HomeMy WebLinkAboutM-2.01 Mechanical Specificationsli����:��������i,���i���i��������i Su6jec��o compliance with allregula�ions of Sla�e antl Local Codes City of Carmel �i `��¢m�' lamn�Mn? � � HVAC SPECIFlCATIONS 1. GENERAL PROVISIONS A. THE PROVISIONS OF THE INSTRUCiIONS TO BI�DERS, GENERAL CON�ITIONS, SUPPLEMENTARY CONDITIONS, ALTERNATES, ADDENDA'S', AND DIVISION 1 ARE A PART OF THIS SPEqFlCAT10N. CONTRACTORS AND SUBCONTRACTORS SHALL ExAMINE SAME AS WELL AS OTHER DNISIONS OF THE SPEQFlCATIONS WHICH AFfECT WORK UNDER THIS DIVISION. 8. THIS CONTRACTOR SHALL PROVIDE ALL UBOR, EQUIPMENT, SUPPLIES, SERVICES, AN� SHALL PERFORM ALL WORK COMPLEfE AND IN STRICT ACCORDANCE WITH THIS SPEqFlCAT10N AN� APPLICABLE DRAWINGS. ANY �EVIATIONS SHALL BE CLEARLY DEFMED AND ITEMRED IN ACCORDANCE WITH SECTION 1Qf Of THIS SPECIFICATION. G THIS CONTRACTOR IS INSTRUCTED TO READ CAREfULLY THE SPEQFlCATIONS FOR ALL PARTS OF THE WORK, WHICH INCLUDE THE ARCHITECTURAL, ELECTRICAL, MECNANICAL, PLUMBING, FIRE PROTECTION, CIVIL, STRUCTURAL AND ALL OTHER DRAWINGS AS WELL AS THE SPEqFlCATI0N5 FOR ALL THE DIVISIONS THAT ARE PART OF THE CONTRACT DOCUMENTS. D. ALL ITEMS OF IABOR, MATERIAL, AND EOUIPMENT NOT SPEQFlCALLY MENTIONED �� HEREIN OR SHOWN ON PIAN, BUT INCIDENTAL T0, OR REOUIRED FOR THE COMPLEfE INSTALLATION AND PROPER OPERATION OF THE WORK, SHALL BE FURNISHED AS IF CALLED FOR IN DEfAIL BY THE SPECIFICATIONS OR �RAWINGS. E AS USED IN THIS SPEqFlCATION, 'PROVI�f' MEANS 'FURNISH AND INSTALL'. 'FURNISH"MEANS 'TO PURCHASE AND DELNER TO THE PROJECT SITE COMPLEfE WITH EVERY NECESSARY APPURTENANCE AND SUPPORT; AND 1NSTALL'MEANS 'TO UNLOAD AT THE DELNERY POINT AT THE SITE AND PERFORM EVERY OPERATION NECESSARY FOR PROPER INSTALLATION PER CODES AND MANUfACTURERS RE�UIREMENTS, TO ESTABLISH SECURE MOUNTING AND CORRECT OPERATION AT THE PROPER LOCATION IN THE PROJECT: 2.PERMITS, CODES, INSPECTIONS AND TESTS. A. THE HVAC CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AND INSPECTIONS REQUIRED FOR THE PROSECUTION OF HVAC WORK. ALL PERMITS AND CERTIFlCATES OF INSPECTION AND APPROVAL SIGNED BY THE CONTROLLING BUILDING DEPARTMENT SHALL BECOME PROPERtt OF THE OWNER 8. DRAWINGS INDICATE THE MINIMUM DESIGN REQUIREMENTS. NATIONAL, STATE, AND LOCAL CO�ES SHALL BE PoLLOWED, COMPLY WITH THE UTE4 EDITIONS OF THE STATE MECHANICAL CODE, NFPA, SMACNA, AND ASHRAE STANDARDS. 7HE CONTRACTOR SHALL INCLUDE THE COST OF SATISFYING SUCH CODES AND STANDARDS IN THE BID. C. FOLLOWING COMPLEfION OF THE HVAC WORK, FURNISH TO THE OWNER, IN DUPLICAiE, CERiIFlCAiES OF INSPECiION AND APPROVAL BY REGUlAiORY AGENCIES HAVING JURISDICTION. (1) �EMONSiRAiE i0 iHE OWNER�S SA715FACilON iHE PROPER OPERAiION OF EACH OF THE SYSTEMS COMPRISING THIS CONTRACT BEFORE FINAL PAYMEM. (2) I�AME�IATELY WRRECT ANY WORK FOUN� AT VARIANCE WIiH THESE SPECIFlCATIONS, THE NATIONAL, STATE, AN� LOCAL CO�ES, AN� REOl11REMENTS OF GOVERNING REGUUTORY AGENCIES. (3) TEST PIPING FOR LEAKS: REPAIR LEAKS IN COPPER TUBING BY SWEATING OUT JOMT; THOROUGHLY QEANING BOTH TUBE AND FIiTING, AND RESOLDERING. CORRECT LEAKS IN SCREWE� JOINT BY REPUCING THREA� OR FITTING OR BOTH. (4) PROVIDE SERVICES OF A CERiIFlE� AA.B.C. OR N.E.E.B. TESi AGENCY. CON�UCi ALL iESiS IN ACCOR�ANCE WRH ASSOCIAiEO AIR BAIANCE COUNCIL STANDAR�S. iEST AND A�JU57 AIR HAN�LING SYSTEM i0 WIiHIN 5% OF DESIGN REOUIREMENIS. S VISIi i0 iHE SRE A. iHE CONiRACiOR SHALL VISIi iHE SITE OF iHE WORK AND BECOME FAMILIAR WIiH ALL COND1710NS AFPECiING iHE WORK. iHE SUBMISSION OF A PROPOSAL SHALL PRESUPPOSE KNOWIE�GE OF ALL SUCH CON�IiIONS ANO NO A��IiIONAL COMPENSAiION SHALL BE ALLOWED WHERE EMRA IABOR OR MAiERIALS ARE REOUIRE� BECAUSE OF IGNORANCE OF iHESE CON�IilONS.. 4.PROiECiION A. iHE HVAC CONiRACiOR SHALL PROVIOE ALL NECESSARY PROiECiION FROM DIRT AND WAiER OURING CONSiRUCiION NECESSIiAiE� 9Y HVAC WORK. PROiECiION MEfHODS ARE SUBJECi 70 APPROVAL BY iHE ARCHRECi. 5.EQUIPMEN7 AN� MAiERIALS A. ALL EQUIPMENi AN� MAiERIALS SHALL BE NEW AN� SHALL CONFORM 70 UN�ERWRITERS' UBORATORIES STAN�AR�S, WHERE APPLICABLE. WHERE SPECIFlCATIONS �ESCRIBE, OR PLANS SHOW, MATERIALS OR EOl11PMENT OF HIGHER OUALIiY THAN REOUIRE� BY CODE AN� LOCAL RULING, THE DRAWINGS AN� SPECIFICATIONS SHALL GOVERN THE QUALIIY OF THE MATERIAL OR EOl11PMEM. USE� EOUIPMEM OR MAiERIALS ARE PROHIBITE� ONLESS NOTE� OTHERWISE. B. NEW OR EXISTING TO REMAW EOl11PMEM SHALL NOT BE OPERATE� �URINC CONSTRUCTION. HVAC CONTRACTOR SHALL WOR�INATE WITH OTHER TRA�ES AN� PROVI�E TEMPORARY SPACE CON�ITIONING IN OR�ER TO MAINTAIN TEMPERATURES AN� HUMI�IIY LEVELS AS REQUIRE� FOR GENERAL CONSTRUCTION. C. THE CONTRACTOR SHALL SOBMIT PROOF, IF RE�UESTED BY THE OWNER, THAT 7HE MAiERIALS, APPLIANCE$ E�UIPMENT OR DEVICES FURNISHE� AND INSTALLED 11NDER THIS CONTRACT MEET THE REOUIREMEMS OF THE UNDERWRITERS' UBORATORIES, INC. IN REGAR�S TO FlRE AND CASl1ALN HAZARDS. THE UBEL OF OR LISTING BY iHE UN�ERWRIiERS� UBORPi0RIE5, INC. WILL 9E ACCEPiE� AS WNFORMING 70 THIS REOUIREMENT. M LIEU OF THE IABEL OR LISTING, THE CONTRACTOR MAY SUBMIT INDEPENDENT PROOF SATISfACTORY TO THE ARCHITECT THAT THE MATERIAL, APPLIANCES OR DEVICES WNFORM i0 iHE PUBLISHED SiANDAR�S, INCLU�INC MEiH0�5 OF iESi FOR iHE UN�ERWRIiERS' IABORAi0RIE5 INCORPORAiE�. UN�ERWRITERS UBORATORIES, INC. AN� ITS PUBLICATIONS WILL BE REFERRE� TO HEREINAFiER BY 7HE ABBREVIATION UL WIiH OR WITHOUT ADOITIONAL IDENTIFYING SYMBOLS. 6. GIIARAMEE A. THE HVAC CONTRACTOR SHALL GUARANTEE FOR A PERIO� OF ONE YEAR THAT ALL WORK AN� EQUIPMEN7 WILL REMNN FREE FROM ALL �EFECTS IN WORKMANSHIP AN� MAiERIALS, AN� THAT IT WILL COMPLY WITH ALL THE SPEQFlC REQUIREMENTS OF THE SPECIFlCATIONS AN� OTHER COMRACT OOCOMENTS GOVERNING THE WORK. B. ALL WORK FOUN� BY THE ENGMEER TO BE OEFECTIVE WILL BE REPUCED WITH NEW WORK MEEfING ALL THE REOIIIREMENTS OF iHE CONTRACL THE HVAC CONiRACiOR WILL BEAR ALL COSiS OF SUPPLYING SUCH NEW, AN� WSiALLING AN� FlNISHING SAME, AN� WIl1 ASSUME ALL COSTS FOR REPIACING OTHER WORK �AMAGE� BY THE REMOVAL AN� REPIACEMENT OF ANY OF THE WORK. THE HVAC CONTRACTOR WILL BEAR ALL COSTS FOR FREIGHT, DRAYAGE AN� DEMURRAGE, AN� ALL IABOR IN CONNECiION iHEREWIiH. 7. COTfING, PAiCHINQ FIRESiOPPING AN� PAINiING A. iHIS COMRACiOR SHALL BE RESPONSIBLE FOR CUTfING ALL HOLES REOl11RE� FOR INSTALLATION OF HVAC WORK. HOLES SHALL BE CUT IN A NEAT MANNER SATISFACTORY TO THE ARCHITECT. B. CONTRACTOR SHALL EMPLOY AN BUILDING OWNER APPROVED ROOFING CONiRACTOR FOR ALL ROOF PENEIRATIONS. ROOF SHALL BE REPAIRE� 50 AS NOT TO V01� ROOF WARRANiY. G UNLESS NOiED OiHERWISE, ALL HOLES OR �AMAGE CAOSE� BY iHE REMOVAL OF EXISTING WORK OR THE INSTALIATION OF NEW WORK SHALL BE PROPERLY PATCHE� BY iH15 CONTRACTOR. HOLES SHALL BE NEATLY PATCHE� AND PAW7E� WITH SOITABLE MATERIAL TO MATCH E%ISTINC SURFACES. HOLES THROl1GH FLOORS OR FIRE WALLS SHALL BE SEALED WIiH iHE APPROPRIAiE INiUMESCENi CAULK, PUitt, STRIP OR SHEEf FlRE BARRIER PRO�UCT. D. FlRESTOP SVSTEM (REOUIRED FIRESTOPPING �AATERIALSJ SHALL BE DEfERMINED BY THE WALL OR FLOOR/CEILING ASSEMBLY AND PENEfRATION IYPE AND SHALL BE UL LISTED AND TE4ED IN ACCORDANCE WITH ASTM E814, PIRE RATING OF THE FIRESTOP SY4EM SHALL BE EQUIVALENT TO THE ASSEMBLY WHICH IS PENEfRATED. E ACCEPTABLE FIRE BARRIER PRODUCTS: HILTI "FS-ONE" NELSON FLAMESEAL" OR APPROVED EQUAL AS MANUFACTURED BY 3M. 8. CLEANING AND PAINTING A. 0.EAN NEV! PIPING AFfER WORK IS COMPLEfE TO REMOVE PIPE DOPE LOOSE MILL SCALE, AND OTHER EXTRANEOUS MATERIALS. 8. TOUCH UP AND REPAIR ANY DAMAGE� FACTORY FINISHES ON EQUIPMENT AND MATERIALS FURNISHED. OTHER PAINTING WILL BE DONE UNDER THE PNNTING DIVISION OF THE SPECIRCATIONS. C. ALL E%ISTING AIR DISTRIBUTION DEVICES THAT ARE TO BE REUSED SHALL BE 0.EANED WITH MIL� SOAP AND WATER SOLUTION AND THOROUGHLY DRIED. D. ALL EXISTING TO REMAIN HVAC SYSTEMS SHALL BE CLEANED PER CURRENT NA710NAL AIR DUCi CLEANING ASSOCIAiION GENERAL SPECIFlCATIONS. 9. COORDINAiION ANO CON�UCT OF WORK A. HVAC DRAWINGS ARE DIAGRAMMAiIC, INOICATING GENERAL ARRANGEMEN7, APPROXIMATE SIZES, GENERAL LOCATIONS OF EOUIPMENT AND PIPING. VERIFY �IMENSIONS M FlELO; A�JUST TO MANUFACTURER'S SHOP �RAWINGS. �0 NOT sca�e oanwiNcs. B. ALL REQUESiS FOR INFORMATION SUPPLEMENTAL TO THE CONSiRUCTION �OCl1MEN7S SHALL BE SUBMIiTEO IN WRI7ING i0 iHE ARCHIiECT FOR �ISiRIBOiION i0 1HE APPROPRIATE PAR7Y(S). C. �RAWINGS AN� SPECIFlCATIONS ARE TO BE CONSI�ERED AS SUPPLEMENTING EACH OTHER. WORK SPECIFlE� BUT NOT SHOWN, OR SHOWN Bl1T NOT SPECIFlE�, SHALL BE PERFOR�AED OR FORNISHE� AS THOUGH MENTIONED IN BOTH SPECIFlCATIONS AN� �RAWMGS. 0. ANY �ISCREPANCIES BE7WEEN THE �RAWINGS AN� SPECIFlCATIONS SHALL BE BROUGHT TO THE ATiENTION OF THE ARCHITECT AN� ENGINEER. E. ARCHITECTURAL AND STRUCTORAL �RAWINGS SUPERSEDE HVAC DRAWINGS. DETERMWE THAT WORN OF THIS �IVISION CAN BE ACCOM�AO�ATE� WITHIN SPACES PROVIDE�. NOTIfY ARCHITECT OF ANY IMERFERENCE BEFORE STARTING INSTALLATION. F. DHERMWE SRE$ LOCATIONS FOR CHASES AN� OPENINGS NECESSARY FOR INSTALLATION OF HVAC WORK, COOPERATE WITH OTHER TRADES IN PROVIDING SLEEVES, INSERTS AN� HANGERS. G. COORDINATE THIS WORK WITH ALL TRA�ES. ARRANGE OPERATIONS SO AS NOT TO �EIAY COMPLEfION OF INSTALLATION OF ANY PARTS OF INTERREUTE� WORK 50 THAT WNSTROCTION MAY PROCEE� ON SCHE�ULE. H. COOPERATE WITH ALL TWIDES IN PREPARING WTERFERENCE DRAWINGS FOR AREAS WHERE THERE IS POSSIBLE CONFLICT BER4EEN TRADES EXACT LOCATION OF PIPES, DOCTS AND EQl11PMENT SHALL BE BASEO ON FlEL� MFASUREMENT WIiH FlNAL ARRANGEMENT DEfERMWED BY INTRA-TRADE AGREEMENTS SUBJECT TO ARCHITECT'S APPROVAL. L ARCHIiECi RESERVES iHE RIGHT TO MAKE REASONA9LE CHANGES IN INDICAiED LOCATIONS WIiHOUi EX�RA WSi i0 THE OWNER. J. ALL WORK SHALL BE INSiALLE� IN NEAi AND WORKMANLIKE MANNER BY FlRS1-CVSS MECHANICS. iHE CONIRACTOR SHALL PROVIDE A�EOUAff AND COMPEfENT SUPERVISION OF THE JOB AS RE�UIRED. K. DUCTNORK, PIPING AND EQUIPMENT SHALL BE ARRANGED SUBSTANTIALLY AS INOICATE�. ANY CHANGE RESULiING IN A SAVINGS IN LABOR OR MAiERIAL SHALL BE MADE ONLY IN ACCORDANCE WIiH A CONiRACi CHANGE ORDER. DEVIAiIONS SHALL BE MA�E ONLY WHERE NECESSARY i0 AVOID INiERFERENCES AND ONLY AFTER DRAWINGS SHOWING THE PROPOSED DEVIATIONS HAVE BEEN SUBMITfED TO ANO APPROVED BY iHE ARCH17ECi. L COOR�INAiE ALL SHUiDOWNS OF ANY HVAC SYSiEM IN A�VANCE WIiH 7HE OWNER. SUBMIiTALS A. PROVI�E A MINIMOM OF SIX (6) SETS OF SHOP �RAWINGS/SOBMITfALS FOR ALL SCHEDOLED AN�/OR SPEQFlED E�UIPMENT FOR APPROVAL 6Y THE ARCHITECT AND ENGMEER. WFORMATION SHALL INCWDE. BU� IS NOT LIMITED T0; CFM, HP, GPM, MBH, EER, COP, %EFF, VOLTAGE/PHASE, MCA, CONNECTION SIZES, WEIGHT, DIMENSIONS, SCHEDULED EQUIPMENT, DIFFUSERS, DAMPERS, 115TED ACCESSORIES, EfC. AND OTHER COMPONENTS REQUIRED FOR A COMPLETE INSTALLATION. B. WHERE ONLY ONE MAKE OF EQUIPMENT IS NAMED, IT SHALL BE PROVIDE AS sacariEo. C. VERBAL REOUESTS OF APPROVALS FOR ANY SUBSTITUTION WILL NOT BE BINDING ON iHE ARCHI7ECT, ENGWEER AND OWNER. �. iH15 WNiRACTOR ASSUMES ALL RESPONSI91LIlY FOR ALL COSiS FOR RE�ESIGN AN� CHANGES NECESSARY BY ALL TRADES TO ACCOMMODATE THE USE OP EQUIPMENT NOT SPEQFlED ON PROJECT �OCUMENTS. E. BIDS SHALL BE BASED UPON THE SPEqFlE� PRO�UCTS OR LISTED ALTERNATIVES. DRAWINGS AND SPECIFlCATIONS ARE BASED ON THE PRODUCTS SPECIFlED BY ttPE, MODEL, AND SIZE, AND iHUS ESiABLISH MINIMUM QUALRIES, WHICH SU65iliUTES MUST MEEf TO QUALIFY FOR REVIEW. P. SHOULD THE CONTRACTOR PROPOSE TO FURNISH MATERIALS, EQUIPMENT, AND DEVICES, OTHER THAN THOSE SPEqFlED AND LISTED. THE CONTRACTOR SHALL SUBMIT A WRITfEN REQUEST FOR SUBSTITUTIONS TO THE ENGWEER AT LEAST FOURIEEN (14) CALENOAR �AYS PRIOR 10 BID OPENING. iHE REOIIESi SHALL BE AN ALTERNAiE i0 iHE ORIGINAL BI� AND SHALL INCWDE AN� BE ACCOMPANIE� WITH COMPIETE SPEQFlCATION CUT SHEEf SUBMITfALS AS OUTLINEO IN SECTION 1� A OF THIS SPEQFlCATION SECTION, COMPLEfE WITH �ESCRIPTNE (MANUFACTURER, BRAND NAME, CATALOG NUMBER, EfC) AND TECHNICAL DATA FOR ALL ITEMS. IN�ICATE ANY ADDITIONS OR DEDUCTIONS TO THE CONTRACT PRICE ON BOTH THE SUBSTITUTION SUBMIITAL AND THE BID FORM. FAILURE TO PERFORM THESE ACTIONS EOUATES TO ACKNOWLEDGEMENT THAT THE PROJECT HAS BEEN BI� WITH STRICT ACCORDANCE TO THIS SPEQFlCATION AND APPLICABLE DRAWINGS. G. ACCEPTANCE OR REJECTION OF THE PROPOSED SUBSTITUTIONS SHALL BE SUBJECT TO APPROVAL OP THE ARCHITECT AND ENGWEER. IF REOUESTED, THE WNTRACTOR SHALL SUBMIT WSPECTION SAMPLES OF BOTH THE SPECIFlED AND THE PROPOSED SOBSTITUTE REMS. H.IF ANY SUBSTITOTIONS ARE APPROVED, AN A�DEN�OM LISTING THE APPROVED REMS(5) WILL BE ISSUE� i0 ALL BIO�ING CON7RACi0R5 PRIOR i0 iHE BI� DAiE. I. IN ALL CASES WHERE SUBSiIiViIONS ARE PERMITfE�, iHE CON7RACi0R SHALL BEAR ANY E%iRA COSi OF EVAWAiING THE EQUALIIY OF iHE MAiERIAL AND EOUIPMENi i0 BE INSiALLED. EQUIPMEN7 IDENiIFlCATION A. iHE CONIRACIOR SHALL FURNISH AN� INSIALL A SYSTEM OF NAMEPlA1ES �ESIGNED i0 IDENiIFY EACH PIECE OF EQUIPMENi. (1) NAMEPIATE LETfERS AND NUMBERS SHALL MATCH EOUIPMENT DESIGNATION AS INDICATED ON THE �RAWINGS. (2) NAMEPIATES SHALL BE IAMINATED PHENOLIC WITH BLACK Sl1RFACE AND WHITE CORE USE 1�16" iHICK MAiERIAL FOR PU7ES UP ID 2" BY 4l FOR URGER SIZES USE 1/8"THICK LEffERS AN� NUMBERS SHALL BE A MINIMl1M OF �{�" HIGH. (3) FASTEN NAMEPLATES TO ALL EOUIPMEM BY THE USE OF STAMLE55 STEEL SHEET MEfAL SCREWS. AS-BOILT DRAWINGS A. AS WORK PROGRESSES, REWR� ON A SET OF -A5-BUILT' PRMTS ANY �EVIATIONS FROM DESIGN DRAWINGS. �ELIVER THIS SET TO THE OWNER BEFORE SUBMITiING REQUEST FOR FlNAL PAYMENT. THE -AS-BUILT' PRINTS SHALL BE AN ACCURATE DEPICTION OF THE PROJECT AS COMPLETED. OPERATING AN� MAINTENANCE MANUALS A. PROVIDE TO OWNER AT PROJECT TURNOVER, THREE (3) HARDBOUND COPIES OP OPERATING AN� MNNTENANCE MANUALS FOR ALL EOUIPMENT AND SYSTEMS INSTALLE�. B. MANUALS SHALL INCLUDE ALL RELEVANT MFORMATION NEEDED FOR DAY-TO-DAY OPERATION AND MANAGEMENT OF EACH SYSTEM AND EQUIPMENT MAIMENANCE INFORMATION REOUIRED TO SUPPORT THE MAIMENANCE PROGRAM. C. MANUALS SHALL INCLUDE THE SEWENCE OF OPERATION FOR EACH SYSTEM WHICH DESCRIBES THE CONTROL COAIPONENTS AND HOW THE SY4EM WILL START, STOP AN� OPERPTE. INSUTA710N A. PROVI�E ALL INSUUTION MATERIALS QNSUlATION, JACKEf$ FlTfING COVERS, ADHESNES, CEMENTS, MASTICS, SEALERS AND FINISHES) WITH A FIAME-SPREAD INDE% OF 25 OR LESS AND SMOKE DEVELOPED INDE% OF 50 OR LE55. AS iESTED UNDER PROCEDURE AS1M E-84 (NFPA 255) B. Al1 INSUTAiION SHALL BE INSIALLED OVER CLEAN, �RY SURFACES. INSUU110N MUSi BE DRY AN� IN G00� CON�IiION. WEf OR DAMAGED INSUUiION IS NOT ACCEPTABLE NO INSUTATION SHALL BE APPLIED PRIOR TO PRESSURE TEST COMPLEfION OF iHE RESPECiIVE SYSiEM. C. ALL INSUTAiION SHALL BE CONTIN0005 (INCLU�ING VAPOR BARRIER) THROUGH WALL AND CEILING OPENINGS AN� SLEEVES. OVERUP AT SEAMS PER MANUFACTURER'S RECOMMENOATIONS. �. ALL INSUlATION PRODOCTS SHALL BE APPLIED IN ACCORDANCE WITH MANUFACiURER�S WRITfEN RECOMMEN�ATION. iHE WORKMANSHIP SHALL 9E FlRA CIASS AND ALL JOINTS SHALL BE MADE TIGHT. E INSUlATION MUST MEEf ADOPTED ASHRAE 90.1 STAN�ARDS. E INSUTATE CONCFALED SUPPLY AIR DUCTNORK WITH T' THICK OWENS-CORNING FIBERGVSS DUCIWRAP WITH FOIL FACED ALL-SERVICE JACKEf. E INSUTATE SUPPLY AIR �UC7WORK LOCAiE� IN PLENUM SPACES WITH 1-1�7' THICN OWENS-CORNING FIBERGIASS Dl1CPNRAP WITH FOIL FACE� ALL-SERVICE JACKET. G.INSOUTE OOT�OOR AIR DUCiWORK WITH 1-1/2' THICN OWENS-CORNING FIBERGUSS OUCIWRAP WITH FOIL FACE� ALL-SERVICE JACKEf. H.INTERNAL DOCT INSUlA710N SHALL BE USE� ON EXPOSEO �UCIV/ORK. I. INSUTATE SOPPLY AIR �UCIVlORK �OWNSTREAM OF DUCT TERMINAL UNITS WITH 1-1/2" THICK OWENS-CORNING FIBERGLA55 DUCTNRAP WITN PoIL PACED ALL-SERVICE JACKET. J. REPAIR E%ISTING INSUUTION WNERE REMOVED FOR NEW CONNECTIONS OR INSOUTION DAMAGED DURING CONSTRIICiION. INSUUTION SHALL 6E THE SAAIE AS SPECIFlED FOR NEW SERVICE. K. ALL INSUTAiION USE� AS PLENUM WRAP COVERING FOR COMBUSiIBLE MATERIALS IN A PLENUM SPACE SHALL BE 3M PLENUM PRO1EC110N SYSTEM (PP-100-P), ONE IAYER OF 3M FlRE BARRIER �UCT WRAP 5A, IN ACCOR�ANCE WIiH UL91� & UL1687. L ACOUSTICAL OUCi LINING: (1) IMERNALLY LINE FlRST TEN FEEf OF �UCIWORK FROM AIR HAN�LERS AN� TERMINAL UNIiS AN� WHERE IN�ICAiE� ON PlANS. (2) FIBROUS GlASS, COMPLYING WITH THERMAL INSOUTION MANUFACTURERS nssocianoN (nMn) nHc-ioi. (3) ASiM C 1071, IYPE II, WI1H COATE� Sl1RFACE E%POSE� 70 AIRSiREAM i0 PREVEM EROSION OF GlASS FIBERS 1" THICK. 1- � LB. OENSItt. COATING MATERIAL SHALL BE ANTI-MICROBIAL AND COMPLY WITH NFPA 90A AN� 90B. (4) K-PACTOR'EQl1AL TO 028 OR BETfER, AT MEAN TEMPERATl1RE OF 75 DEG. F. (5) FUME SPREAD INDEX SHALL BE 25 OR LESS AND SMOKE DEVELOPED IN�EX SHALL BE 5� OR LESS, AS iE57ED IN ACCOR�ANCE W17H ASiM C 411. (6) �UCT LINING A�HESNE SHALL COMPLY WITH ASTM C 916 SPECIFlCATIONS FOR ADHESNES FOR "DUCT THERMAL INSUUTIOM'. DOCT LINING FASTENERS ALL COMPLY WITH SMACNA DOCT CONSTRUCTION STANDARDS, ARTICLE 5211 (7) ALTERNATE DUCT 11NING MATERIAL - ARMACELL AP ARMAFLEX SA BIACK DUCT LINER, 3/4" THICK, MICROBAN ANTI-MICROBIAL PROTECTION. MEfAL �UC7WORK A. HVAC COMRACTOR SHALL VERIFY ALL EXISTING CON�ITIONS PRIOR ID FABRICATION OF �UCPNORN. ANY CONFLICTS OR INTERFERENCES SHALL BE BROUGHT TO THE ATfENiION OF iHE ENGINEER. B. GALVANIZE� �UCPNORN SHALL BE FABRICAiED OF N0.1 PRIME GALVANIZE� SHEEf MEfAL OF LOCK FORMING QUALIIY. C. SEALING MATERIALS SHALL BE SUITABLE FOR; USE WITH AIR �ISTRIBUTION �UCTNORN. ACCEPTABLE MANUFACiURERS ARE MONOCO IN�USTRIES, JM, OR UNITE� SHEEf MEfAL. �. PROVI�E ALL �UCIWORK AS INDICATED ON THE DRAWINGS, MAKING ALL NECESSARY OFFSETS (WHEfHER OR NOT SPEQFlCALLY IN�ICTEO) AS REQUIRED TO MEET THE VARIOUS BUILDING CONDITIONS. �UCiWORK INSTALUTION SHALL NOT CONFLICT WITH EQUIPMENT OR PIPING. � 12. 13. 14. 15. E E%POSE� DUCTNORK SHALL 6E PRIME� AN� PAIMEO. COORDINAiE WITH ARCHITECTURAL PWJS FOR COLOR SELEECTION. E ALL CHANGES M CROSS SECTION SHALL BE MADE WITHOUT REDUQNG THE �ESIGN AREA OF THE OUCT OR RAISING THE PRESSURE DROP PER 100 FEEf OF DOCT SHOWN ON DOCOMENTS. G. NO PIPE OR OTHER OBSTRUCTIONS SHALL PASS THROOGH AIR �OCTS, ONLESS SPEQFlCALLY SHOWN ON PUNS. H. CAP ALL OPEN ENOS TO DOCTWORK DURING CONSTRUCTION TO PREVEM ENTRANCE OF DUST, DEBRIS, MOISNRE ETC. I, INSTALL DUCiWORK RUN ABOVE CEILING AS HIGH AS POSSIBLE 50 AS TO MNNTAIN DESIGN CEILING HEIGHTS EXPOSE� DUCiWORK SHALL BE INSTALLED TO PROVIDE MAXIMUTA HEADROOM OR AT HEIGHT SPECIFlED ON PLANS. J. DUCPNORK SHALL NOT BE HONG FROM E�l11PMENT, PIPING, CONOWT, ROOF DECKING OR OTHER DUCTNORK. K. ALL DUCTNORK JOINTS ANO SEAMS SHALL BE AIR-TIGHT PER SMACNA TABLE 1.1. POORLY MADE JOINTS, SPLITS, VISIBLE HOLES AT CORNERS, ETC SNALL BE REWORKED AND REPAIRED. WHERE E%CESSNE PULSATING OF DUCPNORK IS FOUND, AD�IiIONAL STIFFENERS SHALL BE ADDED. ANY CRACKING IN THE SEAUNT THAi IS APPARENT UPON INSPECiION SHALL BE SUFFlCIENT TO WARRANT REJECTION. L IF iHE IMERIOR OF SHEEf METAL 6 ERPOSED TO VIEW THROOGH AIR DISTRIBUTION DEVICES M FlNISHED AREAS OF THE BUILDING, IT SNALL BE COATED WITH PRIMER AND A FIAT BIACK FlNISH COAT. M. ALL DUCiWORK SHALL BE SUPPORTED PER SMACNA REQUIREMENTS. N. RECTANGUUR DUCiWORK FlTiINGS. (1) BRANCH CONNECTIONS SHALL BE 45 DEGREES ENTRY. STRAIGHT TAPS ARE NOi PERMITfED. (2) CHANGES IN OIRECTION SHALL BE MA�E WITH FULL RA�WS ELBOWS WITH RADWS EQl1AL TO 1-1/2 TIMES THE HORIZONTAL WIDTH OF THE �UCT OR WITH S�OARE ELBOWS WITH TURNING VANES. TURNING VANES SHALL BE �OUBLE THICKNESS NPE CONSTRUCTED OF THE SA�AE MATERIAL AS THE SURROUNDING �UCiWORK, PER SMACNA REQUIREMENTS. O.ROUN� �UCPNORN FlTTMGS: (1) BRANCH CONNECTIONS SHALL BE MADE WITH 45 DEGREE ENTRY TEES. (2) CHANGE IN DIREC710N SHALL 9E MADE WIiH FULL RADIUS ELBOWS WRH RA�IUS EQUAL TO 1-1/2 TIMES THE �IAMETER OF THE �UCT. P. LOW PRESSURE �OC7WORK SHALL BE CONSTRUCTE� PER SMACNA "HVAC OUCT CONSTRUCTION STAN�ARDS"FOR 2 INCH STATIC PRESSURE, SEAL CIASS "8". Q. HANGERS AN� SUPPORTS (1) PROVIDE GALVANRED 4EEL STRAPS, ALL-THREAD ROD AND HORIZONTAL ANGLE SUPPORTS SIZED PER SMACNA REQUIREMENTS. (2) DUCT ATfACHMENTS SHALL BE MADE USING SHEEf MEfAL SCREWS COMPATIBLE WITH DUCi MAiERIALS. (3) BUIL�ING ATfACHMENTS SHALL BE CONCREfE MSERTS OR STRUCTl1RAL STEEL FASiENERS APPROPRIAiE FOR iHE BUIL�ING MAiERIALS. �0 NOi USE POWER ACTIVATE CONCRETE FASTENERS. 'C IYPE MALIEABLE IRON BEAM ClAMPS ARE ACCEPTABLE ONLY IF USE� WITH CARBON STEEL REfAMER STRAP. FLEXIBLE DUCiWORK A. TESTED AN� CIASSIFlEO BY UN�ERWRIiERS IABORATORIES, INC. AS CVSS I AIR �UCT AND IABELE� IN ACCOR�ANCE WITH U.L 181, STAN�AR� FOR AIR Dl1CTS". iHE FUME SPREA� RAiING SHALL BE 25 OR LESS AN� iHE SMONE �EVELOPEO RATING SHALL BE 50 OR LESS. B. LINER SHALL BE CONSTRUCTE� OF AWMINUM FOIL, FlBERGUSS AN� AWMINIZEO PoLYESiER, MECHANICALLY LOCKE� WITHOUT A�HESIVES, HELIX SHALL BE GALVAMZE� STEEL, FORMED AN� MECHANICALLY LOCNE� TO FABRIC. C. WHERE OUCIWORK IS TO BE INSUTAiE�, FLEXIBLE �UCIWORK LWER SHALL BE COVERED BY A FACTORY WRAPPED, 1-I/2"THICK, 3/4 POON� �ENSIN FlBERGU55 INSOIAiION BUNKET WITH A FlRE RETARDANT REMFORCED AWMINUM OUTER JACNET. �.INSTALL FLE%IBLE DOCiWORK FULLY EX�ENDED, FREE OF SAGS AND KINKS. MAXIMUM LENGTH OF RE%IBLE DUCiWORK SHALL BE 3'-0'l FASTEN REXIBLE DUCTNORK TO RIGI� DUCIYIORK AND DEVICES WITN SELFLOCKING 100 PERCENT NttON, ADJUSTABLE DIAMEfER CLAMPS. E. ACCEPTABLE MANUFACTURERS ARE THERMARE%, FLE%MASTER U.S.A. INC. AND 0.EVAFLE%. BAlANCING DAMPERS A. PROVI�E 9AUNCING �AMPERS FOR ALL AIR TERMINAL �EVICES (SUCH AS BUi NOT LIMITE� T0, DIFFUSERS, REGISTERS, GRILLES, ETCJ AND BRANCH DUCPNORN REOl11RE� FOR PROPER BALANCING OF 51'STEM. B. ROUN� �AMPERS SHALL BE SINGLE BLADE NPE CONSTROCTION, MINIMUM 18 GAUGE GALVANIZE� STEEL PIVOT ROD SHAfT SHALL BE CONTINUOUS. C. RECTANGUUR �AMPERS SHALL BE SINGLE BU�E OR MULTIPLE (OPPOSED BUOE) ttPE CONSTRUCTION. MA%IMUM BUDE WIDTH IS 8 INCHES. �. ALL BAUNpNG DAMPERS SHALL BE CONSTRUCTED IN ACCOR�ANCE WITH SMACNA "HVAC �UCT CONSTRUCTION STAN�ARDS" E FURNISH ALL BAWJCING �AMPERS WITH YOUNG REGUTATOR COMPANY VALCALO% REGUTATORS WITH HANDLE PERMANENTLY ATiACNED. DAMPER HANDLE POSITION SHALL BE SECORELY LOCKED IN PIACE BY iIGHTENING OF A LOCK NUT. WHERE DUCTNORK IS EXTERNALLY INSUTATED, REGUTATOR BASE HEIGHT SHALL ACCOMMODATE INSUUTION THICKNESS. F. PROVIDE ALL MANUAL BAUNQNG DAMPERS WNERE INDICATE� ON THE DRAWINGS AND WHERE NECESSARY TO PROPERLY DISTRIBUTE AND BAUNCE TNE AIR. REGISTERS, GRILLES AND DIFFUSERS A. PROVIDE REGISTERS, GRILLS AND DIFFUSERS WHERE SHOWN ON THE DRAWINGS, OF SIZE ttPE, AND MATERIAL AS INDICATED AND AS REQUIRED FOR A COMPLEfE INSTALUTION. B. BORDER lYPES SHALL BE COMPATIBLE WITH THE CEILINGS WHERE THE GRILLES AND DIFFUSERS ARE TO BE INSTALLED. C. ALL GRILLES AND DIFFUSERS SHALL BE FINISHE� WITH A FACTORY APPLIED OFF-WHITE FINISH UNLESS NOTED OTHERW6E. D. REFER TO ARCHITECTURAL REFLECTED CEILING PUNS FOR E%ACT LOCATION OF GRILLES AND DIFPUSERS, VIBRATION ISOUTION A. PROVIDE ADEQUATE VIBRATION ISOUTION FOR EACH PIECE OF EQUIPMENT. B. PROVIDE FLE%IBLE WNNECTIONS WITH 1" SUCK BEIWEEN DUCTS AND FANS AS MANUPACTURED 8Y DURO-DYNE, OR EQUIVALENT. C. PROVIDE FLE%IBLE FITTING ON PIPING CONNECTIONS TO EOUIPMENT. REFRIGERATION AND AIR CONDITIONING CONDENSATE PIPING SY4EM5 A. USE ttPE DWV COPPER PIPING WRH BRAZED DRNNAGE FITfINGS FOR CONDENSATE PIPING. B. USE ttPE ACR COPPER PIPING WITH BRAZED WROUGNT COPPER FITfINGS FOR ALL REFRIGERATION PIPING. C. PIiCH PUMPE� AN� GRAVIIY CON�ENSAiE PIPING Ai 1/9 INCH PER F007 IN �IREC110N OF FLOW. �. INSUTAiE ALL INiERIOR WNDENSAiE PIPING AN� REFRIGERAiION SUCiION PIPING WITH 3/4 INCH ARMACELL CLOSE� CELL SELF SEALING ARMAFLEN WSOUTION. HVAC PIPMG A. CON�ENSER WATER PIPING AN� FlTiINGS SHALL BE iYPE L HARD COPPER PIPE WITH WROOGHT COPPER SOLDER JOWT FlITINGS THRO L5 PIPE SQES. PIPING 2" AND URGER SHALL BE SCHEDOLE 1� BUCK STEEL VICiAl1LIC PIPING WITH MECHANICAL COUPLINGS DESIGNED FOR SPEQFlC OSE. B. SHUT-0FP VALVES SHALL BE BRONZE OR VICTAOLIC IRON BODY, 7W0 PIECE, FULL PORT, LEVER HAN�LE BALL VALVES WITN TERON SEATS, CHROME PUTED BRA55 OR STEEL BALL RESPECTIVELY, STEEL OR BRASS STEM ANO SOLDER OR GROOVED ENDS. RESPECiNELY. 600 PSI WOG. C. BAUNCING VALVES (1) MANUAL - BRONZE BODY, COMBINAiION VENiURI AND BALL VALVE WIiH 1N0 PRESSURE TEMPERATURE TEST PORTS, MEMORY STOP, WLET UNION CONNECTION AND THREADED ENDS, 400 PSI AT 250'F. ACCEPTABLE MANUfACTURER: FLOW �ESIGN INC. "FLOWSEf'. (2) AUTOMATIC - BRASS Y-NPE BO�Y, IMEGRAL BRASS-BO�Y BALL VALVE WITH iN0 PRESSURE TEMPERATURE TEST PORTS, OVABLE/REPLACEABLE STAINLE55 STEEL FLOW GRTRIDGE AND THREADED ENDS, 400 P51 AT 257F. ACCEPTABLE MANUFACiURER: FLOW �ESIGN INC. "AUiOFLOW". �. INSiALIAiION (1) INSTALL CON�ENSER WATER PIPING SYSTEM AS INDICATED WITH CONNECTIONS MME TO ALL EOUIPMENT AS SHOWN. (2) WHERE LMES ARE REDUCE� IN SRE, ECCENTRIC REDUCING FliTINGS SHALL BE USED TO ALIGN TOP OF MAINS ANO PREVENT AIR POCKEfS. (3) BRANCH CONNECiIONS FROM MAINS i0 R6ER5 OR EOUIPMENi BELOW MAINS SHALL BE TAKEN FROM THE BOTfOM OF THE MAIN AND PROVIDED WITH AT LEAST THREE ELBOWS FOR E%PANSION. SUPPLY RUN-OUTS SHALL PITCH �OWN AWAY FROM MAIN 1 INCH M 5-0". REfURN Rl1N-OOTS SHALL PITCH UP TO MAIN 1 INCH IN 5"-0". (4) BRANCH CONNECTIONS FROM MAINS TO RISERS OR EQUIPMENT ABOVE MAINS SHALL BE TAKEN FROM THE TOP Of MAIN AND PROVIDED WITH AT LEAST THREE ELBOWS FOR E%PANSION. SUPPLY RUN-OUTS SHALL PITCH UP AWAY FROM MAIN 1 INCH IN 5�-0". RENRN RUN-OUiS SHALL PIiCH DOWN i0 MAIN 1 INCH IN 5'-0". �. 17. � � 20. 21 (5) WSTALL MANUAL AIR VENTS AT ALL HIGH POIMS IN THE PIPING SYSiEM WHERE IN�ICATE� AN� WHERE OTHERW6E NEEDE� FOR COMPLETE AIR ELIMINATION FROM THE SYSTEM. INSTALL AIR VENTS ON THE HIGH SI�E OF ALL E�UIPMENT CONNECTIONS. (fi) INSTALL DRAIN VALVES AT ALL LOW POMTS OF THE SYS7EM. (7) PROVIOE A SHU1-OFF VALVE IN iHE SUPPLY 10 EACH COOLING COIL, CONVECiOR, FlNNED iUBE RADIAiOR OR CONOENSER AND A 9AUNCING VALVE IN THE REfURN LME BAIANCING DEVICE SHALL ALSO SERVE AS A SHUT-0FF VALVE. E. iESiING ANO CLEANING (1) ALL CON�ENSER, CMLLEO WATER, HEATING HOT WATER SYSTEMS SHALL BE PRESSURE TESTEO WITH WATER TO 125 PSI. TEST �ORATION SHALL BE 6 HOURS. (2J CLEAN ALL SYSTEMS AS FOLLOWS FlLL S1'STEM WITH CLEAN WATER AND fLUSH; REFlLL WOH CLEAN WATER/DEfERGENT MIXTURE, CIRCUUTE FOR AT LEAST B HOURS, DRAIN SYSTEM AND FLUSH WITH CLEAN COLD WATER. ADD WATER TREATMENT AT THIS TIME. 22. WATER SOURCE HEAT PUMP UNITS A. DESCRIPTION: PACKAGE� WATER-SOURCE HEAT PUMP WITH TEMPERATURE CONTROLS; FACTORY ASSEMBLED, TE4ED, AND RATED ACCORDING TO ARI-150-13256-1, EfL LISTED. B. CABINEf AND CHASSIS: PAIMED 4EEL CASING WITH THE fOLLOWING FEATURES: 1. ACCE55 PANEL FOR ACCE55 AND MAINTENANCE OP INTERNAL COMPONENTS. 2. KNOCKOUTS FOR ELECTRICAL CONNECTIONS. NO KNOCKOUTS FOR PIPING. WATER CONNECTIONS ARE FLUSH MOUNT WITHOUT REOUIRING BACKUP WRENCH. 3. HORIZONTAL PLAT TOP WITH GRILLE AND HINGED CONTROL COVER 4. CABINEf INSUlA110N: FOIL FACE�, MINIMUM �h INCH iHICK, COMPLYING W11H UL 181. S CON�ENSATE �RAINAGE (PVC) PIASTIC �RAIN PAN PITCHE� AS REOUIRED IN ASHRAE fi2 WITH CON�ENSATE �f2AIN PIPING PROJECTMG THROUGH UNIT CABINEf. fi. SOOND ATTENOATION PACKAGE: a. MINIMUM 0.598-INCH-THICK COMPRESSOR ENCLOSURE AN� FRONT PANEL MINIMUM 0.0937-INCH-THICK FOAM GASNET AROON� THE COMPRESSOR AND PERI�AEfER OF EN� PANEL. b. SOOND ATTENOATMG BLANKEf OVER COMPRESSOR. C. FAN: �IRECT DRNEN, CENTRIFUGAL, WITH MULiI-SPEE� MOTOR RESILIENTLY MOUNTE� M FAN MLEf. 1. MOTOR: MULTI-SPEE�, PERMANENTLY WBRICATE�, ECM MOTOR OR AS SCHE�l1LE�. �. WAiER CIRCUIT: 1. REFRIGERANT-TO-WATER HEAT EXCHANGERS 25 'F TO 12PF OPERATING TEMPERATURE RANGE. a. INSULATE4 EX�EN�ED RANGE COAXIAL HEAT EXCHANGERS WITH COPPER WAiER TOBE WITH ENHANCE� HEAT-TRANSFER SORFACES INSI�E A STEEL SHELL; BOTH SHELL AN� TU9E LEAN TESTE� TO 45� PSIG ON REFRIGERANT SI�E AN� 400 PSIG ON WATER SI�E FACTORY-MOUNT HEAT EXCHANGER IN ONIT ON RESILIENT ROBBER VIBRATION ISOIATORS. E REFRIGE2ANT-TO-AIR-COILS: COPPER TUBES WITH AWMINUM FlNS, LEAK TESTE� TO 450 PSIG. E REFRIGERANT CIRCWT WMPONENTS: 1. SEALED REFRIGERANT CIRWIT: CNARGE WITH R-410A REPRIGERANT (R-22 IS NOT ACCEP7A9LE). 2. FILTER-0RYER FAC70RY INSTALLE� TO CLEAN AND �EHY�RAiE THE REFRIGERANT CIRCUIi. 3. CHARGING CONNECiIONS: SERVICE FIifINGS ON SUC710N AND LIQUI� FOR CHARGING AN� 1ESiING. 4. REVERSING VALVE: PILOi-OPERAiEO SLI�ING-iYPE VALVE �ESIGNE� i0 BE FNL-SAFE IN HEAIING POSI110N WI1H REPUCEABLE MAGNEfIC COIL. 5. COMPRESSOR: DUAL CAPACIIY SCROLL COMPRESSOR INSiALLE� ON VIBRAiION ISOlAiORS AN� HOUSE� IN AN ACOUSiICALLY iREAiE� ENCLOSURE WIiH FACiORY-MSiALLED SAFEfIES AS FOLLOWS: a. DUAL CAPACIiY-HEAi PUMP �UiY. b. ANTIRECYCLE iIMER. c. HIGH-PRESSURE CUiOUi. d LOW-PRESSURE CUiOUi OR LOSS OF CHARGE SWITCH. e. IMERNAL iHERMAL-OVERLOAD PROiEC710N. E FREEZE51A1 10 STOP COMPRESSOR IF WAiER-LOOP iEMPEFAiURE IN REFRIGERANi-iO-WAiER HEAi EXCHANGER FALLS BELOW 25 �EG F. g. CON�ENSAiE OVERFLOW SWIiCH i0 SiOP COMPRESSOR WIiH HIGH CON�ENSAiE LEVEL IN CON�ENSAiE �RAIN PAN. 6. REFRIGERANi PIPING MAiERIALS: ASTM B 743 COPPER iUBE WIiH WROUGHi-COPPER FIiTINGS AN� BRAZED JOINiS. 7. PIPE INSUUTION: REFRIGERANT MINIMOM 3/8-INCH-THICN, REXIBLE EIASTOMERIC INSUUTION ON PIPING EXPOSE� TO NRFLOW THROOGH THE UNIT. MAXIMUM 25/50 FIAME-SPREAD/S�AOKE- DEVELOPMENT INDEXES ACCORDING TO ASTM E 84. B. REFRIGERANT MEfERING DEVICE THERMAL EXPANSION VALVE TO ALLOW SPECIFlED OPERATION WITH ENTERING-WATER TEMPERATURES FROM 25 F TO 12P F. G. ELECTRIC HEATING COIL: HEIJ%-WOUND, NICKEL-CHROMIUM WIRE-HEATING ELEMENTS IN CERAMIC INSOIATORS MOIINTED ON 4EEL SUPPORTS ENERGIZE ON CALL FOR HEATING WHEN EMERING-WATER-LOOP TEMPERATURE IS LE55 TNAN 25 DEG F. R FlLTERS: �ISPOSABLE, PLEATE� NPE, 1" INCH THICK MERV 11. I. CONTROLS 1. BASIC UNIi CONTROLS: DDC a. LOW AND HIGN-VOLTAGE PROTECTION. b. OVER CURRENT PROTECTION FOR COMPRESSOR AN� FAN MOTOR. c RANDO�A TIIAE DEUY, THREE TO TEN SECONDS, START ON POWER OP. d. TIME �ELAY OVERRI�E FOR SERVICING. e. CONTROL VOLiAGE TRANSFORMER. 2 THERAIOSTAT: a. UNIT-MOUNiED TEMPERATURE SENSOR. b. LED TO INDICATE FAULT CONDITION AT HEAT PUMP. u DATA ENTRY AND ACCESS PORT. 1)INPUi �AiA INCW�E ROOM iEMPERATURE AND HUMIDIIY SEf POIMS FOR OCCUPoED AND UNOCCUPoED PERI0�5. 2)OOTPOT �ATA INCLO�E ROOM TEMPERATURE ANO HOMI017Y, SUPPLY-AIR TEMPERATURE, ENiERING-WAiER TEMPERATl1RE, OPERATING MO�E, ANO STATl15. 3. TERMINAL CONTROLLER: a. REMOiE COMROL PANEL i0 CONiAIN PROGRAMMABLE iIMER AN� LED FOR FAULT CONOITION. b. COMPRESSOR �ISABLE REIAY TO STOP COMPRESSOR OPERATION FOR �EMAN� LIMITING OR SWITCH TO 11NOCCUPIE� OPERATION. c. AOTOMATIC RESTART ARER FNE MINUTES IF FAULT CLEARS LOCNOUT AFTER THREE ATTEMPTS TO RESTARi FOLLOWING FAULT. IN�ICATE FAOLT FOR SERVICE iECHNICIAN. d. REfORN-NR TEMPERATURE HIGH-LIMIT (FIRESTAT). STOP UNIT ON HIGH TEMPERATURE. e. BACNUP FOR VOIATILE MEMORY. J. ELECTRICAL CONNECTION: SINGLE ELECTRICAL CONNECTION WITH FUSE� �ISCONNECT. 23. HOSE KITS A. GENERAL HOSE KITS SHALL BE STAMLESS STEEL AND DESIGNE� FOR MINIMU�A 400 PSIG WORKING PRESSURE, AND OPERATING TEMPERATURES FROM 25 ID 211 DEG. E TAG HOSE KITS ID EQUIPMENT �ESIGNATIONS. B. HOSE LENGTH 24 MCHES. MINIMUM DIAMHER, EQUAL TO WATER-SOURCE HEAT-PUMP CONNECTION 9ZE. C. ISOUTION VAWES: iW0-PIECE BRON2E-BODY BALL VALVES WITH STAMLESS-STEEL BALL AN� STEM AN� GALVANIZE�-STEEL LEVER HANDLE PROVI�E VALVE FOR SOPPLY AND REfORN. IF BAUNCING DEVICE IS COMBINATION SHOTOFF NPE WIiH MEMORY STOP, THE ISOLITION VALVE MAV BE OMITiED ON iHE RERIRN. D. STRAINER: Y-NPE WITH BLOW DOWN VALVE IN SOPPLY CONNECTION. E BAIANQNG �EVICE: MOONT IN RETl1RN CONNECTION. MCWOE METER PORTS TO ALLOW FLOW MEASUREMENT WITH �IFFERENTIAL PRESSURE GAGE. E AIANUAL, CALIBRAiED-ORIFlCE BAIANCING VALVE. 25. iEMPERAiURE CONiROLS A. ALL 7EMPERAiURE CON7ROL COMPONEMS, WIRING AN� CON�UIi SHALL BE iHE RESPONSIBWiY OF iHE HVAC CONiRACiOR. B. WIRING AND CON�UIi (1) ALL 24 VOLT WIRING SHALL BE WSTALLEO IN CON�UIT, IN ACCORDANCE WITH THE UTEST E�ITION OF THE NATIONAL ELECTRIC CODE. (2) ALL OUT�OOR 24 VOLT WIRING SHALL BE INSTALLED IN CONDUIT, IN ACCORDANCE WITH THE LATEST E�ITION OF THE NATIONAL ELECTRIC CODE. B. HVAC CONTRACTOR SHALL OSE BOIL�ING APPROVE� TEMPERATURE CONTROL CONTRACTOR AND MANUFACTURER. C. TE�APERATURE CONTROL CONTRACTOR SHALL INCWDE COST OF MTEGRATING NEW UNITS INTO BWLDING BAS. IMEGRATION SHALL INCWDE BOT IS NOT LIMITED T0; UPDATING GRAPHICS, POPUUTMG CONTROL POINi LISTS, EfC. TEMPORARY SERVICES A. HVAC CONTRACTOR SHALL COORDINATE WITH OTHER TRADES AN� PROVIOE TEMPORARY SPACE CONDITIONING (HEATING AND COOLING AS REQUIRED) IN ORDER TO MAINTAIN TEMPERATURES AND HUMIDOY LEVELS AS REOUIRED FOR GENERAL CONSTRUCiION. B. U71LIlY CONNECilONS REQUIRE� FOR TEMPORARY HEAiING/CWLING SHALL BE iHE RESPONSIBILIiY OF iHIS CONiRACiOR. COOR�INAiE WIiH GENERAL CONiRACiOR FOR UTILIIY (GAS/ELECTRICJ USE REQUIREMENTS. IT SHALL NOT BE THE RESPONSIBILIIY OF THIS CONTRACTOR TO PAY FOR THE UTILITIES USED �ORING PROJECT CONSTRUCiION. C. E%ISTMG OR NEW HVAC SYSTEMS OSE� �URING WNSTROCTION'. Q) NEW OR EXISTING SY4EM5 SHALL NOT BE USE� WITHOUT THE KNOWLEDGE AND CONSENT OP THE OWNER, ARCHITECT AN� ENGMEER. (2) CONiRACiOR SHALL ADHERE i0 BUILDING GUIDELINES FOR OPERA7ING NEW/EXISTING HVAC SYSTEMS �URING CONSTRl1CTI0N. (3) ALL SYSTEM REfURN AIR GRILLES SHALL BE PROiECTED USING FlLTRATION MEDIA WITH A MINIMUM EFFlCIENCY RATING VALUE (MERVJ OF 8, PER ASHRAE 522. (4) ALL HVAC SYSiEMS AN� AIR �ISiRIBOiION �EVICES USE� �URING CONSiRUCiION SHALL BE CLEANED PER WRRENi NAiIONAL AIR DOC7 CLEANING ASSOCIATION GENERAL SPEQFlCATIONS. PROJECT COMPLEfION: C. UPON COMPLEfION OF PROJECT THIS CONiRACTOR SHALL PROVI�E NEW FlLTERS WITHIN ALL EXISTING AN� FAN POWERE� EOUIPMENT. �. ALL EXISTING AN� NEVI FAN POWERE� EQUIPMENT SHALL HAVE THEIR EX�ERIOR CLEANE� WITH A MIL� SOAP AND WATER SOWTION ANO THOROUGHLY �RIE�. E PROVI�E 3 COPIES OF FlNAL TEST AN� BAIANCE REPORT TO OWNER/ARCHITECT. 26. D. jO� vs�s F,y�":. z,.,�� .vFa y9i a . PC1�3p05]5 I ^ � , STATE OF % p %" H ELLYER LEWIS= ARCHITECTURE INTERIOR DESIGN 211 South 12th St. Phila., PA 19107 215.922.7066 m rwmF ucry o�mMrvvory �c�irvs.�c. n� si.s cnHoinnHs. .Hs ccHcan� cnH.ancr � cooaoirvnle n�� woarc nrvo nxcNErFcr o�nHv�iH rHCF oF nnFCNnNicni . Fi FcraicniF oa ai �nneiNc . . nacrvi.eRuan�woaknrvo aoc Eo Nc wi.H.H�woak oa Project: • Li bcrty Mutual� INSURANCE 350 East 96th Street, 1 st & 2nd Floors Indianapolis, IN 46240 Project No: 047.79 Drawn by: MB Checked by: AM Approved by: AM Client Approval: Dace: Issued For Permits: � ��� 5�� 9 Drawing: Mechanical Specifications No. M-2.01 DATE: O1IZ9IZO Scale: 1 /8•' - 1'_0•'