SEQUENCE OF OPERATIONS
ELECTRIC UNIT HEATERS (UH-1 THRU UH-9)
FAN:
1. THE FAN SHALL CVCLE ON A CALL FOR HEATMG.
HEATING ELEMENT:
L ON A FALL BELOW THE SPACE HEATMG SET POINT OF 60°F(ADJ-), THE
HEATER SHALLTURN ON UNTIL SPACE HEATMG SET POINT IS SATISFIED.
MONITORMG AND CONTROL POINTS (MINIMUM LISTED, PROVIDE ADDITIONAL
POINTS AS NECESSARV TO PROVIDE THE SPECIFIED SEQUENCE OF OPERATION).
1. FAN STATUS
2 FAN ON/OFF
3. SPACETEMPERATURE
4. SENSOR NORMIFAIL STATUS
EXHAUST FANS (EF-1 THRU EF-6)
1. THREELEADEXHAUSTFANSSHALLRUNCONTINUOUSLVATMINIMUM
SPEED. TWO GROUPS OF LEAD EXHAUST FANS SHALL ROTATE WEEKLV
BETWEEN EF-1, EF3, EF-5 AND EF2, EF-4, EF-6-MINIMUM GARAGE
EXHAUST CFM SHALL NEVER DROP BELOW 8,150 CFM TOTAL.
2 WHEN CARBON MONOXIDE LEVELS OF 25 PPM OR GREATER ARE
SENSED, LEAD EXHAUST FANS SHALL RAMP UP TO 50 % FOR 5 MINUTES
(ADJ.) TO REDUCE LEVELS BELOW 25 PPM. AFTER 5 MINUTES IF THE CO
LEVELS ARE ABOVE 25 PPM THE LEAD FANS SHALL RAMP UP TO 80 % FOR
10 MINUTES (ADJ.). ONCE CO LEVELS HAVE BEEN REDUCE TO BELOW 25
PPM, THE LEAD EXHAUST FANS SHALL STAY CONSTANT FOR 20 MINUTES
BEFORE RAMPING BACK DOWN TO MINIMUM SPEED.
3. IF THREE LEAD EXHAUST FANS REACH 80% SPEED WITHOUT
MAMTAINING CO CONCENTRATION FOR 10 MINUTES (ADJ.), THE LEAD
EXHAUST FANS SHALL RAMP DOWN TO 50 % SPEED W HILE THE
REMAIN ING THREE LAG FANS SHALL START AT 50 % SPEED. ALL FANS
SHALL SIMULTANEOUSLV RAMP UP FROM 50 o AS NEEDED TO MEET
AND MAINTAIN CO CONCENTRATION LEVELS BELOW 25 PPM. ONCE CO
LEVELS ARE REDUCEDTO BELOW 25 PPM, THE FANS SHALL REMAIN
CONSTANT FOR 20 MINUTES (ADJ.). AFTER 20 MINUTES, ALL FANS
SHALL RAMP DOWN TO 50% SPEED.ONCE THE FANS HAVE RAMPED
DOW N TO 50 % SPEED AND CO LEVELS ARE BELO W 25 PPM, TH E LAG
FANS SHALL TURN OFFAND LEAD FANS SHALL RAMP DOWN TO
MINIMUM SPEED.
ALARMS'
ALARMS (MINIMUM LISTED , PROVIDE ADDITIONAL POINTS AS NECESSARY TO
PROVIDE THE SPECIFlED SEpUENCE OR OPERATION)
L FAN FAILURE (DRNE OR MOTOR)
MONITORMG AND CONTROL POINTS (MINIMUM LISTED, PROVIDE ADDITIONAL
POINTS AS NECESSARV TO PROVIDE THE SPECIFIED SEQUENCE OF OPERATION)
1. FAN STATUS
2 FAN ENABLNDISABLE
3. FANVARIABLEFREQl1ENCVDRNEOl1TPl1T(%)
7 I 8 I 9
FAN SCHEDULE MARK NO: EF
PLAN ESP WHEEL ELECTRICAL
MARK TVPE SERVICE CFM �.WC) SRE DRIVE SONES NOTES
HP VOLT PHASE
EF-1 GREENHECKMODELSE2-48 GARAGE 21,8]5 025" - DIRECT 40 3 480 3 1,2,3,4,5,6
EF2 GREENHECKMODELSE2-48 GARAGE 21,8]5 025" - DIRECT 40 3 480 3 1,2,3,4,5,6
EF3 GREENHECKMODELSE2-48 GARAGE 21,8]5 025" - DIRECT 40 3 480 3 1,2,3,4,5,6
EF-4 GREENHECKMODELSE2-48 GARAGE 21,8]5 025" - DIRECT 40 3 480 3 1,2,3,4,5,6
EF-5 GREENHECKMO�ELSE2-48 GARAGE 21,8]5 025" - �IRECT 40 3 480 3 1,2,3,4,5,6
EF-6 GREENHECKMO�ELSE2-48 GARAGE 21,8]5 025" - �IRECT 40 3 480 3 1,2,3,4,5,6
NOTES:
1 PROVIDE WITH MOTORSAFETV GUARDHOl1SING WITH BIRDSCREEN
2 VARIABLE FREQl1ENCV �RIVE
3 PROVIDE MANUFACTURER APPROVED SUSPENSION WITH VIBRATION ISOLATION
4 INTERFACE WITH CO MONITORSVSTEM
5 PROVIDEDISCONNECTSWITCH.INSTALLEDBVE.C.
6 WALLHOUSMG
ELECTRIC HEATER SCHEDULE MARK NO: UH
P�AN ELECTRICAL DIMENSIONS
MARK ARFA MFR MODEL TVPE CFM KW NOTES
SERVED VIPH MCA LENGTH HEIGHT DEPTH RECESS
UH-1 STAIRWELL MARKEL 3450 WALL 245 5 208/3 - 141/4" 231/i6" 41/4" VES 1,2,4,5
UH-2 STAIRWELL MARKEL 3450 WALL 245 5 208/3 - 141/4" 231/i6" 41/4" VES 1,2,4,5
UH3 STAIRWELL MARKEL 3450 WALL 245 5 208/3 - 141/4" 231/i6" 41/4" VES 1,2,4,5
UH-4 STAIRWELL MARKEL 3450 WALL 245 5 208/3 - 141/4" 231/i6" 41/4" VES 1,2,4,5
UH-5 STAIRWELL MARKEL 3450 WALL 245 5 208/3 - 141/4" 231/i6" 41/4" VES 1,2,4,5
UH-6 STORAGEROOM MARKEL UH SUSPENDED 400 5 480/3 - 20" 13" 11" NO 1,2,3,5
UH4 STORAGEROOM MARKEL UH SUSPENDED 400 5 480/3 - 20" 13" 11" NO 1,2,3,5
UH-8 STORAGEROOM MARKEL UH SUSPENDED 400 5 480/3 - 20" 13" 11" NO 1,2,3,5
UH-9 STORAGEROOM MARKEL UH SUSPENDED 400 5 480/3 - 20" 13" 11" NO 1,2,3,5
NOTES:
1 INTERNAL TEMPERATURE DOUBLE POLE THERMOSTATICIRCUIT BREAKER DISCONNECT
2 DISCONNECT PROVIDED BV E.C.
3 PROVIDE WALL MOUNTMG BRACKET
4 PROVIDE RECESSED WALL MOUNT KIT
5 NEMA PREMIUM EFFlCIENCV MOTOR
LOUVER SCHEDULE MARK NO: L
BASIS OF DESIGN
MARK DESCRIPTION MOUNTING FINISH MATERWL ACCESSORIES NOTES
MFR MODEL
Li AREAWELLLOUVER AIROLITE K6]]6 WALL KVNAR AWM. - �,p
NOTES:
1 COLORTOBESELECTEDBVARCHITECTFROMMANUFACTURERSTANDARDCOLORS.
2 PROVIDE W ITH BIRDSCREEN
02/22/18 - GARAGE PERMIT
,._ ��S� +
♦ 1 V
WQ�i3LRE C2T
]RCXRECTVRE�HpMEERIHpIpEWPfiIfL
76351nteractive Way
Suite 100
� Indianapolis, IN
46278
317.299.7500
FAX: 317.291.5805
F
E
�:
C
1:3
-.�.1 n PiJ(,
::�FiilSi�q�
i��U
� �� (j(iiir^��i�i(.'
ci. � ,
�
�A`
W
�
O
W
�^
�
�
�
U �
J•�
J �
�U
� �
�- O
o �
�
^>l�W
� �
� �
U �
�
�
�
L
c�
�
�
�
m
�
�
0
N
N (h
� O
N
N�
U �p
c
`o m
c -o
o c
N N
��
��
� U
Proi. No.: 074904
Date: 02/22/18
A Sheet Name:
HVAC SCHEDULES &
SEQUENCE OF
OPERATIONS
_ N❑ P-601
�� Jssuances: