HomeMy WebLinkAboutE-0.01 Electrical Notes Schedules and LegendsSYMBOL
�
�
W
WIRING (OUTLET) DEVICE SYMBOL LEGEND
DESCRIPTION
�UPLEX RECEPTACLE - 125 VOLT, 20 AMPERE, 2 POLE, 3 WIRE, GROUN�ING IYPE MOUME�
Ai 19' AFF UNLESS NOiE� OTHERWISE
DOUBLE �UPLEX RECEPTACLE - 125 VOLT, 20 AMPERE, 2 POLE, 3 WIRE, GROUN�ING iYPE
MOUNTE� AT 18" AFF UNLESS NOTE� OTHERWISE
GFCI GROUN� iYPE DOPLEX RECEPTACLE - 125 VOLT, 20 AMPERE, 2 POLE, 3 WIRE.
GROON�ING ttPE MOONTED AT 18' AFF ONLESS NOTE� OTHERWISE
RECEPTACLE SYMBOL WITH AO�ITIONAL SUBSCRIPT OESIGNATES IYPE OR SPECIFlC
�X RE�UIREMENTS AS FOLLOWS:
"AC" IN�ICATES MOUMED 1B" ABOVE COUMER UNLESS NOTED OTHERWISE ON
ARCHITECTURAL ELEVATIONS
"c° FwsH cEiuNc uouNrEo oR iz' neovE wiNoow
"+48' RECEPTACLE MOUME� AT HEIGHT IN�ICATE�
"WP" WEATHERPROOF 'WMLE-IN-OSE' (HUBBELL NWP26MJ COVER
O PLOOR MOIINTED OUTLET POKE THROOGH DEVICE:
WIREMOLD EVOLUTION 6ATCBK RECESSED POKE THRU ASSEMBLY OR APPROVED EOUAL, W/ (1)
20 AMP DUPLE% RECEPTAQE, (3) DATA JACKS AND (i) AV JACK FOR HDMI CONNECTION. G.C.
TO PROVIDE ALL �EVICE PLATES. PROVI�E 1-1/4" CON�WT TO THE °AV" MUD RING, AN�
CONDUIT AS REQUIRED FOR POWER AND DATA WHICH WILL TERMINATE ABOVE THE CEILING AT
THE NEAREST PARTITION BY G.C.�S ELECTRICAL CONTRACTOR. AV TERMINATIONS BY THE AV
VENDOR.
4 WALL MOUNiE� POWER OUiLEf (4-11�16° SQUARE x 2-1�8" �EEP JUNCiION BO%)
COMPLEiE WITH SINGLE GANG �EVICE RING AN� COVER PIAiE (WLOR SELECiION 9Y
ARCHITECT) TO ACCEPI FURNIIURE WHIP. PROVI�E ALL NECESSARY APPURTENANCES
INCWDING WHIP IF REQUIRE� AND MAHE FINAL WNNECilONS i0 SYSIEMS fURNIiURE MOUNi
AT B° AEF. UNLESS N01ED OIHERWISE.
4 WALL MOUME� TELECOMMONICATIONS JUNCiION BOX FOR WNNECTION TO SYSTEMS
FURNITURE. JUNCTION BON SHALL BE 4-11/ifi" SOUARE x 2-1/8" DEEP COMPLEfE WITH
SINGLE GANG DEVICE RMG AND 1-1/4" CONDOIT WITH INSULATING BUSHING AN� PULLSTRING
STUBBE� 17 MTO ACCESSIBLE CEILING SPACE. MOUNT AT 8" AEF. UNLESS NOTE�
OTHERWISE.
AV SINGLE GANG MUD RING WRH 1W0 PULL STRINGS AT 1B" AFF WITH 1-1/4" CONDUR TO THE
FLOOR STUB BY ELECTRICAL CONTRACTOR. AV TERMINATIONS BY THE TENANT'S AV VENDOR.
AV VEN�OR TO PROVIDE RE UIRED FACEPUTES.
a
/ z iHREE(3) SIUBBE� CON�OIIS FOR POWER, �A1A AN� AV. COOR�INAIE LOCA110N WI1H
��� ARCHITECT AN� FURNITURE VEN�OR PRIOR TO CORING FOR COORDINATION WITH THE TABLE
LEG.
aawER: (oNE) i/z' coNowT sTue.
DATA: (ONE) 3/4" CONDUIT STUB
nv: (oNE) i-i/a" coNouit stue
LIGHTING CONTROLS SYMBOL LEGEND
SYMBOL
�
�x
� �
��
SYMBOL
0
DESCRIPTION
LIGHi SWIiCH. SINGLE POLE, 20 AMPERE, 120/D7 VOL7, 1HP.
ucHr swircH. "x' iNoicnrEs THE Fo��owiNc:
"3' 3-WAY IYPE
V�" WALLBOX PIR VAVANCY SENSOR WITH 0-10V DIMMMG.
ACUIIY CONTROLS: WS% P�T-0-VA-WH
CEILING MOUNiE� �UAL TECHNOLOGY OCCUPANCY SENSOR.
acuitt coNteo�s: cMe-Pot-m
TELECOMMUNICATION OUTLET SYMBOL LEGEND
�ESCRIPTION
COMBINATION VOICE/DATA OUTLEf (4-11/16" � 2-1/8" DEEP JUNCTION BOX) COMPLETE
WITH SINGLE GANG DRY WALL RING (VERIFY DRYWALL THICKNESS) MOUMED AT 18" AEF.
PROVIDE 3/4" CON�UIT WITH INSULATING BUSHING AND PULLSTRING STUBBED UP 12" INTO
ACCESSIBLE CBLING SPACE
VOICE AN��OR �AiA SYMBOL WITH A��IiIONAL SUBSCRIPi DESIGNAiES IYPE OR SPECIFIC
REQUIREMENiS AS FOlLOWS:
AC° INDICAiES MOUME� 18" ABOVE COUMER UNLESS NO1E0 01HERWISE ON
ARCHIiECiURAL EIEVATIONS
"C" FWSH CEILING MOUNIED
°+48' SPECIFIC MOUNiING HEIGHi OF DEVICE
DOOR ACCESS CONTROL SYMBOL LEGEND
SYMBOL
CR
M�
�ESCRIPTION
CARD ACCESS PROXIMIiY REA�ER FOR iENANYS SECURIIY SYSiEM BY SECURIIY VENDOR,
BACK BOX, SAFEfY GROMMEf AND PULL STRING BY G.C.$ ELECTRICAL CONTRACTOR.
MOTION RELEASE 0&ICE FOR TENANT'S SECURIN SYSTEM BY SECURIN VENDOR. OSE� TO
MTERRUPT POWER TO THE MAGNEfIC LOCK AN� SHONT THE DOOR CONTACT IN OR�ER FOR
THE ACCESS CONTROL SYSTEM TO RECOGNRE THE DOOR IS OPENING BY SOMEONE E%ITING
AN� NOT FORCEO OPEN FROM THE OUTSI�E.
CIRCUITING AND RACEWAY LEGEND
SYMBOL DESCRIPTION
----- UN�ER FLOOR OR IN-SIAB CIRCOIiING OR RACEWAY
CIRCUITRY TORNING UP
LIGHTING SYMBOL LEGEND
SYMBOL
�
�
�
DESCRIPTION
RECESSED OR SURFACE MOUME� 7x4� WMINAIRE "A" IN�ICATES IYPE; "a° IN�ICAiES
SWIiCH CONTROL REFER ID WMINAIRE SCHEDULE FOR A�DIilONA1 INFORMAiION.
RECESSE� OR SORFACE MOUNTE� 7x7 WMINAIRE. °A1" IN�ICATES ttPE; "a" IN�ICATES
SWITCH CONTROL REFER ID WMINAIRE SCHE�ULE FOR A��IiIONAL INFORMATION.
RECESSED �OWN LIGHi OR SURFACE MOUNiED CYLIN�ER.
