HomeMy WebLinkAboutE-802-Emergency-Electrical-One-Line-Diagram-Rev.4SCALE: TRANSFER SWITCH ATS-LR NOTES TRANSFER SWITCH TYPE: AUTOMATIC CURRENT RATING: 400 A RATED VOLTAGE: 480 V 3-PHASE/ 4 WIRE # OF POLES: 4 NEUTRAL CONFIGURATION: SWITCHED IN-SYNC TRANSFER: N MAIN CIRCUIT BREAKER: N GROUND FAULT ON MAIN: N SERVICE ENTRANCE RATED: N REMOTE ANNUNCIATION: N BY-PASS/ISOLATION: N NEC LOAD BRANCH: 700 KAIC: 42 SEE SPECIFICATIONS FOR ADDITIONAL FEATURES NEMA RATING: 1 FEEDER SCHEDULE AMPS PARALLEL RUNS CONDUCTOR GROUND CONDUIT SIZE CU AL CU AL CU AL 1 3000 8 500 kCMIL 750 kCMIL 500 kCMIL 750 kCMIL 4" EACH 4" EACH 2 2500 7 500 kCMIL 750 kCMIL 350 kCMIL 500 kCMIL 4" EACH 4" EACH 3 2000 6 500 kCMIL 750 kCMIL 250 kCMIL 350 kCMIL 4" EACH 4" EACH 4 1800 5 500 kCMIL 750 kCMIL 250 kCMIL 350 kCMIL 4" EACH 4" EACH 5 1600 5 500 kCMIL 750 kCMIL #4/0 350 kCMIL 4" EACH 4" EACH 6 1200 4 500 kCMIL 750 kCMIL #3/0 250 kCMIL 4" EACH 4" EACH 7 1000 3 500 kCMIL 750 kCMIL #2/0 #4/0 4" EACH 4" EACH 8 900 3 350 kCMIL 500 kCMIL #2/0 #4/0 4" EACH 4" EACH 9 800 2 500 kCMIL 750 kCMIL #1/0 #3/0 4" EACH 4" EACH 10 600 2 350 kCMIL 500 kCMIL #1 #2/0 4" EACH 4" EACH 11 500 2 250 kCMIL 350 kCMIL #2 #1/0 4" EACH 4" EACH 12 400 - 500 kCMIL 750 kCMIL #3 #1 4" 4" 13 350 - 400 kCMIL 750 kCMIL #3 #1 3-1/2" 3-1/2" 14 300 - 350 kCMIL 500 kCMIL #4 #2 3" 3" 15 250 - 250 kCMIL 350 kCMIL #4 #2 3" 3" 16 225 - #4/0 350 kCMIL #4 #2 2-1/2" 2-1/2" 17 200 - #3/0 250 kCMIL #6 #4 2" 2" 18 175 - #2/0 #4/0 #6 #4 2" 2" 19 150 - #1/0 #3/0 #6 #4 2" 2" 20 125 - #1 #2/0 #6 #4 2" 2" 21 110 - #2 #1/0 #6 #4 1-1/2" 1-1/2" 22 100 - #3 #1 #6 #6 1-1/4" 1-1/4" 23 80 - #4 - #8 - 1" - 24 60 - #6 - #10 - 1" - 25 50 - #8 - #10 - 3/4" - 26 30 - #10 - #10 - 3/4" - 27 20 - #12 - #12 - 3/4" - 'TLR1' 480- 208/120 NEW 45kVA 1 ELEV-1 ELEV-3 700 - LIFE SAFETY SYSTEMS 702 - OPTIONAL STANDBY SYSTEMS NEC LOAD BRANCH OPTIONS: LLR1 120/208 3P-4W 100A MCB HLR1 277/480 3P-4W 400A MLO HLR2 277/480 3P-4W 100A MLO HLR3 277/480 3P-4W 100A MLO HLR5 277/480 3P-4W 100A MLO ATS-LR X HLR7 277/480 3P-4W 250A MLO LLR3 120/208 3P-4W 100A MLO LLR5 120/208 3P-4W 100A MLO 'JH1' 30AS/NF - AUX CONTACT IN SHAFT AT TOP 'JH' 30AS/25AF ADJACENT HLR7 EMERGENCY ELECTRICAL ONE-LINE DIAGRAM NOT TO SCALE DRAWING NO. DATE CDG PROJECT NO. DRAWING TITLE 3555 NW 58TH Street Suite 700-W Oklahoma City, OK 73112 T: 405.848.9549 F: 405.848.9783 www.gsb-inc.com Copyright ©GSB, Inc E-802 08/27/18 Emergency Electrical One-Line Diagram 17089 CARMEL, INCARMEL, IN 2018 ARCHITECT GSB, INC 3555 NW 58th Street, Suite 700W Oklahoma City, OK 73112 405 / 848-9549 CIVIL ENGINEER Circle Design Group 9229 Delegates Row, Suite 150 Indianapolis, IN 46240 317 / 706-2075 STRUCTURAL ENGINEER StructurePoint 7260 Shadeland Station Indianapolis, IN 46256 317 / 547-5580 MEP ENGINEER Circle Design Group 9229 Delegates Row, Suite 150 Indianapolis, IN 46240 317 / 706-2075 INTERIOR DESIGNER HBA Hirsch Bedner Associates 171 17th Street NW, Suite 600 Atlanta, GA 30363 404 / 928-1333 FOOD SERVICE CONSULTANT Ricca Newmark Design 5325 South Valentia Way Greenwood Village, CO 80111 303 / 928-1333 SHEET KEYNOTES 8 EXTEND TO EXISTING GENERATOR. 10 EXTEND TO HDPN. SEE KEYNOTE #2 ON SHEET E-801 FOR CONTINUATION. 13 (2) 1"C WITH MANUFACTURES RECOMMENDED CONTROL CONDUCTORS TO GENERATOR. 16 SEE 13/E-501 FOR GROUNDING DETAIL. 17 INTERLOCK AUX CONTACTS TO ELEVATOR #1 AND #3 CONTROLLERS. 16 10 8 17 20 20 22 2226 20 15 20 1012 20 20 NO. DATE DESCRIPTION 09/12/2018 ADD #2 1 08/27/2018 Issued for Construction 6 03/22/2019 Revision 8 7 05/15/2019 Revision 10 13 7 7 7