HomeMy WebLinkAboutA010.0 LEGACY AMENITY AREA SHELTER4 - A2.1ELECTRICAL SPECIFICATIONS AND GENERAL REQUIREMENTS:
THE CONTRACT DOCUMENTS CONSIST OF THE DRAWINGS AND
SPECIFICATIONS ON THE DRAWINGS. THE INTENT OF THE CONTRACT
DOCUMENTS IS TO INCLUDE ITEMS NECESSARY FOR THE PROPER EXECUTION
OFTHE WORK.
BUILDING CODES: NEW CONSTRUCTION SHALL CONFORM TO ALL APPLICABLE
CITY, STATEAND LOCAL BUILDING CODES FORTHIS CLASS OF WORK.
ELECTRICAL CONTRACTOR SHALL VERIFY EXISTING CONDITIONS AND
DIMENSIONS AT THE JOBSITE. IF DISCREPANCIES ARE FOUND THE GENERAL
CONTRACTOR SHALL BE NOTIFIES BEFORE PROCEEDING WITH ANY WORK OR
ORDERING ANY EQUIPMENT OR MATERIAL IN THE AFFECTED AREA.
FIT AND QUANTITY OF THE WIRING, ELECTRICAL EQUIPMENT, THE VARIOUS
NECESSARY PARTS AND MATERIALS TO MAKE A COMPLETE AND FINISHED JOB
SHALL BE VERIFIED AND COORDINATED PRIOR TO START OF CONSTRUCTION
AND ARE THE EXCLUSIVE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
LOCAL UTILITY COORDINATION: ELECTRICAL CONTRACTOR SHALL
COORDINATE TRANSFORMERS AND SERVICE REQUIREMENTS WITH THE LOCAL
UTILITY COMPANY. THE EC. SHALL CONSULT WITH THE LOCAL UTILITY TO
ESTABLISH REQUIRED kACI RATINGS.
ALL FIXTURES, EQUIPMENT AND MATERIALS SHALL BE INSTALLED PER THE
MANUFACTURER'S SUGGESTED INSTALLATION REQUIREMENTS IN A NEAT AND
WORKMANLIKE MANNER.
UL LABELING: ALL ELECTRICAL EQUIPMENT SHALL HAVE "UL" LABELS.
WIRING DEVICES SHALL BE SPECIFICATION GRADE.
PROVIDE ALL DISCONNECTS REQUIRED PER NATIONAL AND LOCAL ELECTRICAL
CODES RATED TO UTILITY SUPPLIED kAIC LIMITS, OR, IF NOT SUPPLIED, TO NEC
MINIMUMS.
ALL EXPOSED WIRE AND WIRING BELOW CONCRETE SLABS SHALL BE IN
CONDUIT.
WIRE: ALL WIRE SHALL BE COPPER, MINIMUM SIZE #12 AWG. ALL
CONDUCTORS SHALL HAVE TYPE "THHN" INSULATION. CONDUCTORS #10 AND
SMALLER MAY BE SOLID. GROUNDING CABLES SHALL BE NO SMALLER THAN 4
COPPER.
BREAKER PANELS: FURNISH AND INSTALL A BREAKER PANEL AS
MANUFACTURED BY SQUARE D OR ITE. INSTALL PANEL SO TOP BREAKER IS NO
HIGHER THAN 6'-0".
FURNISH AND INSTALL TYPEWRITTEN DIRECTORY. IDENTIFY AND LABEL ALL
ELECTRICAL SERVICE EQUIPMENT.
GROUNDING: GROUNDING SHALL BE DONE STRICTLY ACCORDING TO SECTION
250.52 OF THE NATIONAL ELECTRIC CODE USING ACCEPTABLE ELECTRODES
AND CONNECTIONS.
SWITCHES: ALL SWITCHES SHALL BE RATED 20 AMP, 125 VOLT AND SHALL BE
MOUNTED 4'-6" AFF, UNLESS NOTED OTHERWISE.
RECEPTICALS: ALL RECEPTA0.ES TO BE 15 AMP, 125 VOLT, GROUNDING TYPE
AND SHALL BE MOUNTED 18" AFF, UNLESS NOTED OTHERWISE.
PROVIDE TEMPORARY POWER REQUIRED BY THE GENERAL CONTRACTOR AND
OTHER TRADES. COORDINATE POWER REQUIREMENTS WITH GC PRIOR TO
INSTALLATION.
LIGHTING FIXTURES: LIGHTING FIXTURES TO BE FURNISHED AND INSTALLED
COMPLETE WITH LAMPS AS DETAILED ON THE PLANS OR AS INTENDED. SEE
REFLECTED CEILING PLAN ANDIOR LIGHTING PLAN FOR THE EXACT LOCATION
OF THE CEILING GRID, LIGHT FIXTURES, OR THE GENERAL INTENT OF THE
DRAWINGS.
SEE THE ELECTRICAL DRAWING(S) FOR THE FIXTURE SCHEDULE, NOTES AND
OTHER SPECIFICATION REQUIREMENTS.
CONTRACTOR SHALL BE RESPONSIBLE FOR NOTICE TO THE INSPECTING
AUTHORITIES, ARCHITECT, OR GENERAL CONTRACTOR, SO THAT WORK CAN BE
INSPECTED OR APPROVED BEFORE COVERING. THIS PROCEDURE SHALL
OCCUR WITHOUT AFFECTING CONSTRUCTION PROGRESS AND COMPLETION.