TYPICAL DEVICE MOUNTING
FlRE AURM AU�I6LE/VISUAL AND
VISUAL ONLY SIGNALING DEVICES
RECEPTACLES BEHIND
[G',',, REFRIGERATORS AND
� � VEN�ING MACHINES
�WALL TELEPHONES
FIRE AIARM MANUAL PULL SiAiION
LIGNTING CONTROLS (CONFIRM MOUNTING HEIGHT
WI1H LOCAL CO�E REQOIREMENIS
� � VOWME WNTROLS )
�EVICES ABOVE COUMERTOP
� AN� OR BACKSPUSH
� � � �� RECEPTACLES IN MECH�ELEC �
SPACES AND ADJACENT TO � �
LAVAiORIES � � �
� �� kECEPTACLES BEHIND
p � �OMESTIC WASHERS
AN� �RYERS
�GENERAL PURPOSE � �
RECEPTACLES
n � � � RE�CE T�ACLES SERVING �
oisHwnsHER nNo
_ GARBAGE �ISPOSAL
FlNISHE� FLOOR
GENERAL ELECTRICAL NOTES
1. ALL "BWL�ING STANOARDS" AND/OR "BOILDING SPECIFlCATIONS" SHALL BE CONSIOERED AN INTEGRAL PART OP
THESE DOCUMENTS AND THE CONTRACTOR SHALL BE RESPONSIBLE TO OBTNN A COPY OF THESE DOWMENTS
AND COMPLY WITH ALL REQUIREMENTS, STANDARDS, AND SPECIFlCATIONS CONTAINED WITHIN.
2 THESE �RAWINGS ARE GENERALLY DIAGRAMMATIC AND ARE IMENDE� TO CONVEY THE SCOPE OF WORK AND
INDICATE GENERAL ARRANGEAIENT OF LIGHTING FI%TURES, DEVICES, CONTROLS, ELECTRICAL FI%TURES, MOTORS,
PANELBOARDS, EQUIPNENT, EfC. THE LOCATIONS OF ALL ITEMS SHOWN ON TNESE �RAWINGS OR CALLED PoR IN
THE SPECIFlCATIONS THAT ARE NOT DEFINITELY FlXED BY DIMENSIONS ARE APPROXIMATE THE E%ACT LOCATIONS
NECESSARY TO SECURE THE BEST CONDITIONS AND RESOLTS MOST BE �ETERMMED AT THE PROJECT. ALL
LOCATIONS OF WORK ERPOSED TO VIEW ARE SUBJECT TO APPROVAL OF THE ARCHITECT PRIOR TO ROUGH-INS.
J. THE ELECTRICAL CONTRACTOR SNALL VERIfY E%ISTING CONDITIONS TO INSURE THAT ALL NEW WORK WILL FlT INTO
THE ENISTING SiRUCTURE ANO CON�ITIONS IN THE MANNER INTENOED AN� AS SHOWN ON THE DRAWINGS. THE
CONTRAC70R SHALL NOiIFY iHE ARCHIiECi�OWNERS REPRESENiATIVE PRIOR i0 ANY ROUGH-INS, FA9RICA710NS,
OR PERFORMING ANY WORK IN iHE AREA INVOWING DIFFERENCES. N071FlCAilON SHALL BE IN iHE FORM OF A
RFI, MCLU�ING A �RAWING OR SNEfCH INDICAiING FlEID MEASUREMENiS AND NOiES REUiE� i0 THE AREA.
4. ANY �ISCREPANCIES BEIWEEN DRAWINGS AN� SPECIFlCAilONS SHALL BE PROMPiLY BROUGHi i0 iHE ATfENiION
OF THE ENGINEER FOR CURIFICAiION DURING 1HE BI��ING PERIO�. NO ALLOWANCE SHALL SUBSEQUEMLY BE
MA�E i0 iHE COMRACiOR BY REASON OF HIS FAIWRE i0 HAVE BROUGHi SAID �ISCREPANCIES i0 7HE
ATfENTION OF THE ENGMEER �URING THE BIO�ING PERIO� OR OF ANY ERROR ON THE CONTRACTOR'S PART.
5. ALL EQUIPMENT SHALL BE WSTALLE� IN A NEAT, PROFESSIONAL AN� WORKMANLIKE MANNER, RECTILMEAR TO
FINISHES AN� BUIL�ING STRUCTURE.
6. ALL COMPONENTS SHOWN ON THE RISER/ONE-LME �IAGRAMS, BOT NOT ON THE PIAN OR VICE VERSA, SHALL BE
INCLU�ED AS IF SHOWN ON BOTH.
7. REFER TO ARCHITECTURAL ELEVATIONS TO DERNE E%ACT LOCATIONS OF ALL RECEPTA0.E5, OUTLEfS/JACKS,
SWITCHES, WALL AN� PENOANT/CABLE MOUME� WMINAIRES, ETC. WMINAIRES AND CEILING MOUNTE� EQUIPMENT
sHnu eE cooRoiNn�o wiTH THE nRcwTEcruan� Rca (aEF�EcrEo cEwNc a�aNs).
8. ALL CIRCUITING SHALL BE RUN CONCEALED UNLESS SPEQFlED O7HERWISE.
9. ALL RACEWAYS RUNNING THROUGH BWLDING EXPANSION JOINTS SHALL BE EQOIPPED WITH APPROPRIATE
E%PANSION FlTTINGS.
10. CON�UIT HOME RUNS SHOWN ON THE DRAWING WITH MORE THAN (3) CURRENT CARRYING CONDUCTORS ARE
SHOWN DIAGRAMAIICALLY. THIS CONiRAC10R SHALL NOT INSTALL MORE iHAN (3) CURRENi CARRYING CON�UCiORS
IN A RACEWAY ONLESS NATIONAL ELECTRIC CO�E (N.EC), ARTICLE 310.15 DERATING FACTORS ARE APPLIED.
11. ALL LIGHTMG AND GENERAL POWER BRANCH CIRCUITS SHALL INCLU�E A SEPARATE NEUTRAL CON�OCTOR, UNLESS
SPEQFlCALLY IN�ICATEO OTHERWISE.
12 THE ELECTRICAL CONTRACTOR SHALL REFER TO THE ELECTRICAL SPECIFlCATIONS FOR ACCEPTABLE CON�UIT
NPES/LOCATIONS. ALL WNDUIT SRES ON THE DRAWINGS ARE BASE� ON THE CURRENT ADOPTED E�ITION OF THE
N.EC. CON�UR FlLL TABLES FOR ELECiRICAL MEfALLIC iUBING (E.M.i). WNDUIi SIZES SHALL BE REVISE� i0
THE SIZE REQUIRED, REIATNE TO THE ACTUAL CON�UIT ttPE TO BE INSTALLED.
13. IT IS NOT INTENDED THAT THE PLANS INDICATE ALL OBSTRUCTIONS, NECESSARY BENDS, OFFSEfS, AND PULL
BO%ES. li SHALL BE iHE RESPONSIBILIIY OF iHE CONiRACiOR i0 INSiALL HIS WORK i0 CONFORM i0 REG.
REQUIREMENTS, THE STRUCTURE, MAINTAIN HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLFAR, REFER TO
THE ARCHITECNRAL �RAWINGS FOR ALL DIMENSIONS AS REQUIRED.
14. li IS N07 INTEN�ED iHAi iHE PUNS INDICAiE ALL CON�UIi ROUiES, PULL BOXES, JUNCTION BO%ES, EfC.
CONTRACTOR SHALL BE RESPONSIBLE FOR DEfERMINING ACTUAL WNDUIT ROUTING, QUANTItt AND LOCATION OP
PULL BO%ES WITHIN ACCESSIBLE LOCATIONS.
15. PROVI�E SCREW-COVER PULL BOXES IN CON�UIi RUNS AS REQUIRED i0 LIMR iHE NUMBER OF BENDS i0 NO
MORE iHAN FOOR (4) 90' OR 360 DEGREES iOiAL SRE PULL BOXES IN ACCOR�ANCE WIiH NEC, ARiICIE
31428. DOCUMENT ON RECOR� �RAWINGS, SRE AN� LOCATION OF PULL BOXES USED M FEEDER CON�UIT
RUNS.
NOTES;
1. ALL MOUNTING HEIGHTS SHALL BE MEASURED FROM FlNISHED FLOOR TO THE CENTERLME OF DEVICE
EXCEPT FlRE AIARM STROBE LIGHT.
2 NO WIRMG DEVICE OUTLET BOXES SHALL BE MOOMED aACN TO BACK.
3. ALL MOOMING �EVICES SHALL BE INSTALLE� AT MOONTING HEIGHTS AS IN�ICATED ON THIS OETAIL
uN�Ess orHEawisE NorEo.
