HomeMy WebLinkAboutM0-01-MECHANICAL-SYMBOLS-AND-ABBREVIATIONS-Rev.1ACCESS TO FIRE/SMOKE DAMPERS MUST BE PROVIDED WHETHER SHOWN ON PLANS OR NOT. ACCESS MUST KNOW EASY SERVICE OF FUSIBLE LINK OR ANCHOR FOR RESET AND BE CLEARLY MARKED.28. DURING REMOVAL OF ITEMS SO INDICATED, CAUTION SHALL BE USED TO PREVENT DAMAGE TO ANY EQUIPMENT HAVING SALVAGE VALUE. ALL REUSABLE SALVAGED MATERIAL SHALL REMAIN THE PROPERTY OF THE OWNER AND BE RETAINED FOR HIS INSPECTION. ONLY ITEMS SO INSPECTED AND REJECTED BY THE OWNER SHALL BE DISPOSED OF BY THE CONTRACTOR. ALL OTHER ITEMS SHALL BE TURNED OVER AND DEPOSITED AS DIRECTED BY THE OWNER. 27. DO NOT ROUTE ANY SYSTEMS THROUGH ELECTRIC ROOMS. FOR SYSTEMS THAT SERVE ELECTRIC ROOMS, DO NOT ROUTE OVER EQUIPMENT, PANELS, TRANSFORMERS, VFD'S, OR ELECTRICAL COMPONENTS AND DO NOT HINDER SERVICE ACCESS. :ELECTRICAL EQUIPMENT ROOMS SERVE T-COMM ROOMS, DO NOT ROUTE OVER EQUIPMENT OR ELECTRICAL COMPONENTS AND DO NOT HINDER SERVICE ACCESS. DO NOT ROUTE ANY SYSTEMS THROUGH TELECOMMUNICATIONS ROOMS. FOR SYSTEMS THAT :TELECOMMUNICATIONS ROOMS (MDF AND IDF) SERVE ELEVATOR EQUIPMENT ROOMS, DO NOT ROUTE OVER ELEVATOR EQUIPMENT OR ELECTRICAL COMPONENTS AND DO NOT HINDER SERVICE ACCESS. DO NOT ROUTE ANY SYSTEMS THROUGH ELEVATOR EQUIPMENT ROOMS. FOR SYSTEMS THAT :ELEVATOR EQUIPMENT ROOMS COORDINATE EQUIPMENT SERVICE ACCESS. CLEARANCES INDICATED ARE BASED UPON BEST AVAILABLE INFORMATION. CONTRACTOR SHALL VERIFY PIPING, DUCTWORK, ETC., ROUTING PRIOR TO SUBMITTING A BID PROPOSAL AND INCLUDE ANY SUCH COSTS AS REQUIRED TO INSTALL WORK AS SHOWN AND INTENDED. 26. PROVIDE NEC CLEARANCES AND SERVICE CLEARANCES FOR EQUIPMENT.25. FURNISH AND INSTALL ACCEPTABLE CONCRETE INSERTS, ANCHORS, CLAMPS, BRACKETS, HANGERS, STRUCTURAL MEMBERS (ANGLES, CHANNELS, ETC.) AND FRAMES, ETC., REQUIRED FOR SUPPORTING ALL RESPECTIVE WORK. SUPPORTING DEVICES, ASSEMBLIES AND ATTATCHMENTS SHALL BE DESIGNED AND ARRANGED TO CARRY THE WEIGHT OF THE SUPPORTED ITEMS INCLUDING HANGER AND CONTENTS WITHOUT TRANSMITTING VIBRATION OR NOISE TO THE BUILDING CONSTRUCTION; DESIGNED, APPROPRIATE AND APPROVED FOR THE PURPOSE USED; HAVE A NEAT AND FINISHED APPEARANCE AND COMPLEMENT THE INSTALLATION; HAVE CORROSION PROTECTION SUITABLE FOR THE ATMOSPHERE WHERE INSTALLED; ADEQUATELY AND SAFELY ATTACHED TO THE BUILDING STRUCTURE OR STRUCTURAL MEMBERS. EXPOSED SUPPORTS SHALL BE PAINTED UNLESS OF NON-FERROUS MATERIAL OR PROVIDED WITH PLATED (RUSTPROOF) FINISH. 24. CONTRACTOR SHALL CLEAN ALL OF HIS WORK INSIDE AND OUT. AIR DISTRIBUTION SYSTEMS SHALL HAVE ALL DIRT AND FOREIGN MATERIAL REMOVED FROM INSIDE AND OUTSIDE OF DUCTS, PLENUMS, HOUSINGS, DEVICES, TERMINALS, ETC. AS INSTALLATION PROGRESSES, PROTECT OPEN ENDS OF DUCTWORK AND INLETS AND OUTLETS OF EQUIPMENT AND DEVICES DURING CONSTRUCTION. CLEAN ALL ACCESSIBLE PARTS OF DUCTWORK AND AIR PASSAGES IN EQUIPMENT BEFORE FILTERS ARE INSTALLED OR REPLACED FOR SYSTEM BALANCING. 23. ALL ROOF PENETRATIONS TO BE SEALED WATER TIGHT. PACK VOID BETWEEN DUCT PENETRATING ROOF AND STRUCTURE WITH FIBERGLASS INSULATION AND CAULK WATER TIGHT. FOR HIGH TEMPERATURE OR GREASE DUCTS UTILIZE MINERAL WOOL. 22. ALL EXHAUST FANS, RELIEF VENTS, AND PLUMBING VENTS TO BE INSTALLED A MINIMUM OF 10 FT. FROM OUTDOOR AIR INTAKES.21. ALL HARD 90° ELBOWS IN SUPPLY DUCTWORK ARE TO HAVE TURNING VANES PER SPECIFICATION AIR DUCT ACCESSORIES.20. ALL TRANSFER AIR DUCTS TO BE INTERNALLY INSULATED TO DETER NOISE TRANSFER. SIZE SHOWN ON PLANS INDICATES ACTUAL FREE AREA.19. ALL DUCTWORK CONSTRUCTION SHALL BE FABRICATED SHEET METAL & BUILT IN ACCORDANCE WITH "SMACNA" STANDARDS.18. ROUND DUCT SIZE TO BE THE SAME SIZE AS THE DIFFUSER NECK; UNLESS OTHERWISE NOTED. MAXIMUM LENGTH OF FLEXIBLE DUCTWORK CONNECTED TO A DIFFUSER SHALL BE 6'-0".17. ALL NEW PIPING AND DUCTWORK CROSSING THRU CORRIDOR AND/OR ROOM WALLS TO DECK; COORDINATE ALL OPENINGS THROUGH WALL CONSTRUCTION WITH GENERAL TRADES. SEAL AROUND DUCTWORK AND PIPING TO HELP REDUCE THE TRANSFER OF NOISE BETWEEN ROOMS. 16. PROVIDE VOLUME DAMPERS IN ALL BRANCH DUCTWORK AS REQUIRED TO BALANCE EACH SYSTEM. ALL VOLUME DAMPERS LOCATED ABOVE DRYWALL CEILINGS SHALL BE CABLE OPERATED WITH REMOTE REGULATOR LIKE YOUNG REGULATOR. FIELD VERIFY EXISTING CEILINGS FOR DRYWALL CEILINGS. COORDINATE LOCATION OF ALL DAMPERS WITH AIR BALANCE CONTRACTOR. IN HARD CEILINGS PROVIDE VOLUME DAMPER BEHIND THE GRILLE, REGISTER, OR DIFFUSER. 15. CONTRACTOR SHALL COORDINATE EXACT LOCATION OF ALL GRILLES, REGISTERS AND DIFFUSERS IN CEILINGS WITH THE CEILING SYSTEM AND LIGHT FIXTURES. PROVIDE FLEXIBLE DUCT UPSTREAM OF EACH DIFFUSER WHERE SHOWN. 14. ALL EQUIPMENT SHALL BE OF, AND CONSIST OF, AT LEAST MINIMUM SIZES SELECTED, AND SHALL PERFORM TO OR SURPASS THE MINIMUM REQUIREMENTS, SCHEDULES, NOTED AND SPECIFIED.13. DIVISION 23 CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL OF HIS WORK TO BE INSTALLED WITH ANY AND ALL OTHER CONTRACTORS TO BE AFFECTED BY SUCH WORK, PRIOR TO ORDERING ANY OF THE EQUIPMENT. THIS SHALL INCLUDE BUT NOT LIMITED TO ELECTRICAL CHARACTERISTICS, CONNECTIONS REQUIRED, PHYSICAL SIZE, COLOR AND FIT. ALSO REFER TO SPECIFICATIONS. 12. DIVISION 23 CONTRACTOR SHALL BE RESPONSIBLE FOR HIS RESPECTIVE WORK FOR REPAIRING AND PATCHING TO MATCH EXISTING SURFACES, SIDEWALKS, STREETS, FLOORS, WALLS, ROOFS, CEILING AND PAVEMENT. CONTRACTOR SHALL INCLUDE IN BID PROPOSAL ALL COSTS FOR CUTTING AND PATCHING REQUIRED TO INSTALL NEW OR REMOVE EXISTING WORK, EQUIPMENT, OR SYSTEMS. 11. ALL WALL THERMOSTATS, TEMPERATURE SENSORS, AND/OR HUMIDISTATS SHALL BE APPROXIMATELY 48" ABOVE FINISHED FLOOR TO CENTER AND LINED UP HORIZONTALLY WITH LIGHT SWITCHES UNLESS OTHERWISE NOTED OR DIRECTED BY THE ARCHITECT/ENGINEER. 10. ALL RECTANGULAR SHEET METAL DUCT SIZES ARE INSIDE DIMENSIONS. ALL ROUND DUCT SIZES SHOWN ARE INSIDE DIAMETERS. ALLOWANCE FOR ACOUSTICAL LINER WHERE INDICATED ON DRAWINGS MUST BE ADDED TO OBTAIN OUTSIDE SHEET METAL DIMENSION. 9. DUCT AND PIPING PENETRATING FLOOR SLABS AND/OR WALLS SHALL BE SEALED WITH ACOUSTIC SEALANT. IF THE FLOOR OR WALL IS FIRE RATED PROVIDE THE FIRE STOPPING OR FIRE DAMPER TO MAINTAIN THE FIRE RATING. 8. PIPING BRANCHES TO EQUIPMENT SHALL HAVE SAME SIZE VALVES AND FITTINGS AS THAT OF THE LINE SIZE.7. DIVISION 23 SHALL BE GUIDED BY THE ARCHITECT/ENGINEER'S REFLECTED CEILING PLAN FOR LOCATION OF DIFFUSERS, REGISTERS, GRILLES SHOWN OR COVERED BY THESE PLANS.6. ALL VALVES, ETC. SHALL BE INSTALLED ALLOWING EASY ACCESS BETWEEN LIGHT FIXTURES AND NO HIGHER THAN 12" TO 24" ABOVE THE CEILING. PROVIDE FITTINGS IN DUCTWORK AND PIPING AS REQUIRED SO THAT NO PIPING REMAINS TIGHT TO ROOF STRUCTURE. PROVIDE ACCESS PANELS AS REQUIRED. AREA ADJACENT TO THE ACCESS PANELS SHALL BE CLEAR OF ANY OBSTRUCTIONS. PROVIDE EXTENDED VALVE HANDLES FOR INSULATED PIPING. 5. ALL DUCTWORK, PIPING, AND VALVES SHALL BE CONCEALED ABOVE CEILING AND WITHIN WALLS IN FINISHED AREAS UNLESS OTHERWISE INDICATED.4. MAY NOT BE SHOWN. DIVISION 23 SHALL INSTALL HIS WORK IN A MANNER THAT WILL CONFORM WITH THE STRUCTURE. DIVISION 23 SHALL AVOID OBSTRUCTIONS, PRESERVE HEADROOM AND MAINTAIN MAXIMUM CLEARANCE WITHOUT FURTHER INSTRUCTION FROM THE ARCHITECT/ENGINEER OR ADDITIONAL COST TO THE OWNER. THESE DRAWINGS INDICATE REQUIRED SIZE AND POINTS OF TERMINATION FOR PIPING, DUCTWORK, CONDUIT, ETC.. THE EQUIPMENT SHOWN ILLUSTRATES SUGGESTED ROUTING, BUT ALL NECESSARY OFFSETS 3. ON MECHANICAL "M" SERIES DRAWINGS, DARK LINE ITEMS INDICATE NEW WORK. LIGHT LINE ITEMS ARE FUTURE WORK.2. THESE GENERAL NOTES APPLY TO M-SERIES DRAWINGS. ADDITIONAL GENERAL NOTES SPECIFIC TO A PARTICULAR DRAWING ARE NOTED ON THOSE SHEETS.1. REQUIREMENTS. REFER TO PLUMBING PLANS FOR CONDENSATE PIPING5. WITH PVC JACKETING. INSULATED WITH 1" FLEXIBLE ELASTOMERIC INSULATION ALL EXTERIOR REFRIGERANT PIPING SHALL BE4. WITH 1/2" FLEXIBLE ELASTOMERIC INSULATION. ALL REFRIGERANT PIPING INDOORS SHALL BE INSULATED3. ON PLANS. INSULATION, EXCEPT WHERE NOTED OTHERWISE EXTERNALLY WRAPPED WITH 1" FIBERGLASS STREAM OF INDOOR FAN COIL UNITS SHALL BE ALL SUPPLY AND OUTDOOR AIR DUCTWORK DOWN 2. 1. DUCTWORK SHALL NOT BE INSULATED. EXTERNALLY INSULATED. ALL OTHER EXHAUST AIR EXHAUST FAN BACK DRAFT DAMPER SHALL BE THE ROOF CURB OR WALL PENETRATION TO THE ALL EXHAUST AIR DUCTWORK FROM THE BOTTOM OF MXXX XX MXXX XX SCALE: 1/8" =1'-0" SHEET TITLE NORTH ARROW REVISION TRIANGLE# PLAN TITLE DESIGNATIONSCALE: 1/8" =1'-0" SHEET TITLE NOTE SYMBOLS (SHADED PORTION INDICATES EXISTING TO REMAIN) POINT OF DISCONNECTION (USE WHEN IDENTIFYING BIDDING ALTERNATES) STEAM TRAP DESIGNATION APPLY RECOMMENDED RUNNING LOAD, LBS/HR SAFTY FACTOR PSIG DISCHARGE PRESSURE PSIG STEAM PRESSURE EQUIPMENT E = FURNISHED WITH FT = FLOAT/THERMOSTATIC F = FLOAT T = THERMOSTATIC TRAP STYLE: DEMOLITION PLAN NOTE DETAIL NOTE DESIGNATION EQUIPMENT TAG DETAIL TITLE DESIGNATION ALTERNATE TAG POINT OF NEW CONNECTION EXISTING TO REMAIN DESIGNATION VALVE DESIGNATION WATER HAMMER DESIGNATION NEW WORK PLAN NOTE MECHANICAL HVAC, PIPING & PLUMBING SYMBOLS AND ABBREVIATIONS THERMO-WELL TEMPERATURE TRANSMITTER W/ GAUGE W/ THERMO-WELL SOLAR POWERED TEMPERATURE GREASE WASTEGW DTR DTS DUAL TEMPERATURE SUPPLY DUAL TEMPERATURE RETURN CD CONDENSATE DRAIN CHR CHS CTR CTS CONDENSER WATER SUPPLY TO FLUID COOLER CHILLED WATER SUPPLY CHILLED WATER RETURN CONDENSER WATER RETURN FROM FLUID COOLER COMPRESSED AIRA LINE TYPES DOMESTIC COLD WATER SUPPLY WASTE SANITARY SOIL BELOW GRADE NON-POTABLE WATER REFRIGERANT HOT GAS LINE ACID VENT ACID WASTE GAS STORM SEWER BELOW GRADE STORM SEWER ABOVE GRADE SANITARY SOIL ABOVE GRADE INDIRECT WASTE REFRIGERANT LIQUID LINE VENT BOILER BLOW DOWN BOILER GRAVITY RETURN VACUUM SERVICE VACUUM PUMP DISCHARGE FUEL OIL SUPPLY FUEL OIL DISCHARGE FUEL OIL RETURN FOV FOF FOG HWS HWR LPS MPS HPS PD STMR RS HEATING HOT WATER RETURN REFRIGERANT SUCTION LINE FUEL OIL VENT LINE FUEL OIL FILL FUEL OIL GAGE LINE HEATING HOT WATER SUPPLY LOW PRESSURE STEAM MEDIUM PRESSURE STEAM HIGH PRESSURE STEAM PUMPED DISCHARGE STEAM RETURN HW HWR DOMESTIC HOT WATER RETURN DOMESTIC HOT WATER SUPPLY CW ST G SAN BBD V BGR VAC VPD FOS FOD FOR RL IW NPW RHG ST AW AV SAN W DUCT CONTINUATION. MECHANICAL GENERAL