Loading...
HomeMy WebLinkAboutMP-601-HVAC-SCHEDULES-&-SEQUENCE-OF-OPERATIONS-Rev.1� Q Z ro � m � � J a x U w � m m m m C� v 0 w v � m K E � c U 0 a 1 RELEASED FOR CONSTRl1CTI0N Su6jec��o compliance with allregula�ions of Sla�e antl Local Codes City of Carmel Y�, : m v.i \ o;, v�Ativ. J�.�. DATE: OIIZZIZO f`J 3 G! 5 I 6 SEQUENCE OF OPERATIONS ELECTRIC UNIT HEATERS (UH-1 THRU UH-9) FAN: 1. THE FAN SHALL CVCLE ON A CALL FOR HEATMG. HEATING ELEMENT: L ON A FALL BELOW THE SPACE HEATMG SET POINT OF 60°F(ADJ-), THE HEATER SHALLTURN ON UNTIL SPACE HEATMG SET POINT IS SATISFIED. MONITORMG AND CONTROL POINTS (MINIMUM LISTED, PROVIDE ADDITIONAL POINTS AS NECESSARV TO PROVIDE THE SPECIFIED SEQUENCE OF OPERATION). 1. FAN STATUS 2 FAN ON/OFF 3. SPACETEMPERATURE 4. SENSOR NORMIFAIL STATUS EXHAUST FANS (EF-1 THRU EF-6) 1. THREELEADEXHAUSTFANSSHALLRUNCONTINUOUSLVATMINIMUM SPEED. TWO GROUPS OF LEAD EXHAUST FANS SHALL ROTATE WEEKLV BETWEEN EF-1, EF3, EF-5 AND EF2, EF-4, EF-6-MINIMUM GARAGE EXHAUST CFM SHALL NEVER DROP BELOW 8,150 CFM TOTAL. 2 WHEN CARBON MONOXIDE LEVELS OF 25 PPM OR GREATER ARE SENSED, LEAD EXHAUST FANS SHALL RAMP UP TO 50 % FOR 5 MINUTES (ADJ.) TO REDUCE LEVELS BELOW 25 PPM. AFTER 5 MINUTES IF THE CO LEVELS ARE ABOVE 25 PPM THE LEAD FANS SHALL RAMP UP TO 80 % FOR 10 MINUTES (ADJ.). ONCE CO LEVELS HAVE BEEN REDUCE TO BELOW 25 PPM, THE LEAD EXHAUST FANS SHALL STAY CONSTANT FOR 20 MINUTES BEFORE RAMPING BACK DOWN TO MINIMUM SPEED. 3. IF THREE LEAD EXHAUST FANS REACH 80% SPEED WITHOUT MAMTAINING CO CONCENTRATION FOR 10 MINUTES (ADJ.), THE LEAD EXHAUST FANS SHALL RAMP DOWN TO 50 % SPEED W HILE THE REMAIN ING THREE LAG FANS SHALL START AT 50 % SPEED. ALL FANS SHALL SIMULTANEOUSLV RAMP UP FROM 50 o AS NEEDED TO MEET AND MAINTAIN CO CONCENTRATION LEVELS BELOW 25 PPM. ONCE CO LEVELS ARE REDUCEDTO BELOW 25 PPM, THE FANS SHALL REMAIN CONSTANT FOR 20 MINUTES (ADJ.). AFTER 20 MINUTES, ALL FANS SHALL RAMP DOWN TO 50% SPEED.ONCE THE FANS HAVE RAMPED DOW N TO 50 % SPEED AND CO LEVELS ARE BELO W 25 PPM, TH E LAG FANS SHALL TURN OFFAND LEAD FANS SHALL RAMP DOWN TO MINIMUM SPEED. ALARMS' ALARMS (MINIMUM LISTED , PROVIDE ADDITIONAL POINTS AS NECESSARY TO PROVIDE THE SPECIFlED SEpUENCE OR OPERATION) L FAN FAILURE (DRNE OR MOTOR) MONITORMG AND CONTROL POINTS (MINIMUM LISTED, PROVIDE ADDITIONAL POINTS AS NECESSARV TO PROVIDE THE SPECIFIED SEQUENCE OF OPERATION) 1. FAN STATUS 2 FAN ENABLNDISABLE 3. FANVARIABLEFREQl1ENCVDRNEOl1TPl1T(%) 7 I 8 I 9 FAN SCHEDULE MARK NO: EF PLAN ESP WHEEL ELECTRICAL MARK TVPE SERVICE CFM �.WC) SRE DRIVE SONES NOTES HP VOLT PHASE EF-1 GREENHECKMODELSE2-48 GARAGE 21,8]5 025" - DIRECT 40 3 480 3 1,2,3,4,5,6 EF2 GREENHECKMODELSE2-48 GARAGE 21,8]5 025" - DIRECT 40 3 480 3 1,2,3,4,5,6 EF3 GREENHECKMODELSE2-48 GARAGE 21,8]5 025" - DIRECT 40 3 480 3 1,2,3,4,5,6 EF-4 GREENHECKMODELSE2-48 GARAGE 21,8]5 025" - DIRECT 40 3 480 3 1,2,3,4,5,6 EF-5 GREENHECKMO�ELSE2-48 GARAGE 21,8]5 025" - �IRECT 40 3 480 3 1,2,3,4,5,6 EF-6 GREENHECKMO�ELSE2-48 GARAGE 21,8]5 025" - �IRECT 40 3 480 3 1,2,3,4,5,6 NOTES: 1 PROVIDE WITH MOTORSAFETV GUARDHOl1SING WITH BIRDSCREEN 2 VARIABLE FREQl1ENCV �RIVE 3 PROVIDE MANUFACTURER APPROVED SUSPENSION WITH VIBRATION ISOLATION 4 INTERFACE WITH CO MONITORSVSTEM 5 PROVIDEDISCONNECTSWITCH.INSTALLEDBVE.C. 6 WALLHOUSMG ELECTRIC HEATER SCHEDULE MARK NO: UH P�AN ELECTRICAL DIMENSIONS MARK ARFA MFR MODEL TVPE CFM KW NOTES SERVED VIPH MCA LENGTH HEIGHT DEPTH RECESS UH-1 STAIRWELL MARKEL 3450 WALL 245 5 208/3 - 141/4" 231/i6" 41/4" VES 1,2,4,5 UH-2 STAIRWELL MARKEL 3450 WALL 245 5 208/3 - 141/4" 231/i6" 41/4" VES 1,2,4,5 UH3 STAIRWELL MARKEL 3450 WALL 245 5 208/3 - 141/4" 231/i6" 41/4" VES 1,2,4,5 UH-4 STAIRWELL MARKEL 3450 WALL 245 5 208/3 - 141/4" 231/i6" 41/4" VES 1,2,4,5 UH-5 STAIRWELL MARKEL 3450 WALL 245 5 208/3 - 141/4" 231/i6" 41/4" VES 1,2,4,5 UH-6 STORAGEROOM MARKEL UH SUSPENDED 400 5 480/3 - 20" 13" 11" NO 1,2,3,5 UH4 STORAGEROOM MARKEL UH SUSPENDED 400 5 480/3 - 20" 13" 11" NO 1,2,3,5 UH-8 STORAGEROOM MARKEL UH SUSPENDED 400 5 480/3 - 20" 13" 11" NO 1,2,3,5 UH-9 STORAGEROOM MARKEL UH SUSPENDED 400 5 480/3 - 20" 13" 11" NO 1,2,3,5 NOTES: 1 INTERNAL TEMPERATURE DOUBLE POLE THERMOSTATICIRCUIT BREAKER DISCONNECT 2 DISCONNECT PROVIDED BV E.C. 3 PROVIDE WALL MOUNTMG BRACKET 4 PROVIDE RECESSED WALL MOUNT KIT 5 NEMA PREMIUM EFFlCIENCV MOTOR LOUVER SCHEDULE MARK NO: L BASIS OF DESIGN MARK DESCRIPTION MOUNTING FINISH MATERWL ACCESSORIES NOTES MFR MODEL Li AREAWELLLOUVER AIROLITE K6]]6 WALL KVNAR AWM. - �,p NOTES: 1 COLORTOBESELECTEDBVARCHITECTFROMMANUFACTURERSTANDARDCOLORS. 2 PROVIDE W ITH BIRDSCREEN 02/22/18 - GARAGE PERMIT ,._ ��S� + ♦ 1 V WQ�i3LRE C2T ]RCXRECTVRE�HpMEERIHpIpEWPfiIfL 76351nteractive Way Suite 100 � Indianapolis, IN 46278 317.299.7500 FAX: 317.291.5805 F E �: C 1:3 -.�.1 n PiJ(, ::�FiilSi�q� i��U � �� (j(iiir^��i�i(.' ci. � , � �A` W � O W �^ � � � U � J•� J � �U � � �- O o � � ^>l�W � � � � U � � � � L c� � � � m � � 0 N N (h � O N N� U �p c `o m c -o o c N N �� �� � U Proi. No.: 074904 Date: 02/22/18 A Sheet Name: HVAC SCHEDULES & SEQUENCE OF OPERATIONS _ N❑ P-601 �� Jssuances: