HomeMy WebLinkAboutE-501-Electrical-Details-Rev.2CU GRD. BAR RACKS #6 AWG INSULATED GROUND CONDUCTOR MDF & IDF'S GMAIN EQUIPMENT BONDING JUMPER (SIZE IN ACCORDANCE WITH NEC ARTICLE 250) TO MAIN SERVICE EQUIPMENT SWITCHBOARD OR PANELBOARD GROUND BUS AT SERVICE ENTRANCE N G PANELBOARD G DISTRIBUTION PANELBOARD N N G PANELBOARD EQUIPMENT GROUND - SIZE AS SHOWN ON DRAWINGS TRANSFORMER C N B A BONDING JUMPERS (SIZE IN ACCORDANCE WITH NEC ARTICLE 250) N G COMMUNICATIONS SYSTEMS EQUIPMENT CABINET GROUND COMMUNICATIONS PLYWOOD BACKBOARD GROUND BAR TELEPHONE SERVICE DEMARK GROUND BAR 3/4"X10' CU GROUND ROD AS REQUIRED (SEE SECTION 260526) #3/0 CU BONDING JUMPER IF NOT FACTORY INSTALLED EQUIPMENT GROUND. SIZE AS SHOWN ON DRAWINGS EQUIPMENT GROUND - SIZE AS SHOWN ON DRAWINGS G NEUTRAL BUS GROUND BUS BUILDING STEEL (INDOOR) OR GROUND ROD (OUTDOOR) GENERATOR FRAME AND ENCLOSURE N C GENERATOR B A #3/0 BARE CU GROUNDING ELECTRODE CONDUCTOR #3/0 CU EQUIPMENT BONDING JUMPER BONDING BUSHING (TYPICAL) SERVICE EQUIPMENT ENCLOSURE (MAIN SWITCHBOARD) MAIN BONDING JUMPER (SIZE IN ACCORDANCE WITH NEC ARTICLE 250) PANELBOARD AUTOMATIC TRANSFER SWITCH ENCLOSURE (SWITCHED NTL) BUILDING STEEL OR INTERIOR METAL WATER PIPE AND GROUND ROD IF STEEL IS NOT AVAILABLE #3/0 BARE CU GROUNDING ELECTRODE CONDUCTOR 3/4"X10' CU GROUND ROD BUILDING FOUNDATION REBAR #3/0 BARE CU GROUND RING INCOMING METAL WATER SERVICE BUILDING STEEL #3/0 BARE CU GROUNDING ELECTRODE CONDUCTOR 3/4"X10' CU GROUND ROD 3/4"X10' CU GROUND ROD INCOMING SERVICE METAL CONDUITS TRANSFORMER ENCLOSURE #3/0 BARE CU GROUNDING ELECTRODE CONDUCTOR IG IG IG TRANSFORMER C N B A NTL AS SHOWN ON DRAWINGS NO GROUND CABLE TO NTL UTILITY TRANSFORMER TO UTILITY TRANSFORMER ISOLATED GROUND- SIZE AS SHOWN ON DRAWINGS WHEN REQUIRED 10'-0"10'-0"10'-0" 3/0 COPPER CABLE EXOTHERMICALLY WELD CABLE TO GROUND RODS 3/4" DIA. X 10' LONG COPPER CLAD STEEL GROUND ROD 3/0 COPPER CABLE PANEL DESIGNATION GROUND CONDUCTOR(S) PHASE CONDUCTOR(S) NEUTRAL CONDUCTOR(S) ALL CONDUCTORS NOT LESS THAN #12 ALL CONDUIT NOT LESS THAN 3/4"CIRCUIT NO. DESIGNATION AL1 1,3,5 }DRINKING WATER COOLER BY OTHER DIVISION. FLOOR VERIFY ROUGH-IN-HEIGHT WITH APPROVED MFG. SHOP DWG. CONTRACTOR TO USE DUPLEX RECEPTACLE. CB FACP ZAM ZAM ZAM SSSSS ZAMZAM CB CAB CONTROL IN HOISTWAY ROOM EQUIPMENT IN ELEVATOR FIRST FLOOR LOBBY THIRD FLOOR LOBBY SECOND FLOOR LOBBY NOTES: 1. PROVIDE ENGRAVED PHOENELIC NAMEPLATE ON DISCONNECTS STATING MORE THAN ONE SOURCE SERVES THE ELEVATOR CABINET. 2. SHOULD THE GENERAL CONTRACTOR UTILIZE AN ELEVATOR MANUFACTURER THAT REQUIRE MORE ELECTRICAL WORK THAN SHOWN ON THIS DETAIL, THE COSTS SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. 3. F ELEVATOR CAN BE OPERATED FROM NEC 702 OPTIONAL POWER SYSTEM, ALL HVAC EQUIPMENT SERVING THE ELEVATOR EQUIPMENT ROOM SHALL BE CONNECTED TO THE OPTIONAL POWER SYSTEM. 4. EQUIPMENT SHOWN SHADED IS BY ELEVATOR MANUFACTURER. ITEMS SHOWN DARK ARE BY DIVISION 26. TO DEDICATED CIRCUIT IN 120/208 VOLT PANEL 600V 3P FUSIBLE DISCONNECT WITH AUXILIARY N.O. CONTACT IN ELEVATOR MACHINE ROOM - SEE PLANS FOR SIZE AND ADDITIONAL INFORMATION 1P-30 AMP FUSIBLE DISCONNECT FUSED AT 20 AMPS IN ELEVATOR MACHINE ROOM FOR ELEVATOR CAB LIGHTS 480 VOLT 3 PHASE OR 208 VOLT 3 PHASE ELEVATOR FEED (SIZED PER POWER DISTRIBUTION DIAGRAM/ ONE LINE DIAGRAM) 3/4"C, 2-#12 AND 1-#12 GRD #18 SHIELDED TWISTED PAIR BY DIVISION 26 JUST OUTSIDE HOISTWAY IN ELEVATOR EQUIPMENT ROOM NEAR ELEVATOR CONTROLS FIRST FLOOR LOBBY SECOND FLOOR LOBBY THIRD FLOOR LOBBY 3/4"C, 2-#14 (MAY BE COMBINED IN A SINGLE RACEWAY) TO CAB LIGHTS BY ELEVATOR MANUFACTURER/ INSTALLER BY DIVISION 26 TO 120/208 VOLT OR 277/480 VOLT PANEL PER PLANS 3/4"C, 2-#12 AND 1-#12 GRD 3/4"C, 2-#10 AND 1-#10 GRD TELEPHONE OUTLET NEAR CONTROLLER 3/4"C, 2-#14 3/4"C, 2-#12 AND 1-#12 GRDGFI RECEPTACLE IN ELEVATOR PIT LED VAPORTITE LIGHTING FIXTURES IN ELEVATOR PIT TO DEDICATED CIRCUIT IN 120/208 VOLT PANEL 3/4"C, 2-#12 AND 1-#12 GRD 3/4"C, 2-#12 AND 1-#12 GRD 3/4"C, 2-#12 AND 1-#12 GRD GFI RECEPTACLE IN ELEVATOR MACHINE ROOM LIGHTING FIXTURES IN ELEVATOR MACHINE ROOM TO 120/208 VOLT PANEL PER PLANS CCTV CONNECTION NEAR CONTROLLER ACCESS CONTROL NEAR CONTROLLER ACCESS CONTROL CABLE CCTV CABLE TELEPHONE CABLE EXIT NOTES: 1. EQUIPMENT MOUNTING HEIGHTS SHALL BE INDICATED UNLESS OTHERWISE NOTED ON THE DRAWINGS OR IN THE SPECIFICATIONS. 2. CONCEAL RECEPTACLE BEHIND WATER COOLER. VERIFY EXACT MOUNTING HEIGHTS. 3. WHERE DEVICES ARE LOCATED IN MASONRY WALLS LOCATE DEVICE WITHIN COARSING SO THAT MOUNTING INDICATED HERE IN IS NOT EXCEEDED. 4. ALL RECEPTACLES ABOVE KITCHEN COUNTER AND NEAR BATH VANITIES SHALL BE INSTALLED HORIZONTALLY AT +44" AFF TO TOP OF THE BOX. CEILING F H S F STV VC IC F96"96"48"48"72"48"36"20"20"20"NOTE 220"20"96"96"72"96"48"20"48"48"84"SYMBOLS: FLOOR W WC J C S M D M (2) 1/2" DIA. X 3-1/2" EXPANSION ANCHOR (COORD. ANCHOR LOCATION WITH REINFORCING) TYPICAL COLUMN/WALL TYPICAL FLANGED-UP TYPE CHANNEL TYPICAL RISER TYPICAL B-LINE SYSTEMS FIGURE B3149 PIPE CLAMP NOTES: 1. IF ADDITIONAL DISTANCE FROM COLUMN OR WALL IS REQUIRED OR IF RISER IS MOUNTED AT EDGE OF COLUMN, USE B-LINE SYSTEMS FIGURE B3149 CLAMP. BEND AND DRILL HOLES IN LEGS AS REQUIRED. 2. CHANNEL OR CLAMP ARE NOT TO EXTEND PAST EDGE OF COLUMN OR WALL. IF OUTSIDE DIMENSION OF CLAMP IS GREATER THAN THICKNESS OF WALL OR COLUMN, USE A B-LINE SYSTEMS FIGURE B3149 HANGER, BEND LEGS INWARD AND DRILL HOLES AS REQUIRED. 3. ALL MATERIALS AND HARDWARE SHALL BE HOT DIPPED GALVANIZED OR STAINLESS STEEL. 4. SPECIFY TYPE OF PIPE FOR SIZING PIPE CLAMPS. FINISHED FLOOR THREADED PLUG THREADED COUPLING CONDUIT ROOFING (BY OTHERS) BUILT-UP ROOF DECK. (BY OTHERS) STEPPED PVC BOOT CONDUIT STAINLESS STEEL CLAMPS SPUN ALUMINUM FLASHING BASE CONDUIT BONDING PLATE OR EXOTHERMIC WELD TO STEEL COLUMN EXOTHERMIC CONNECTION TO GROUND ROD CLASS II COPPER GROUNDING CONDUCTOR 3/4" x 10'-0" COPPER CLAD STEEL GROUND ROD IND VFL HOUSING TYPE CAMERA/LENS TYPE VFL VARIFOCAL LONG LENS VFM VARIFOCAL MEDIUM LENS VFW VARIFOCAL WIDE ANGLE LENS PTZ PAN/TITL/ZOOM CAMERA AND LENS CAMERA/LENS TYPES HOUSING TYPES IND INDOOR DOME EXD EXTERIOR DOME (HEATED AND COOLED) CONC CONCEALED MOUNTING Slotted Channel to Support 400% of Conduit Weight. Double Nut Top and Bottom Beam Clamp Threaded Rod Conduit Clamps Support Structure Conduit Beam Clamp Beam Clamp Conduit Clamps Slotted Channel to Support 400% of Conduit Weight DRAWING NO. DATE CDG PROJECT NO. DRAWING TITLE 3555 NW 58TH Street Suite 700-W Oklahoma City, OK 73112 T: 405.848.9549 F: 405.848.9783 www.gsb-inc.com Copyright ©GSB, Inc E-501 08/27/18 Electrical Details 17089 CARMEL, INCARMEL, IN 2018 ARCHITECT GSB, INC 3555 NW 58th Street, Suite 700W Oklahoma City, OK 73112 405 / 848-9549 CIVIL ENGINEER Circle Design Group 9229 Delegates Row, Suite 150 Indianapolis, IN 46240 317 / 706-2075 STRUCTURAL ENGINEER StructurePoint 7260 Shadeland Station Indianapolis, IN 46256 317 / 547-5580 MEP ENGINEER Circle Design Group 9229 Delegates Row, Suite 150 Indianapolis, IN 46240 317 / 706-2075 INTERIOR DESIGNER HBA Hirsch Bedner Associates 171 17th Street NW, Suite 600 Atlanta, GA 30363 404 / 928-1333 FOOD SERVICE CONSULTANT Ricca Newmark Design 5325 South Valentia Way Greenwood Village, CO 80111 303 / 928-1333 NOT TO SCALE Typical Grounding Detail13 NOT TO SCALE Service Grounding Electrode Arrangement6 NOT TO SCALE Key to Electrical Circuit Wiring9 NOT TO SCALE EWC Wiring7 NOT TO SCALE Elevator Wiring Diagram11 NOT TO SCALE Electrical Elevation12 NOT TO SCALE Conduit Support Detail5 NOT TO SCALE Conduit Stub Up Detail3 NOT TO SCALE Conduit Roof Penetration4 NOT TO SCALE Column Grounding - No Sleeve10 NOT TO SCALE CCTV Camera Type Legend8 NOT TO SCALE 2in And Larger Conduit Support1 NOT TO SCALE 1.5in And Smaller Conduit Support2 REVISIONS NO. DATE DESCRIPTION 1 08/27/2018 Issued for Construction