NOTES 3-WAY BY-PASS VALVE (PLUMBING) PIPING SYMBOLS WATER/GAS METER FLOOR CLEANOUT END OF MAIN C.O. FLANGE PH SENSOR LINE CLEAN OUT PIPING REDUCER TRANSMITTER DIFFERENTIAL PRESSURE PRESSURE SWITCH VACUUM BREAKER FLOAT SWITCH FLOW METER VALVE IN ROAD BOX LEVEL CONTROLLER LEVEL SWITCH TEMPERATURE SENSOR STRAP-ON/OUTSIDE AIR FLOW SWITCH THERMOSTATIC MIXING VALVE PRESSURE GAGE, WITH SHUTOFF COCK AND SHUTOFF COCK PRESSURE GAGE, WITH SNUBBER SHUTOFF COCK PRESSURE GAGE, WITH PIGTAIL AND BALL VALVE FOR EXTRACTION FLOW TRANSMITTER W/ FULL PORTED DIFFERENTIAL PRESSURE SWITCH SLOPE ARROW SOLENOID VALVE STRAINER WITH BLOW DOWN 2-WAY VALVE (PNEUMATIC) GAS PRESSURE REGULATING VALVE VALVE IN RISER DOMESTIC HWR FLOW STATION GLOBE VALVE GATE VALVE BALANCE PLUG VALVE SHUT-OFF COCK. PRESSURE TRANSDUCER WITH TOTAL DISOLVED SOLIDS SENSOR. MOTORIZED BUTTERFLY VALVE PRESSURE RELIEF VALVE PIPING TURN UP PIPING TURN DOWN PIPE CAP PT PORT PIPE GUIDE EXPANSION JOINT FLEX CONNECTION UNION PITOT DEVICE FLOOR DRAIN PIPING TEE DOWN STRAINER PIPE ANCHOR GAS COCK CHECK VALVE SPRING LOAD CHECK VALVE PRESSURE REGULATING VALVE W/ FLOW DIRECTION HOSE BIBB / WALL HYDRANT PRESSURE INDEPENDENT CONTROL VALVE PNEUMATIC MODULATING BUTTERFLY VALVE BUTTERFLY VALVE BACK FLOW PREVENTER BALL VALVE 3-WAY MOTORIZED VALVE (MECHANICAL) 3-WAY BLINDER VALVE (PLUMBING) 2-WAY MOTORIZED VALVE 2-WAY GEAR DRIVE VALVE MANUAL BALANCE VALVE MANUAL AIR VENT AUTOMATIC AIR VENT AUTOMATIC FLOW LIMITING VALVE E/A LONG 90° RECTANGULAR ELBOW (DOWN). E/A LONG 90° RECTANGULAR ELBOW (UP). LONG 90° ROUND ELBOW (UP). S/A LONG 90° RECTANGULAR ELBOW (UP). LONG 90° ROUND ELBOW (DOWN). S/A LONG 90° RECTANGULAR ELBOW (DOWN). R/A LONG 90° RECTANGULAR ELBOW (UP). R/A LONG 90° RECTANGULAR ELBOW (DOWN). 24x4 S/A SLOT DIFFUSER. 48x4 S/A SLOT DIFFUSER. 12x12 S/A DIFFUSER W/ 8" FLEX DUCT. 24x24 S/A DIFFUSER W/ 10" FLEX DUCT. 24x24 R/A GRILLE. INSULATED BOOT. 24x24 R/A GRILLE W/ RECTANGULAR INTERNALLY INSULATED FLEX BOOT. 24x24 R/A GRILLE W/ ROUND INTERNALLY VVT. EXHAUST FAN HOOD. FAN HOOD ON ROOF ABOVE). EXHAUST FAN IN FLOOR PLAN (SHOWING EXHAUST DUCT IN FLOOR SPACE BELOW). EXHAUST FAN ON ROOF PLAN (SHOWING EXHAUST O/A INTAKE DUCT IN FLOOR PLAN. FLOOR SPACE BELOW). O/A ROOF PLAN (SHOWING EXHAUST DUCT IN FIRE-SMOKE DAMPER (HORIZONTAL). SMOKE DAMPER (HORIZONTAL). FIRE DAMPER (HORIZONTAL). FIRE-SMOKE DAMPER (VERTICAL). SMOKE DAMPER (VERTICAL). FIRE DAMPER (VERTICAL). SOUND ATTENUATOR. VOLUME DAMPER. BACKDRAFT DAMPER. UNDERCUT DOOR. ACCESS DOOR. SMOKE DETECTOR. STATIC PRESSURE SENSOR. THERMOSTAT. HUMIDISTAT. C02 SENSOR. ALARM. AIRFLOW ARROW. AIRFLOW ARROW. DOOR GRILLE. DOOR LOUVER. CFM TAG. DOUBLE LINE ROUND DUCT CONTINUATION. MOTORIZED DAMPER (ELEVATION). MOTORIZED DAMPER. SINGLE OR DOUBLE LINE RECTANGULAR SINGLE LINE ROUND DUCT CONTINUATION. DENOTES SPRIAL DUCT. HVAC SYMBOLS DUCT. RECTANGULAR 45° KICKERS FOR (INSIDE CLEAR DIMENSIONS). 