Loading...
HomeMy WebLinkAboutE-401-Electrical-Enlarged-Plans-Rev.7FEINSTEIN CLUB LIGHTING CONTROL SEQUENCE NOTES: 1. LIGHTING SHALL COMPLY WITH THE FOLLOWING CODES AND STANDARDS: NATIONAL ELECTRIC CODE (NEC), NATIONAL FIRE PROTECTION AGENCY (NFPA), IES LIGHTING HANDBOOK 10TH EDITION, AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI), INDIANA BUILDING CODE, ASHRAE 90.1-2007. 2. EXTERIOR LIGHTING SHALL COMPLY WITH CITY OF CARMEL EXTERIOR LIGHTING STANDARDS. 3. SPACE TO BE OCCUPIED INTERMITTENTLY. 4. SURFACE REFLECTANCE TO VARY BASED ON SPACE/AREA TYPE. 5. LIGHTING IN THE FEINSTEIN CLUB TO BE CONTROLLED BY CONSOLE AT SOUND BOOTH WITH OVERRIDE SWITCH IN THE SERVICE AREA FOR CLEANING. CONTROL DESIGNATION SPACE/AREA TYPE CONTROL INTENT DIMMING / SWITCHING/ SENSORS EMERGENCY CEILING HEIGHT < 8'-0" FL1 RECEPTION 109 ARCHITECTURAL LIGHTING AND DECORATIVE LIGHTING TO BE CONTROLLED SEPARATELY. CONTROL INTENT TO FUNCTION DEPENDENT ON USE OF CLUB SPACE. ARCHITECTURAL LIGHT FIXTURES TO HAVE CONTINUOUS 0-10V DIMMING TO 10%. DECORATIVE LIGHT FIXTURE DIMMING TO BE COORDINATED WITH FIXTURE LAMPING. EMERGENCY FIXTURES FORCED ON TO 100% BY INVERTER OR GTD UPON LOSS OF NORMAL POWER. YES FL2 PRIVATE DINING 111 LIGHTS PROGRAMMED FOR PRESET SCENES TO COINCIDE WITH PERFORMANCES AND CLEANING. SCENES TO BE COORDINATED WITH OWNER/OPERATOR. ROOM TO HAVE CAPABILITY TO FUNCTION INDEPENDENTLY FROM CLUB. ARCHITECTURAL LIGHT FIXTURES TO HAVE CONTINUOUS 0-10V DIMMING TO 1%. DECORATIVE LIGHT FIXTURE DIMMING TO BE COORDINATED WITH FIXTURE LAMPING. FIXTURES DESIGNATED AS NIGHT LIGHTS TO REMAIN ON 24/7 AND BE USED FOR EMERGENCY LIGHTING. YES FL3 FEINSTEIN CLUB 110 STAGE LIGHTING SCENES TO BE COORDINATED WITH OWNER/OPERATOR. ARCHITECTURAL LIGHTING AND DECORATIVE LIGHTING TO BE CONTROLLED INDEPENDENT FROM EACH OTHER AND STAGE LIGHTING. PRESET SCENES FOR SPACE TO BE COORDINATED WITH OWNER/OPERATOR. ARCHITECTURAL LIGHT FIXTURES TO HAVE CONTINUOUS 0-10V DIMMING TO 1%. DECORATIVE LIGHT FIXTURE DIMMING TO BE COORDINATED WITH FIXTURE LAMPING. EMERGENCY FIXTURES FORCED ON TO 100% BY INVERTER OR GTD UPON LOSS OF NORMAL POWER. YES FL4 BAR 112 ARCHITECTURAL LIGHTING TO BE CONTROLLED SEPARATE FROM DECORATIVE LIGHTING. PRESET SCENES TO BE COORDINATED WITH OWNER AND OPERATE CONSISTENTLY WITH CLUB LIGHTING. ARCHITECTURAL LIGHT FIXTURES TO HAVE CONTINUOUS 0-10V DIMMING TO 10%. DECORATIVE LIGHT FIXTURE DIMMING TO BE COORDINATED WITH FIXTURE LAMPING. EMERGENCY FIXTURES FORCED ON BY INVERTER OR GTD UPON LOSS OF NORMAL POWER. YES FL5 SERVICE 114, 136 LIGHTING TO BE CONTROLLED BY WALL BOX DIMMER WITH OVERRIDE SWITCH. LIGHTING CONTROL TO FUNCTION WITH CLUB LIGHTING WHILE SPACE IS IN USE. ARCHITECTURAL FIXTURES TO HAVE CONTINUOUS 0-10V DIMMING TO 10%. EMERGENCY FIXTURES FORCED ON TO 100% BY INVERTER OR GTD UPON LOSS OF NORMAL POWER. YES FL6 THEATRICAL STAGE STAGE LIGHTING FIXTURE TO BE INDIVIDUALLY ADDRESSABLE AND PROGRAMMABLE. GOBO PROJECTORS TO BE USED AS REQUIRED BY SPACE USE. PRESET SCENES TO BE COORDINATED WITH OWNER/OPERATOR. STAGE LIGHTING AND LIGHTING CONTROL TO HAVE CAPABILITY TO BE UPGRADED. PATHWAY DMX512 COGNITO2 LIGHTING CONTROLLER #0700-7112 OR ENGINEER APPROVED SUBSTITUTE. SYSTEM TO HAVE CAPABILITY TO BE UPGRADED OR ADDED ON TO IN FUTURE. SYSTEM TO HAVE +20 VIRTUAL PLAY-LISTS / SCENES, 1 EXTERNAL AND 3 INTERNAL TIME-CLOCKS OR TIME CLOCK EVENT TRIGGERING, (4)PUSH-BUTTONS TO CONTROL INTENSITY, COLOR, POSITION AND SHAPE ATTRIBUTES, (4) PUSH BUTTONS FOR RELEASE, HELP, EDIT AND RECORD FUNCTION, (2) DMX512 OUTPUT PORTS AND DMX512 INPUT PORT, (3) CONTACT CLOSURES, N/A YES FL7 VESTIBULE 113 PRESET SCENES TO BE COORDINATED WITH OWNER AND OPERATE CONSISTENTLY WITH CLUB LIGHTING. ARCHITECTURAL FIXTURES TO HAVE CONTINUOUS 0-10V DIMMING TO 10%. EMERGENCY FIXTURES FORCED ON TO 100% BY INVERTER OR GTD UPON LOSS OF NORMAL POWER. YESMMDM DD J JMJ J J J JJ J J J JJ J J J J J M M M J J J J J J J 21 21 23 23 26 26 28 28 Y Y U U W W RR 29 29 27 2725 25 XX SS VV QQ ZZ PRIVATE DINING 111 FEINSTEIN'S CLUB 110 RECEPTION 109 SERVICE 136 BAR 112 VESTIBULE 113 X1 HLR1 - 15 L1 HN1 - 3 1 X1 HLR1 - 15 X1 HLR1 - 15 F4 HLR1 - 15 F4 HN1 - 3 F4 HN1 - 3 F4 HN1 - 3 F4 HLR1 - 15 F4 HN1 - 3 L2 HN1 - 3 F6 LN1C - 45 F4 HLR1 - 15 F4 HN1 - 3 F1 HN1 - 3 F1 HN1 - 3 F5 LN1C - 45 F5 LN1C - 45 F5 LN1C - 45 1 1 1 1 1 1 1 1 F4 HLR1 - 15 F4 HN1 - 3 F4 HN1 - 3 X1 HLR1 - 15 X1 HLR1 - 15 F3 2 3 4 L6 HN1 - 3 L6 HLR1 - 15 6 3 21 21 23 23 26 26 28 28 T T Y Y U U W W RR 29 29 27 2725 25 XX SS VV 22 22 24 24 QQ ZZ F4 HLR1 - 15 F4 HLR1 - 15 X1 HLR1 - 15 8 F1 HN1 - 3 8 9 F4 HLR1 - 15 9 9 9 F4 HLR1 - 15 F4 HN1 - 3 F4 HLR1 - 15 9 F5 LN1C - 45 F5 LN1C - 45 F5 LN1C - 45 F5 LN1C - 45 9 9 9 10 9 F4 HLR1 - 15 F4 HN1 - 3F4 HLR1 - 15 F4 HLR1 - 15 F4 HN1 - 3 F4 HLR1 - 15 F4 HLR1 - 15 9 F4 HLR1 - 15 F4 HN1 - 3 F4 HN1 - 3 F4 HN1 - 3 F4 HN1 - 3 F4 HN1 - 3 F4 HN1 - 3 F4 HN1 - 3 9 9 Y Y U U W W RR XX SS VV QQ ZZ F4 HN1 - 3 1 11 F9-4' 12 F8 F10 HN1 - 3 L6 HLR1 - 15 L6 HN1 - 3 L6 HN1 - 3 L6 HN1 - 3 L6 HLR1 - 15 L6 HN1 - 3 GREEN 115 UNISEX TLT 116 SERVICE 114 CLUB OFFICE 119L1 HLR1 - 15 9 9 X1 HLR1 - 15 X1 HLR1 - 15 F9-4' F9-4' 12 127 8 4 F6 LN1C - 45 4 4 F6 LN1C - 45 X2 HLR1 - 15 X2 HLR1 - 15 LN1C - 43 LN1C - 43 LN1C - 43LN1C - 43 LN1C - 43 LN1C - 43LN1C - 59 LN1C - 59 LN1C - 59 LN1C - 59 LN1C - 59 CLUB STOR 124 LN1C - 45 LN1C - 45 LN1C - 45 LN1C - 53 LN1C - 53 LN1C - 53 F6 LN1C - 45 LN1C - 55 13 13 F2F2F2F2F2 F2 F1 HLR1 - 15F2 F2 5 F2 F2 F2 F2 F2 F2 F2 F2 F2 F2 F2 F2 F2F2 F2 F2 F2 F2 F2 F2 F2F2 F2 F2 F2 F2 5 5 5 5 8 9 PIPE GRID: 1.5" SCHEDULE 40 STEEL PIPE ON THREADED ROD WITH TURNBUCKLE MOUNTED 11'-6" ABOVE STAGE 5 5 5 PIPE GRID HANGER ASSEMBLY SPACED 8'-0" ON CENTER (TYP) 9 HLR1 - 15 X1 11 1 1 1 5 5 5 5 5 5 5 5 9 9 9 99 15 1 LN1C - 45 LN1C - 59 1 LN1C - 59 1 F5 LN1C - 45 9 L6 HLR1 - 15 L6 HN1 - 3 LN1C - 59 LN1C - 59 1 1 F10 HN1 - 3F4 HN1 - 3 A. SEE SHEET E-000 FOR ELECTRICAL SYMBOLS AND ABBREVIATIONS. B. SEE E-400 SHEETS FOR ENLARGED AREA PLANS AND ELEVATIONS. C. SEE E-500 SHEETS FOR ELECTRICAL DETAILS. D. SEE E-600 SHEETS FOR LIGHTING FIXTURE SCHEDULE, LIGHTING CONTROL INTENT AND PANEL SCHEDULES. E. ALL WORK SHALL COMPLY WITH NATIONAL, STATE, AND LOCAL CODES AND ORDINANCES PERTAINING TO WORK ON THIS PROJECT. F. REFER TO ARCHITECTURAL AND INTERIOR DESIGN DRAWINGS FOR DESIGNATION AND LISTING OF FIRE RATED ASSEMBLIES. COORDINATE ALL DESIGN EFFORTS WITH FIRE RESISTANCE OF MATERIALS AND CONSTRUCTION. G. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS, ROOM AND AREA FINISHES, CEILING PLANS, DOOR SWINGS, FIRE-RATED PARTITIONS, CABINET, CASEWORK, AND BUILT IN DETAILS. H. ALL LIGHTING AND LIGHTING CONTROLS ON THE PROJECT WILL BE IN ACCORDANCE WITH MARRIOTT AUTOGRAPH COLLECTION BRAND STANDARDS. I. EMERGENCY LIGHTING SHOWN ON THIS DRAWING INDICATES CODE REQUIRED EMERGENCY LIGHTING FED FROM THE `LEGALLY REQUIRED BRANCH' OF THE ESSENTIAL ELECTRICAL SYSTEM. J. LABEL ALL RELAYS AND POWER SUPPLIES (ON THE DEVICE OR ON THE BOX THEY ARE CONNECTED TO) WITH THE AREA THE DEVICE SERVES, THE BRANCH CIRCUIT IT CONTROLS, AND THE DEVICE ADDRESS (IF APPLICABLE). K. EXIT SIGNS MOUNTED ABOVE DOORS TO BE +0'-6" ABOVE FINISHED DOOR FRAME TO BOTTOM OF FIXTURE. EXITS NOT LOCATED ABOVE DOOR TO BE MOUNTED 7'-6" AFF TO BOTTOM OF FIXTURE UNLESS OTHERWISE NOTED. L. ALL DECORATIVE FIXTURES THAT ARE CONSIDERED PLUG LOAD AND ARE NOT HARDWIRED WILL BE SHOWN ON INTERIOR FF&E DRAWINGS. M. ALL CEILING MOUNTED OCCUPANCY SENSORS LOCATED IN PUBLIC AREAS TO BE RECESSED IN CEILING ACUITY RM-PDT-9 OR ENGINEER APPROVED SUBSTITUTE. FOR AREAS WHERE CEILINGS ARE GREATER THAN 10'-0" SENSORS TO BE ACUITY RM-PDT-9-6 OR ENGINEER APPROVED SUBSTITUTE. N. ALL CEILING MOUNTED OCCUPANCY SENSORS LOCATED IN BACK OF HOUSE AREAS TO BE SURFACE MOUNTED ACUITY CM-PDT10 OR ENGINEER APPROVED SUBSTITUTE. O. SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR LOCATIONS OF ACOUSTICALLY ISOLATED SPACES AND ADDITIONAL REQUIREMENTS. COORDINATE ALL MEP ITEMS WITH ACOUSTICAL ISOLATION SYSTEMS, INCLUDING BUT NOT LIMITED TO DUCTS, PIPES, WIRES, CONDUITS, ANCHORS, HANGERS, AND EQUIPMENT.COORDINATE INSTALLATION WITH GENERAL CONTRACTOR. P. WHERE MULTIPLE SWITCHES ARE ADJACENT TO EACH OTHER, GANG TOGETHER ON SINGLE FACE PLATE WITH MULTIPLE SWITCH/OUTLET. Q. ALL DECORATIVE LIGHT FIXTURES NOT INCLUDED IN LIGHT FIXTURE SCHEDULE ON SHEET E-601 TO BE INCLUDED IN FF&E BUDGET AND WILL NOT BE BID WITH ARCHITECTURAL LIGHTING PACKAGE. GENERAL SHEET NOTES DRAWING NO. DATE CDG PROJECT NO. DRAWING TITLE 3555 NW 58TH Street Suite 700-W Oklahoma City, OK 73112 T: 405.848.9549 F: 405.848.9783 www.gsb-inc.com Copyright ©GSB, Inc E-401 08/27/18 Electrical Enlarged Plans 17089 CARMEL, INCARMEL, IN 2018 ARCHITECT GSB, INC 3555 NW 58th Street, Suite 700W Oklahoma City, OK 73112 405 / 848-9549 CIVIL ENGINEER Circle Design Group 9229 Delegates Row, Suite 150 Indianapolis, IN 46240 317 / 706-2075 STRUCTURAL ENGINEER StructurePoint 7260 Shadeland Station Indianapolis, IN 46256 317 / 547-5580 MEP ENGINEER Circle Design Group 9229 Delegates Row, Suite 150 Indianapolis, IN 46240 317 / 706-2075 INTERIOR DESIGNER HBA Hirsch Bedner Associates 171 17th Street NW, Suite 600 Atlanta, GA 30363 404 / 928-1333 FOOD SERVICE CONSULTANT Ricca Newmark Design 5325 South Valentia Way Greenwood Village, CO 80111 303 / 928-1333 SHEET KEYNOTES 1 DECORATIVE LIGHTING FIXTURE SHOWN FOR REFERENCE. REFER TO INTERIOR DESIGN, FF&E AND ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION. 2 LIGHTING CONTROL CONSOLE TO BE LOCATED IN SOUND BOOTH