Loading...
HomeMy WebLinkAboutE-801-Electrical-One-Line-Diagram-Rev.5SCALE: 'TN1'NEW 480-300kVA 208/120 'TN3'NEW 480-300kVA 208/120 'TN5' 480- 208/120 NEW 300kVA 'TND' 480- 208/120 NEW 75kVA 'TNK' 480- 208/120 NEW 150kVA 400AS 400AF 800AS 800AF PENTHOUSE PENTHOUSE 4TH FLOOR ELECTRICAL ROOM 3RD FLOOR ELECTRICAL ROOM 800AS 800AF 2ND FLOOR MECH ROOM 2ND FLOOR MECH ROOM FEEDER SCHEDULE AMPS PARALLEL RUNS CONDUCTOR GROUND CONDUIT SIZE CU AL CU AL CU AL 1 3000 8 500 kCMIL 750 kCMIL 500 kCMIL 750 kCMIL 4" EACH 4" EACH 2 2500 7 500 kCMIL 750 kCMIL 350 kCMIL 500 kCMIL 4" EACH 4" EACH 3 2000 6 500 kCMIL 750 kCMIL 250 kCMIL 350 kCMIL 4" EACH 4" EACH 4 1800 5 500 kCMIL 750 kCMIL 250 kCMIL 350 kCMIL 4" EACH 4" EACH 5 1600 5 500 kCMIL 750 kCMIL #4/0 350 kCMIL 4" EACH 4" EACH 6 1200 4 500 kCMIL 750 kCMIL #3/0 250 kCMIL 4" EACH 4" EACH 7 1000 3 500 kCMIL 750 kCMIL #2/0 #4/0 4" EACH 4" EACH 8 900 3 350 kCMIL 500 kCMIL #2/0 #4/0 4" EACH 4" EACH 9 800 2 500 kCMIL 750 kCMIL #1/0 #3/0 4" EACH 4" EACH 10 600 2 350 kCMIL 500 kCMIL #1 #2/0 4" EACH 4" EACH 11 500 2 250 kCMIL 350 kCMIL #2 #1/0 4" EACH 4" EACH 12 400 - 500 kCMIL 750 kCMIL #3 #1 4" 4" 13 350 - 400 kCMIL 750 kCMIL #3 #1 3-1/2" 3-1/2" 14 300 - 350 kCMIL 500 kCMIL #4 #2 3" 3" 15 250 - 250 kCMIL 350 kCMIL #4 #2 3" 3" 16 225 - #4/0 350 kCMIL #4 #2 2-1/2" 2-1/2" 17 200 - #3/0 250 kCMIL #6 #4 2" 2" 18 175 - #2/0 #4/0 #6 #4 2" 2" 19 150 - #1/0 #3/0 #6 #4 2" 2" 20 125 - #1 #2/0 #6 #4 2" 2" 21 110 - #2 #1/0 #6 #4 1-1/2" 1-1/2" 22 100 - #3 #1 #6 #6 1-1/4" 1-1/4" 23 80 - #4 - #8 - 1" - 24 60 - #6 - #10 - 1" - 25 50 - #8 - #10 - 3/4" - 26 30 - #10 - #10 - 3/4" - 27 20 - #12 - #12 - 3/4" - TRANSFORMER UTILITY 1 3000AF 3P 2500AT LSIG 25 FIRE PUMP ELEV-2 X HDPN 208Y/120V, 3P, 4W, 3,000A 42kAIC LN1A 120/208 3P-4W 200A MLO LN1B 120/208 3P-4W 200A MLO LN1C 120/208 3P-4W 200A MLO HN1 277/480 3P-4W 225A MLO M LN3A 120/208 3P-4W 200A MLO LN3B 120/208 3P-4W 200A MLO LN3C 120/208 3P-4W 200A MLO LN4A 120/208 3P-4W 200A MLO LN4B 120/208 3P-4W 200A MLO LN4C 120/208 3P-4W 200A MLO LN5A 120/208 3P-4W 200A MLO LN5C 120/208 3P-4W 200A MLO LN6A 120/208 3P-4W 200A MLO LN6B 120/208 3P-4W 200A MLO LN5B 120/208 3P-4W 200A MLO LN6C 120/208 3P-4W 200A MLO HN3 277/480 3P-4W 125A MLO HN5 277/480 3P-4W 125A MLO LN7 120/208 3P-4W 200A MLO HN7 277/480 3P-4W 100A MLO ATS-FP LN2A 120/208 3P-4W 200A MLO LN2B 120/208 3P-4W 200A MLO LN2C 120/208 3P-4W 200A MLO HN2 277/480 3P-4W 125A MLO LN1D 120/208 3P-4W 100A MCB DUKE ENERGY PRIMARY BY OTHERS HSK 277/480 3P-4W 400A MLO HDPN2 277/480 3P-4W 400A MLO HDPN7 277/480 