PURPOSE RECEPTACLE. REFER TO FLOOR PLANS FOR NEMA
�
GENERAL LIGHTING/POWER NOTES
L LIGHTFIXTURESDESIGNATEDAS"NIGHTLIGHTS"SHALLBEONUNSWITCHEDCIRCUIT,UNLESS
NOTED.
2 EXIT LIGHTS SHALL BE ON UNSW ITCHED CIRCUIT, UNLESS NOTED.
3. ALL RECESSED DOWNLIGHTS MOUNTED W GRID CEILWG SHALL BE CENTERED IN CEILWG TILE,
UNLESSNOTED.
4. IN ALL MECHANICAL ROOMS, COORDINATE EXACT LOCATION OF LIGHT FlXTURES WITH HVAC
DUCTWORK.
S CONDUCTORS FOR BRANCH CIRCUITRV ARE #12 AWG MINIMUM, UNLESS NOTED. DERATE PER CODE
WHERE CIRCUITSARE COMBWED.
6. ALL HOMERUN CONDUCTORS BACK TO PANEL SHALL BE #10AWG MINIMUM, UNLESS NOTED.
PROVIDE AGREEN GROUND CONDUCTOR INALL BRANCH CIRCUITRV. DERATE PER CODE WHERE
CIRCUITS ARE COMBINED.
1. WHERE TERMINATED IN J-BOX, ALL SPARE CIRCUITRV SHALL BE LABELED W ITH PANEL AND CIRCUIT
NUMBER.
8. COORDINATEWITHMECHANICALCONTRACTORANDPROVIDEALLNECESSARYAUXILIARY
CONTACTS, RELAV, ETC. IN MOTOR STARTERS FOR REpUIRED CONTROLOF MECHANICAL
E�UIPMENT.
9. ALL HOME RUN W IRING SHALL BE INSTALLED IN EMT OR RGS CONDUIT, UNLESS NOTED.
10. ALLUNDERGROUNDPVCCONDUITSSHALLHAVERIGIDGALVANIZEDSTEELELBOWS.
11. ALL LIGHT FlXTURES SHALL BE SEISMICALLV BRACED WITH AN INDEPENDENT WIRE (CEILWG GRID
TVPE W IRE) FROM TW O OPPOSITE CORNERS TO STRUCTURAL CEILING OR BAR JOIST.
12. DONOTSUPPORTCONDUITOFFOFCEILWGGRID,CEILWGGRIDSUPPORTS,MECHANICAL
SUPPORTS,ORANYOTHERTRADPS SUPPORTS.INSTALLCONDUITSANDBOXESONSEPARATE
SUPPORTS FROM BAR JOIST OR STRUCTURE.
13. DO NOT SUPPORT FROM METAL ROOF DECK. PROVIDE SUPPORT FROM CONCRETE SIABS, BAR
JOIST, STRUCTURAL BEAMS, COWMNS OR UNISTRUT BETWEEN STRUCTURAL ELEMENTS.
14. ALL SINGLE PHASE CIRCUITS SHALL HAVE A SEPARATE DEDICATED NEUTRAL CONDUCTOR FOR EACH
CIRCUIT. SHARING OF NEUTRALCONDUCTOR IS NOT PERMITTED.
15. PROVIDE 4" HIGH, SMOOTH FINISH CONCRETE HOUSEKEEPING PADS UNDER ALLTRANSFORMERS
(45KVA AND LARGER) AND MAIN DISTRIBUTION SW ITCHBOARDS. PAD SHALL BE 4" LARGER THAN
TRANSFORMER AND SW ITCHBOARD W EACH DIRECTION. USE 3000 PSIG, 28 DAV COMPRESSNE
STRENGTHCONCRETE.ROUNDALLEDGESANDCORNERSOFCONCRETEPAD.
GENERAL PROJECT NOTES
1. WORK SHALL BE DONE IN ACCORDANCE W ITH LOCAL, STATE OF INDIANA, 2014 NEC
AND NATIONALCODES,RECOMMENDATIONS,REGULATIONS,ANDREpUIREMENTS.
2 CONTRACTORSSHALLVISITPROJECTSITEPRIORTOBIDDINGTOASCERTAINAND
BECOM E FAM ILIAR W ITH EXISTING CONDITIONS AS THEV PERTAIN TO THE SCOPE OF
WORK. CONTRACTOR SHALL VERIFV EXACT LOCATION AND SIZES OF ELECTRICAL
EpUIPMENTAND ALL OTHER APPURTENANCES ASSOCIATED W ITH THE WORK.