AND SHALL BE PATHWAY COGNITO2 PRO512 007-7111 OR ENGINEER APPROVED SUBSTITUTE. CONSOLE TO BE UPGRADABLE. CONSOLE TO HAVE (3) INTERNAL TIMECODE CLOCKS, ASTRONOMINAL TIMECLOCK FOR EVENT TRIGGERING, PUSH BUTTONS TO CONTROL INTENSITY, COLOR, POSITION AND SHAPE ATTRIBUTES, PUSH BUTTONS TO ACCESS RELEASE, HELP, EDIT AND RECORD FUNCTIONS, 2 PLAYBACKS, MINIMUM OF 20 PLAYLISTS OR CHASES, AND DMX INPUT/OUTPUT PORTS. 3 FIXTURES MOUNTED BELOW COUNTERLINE AND CONCEALED BY BAFFLE OR TRIM PIECE. SEE INTERIOR/ARCH. DRAWINGS FOR ADDITIONAL INFORMATION. 4 MOUNT FIXTURE +1'-6" ABOVE FINISHED FLOOR TO BOTTOM OF FIXTURE. 5 THEATRICAL FIXTURES AFFIXED TO 1-1/2" SCHEDULE 40 STEEL PIPE WITH CLAMPS AND SUSPENDED FROM STRUCTURE ABOVE. SAFETY CABLE PROVIDED BY MANUFACTURER. AIM AND FOCUS OF FIXTURES TO BE CONDUCTED WITH OWNER, LIGHTING DESIGNER AND ELC. FINAL PLACEMENT TO BE COORDINATED WITH OTHER DISCIPLINES. 6 LED TAPE LIGHT IN ALUMINUM EXTRUSION MOUNTED TO UNDERSIDE LIP OF TOE-KICK. SEE ELECTRICAL DETAILS FOR MOUNTING INFORMATION. 7 PROVIDE A QUANTITY OF (2) ETC: CSSPOTS LIGHT FIXTURES FOR GOBOS. FINAL PLACEMENT OF FIXTURE TO BE COORDINATED WITH OWNER/OPERATOR. 8 MOUNT FIXTURE 10'-0" AFF TO BOTTOM OF FIXTURE. 9 PROVIDE AND INSTALL BODINE GTD20A GENERATOR TRANSFER DEVICE (GTD) OR EQUAL PRODUCT AS APPROVED BY ENGINEER FOR LIGHTING LOAD. FIXTURE TO BE CONNECTED TO LOCAL NORMAL CIRCUIT. 10 MANUAL OVERRIDE SWITCH FOR LIGHTS DESIGNATED FOR CLEANING. 11 FIXTURE SURFACE MOUNTED TO UNDERSIDE OF COUNTER IN EXTRUDED ALUMINUM HOUSING WITH LENS BY MOUNTING CLIPS. POWER FEED TO BE PROVIDED THROUGH ENDCAP. 12 LINEAR LED TAPE SURFACE MOUNTED TO UNDERSIDE OF UPPER CABINET ~5'-0" A.F.F AND BEHIND BAFFLE. ADDITIONAL RUN OF TAPELIGHT RECESSED WITHIN TOP OF UPPER CABINET AND CENTERED OVER TOP SHELF. SEE INTERIOR DESIGN DRAWINGS FOR ADDITIONAL INFORMATION. FINAL PLACEMENT TO BE VERIFIED WITH MILLWORK, INTERIOR DESIGN AND ARCHITECTURAL DRAWINGS. 13 LED STRIP SURFACE MOUNTED IN NICHE AT DRAPERY POCKET TO FILL WALL TO WALL. SEE INTERIOR DESIGN CEILING DETAILS FOR MOUNTING INFORMATION. REMOTE POWER SUPPLY PLACEMENT TO BE COORDINATED IN FIELD. 15 LOCAL CONTROL FOR FIXTURES IN PRIVATE DINING 111. 1/4" = 1'-0" Enlarged Lighting - Feinstein Club10 8'4'2' N NO. DATE DESCRIPTION 1 08/27/2018 Issued for Construction 3 12/03/2018 Revision 3 6 03/22/2019 Revision 8 18 11/06/2019 Revision 20