3P-4W 800A MLO LN2D 120/208 3P-4W 200A MCB LSK 120/208 3P-4W 400A MLO SPD 277/480 3P-4W 60 MLO LDPN5 208Y/120V, 3P, 4W, 800A 22kAIC LDPN3 208Y/120V, 3P, 4W, 800A 22kAIC LDPN1 208Y/120V, 3P, 4W, 800A 22kAIC 'JH1' 30AS/NF - AUX CONTACT IN SHAFT AT TOP 'JH' 30AS/25AF ADJACENT HLR7 400A 3P 400A 3P 400A 3P 400A 3P 800A 3P 200A 3P 200A 3P 200A 3P 200A 3P 200A 3P 200A 3P 100A 3P 200A 3P 225A 3P 125A 3P 125A 3P 125A 3P 400A 3P 400A 3P 125A 3P 225A 3P 100A 3P 200A 3P 200A 3P 800A 3P 200A 3P 200A 3P 200A 3P 200A 3P 200A 3P 200A 3P 800A 3P 200A 3P 100A 3P 200A 3P 200A 3P 200A 3P 200A 3P 200A 3P 200A 3P 800A 3P 200A 3P 60A 3P 200A 3P ELECTRICAL ONE-LINE DIAGRAM NOT TO SCALE DRAWING NO. DATE CDG PROJECT NO. DRAWING TITLE 3555 NW 58TH Street Suite 700-W Oklahoma City, OK 73112 T: 405.848.9549 F: 405.848.9783 www.gsb-inc.com Copyright ©GSB, Inc E-801 08/27/18 Electrical One-Line Diagram 17089 CARMEL, INCARMEL, IN 2018 ARCHITECT GSB, INC 3555 NW 58th Street, Suite 700W Oklahoma City, OK 73112 405 / 848-9549 CIVIL ENGINEER Circle Design Group 9229 Delegates Row, Suite 150 Indianapolis, IN 46240 317 / 706-2075 STRUCTURAL ENGINEER StructurePoint 7260 Shadeland Station Indianapolis, IN 46256 317 / 547-5580 MEP ENGINEER Circle Design Group 9229 Delegates Row, Suite 150 Indianapolis, IN 46240 317 / 706-2075 INTERIOR DESIGNER HBA Hirsch Bedner Associates 171 17th Street NW, Suite 600 Atlanta, GA 30363 404 / 928-1333 FOOD SERVICE CONSULTANT Ricca Newmark Design 5325 South Valentia Way Greenwood Village, CO 80111 303 / 928-1333 SHEET KEYNOTES 1 CONTINUED TO ATS-LR ON SHEET E-802. 2 FIRE PUMP ATS/CONTROLLER FURNISHED AND INSTALLED BY FIRE SUPPRESSION CONTRACTOR. TERMINATIONS BY ELECTRICAL CONTRACTOR. 3 SEE 13/E-501 FOR GROUNDING DETAIL. 4 (2) 1"C MANUFACTURES RECOMMENDED CONTROL CONDUCTORS FROM ATS-FP TO GENERATOR. SEE KEYNOTE #6 ON SHEET E-802 FOR CONTINUATION. 5 EXTEND TO EXISTING GENERATOR. 6 FURNISH PANEL WITH INTEGRAL SHUNT TRIP MAIN CIRCUIT BREAKER. SHUNT TRIP TO BE ACTIVATED BY SIGNAL FROM FIRE ALARM CONTROL PANEL. IN THE EVENT OF A GENERAL FIRE ALARM THE FIRE ALARM CONTROL PANEL SHALL SEND A SIGNAL TO THE SHUNT TRIP ACTIVATING IT SO THAT POWER TO THE PANEL HAS BEEN CUT. 7 3/4" CONDUIT WITH MANUFACTURERS RECOMMENDED CONTROL CABLE TO FIRE ALARM CONTROL PANEL. 1 2 5 3 4 3 3 3 23 20 23 12 8 16 9 12 2 12 12 9 9 17 17 17 17 17 17 17 17 17 17 17 17 17 17 17 12 17 17 17 17 7 6 12 12 22 20 16 16 12 3 3 24 NO. DATE DESCRIPTION 1 08/27/2018 Issued for Construction 6 03/22/2019 Revision 8 7 05/15/2019 Revision 10 12 9 9 26 7 7 7