THE INTENTION OF THESE DOCUMENTS IS TO PROVIDE THE OWNER WITH A
BUILDING COMPLETE IN ITS ENTIRETY AT THE TIME OF OCCUPANCY. IT IS THE
SUB-CONTRACTOR'S RESPONSIBILITY TO CONTACT THE GENERAL
CONTRACTOR DURING THE BIDDING/PRICING PHASE OF ANY DETAILS MISSING,
RELEASED FOR CONSTRl1CTI0N ETE SO THAT AN APPROPRIATE ADDENDUM OR
3E ISSUED. THE SELECTED CONTRACTOR SHALL PROVIDE
Su6jec��ocompliancewithallregula�ions �R, TOOLS, EQUIPMENT, AND SERVICES NECESSARY FOR A
o4S�a�eantlLocalCodes NAL,ANDOPERATIONALFACILITY.
City of Carmel
`�j sv�� �\'��v�AWnT �
TOO 100 AMP PANEL IN
POOLHOUSE
I I I ,��
I I I /
/
P LED CAN LIGHTS IN �
WOOD SOFFIT /
(TVPICAL FOURJ (/ --�
CEILING CONVEIyIENCE
�JTLET �
I
WOOD SOFFIT CEILING � ; —
\
°'�_______________ b
CONDUIT FEED FROM POOL
HOUSE AS REQUIRED
ELECTRICAL AND LIGHTING PLAN
SCHLE 1/S" - 1'-O"
PARTIAL POOL HOUSE PLAN
SHOWING ELECTRICAL PANEL
G(:A1 F 'I /R•• ='I•-0••
10 AMP
ISFORM R gREAKERS AS
=QUIRE REQUIRED—
rwo a vz• coNowTs =
W/4-500 MCM -
IF REQUIRE�
[H��
PERGOLA
6 FOOT HIGH POOL
FENCE
RISER DIAGRAM
NOT TO SCALE
GROUND PER
NEC
ELECTRICAL SYSTEM GROUNDING REQUIREMENTS:
STRICTLY FOLLOW NEC 250.50 AND 250.52.
YCII�[H��
PERGOLA
6 FOOT HIGH POOL
FENCE
INSTALL GROUNDING ELECTRODE ACCORDING TO THE FOLLOWING LIST:
WATER PIPE IF 10 FEET OR MORE OF METAL WATER PIPE IS IN CONTACT
WITH THE EARTH.
METAL FRAME OF THE BUILDING OR STRUCTURE WHERE ANY OF THE
FOLLOWING FOUR METHODS ARE USED TO MAKE AN EARTH
CONNECTION:
1. CONCRETE-ENCASED ELECTRODE IN AT LEAST 2 INCHES OF
CONCRETE LOCATED WITHIN OR NEAR THE BOTTOM OF A
CONCRETE FOUNDATION OR FOOTING THAT IS IN INDIRECT
CONTACT WITH THE EARTH.
2. GOUND RING ENCIRCLING THE BUILDING OR STRUCTURE IN
DIRECT CONTACT WITH THE EARTH.
3. ROD OR PIPE ELECTRODE NOT LESS THAN 8 FEET IN LENGTH.
4. OTHER LOCAL UNDERGROUND SYSTEMS SUCH AS PIPING,
UNDERGROUND TANKS AND UNDERGROUND WELL CASING.
COMMUNICATIONS EQUIPMENT: COMMUNICATIONS EQUIPMENT SHALL BE
GROUNDED TO BUILDING GROUNDING ELECTRODE SIMILAR TO OTHER
ELECTRICAL EQUIPMENT. FOLLOW NEC 800.100 (B).
ALL GROUNDING ELECTRODES THAT ARE PRESENT AT THIS BUILDING
STRUCTURE SHALL BE BONDED TOGETHER TO FORM THE GROUNDING
ELECTRODE SYSTEMS.
BOND ALL GROUNDING ELECTRODES THAT ARE PRESENT AT THIS
BUILDING STRUCTURE TOGETHER TO FORM THE GROUNDING
ELECTRODE SYSTEM. GROUNDING ELECTRODES THAT MAY BE PRESENT
AT THIS BUILDING INCLUDE GROUNDING ELECTRODE RODS, CONCRETE
ENCASED ELECTRODES SUCH AS BUILDING FOUNDATION REBAR,
UNDERGROUND METAL WATER PIPES, AND METAL FRAME OF THE
BUILDING INCLUDING STRUCTURAL STEEL COLUMNS.
SEE GROUNDING DETAIL THAT IS A PART OF DRAWINGS OF THIS SET
NOT PERMITTED:
METAL UNDERGROUND GAS PIPING.
ALUMINUM ELECTRODES
Q
Q
F
U
W
F
2
U
�
Q
Y
�
Q
J
U
Z
�
O
�
�
�
■
W
�
�
�
U
�
�
�
�
�
W
�
J
w
_
�
�����
� N N N �
yt0 N N_
� a N N 0
U � N N �
� � � r W
3 � M M �
C i'
� N � K �
m ms�C7
o�a
N �
W �
V C
�
L.I_
�
�
�
Z
WC
G
Q
�
U
r�n
V
W
J
W
I
�
a
Z
Q
�
Z
}
�
z
�
�
U
Z
�
H
J
�
Q
_
JANUARY 10, 2020
��ninnun.
�o� EDVARp ci.�.
��p9 �G\STEqF �v,p :
= u � No. � 'F'
= e AR00032537 e
STATE OF
�1'D I PNP
�, ;
�� ��,,,.
S ELTER
A2.1