4. FOR ALL EL&ATIONS (WHERE APPLICABLE), CASEVlORK DEfAILS, FIRE WALLS, SMOKE WALLS, LOCATION
OF COUMERTOP RECEPTACLES, LIGHTING FIMURE SWITCHES, TELEPNONE OUTLETS, EOUIPMENT
ROUGH-INS, HEA�WALLS, EfC., SEE ARCM1ECiURAL �RAWINGS. WHERE NO ARCHIiECiURAL ELEVATIONS
OR �EfNLS OCCUR, THE ELECTRICAL CONTRACTOR SHALL USE PRACTICAL MEANS AND MEfHODS AS
WELL AS H6 FlELD KNOWLEDGE TO LOCATE DEVICES IN THE BEST SUITED AND MOST PRACTICAL
LOCATIONS FOR THE DEVICE.
i6. WHERE MULTIPLE �EVICES OF THE SAME iYPE/SNLE ARE SHOWN NEXi ID EACH OTHER, GANG TOGETHER IN A
SMGLE COVER PIATE.
17. ALL FLUSH MOUNTED PANELBOARDS SHALL HAVE THREE (3), 3/4" CONDUITS STUBBED ABOVE ACCESSABLE
CEILINGS PoR FUTURE CIRCUITS.
18. FlEL� VERIFY THE ENACT LOCATION OF MECNANICAL HVAC AND PLUMBING EOUIPMENT THAT REQUIRE ELECTRICAL
CONNECTIONS WITH RESPECTNE WNTRACTORS.
19. ALL CIRCUITS INDICATED ORIGINATING IN E%ISTING PANELBOAR�S ARE BASE� ON WFORMATION OBTAIN PRIOR TO
ANY �EMOLI710N WORK. IF A CIRCUIT NUMBER(S) INDICAiED i0 BE RE-0SED REMAINS `IN-USC' AFfER ALL
�EMOIJTION WORK IS COMPLEfE�, TERMINATE HOMERUN ON A SPARE(S) CIRCUIT BREAKER IN SAME PANEL OR
PROVI�E A NEW CIRCUIT BREAKER(S) TO MATCH EXISTING iYPE AND HOMERUN TO AVNUBLE SPACE(S) IN SAME
PANEL.
20. ALL CONDUIi SRES IN�ICATEO ARE B/SE� ON ELECiRIC MEfALLIC iU91NG (EMT). iHE ELECiRICAL CONiRACTOR
SHALL BE RESPONSIBLE FOR PROPERLY 9ZING ALL OTHER CONDUITS iYPES USED PER NEC REQUIREMENTS.
H ELLYER
LEWIS=
ARCHITECTURE
INTERIOR DESIGN
211 South 12th St.
Phila., PA 19107
215.922.7066
coN reMF ucH o�MMN�oN� �c�iNs=�c= n�
si.s cnHoinnHs. .Hs ccHcan� cnH.ancr
� cooaoirvnle n�� woarc nrvo
nxcNErFcr o�nHv�iH rHCF oF
nnFCNnNicni . Fi FcraicniF oa ai �nneiNc
. . nacrvi.eRuan�woaknrvo
aoc Eo Nc wi.H.H�woak oa
Project:
L,1bC1"ty
M UtUc'll�
NsuRnNCE
350 East 96th Street,
1 st & 2nd Floors
Indianapolis, IN 46240
Project No: 047.79
Drawn by: MB
Checked by: AM
Approved by: AM
Client Approval: Dace:
IssuedForPermits: ����5��9
Drawing:
Electrical Notes,
Schedules &
Legends
RELEASED FOR CONSTRl1CTI0N
Su6jec��o compliance with allregula�ions
of Sla�e antl Local Codes
�.. City of Carmel
`Y��m�� �\o;,N�Yw� �
DATE: O1IZ9IZO
���.''�L��s �eqF: Py':
o l o'; a'.
� �
an isr,a�s
•'. •
q', SiATE OF 1 y.
%PO '..WOIPNP..' ���.
2;
// ��,SSIONP� ENG.••••' 11
V��=.u�!' �.��
r—
No. E-0.01
Scale: NONE