2ND NUMBER - DIMENSION PERPENDICULAR TO VIEW. 1ST NUMBER - DIMENSION IN PLANE OF VIEW. FLAT OVAL DUCT SIZE IN INCHES. (INSIDE CLEAR DIMENSIONS). 2ND NUMBER - DIMENSION PERPENDICULAR TO VIEW. 1ST NUMBER - DIMENSION IN PLANE OF VIEW. RECTANGULAR DUCT SIZE IN INCHES. (INSIDE CLEAR DIMENSIONS). NUMBER - DIAMETER OF ROUND DUCT. ROUND DUCT SIZE IN INCHES. PLAN NOTES:DUCT INSULATION NOTES: 90° SHEET METAL ELBOW 90° SHEET METAL ELBOW MAX. LENGTH 6 FT MIN. LENGTH 3 FT. FLEXIBLE DUCT. LENGTH AT VAV INLET. 3 DIAMETER MINIMUM 32 1 AxBØAAxBAxBAxB A/BA/BØAØAAxBA/BA/BØAØADUCTWORK. EXPOSED, ROUND REGISTER BOX IN S/A GRILLE INSTALLED IN MANUAL VOLUME DAMPER. EXTRACTOR. ADJUSTABLE VANED ROUND DUCT RISING. UNLESS NOTED OTHERWISE. S/A DUFFUSERS ARE 4-WAY THEN BACK TO HORIZONTAL. S/A DUCT TURNING DOWN BRACE FLAT OVAL DUCT. TYPICAL AIR HANDLING UNIT. FLAT OVAL DUCT RISING. 90° LONG RADIUS ELBOW. VAV TERMINAL UNIT. WIDTH. TIMES DIAMETER OR RADIUS = 1 1/2 MAX. LENGTH 6 FT MIN. LENGTH 3 FT. FLEXIBLE DUCT. POSSIBLE. PREFERRED WHENEVER RADIUSED ELBOWS ARE TURNING VANES. 90° MITERED ELBOW W/ DUCT RISING. RECTANGULAR DAMPER. FIRE & SMOKE COMBINATION EVEN IF NO ACCESS DOOR IS SHOWN. FIRE/SMOKE DAMPERS IS REQUIRED, ACCESS TO ALL FIRE, SMOKE AND ACCESS DOOR TO ENSURE ACCESS. ACCESS DOOR (A.D.). FIELD LOCATE LOCATIONS. REFER TO NOTES FOR LINING OR DOUBLE WALL SHEET METAL CONNECTION STANDARDS NOT ALL NOTES, DESIGNATORS, SYMBOLS OR ABBREVIATIONS MAY APPLY TO THIS PROJECT # X XXX # X X # 1 2 3 DP DPT M F.C.O. XX-X CFM ØA ØA A#6 T TT PS LS FLS C.O. FS LC FM VB PH TDS PTS FT P P P M FD PT S PI M M G MV AV L G M U SD SP T H 2CO BDD SA ALL HORIZONTAL CONDENSATE PIPING TO BE INSULATED WITH 1/2" FLEXIBLE ELASTOMERIC INSULATION.29. GUEST ROOM FCU SUPPLY DUCT TO BE INTERNALLY INSULATED WITH 1" FLEXIBLE ELASTOMERIC DUCT LINER. DUCT SIZE SHOWN ON PLANS INDICATE FREE AREA.30. ALL TRANSFER DUCTS TO BE INTERNALLY LINED WITH 1" FLEXIBLE ELASTOMERIC DUCT LINER. DUCT SIZE SHOWN ON PLANS INDICATES FREE AREA.31. ALL SUPPLY AIR DUCT TO BE INSULATED WITH 3/4# FLEXIBLE FIBERGLASS INSULATION, 1-1/2" THICKNESS. 