2"W.G.CLASS,
(TVP) VERSEJ�OINTS NEACOORDANCE
WI SMACNA CLASS "C' (TVP.)
I � MAINDUCT� ..�I::' �
PROVIDEINTERNAL
LINER OR EXTERNAL
WRAP INSULATION
AS SPECIFlED
BRANCH DUCT
45°—/
� � �-VOWMEDAMPERLOCATION
WHEREABOVE LAV-IN CEILING.
PROVIDE W/ LOCKING QUADRANT
18" LONG ORANGE MARKER
„�TAPE ATTAGHED TO
. - �AMPERTOI�ENTIFV
I LOCATION
DUCT CONNECTION TO BOH DIFFUSER SCHEMATIC
"C" CHANNEL
REINFORCING BV
G.C. AROUND
OPENING
MOUNTWG SCREW
FIELD INSTALLED
DRV WALL CEI LI NG
STEEL MOUNTWG
FRAME
� TYP. SQUARE DUCT TAKE-OFF SCHEMATIC
� SCALE:NTS
VANES PREASSEMBLE� ON RUNNER PLATES
USE GHLVHNIZED VHNES FOR GALVHN IZED
OR A W MINUM DUCTS
PLATE SAME GAl1GE AS �l1CT
9
I
�
31/4" 1 V2'•
�-DUCTSIZEOVER38"X38" �DUCTSIZE38"X38"ORUNDER
Sp. ELBOW WITH TVPE "N" Sp. ELBOW WITH 51NGLE
DOUBLETHICKNESSVANES THICKNESSVANES
DRYWALL MOUNTING FRAME SCHEMATIC
SGHLt:N15
LINEAR DIFFUSER SCHEMATIC
TAPE DOWN EXTERNAL
INSULATION
CONICAL OR BELLMOUTH SPIN-
IN FITTING, SEALAIRTIGHT W/
MASTIC
MANUAL BALANCING DAMPER
FASTEN WI MIN. (3) � J � ��� { - ROUND RIGID DUCT
SHT.MTLSCREWS, `���L�'�
SEAL WI DUCT TAPE 1" WRAPPED INSULATION
AN� MASTIC
� TYP. ROUND DUCT TAKE-OFF SCHEMATIC
� TURNING VANES SCHEMATIC
I METAL GAUGE FOR DUCTWORK TO BEAS FOLLOWS:
ROUND DUCT 3 TO 191NCHES TO BE 26 GAUGE
RECTANGULAR DUCT UP TO 121NCHES WIDE TO BE 26 GAUGE
RECTANGULAR DUCT 13 TO 30 INCH ES W IDE TO BE 24 GAUGE.
RECTANGULAR DUCT ABOVE 301NCHES WIDE TO BE 22 GAUGE.
SEISMIC STRAPPING AT 45�
STEELSTRAP HANGER
DUCTWORK
SELF-TAPPWG, SHEET METAL SCREW
HANGER SPACING
DUCT FACE AREA FROM 0 TO 4 Sp. FT. HANGERS 98" OL. MAX
DUCT FACE AREA FROM 4 TO 10 Sa. FT. HANGERS 12" O.G MAX
DUCT FACE AREA FROM 10 AND GREATER HANGERS 48" O.C. MAX
WHERE DUCTS ARE LE55 THAN 2 SQ FT. W FACE AREA, HANGERS
SHALL BE NOT LESS THAN 1"xi/i6" STRAP STEEL.
WHERE DUCT ARE GREATER THAN 2 S0. FT. IN FACE AREA. HANGERS
SHALL BE NOT LESS THAN 1"xil8" STRAP STEEL.
WHERE DUCT ARE 8 SQ. FT. IN FACE AREA. HANGERS SHALL BE
BRACED BV 1"xi"xi/B" STEEL ANGLES ALL AROUN D, SPACED NO
MORETHAN FOUR FEET ON CENTERS.
WHERE DUCTS ARE OVER 48" WIDE. THE HANGERS SHALL BE BROUGHT
DOWN UNDER THE DUCT SIDES 4" AND FASTENED TO THE BOTTOM.
�1 DUCT SUPPORT SCHEMATIC
JI:HLt: N I J
� SCALE:NTS
J SCALE:NTS
I
I
I
I
i
SEPHORA
525 MARKET STREET, 32ND FLOOR
SAN FRANCISCO, CA 94105
Ber me er
g Y
_
�11�
M-Engineering
]50 Brooksedge Blvd.
Westervllle, Ohlo 43081
phone: 614.839.4639
lar: 6f4.8392222
www meigineering.us.com
STAMP
.
..•� GE A. AAp •.
� 1`� ' "�STE '• �O �
�j .,�G Rr`..... i
2 O':
aissoosos `;
Q DATE ISSUEDESCRIPTION
10.01.19 DESIGNDEVELOPMENT
i1.0A]9 ISSUE FOR PERMIT
BV I CHECK
PROJECTLOCATION:
CLAY TERRACE
14390 CLAY TERRACE BLVD
SPACE D13
CARMEL, IN 46032
AREA: 4,129 SF
SHEET TITLE:
MECHANICAL
SCHEMATICS
PROJECTNO.
STORE N0.
SCALE:
DATE:
DRAWN BY:
REVIEWED BY:
SHEET N0.
M-20(
� �za�s(az��srza�e�
�9�22
1326
AS NOTED
11.04.2019
EB
JAH
1-
SCALE:NTS
251/4", 21 1l4", 19114" OR 131/4•'
OUTSIDE DIMENSION