3. COORDINATE AND UTILITI' SHUT DOWNS, (ELECTRIC AND TELEPHONE) WITH THE
OW NER AND PROVIDE NOTICE NOT LESS THAN ]2 HOURS IN ADVANCE.
4. COORDINATE ELECTRICAL RE�UIREMENTS FOR NEW OR WORK WITH THE PLUMBWG
AND MECHANICAL CONTRACTORS. VERIFY VOLTAGE, PHASE AND ACCESSORY
REpUIREMENTS, SUCH AS MOTOR STARTERSAND DISCONNECTS.
5. OPENINGS IN NEW WALLSAND FLOORS SHALL BE PLANNED AND COORDINATED WITH
GENERAL CONTRACTOR FOR THE INSTALLATION OF APPROPRIATE SLEEVES.
6. ALLCONDUITSHALLBE3l4"MINIMUMU.N.O.
�. CONDUITSHALLBECONCEALEDINCEILWGORWALLSWHEREVERPOSSIBLE.
8. ALL UNDERGROUND CONDUIT SHALL BE SCHEDULE 40 PVC UNLESS NOTED
OTHER W ISE.
9. ALLBRANCHCIRCUITSANDFEEDERSSHALLCONTAINAGREENINSULATEDGROUND
CONDUCTOR. GROUNDWG BV MEANS OF RACEWAV IS NOT PERMITTED.
10. REFERTOMECHANICAL,PLUMBING,ANDARCHITECTURALPLANSFOREXACT
LOCATION OF E�UIPMENT.
11. COORDINATE LOCATIONS OF LIGHTING FIXTURES IN MECHANICAIJELECTRICAL ROOMS
W ITH E�UIPMENT, PIPWG AND DUCTWORK.
12 CONTRACTOR SHALL COORDINATE EXACT HEIGHT OF DEVICES DESIGNED AS OVER
COUNTER WITH CASE WORKAND FURNITURE DRAW WGS.
13. VERIFV CEILING TYPES PER THEARCHITECTURAL REFLECTED CEILING PLAN. PROVIDE
APPROPRIATE TYPE FlXTURE, LAV-W FOR GRIq FLANGE FOR DRVWALL, ETC.
14. NO MORE THAN 3 PHASE CONDUCTORS SHALL BE INSTALLED IN ANV ONE CIRCUIT,
UNLESS NOTED OTHER W ISE EACH BRANCH CIRCUIT SHALL CONTAIN THEIR OW N
NEUTRALCONDUCTOR.NOSHAREDNEUTRALS.
iS FURNISHALLELECTRICALACCESSFLOORSTOGENERALCONTRACTORFORHIS
INSTALLATION. REFER TO SPECIFICATIONS FOR ACCESS DOOR REpUIREMENTS.
i6. CONTRACTORSHALLPROVIDEALLFlRESTOPPWGFORCONDUITORCABLETRAV
PENETRATIONS THAT PENETRATE ACOUSTICAL RATED OR SMOKE AND FIRE RATED
ASSEM BLIES. SEE ARCHITECTURAL DRAW INGS FOR LOCATIONS OF ALL RATED
ASSEMBLIES. ALL RATED PENETRATIONS SHALL BE FlRESTOPPED TOORIGINAL
ASSEMBLY RATING. ALL NON-RATED FLOOR PENETRATIONS SHALL BE SEALED WATER
TIGHT W ITH A FLEXIBLE SEALANT.
1]. BRANCHCIRCUITWIRINGCHARTTOBEUTILIZEDASGUIDELINEFORVOLTAGEDROP
COMPENSATION, INCREASE CONDUIT SIZING PER W IRE SIZE (APPLIES TO ALL SHEETS)
A 20A-120 VOLTCIRCUITS
a. #12 W IRE - �5 LENGTH MAX. -#12 GRD.
b. #10 W IRE - 12S LENGTH MAX. -#8 GRD.
c. #8 W IRE - 200' LENGTH MAX. -#8 GRD.
tl. k6 W IRE - 300' LENGTH MAX. -#6 GRD.
18. PROVIDEALLPULLBOXES,INACCESSIBLEAREA,THATEXCEEDNECNUMBEROF
BENDS OR LENGTH W FEEDER AND BRANCH CIRCUITS. INSTALL BOXES WHERE
REpUIRED PER CODE.
19. ALLWIRWGDEVICESSHALLBEOFHEAVVDUTYCOMMERCIALGRADECONSTRUCTION.
REFER TO ARCMTECNRAL SHEETS AND CODE SHEET FOR ALL FIRERATED PARTITION
LOCATIONS AND RATINGS.
20. CONTRACTOR IS RESPONSIBLE FOR ALLCOREDRILLS REpUIRED FOR INSTALLATION
OF ELECTRICAL WORK.
21. VERIFYTHELOCATIONOFALLUTILITIESPRIORTOEXCAVATION,TRENCHING,OR
DRILLING.
22. ALLEXPOSEDMETALCONDUITSARETOBEPAWTEDTOMATCHTHEADJACENT
SURFACE. COORDINATION OF PAINTING OF CONDUIT IS TO BE BV THE ELECTRICAL
CONTRACTOR, WITH PAINTWG BV OTHERS.
23. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDWG ALL RE�UIRED
JUNCTION BOXES, PULL BOXES. ETC FOR A COMPLETE INSTALLATION PER THE N.EC.
AND LOCAL CODES. ALL CONDUCTORS SHALL BE RATED FOR 90 DEGREE CELSIUS.
24. COORDINATE WORK WITH OTHER TRADES. COORDINATION OR SCHEDULWG SHALL BE
RESPONSIBILITV OF THE INVOLVED CONTRACTORS.
2S ALLLOWVOLTAGECABLWGINSTALLEDINSPACESWITHOUTALAV-INORWITHAHARD
CEILING SHALL BE INSTALLED IN CONDUITAND BOXES.
26. ALLELECTRICALROOMSARESHOWNWITHE�UIPMENTDRAWNTOSCALEAND
ARRANGED TO ENSURE FlTAND CODE REpUIRED CLEARANCES. EpUIPMENTSHALL BE
INSTALLED IN THE LOCATIONS SHOW N, UNLESS W RITTEN APPROVAL IS GIVEN BV THE
ENG W EER, BASED UPON 1/4 SCALE DRAW WGS SUBMITTED BV THE CONTRACTOR FOR
REVIEW ANDAPPROVAL.
�
ABBREVIATIONS
A AMPS KW KILOWATTS
AFF ABOVE FINISHED FLOOR LGTG LIGHTING
AFG ABOVE FINISHED GRADE MECH MECHANICAL
BKR BREAKER NIC NOTINCONTRACT
� CONDUIT NL NIGHT LIGHT
CATV CABLETELEVISION NTS NOTTOSCALE
CUH CABWETUNITHEATER PVC POLYVINYLCHLORIDE
CKT CIRCUIT P PHASE (POLE)
Cu COPPER TTB TELEPHONE TERMINALBOX
E EXISTING TYP TYPICAL
EF EXHAUSTFAN UON UNLESSOTHERWISENOTED
ELEC ELECTRICAL UV UNITVENTILATOR
EM EMERGENCV V VOLTS
EMT EMERGENCVMETALLICTUBING VAV VARIABLEAIRVOWME
FCU FAN COIL UNIT VIF VERIFY W FlELD
G GROUND W WATTS
GFI GROUND FAULT INTERRUPTER WC WATER COOLER
GRC GALVANIZEDRIGIDCONDUIT WP WEATHERPROOF
HP HORSEPOWER UH UNITHEATER
� JUNCTIONBOX UNO UNLESSNOTEDOTHERWISE
KVA KILOVOLTAMPERE
ELECTRICAL LEGEND
LIGHTING
�A
�
A NL
. .:,
H
�
�
a�3
Y4
�OS
�P
YD
1:d
1�1
�
LIGHTING FIXTURE. REFER TO FIXTURE SCHEDULE LETTER INDICATES TVPE.
EMERGENCY LIGHTING FIXTURE WITH EMERGENCYBALLAST. "NC' INDICATES
NIGHT LIGHT CIRCUIT. FULL LUMEN OUTPUT MINIMUM 1400 LUMENS ON LAMP.
LIGHTING FIXTURE LETTER INDICATESTVPE.
EMERGENCV LIGHTING FIXTURE WITH EMERGENCV BALLAST.OR POWERED
THROUGH INVERTER SVSTEM.
CEIL W G MOUNTED EXIT SIGN. REFER TO FlXTURE SCHEDULE SHADED AREA
DENOTES FACE OF UNIT. CONNECT TO LOCAL UNSWITCHED LIGHTING
CIRCUIT.
WALL MOUNTED EXIT SIGN. REFER TO FIXTURE SCHEDULE.
SHADED AREA DENOTES FACE OF UNIT. CONNECT TO LOCAL
UNSWITCHED LIGHTWGCIRCUIT.
SWGLE POLE WALL SW ITCH. 120/2�� VOLT, 20 AMP. 44" AFF.
THREE WAY WALL SW ITCH. 120/2��V, 20 AMP.44" AFF
FOUR W AV WALL SW ITCH. 120/2]N, 20 AMP. 44" AFF
OCCUPANCY SENSOR W ALL SW ITCH. 120/2��V, 20 AM P. 44" AFF
S W GLE POLE WALL SW ITCH W ITH PILOT LIGHT. 120/2��V, 20 AMP. 44" AFF
DIMMER SVSTEM CONTROL STATION. REFER TO DWG
OCCUPANCVSENSOR.
EXTERIOR LIGHT FIXNRE.
ER - EXISTWG TO REMAIN.
PLi - NEW FIXTURE. REFER TO FIXTURE SCHEDULE.
POWER
DUPLEX RECEPTAQE 120 VOLT, 20 AMP. 16" AFF UNO.
DUPLEX RECEPTACLE MOUNTED AT 44" OR ABOVE BACKSPLASH. 120 VOLT,
DOUBLE DUPLEX RECEPTACLE 120 VOLT, 20 AMP. 16" AFF UNO.
120 VOLT DOUBLE DUPLEX, 20 AMP RECEPTACLE MOUNTEo AT 44" AFF OR 4"
(� DUPLEX RECEPTACLE W ITH GROUND FAULT PROTECTION. 120 VOLT, 20 AM P.
TYWp 18"AFFUNO.
GFl � WEATHERPROOF OUTLET BOX.
�IG 120 VOLT DUPLEX, 20 AMP, ISOLATED GROUND RECEPTACLE.
120 VOLT DUPLEX , 20 AM P RECEPTACLE CEILING MOUNTED IN NV
��� POCKETfOUTLETFORPROJECTORREFERTOLVDRAWWGSFOR
U FWSH FLOOR DUPLEXRECEPTACLE W FLOOR BOX.
O PT POKE THRU FWSH FLOOR DEVICE WITH POWER, DATAAND NV.
P-POWER
� 120VOLTSWGLE20AMPRECEPTACLE.
\/
�
�
P/P1 \L2�1
' \
0
W C}y
�LV
BAS
�
-ll�
L��I
IC�
�
�CTIONAL HP MOTOR STARTER W ITH THERMAL OVERLOADS.
CTRICAL MOTOR.
ICATES FINAL CONNECTION REpUIRED.
dERUN TO PANELBOARD. NOTION INDICATES PANEL AND CIRCUIT
ABER. (ALL CONDUCTORS SHALL BE#10 UNLESS NOTED OTHERWISE.)
CTRICAL PANELBOARD.
ICTION BOX.
VOLT20AMP DUPLEX, GFI RECEPTACLE FOR ELECTRIC WATER COOLER.
�RDINATE INSTALLATION WITH PLUMBWG CONTRACTOR.
TFORM LIGHTING CONTROL PANEL.
_DING AUTOMATION CONTROL PANEL.
O
❑U
0
�
O
O
SD
FACP
FAAP
�I/
❑F
WPU
�
RPS
❑Z
L
KB
SD
L
C
�
�^
rr
OG
• F
•S
/�\
�
FIRE ALARM
FIRE ALARM PULL STATION. 44" AFF.
FIRE ALARM HORN/STROBE. 80" AFF.
VALVE SUPERVISORV SW ITCH PROVIDED BV OTHERS.
W ATERFLOW SW ITCH PROVIDED BV OTHERS.
FlRE ALARM DUCT MOUNTED SMOKE DETECTOR. S= SUPPLY, R= RETURN
- COORDINATE WITH DUCTWORK. MAKE SAMPLING TUBE FULL WIDTH OF
DUCT W LENGTH.
FIRE ALARM CEILWG MOUNTED SMOKE DETECTOR.
FIRE ALARM CEILING MOUNTED HEAT DETECTOR.
SMOKE DAMPER. PROVIDE SMOKE DETECTOR FOR DAMPER OPERATION AND 120
VOLTPOWERCONNECTIONASSHOWNONTHEPOWERDRAWINGS.COORDINATE
ALL CONNECTIONS W ITH MECHANICAL CONTRACTOR. CONNECT TO ALARM
SVSTEM.
FIRE ALARM CONTROL PANEL.
FlRE ALARM ANNUNCIATOR PANEL.
FlRE ALARM STROBE 80" AFF.
EXTERIOR FIRE ALARM BELL W P- W EATHERPROOF
MAGNETIC DOOR HOLD OPEN.
FIRE ALARM REMOTE POWER SUPPLV
RRE ALARM MOMTOR MODULE
FIRE ALARM PRESSURE SW ITCH.
FIRE ALARM CONTROL RELAV MODULE.
END OF THE LWE RESISTOR.
KNOX BOX WITHALARM CONTACT.
DUCT MOUNTED SMOKE DAMPER BV MECHANICAL CONTRACTOR. PROVIDE A DL
MOUNTED SMOKE DETECTOR, W ITH RELAV BASE, MOUNTED W ITHIN 5'-0" OF THE
DAMPER W ITH NO AIR OUTLETS OR INLETS BETW EEN THE DETECTOR AND THE
DOOR ACCESS
ELECTRIC DOOR STRIKE.
DOOR SW ITCHICONTACT.
KEV OR KEVCARD ACTIVATED SW ITCH IN TAM PER PROOF ENCLOSURE.
W P - W EATHERPROOF.
JUNCTION BOX
HANDICAP DOOR ACCESS BUTTON IN FLUSH WALL BOX.
GROUNDING
GROUND ROD 3/4" DIA. x 10' LONG
GROUND CABLE EXOTHERMIC W ELD CONNECTION TO REBAR ROD IN CONCRETE
FOOTER.
GROUND CABLE EXOTHERMIC WELD CONNECTION TO BUILDWG
STEEL.
UNDERGROUNDCOPPERCABLE.
LIGHTNING PROTECTION
LIGHTNWG PROTECTION CABLE.
LIGHTNING PROTECTIONAIRTERMINAL.
GENERAL
DETAIL# DETAILREFERENCETAG
DRAW ING # REFER TO DETAIL SHEETS
KEVNOTE FOR DRAW WG
DETAIL REFERENCE TAG (SECTION)
RGROl1ND HIGH VOLTAGE OR SECONDARV SERVICE FEED. 1 DOOR OR CABLETRAV CONFlGURATION DETAIL REFERENCE TAG
LETTER NEXT TO TAG REFERS TO SPECIFIC DOOR OR CABLETRAV
iV�ISCONNECTSWITCH (NON-FUSED). E402 B LAVOUT.
CONFlGURATION INDICATED IN DETAIL.
iV DISCONNECT SW ITCH (FUSED). MECHANICAL EpUI PMENT TAG. REFER TO EpUIPM ENT DATA
EF-1 SCHEDULE.
31NATION MOTOR STARTER/DISCONNECT.
HOA SWITCH AT UNIT (FUSIBLE).OR (CIRCUIT BREAKER FOR ELEVATOR).
DATA AND COMMUNICATION
v DATAICOMMUNICATIONOUTLET.TWOPORTSREFERTODETAILFOR
MOUNTWG RWUIREMENTS.
�W WALLPHONE54"AFF.
� DATA WTLET. i6" AFF.
�q DATNCOMMUNICATION.FOURPORTDATA,i6"AFF.
�6 DATNCOMMUNICATION.SIXPORTDATA,i6"AFF.
�
CABLE TRAV ABOVE CEILWG.
WIRELESSACCESSCONNECTIONPOWTWITH CEILINGMOUNTEDCISCO
�Wqp WIRELESSDEVICE.
-COM- UNDERGROUNDCOMMUNICATIONDUCT.
RELEASED FOR CONSTRl1CTI0N
Su6jec� �o compliance with all regula�ions
of Sla�e antl Local Codes
City of Carmel
�i
`��¢m�' lamn�Ml1 �
DATE: O1IZZ/ZO
02/22/18 - GARAGE PERMIT
�J�
�
WOOLPEQT
R0.CXREttU0.E�H61HEE0.1H616E09PRTIRL
76351nteractive Way
Suite 100
� Indianapolis, IN
462%a
317.299.7500
FAX: 317.291.5805
�y
��
��.
ty
�j
' ., � v1 I�i��
�.:NFC,ISTFj�F'
���Q
�.:�' 6Gi;sp:ii(:
�'�' ._J �, ��,,., .�.
��r."'.!ArDL� �
�^
i^`
W
�
�
O
W
�^`
W
�
�
U �
J•�
J �
� K
y--�
� U =
�
� � �
c
m
Q O �
� �
�
� � �
� o`
> N M
V/ � O
� �
N�
� U m
� Q! `o `m
c o
� � � o�
L L � -
N N
�
U � C� _ �
Proj. No.: 074904
Date: 03/OS/1 S
A Sheet Name:
ELECTRICAL LEGEND,
GENERALNOTES,AND
ABBREVIATIONS
E�-001