32. DRAWING NO. DATE GSB PROJECT NO. DRAWING TITLE 3555 NW 58TH Street Suite 700-W Oklahoma City, OK 73112 T: 405.848.9549 F: 405.848.9783 www.gsb-inc.com Copyright © GSB, Inc M0-01 03/22/19 MECHANICAL SYMBOLS AND ABBREVIATIONS 171528 CARMEL, INCARMEL, IN HOTEL CARMICHAEL AT CITY CENTER 2018 ARCHITECT GSB, INC 3555 NW 58th Street, Suite 700W Oklahoma City, OK 73112 405 / 848-9549 CIVIL ENGINEER Circle Design Group 9229 Delegates Row, Suite 150 Indianapolis, IN 46240 317 / 706-2075 STRUCTURAL ENGINEER StructurePoint 7260 Shadeland Station Indianapolis, IN 46256 317 / 547-5580 MEP ENGINEER DEEM 6831 E. 32nd Street, Suite 200 Indianapolis, IN 46226 317 / 860-2990 INTERIOR DESIGNER HBA Hirsch Bedner Associates 171 17th Street NW, Suite 600 Atlanta, GA 30363 404 / 873-4379 FOOD SERVICE CONSULTANT Ricca Design Studios 5325 South Valentia Way Greenwood Village, CO 80111 303 / 928-1333 SHEET INDEX SHEET NO. SHEET TITLE M0-01 MECHANICAL SYMBOLS AND ABBREVIATIONS M1-01 MECHANICAL FLOOR PLAN LEVEL 1 - OVERALL M1-01A MECHANICAL FLOOR PLAN LEVEL 1 - AREA A M1-01B MECHANICAL FLOOR PLAN LEVEL 1 - AREA B M1-01C MECHANICAL FLOOR PLAN LEVEL 1 - AREA C M1-02 MECHANICAL FLOOR PLAN LEVEL 2 - OVERALL M1-02A MECHANICAL FLOOR PLAN LEVEL 2 - AREA A M1-02B MECHANICAL FLOOR PLAN LEVEL 2 - AREA B M1-02C MECHANICAL FLOOR PLAN LEVEL 2 - AREA C M1-03 MECHANICAL FLOOR PLAN LEVEL 3 M1-04 MECHANICAL FLOOR PLAN LEVEL 4 M1-05 MECHANICAL FLOOR PLAN LEVEL 5 M1-06 MECHANICAL FLOOR PLAN LEVEL 6 M1-07 MECHANICAL ROOF PLAN M2-01 MECHANICAL PIPING FLOOR PLAN LEVEL 1 M2-02 MECHANICAL PIPING FLOOR PLAN LEVEL 2 M2-03 MECHANICAL PIPING FLOOR PLAN LEVEL 3 M2-04 MECHANICAL PIPING FLOOR PLAN LEVEL 4 M2-05 MECHANICAL PIPING FLOOR PLAN LEVEL 5 M2-06 MECHANICAL PIPING FLOOR PLAN LEVEL 6 M3-01 MECHANICAL SECTIONS M4-01 MECHANICAL ENLARGED PLANS M4-02 MECHANICAL ENLARGED PLANS M4-03 MECHANICAL ENLARGED PLANS M5-01 MECHANICAL DETAILS M6-01 VRF PIPING AND WIRING DIAGRAMS M6-02 VRF PIPING AND WIRING DIAGRAMS M6-03 VRF PIPING AND WIRING DIAGRAMS M6-04 VRF PIPING AND WIRING DIAGRAMS M6-05 VRF PIPING AND WIRING DIAGRAMS M6-06 VRF PIPING AND WIRING DIAGRAMS M6-07 VRF PIPING AND WIRING DIAGRAMS M6-08 VRF PIPING AND WIRING DIAGRAMS M6-09 VRF PIPING AND WIRING DIAGRAMS M6-10 VRF PIPING AND WIRING DIAGRAMS M6-11 VRF PIPING AND WIRING DIAGRAMS M6-12 VRF PIPING AND WIRING DIAGRAMS M6-13 VRF PIPING AND WIRING DIAGRAMS M6-14 MECHANICAL RISER DIAGRAMS M7-01 MECHANICAL SCHEDULES M7-02 MECHANICAL SCHEDULES M7-03 MECHANICAL SEQUENCES M8-01 MECHANICAL ISOMETRICS M8-02 MECHANICAL ISOMETRICS M8-03 MECHANICAL ISOMETRICS REVISIONS NO. DATE DESCRIPTION