Loading...
HomeMy WebLinkAboutM7-01-MECHANICAL-SCHEDULES-Rev.2VOLTS/PHASE MCA MOP CU‐1AHU‐1 DAIKIN RCS025D 25 95 R410A 460/3 50 60 1853 1,2,3,4,5 AIR COOLED CONDENSING UNIT SCHEDULE MARK UNIT ELECTRICAL DATAMANUFACTURER MODEL NOMINAL   TONS REMARKSAMBIENT  TEMP REFRIGERANT  TYPE 5. PROVIDE WITH COMPRESSOR SOUND BLANKET AND PROPELLER  FAN BAFFLES. 3. PROVIDE WITH HOT  GAS REHEAT AND HOT GAS BYPASS KIT. 4. PROVIDE WITH SPRING ISOLATION KIT. REMARKS: 1. PROVIDE WITH115, 20 AMP CONVENIENCE OUTLET.  2. PROVIDE WITH LOW AMBIENT  CONTROL TO 0 DEGREES F. WEIGHT (LBS)SERVES DS-1 1ST MDF DAIKIN FTX12NMVJU 434 10.9 9.5 13.5 DSCU-1 RX12NMVJU 208/1 60 1,2,3,4 DS-2 1ST ELEC DAIKIN FTX12NMVJU 434 10.9 9.5 13.5 DSCU-2 RX12NMVJU 208/1 60 1,2,3,4 DS-3 1ST EMER POWER DAIKIN FTX12NMVJU 434 10.9 9.5 13.5 DSCU-3 RX12NMVJU 208/1 60 1,2,3,4 DS-4 2ND A/V RM DAIKIN FTX12NMVJU 434 10.9 9.5 13.5 DSCU-4 RX12NMVJU 208/1 60 1,2,3,4 DS-5 ELEC DAIKIN FTX12NMVJU 434 10.9 9.5 13.5 DSCU-5 RX12NMVJU 208/1 60 1,2,3,4 DS-6 ELEC DAIKIN FTX12NMVJU 434 10.9 9.5 13.5 DSCU-6 RX12NMVJU 208/1 60 1,2,3,4 DS-7 ELEC DAIKIN FTX12NMVJU 434 10.9 9.5 13.5 DSCU-7 RX12NMVJU 208/1 60 1,2,3,4 DS-8 ELEC DAIKIN FTX12NMVJU 434 10.9 9.5 13.5 DSCU-8 RX12NMVJU 208/1 60 1,2,3,4 REMARKS: WEIGHT 4. FURNISH WITH CONDENSATE PUMP 2. FURNISH WITH WIRELESS REMOTE CONTROLLER KIT / WALL MOUNTED THERMOSTAT. SERVES REMARKSMODEL 3. PROVIDE WITH WIND BAFFLE FOR -4 DEGREE OPERATION. 1. SINGLE POINT POWER CONNECTION. COOLING TOTAL MBH HEATING MBH DX SPLIT UNIT SCHEDULE MARK MANUFACTURER CFM SUPPLY OUTDOOR UNIT COOLING SENS MBH VOLTS/PH INDOOR UNIT MODEL MARK EDH-1-01 GREENHECK IDHC 1624 26 10 1013 35.1 75 95 10.3 SCR 24V 480/3 1,2 EDH-1-21 GREENHECK IDHC 1624 26 10 1013 35.1 75 95 10.3 SCR 24V 480/3 1,2 EDH-1-22 GREENHECK IDHC 1130 20 10 893 24.4 75 95 7.2 SCR 24V 480/3 1,2 EDH-2-03 GREENHECK IDHC 450 10 10 690 9.7 75 95 2.8 SCR 24V 480/3 1,2 EDH-2-04 GREENHECK IDHC 1377 22 10 997 29.7 75 95 8.7 SCR 24V 480/3 1,2 EDH-2-12 GREENHECK IDHC 1377 22 10 997 29.7 75 95 8.7 SCR 24V 480/3 1,2 EDH-2-15 GREENHECK IDHC 2047 24 14 952 44.2 75 95 13.0 SCR 24V 480/3 1,2 EDH-2-17 GREENHECK IDHC 1377 22 10 997 29.7 75 95 8.7 SCR 24V 480/3 1,2 EDH-2-18 GREENHECK IDHC 1094 20 10 864 23.6 75 95 6.9 SCR 24V 480/3 1,2 ELECTRIC DUCT HEATER SCHEDULE KW VOLTS/ PHASEMARKCONTROL VOLTAGEMANUFACTURER MODEL CFM LAT CONTROL TYPE 2. FURNISH WITH SCR CONTROL, CONTROL TRANSFORMER AND AIRFLOW SWITCH. VELOCITY FPM REMARKS: REMARKSDESIGN MBH EAT 1. FURNISH WITH DOOR INTERLOCKING DISCONNECT. DUCT WIDTH DUCT HEIGHT EWH-1 QMARK AWH4408F VEST 106 WALL 350 13.6 4 19.2 208/1 1 EWH-2 QMARK AWH4408F WOMEN 104 WALL 350 13.6 4 19.2 208/1 1 EWH-3 QMARK AWH4408F MEN 103 WALL 350 13.6 4 19.2 208/1 1 EWH-4 QMARK AWH4408F VEST 144 WALL 350 13.6 4 19.2 208/1 1 EWH-5 QMARK AWH4408F STAIR 1-1ST WALL 350 13.6 4 19.2 208/1 1 EWH-6 QMARK AWH4408F CORRIDOR 121 WALL 350 13.6 4 19.2 208/1 1 EWH-7 QMARK AWH4408F STAIR 2-1ST WALL 350 13.6 4 19.2 208/1 1 EWH-8 QMARK AWH4408F CORRIDOR 122 WALL 350 13.6 4 19.2 208/1 1 EWH-9 QMARK AWH4408F STAIR 1-3RD WALL 350 13.6 4 19.2 208/1 1 EWH-10 QMARK AWH4408F STAIR 2-3RD WALL 350 13.6 4 19.2 208/1 1 EWH-11 QMARK AWH4408F STAIR 1-5TH WALL 350 13.6 4 19.2 208/1 1 EWH-12 QMARK AWH4408F STAIR 2-5TH WALL 350 13.6 4 19.2 208/1 1 EWH-13 QMARK AWH4408F STAIR 2-ROOF WALL 350 13.6 4 19.2 208/1 1 EWH-14 QMARK AWH4408F FIRE PUMP WALL 350 13.6 4 19.2 208/1 1 EUH-1 QMARK MUH-07-8 RECYCLING SUSPENDED 650 25.6 7.5 36.0 208/1 2,3,5 EUH-2 QMARK MUH-07-8 CAN SUSPENDED 650 25.6 7.5 36.0 208/1 2,3,5 EUH-3 QMARK MUH-07-8 PENTHOUSE SUSPENDED 650 25.6 7.5 36.0 208/1 2,3,5 EUH-4 QMARK MUH-07-8 PENTHOUSE SUSPENDED 650 25.6 7.5 36.0 208/1 2,3,5 EUH-5 QMARK MUH-07-8 2ND MECH RM SUSPENDED 650 25.6 7.5 36.0 208/1 2,3,5 EUH-6 QMARK MUH-07-8 2ND MECH RM SUSPENDED 650 25.6 7.5 36.0 208/1 2,3,5 EUH-7 QMARK MUH-07-8 2ND MECH RM SUSPENDED 650 25.6 7.5 36.0 208/1 2,3,5 EBH-1 INDEECO BMI 914U 01400C 2ND LOBBY STAIR PEDESTAL - 16.0 4.7 22.6 208/1 1 EBH-2 INDEECO BMI 914U 01400C 2ND LOBBY STAIR PEDESTAL - 16.0 4.7 22.6 208/1 1 EBH-3 INDEECO BMI 914U 01400C 2ND LOBBY STAIR PEDESTAL - 16.0 4.7 22.6 208/1 1 ERH-1 QMARK FRS346S W/F4QL36480 PORT COCHERE RADIANT SUSPENDED 60˚ SYMMETRICAL 69.6 20.4 42.5 480/3 6 ERH-2 QMARK FRS346S W/F4QL36480 PORT COCHERE RADIANT SUSPENDED 60˚ SYMMETRICAL 69.6 20.4 42.5 480/3 6 ERH-3 QMARK FRS346S W/F4QL36480 PORT COCHERE RADIANT SUSPENDED 60˚ SYMMETRICAL 69.6 20.4 42.5 480/3 6 EPUH-1 QMARK MSPH DOCK PLENUM PLENUM 400 34.8 10.2 49.0 208/1 1 EAC-1 MARLEY E72 CORRIDOR 139 AIR CURTAIN 4920 109.2 32 66.7 480/3 1 ELECTRIC HEATER SCHEDULE KW VOLTS/ PHASEMARK MANUFACTURER MODEL CFMTYPESERVES 6. PROVIDE WITH DISCONNECT FOR FIELD MOUNTING AND WIRING BY CONTRACTOR. REMARKS: REMARKSDESIGN MBH 1. PROVIDE WITH INTEGRAL FACTORY MOUNTED AND WIRED THERMOSTAT AND DISCONNECT. AMPS 2. PROVIDE WITH THERMOSTAT AND DISCONNECT FOR FIELD MOUNTING AND WIRING BY CONTRACTOR. 3. PROVIDE LOW VOLTAGE TRANSFORMER FOR 24V CONTROL. 4. UNIT TO BE CONTROLLED BY DOOR SWITCH. PROVIDE WITH INTEGRAL THERMOSTAT. 5. PROVIDE WITH WALL/CEILING MOUNTING BRACKET. ERV‐1 DAIKIN DPS025A 5,700 1.75" 6.79 10 4,200 1.5" 2.59 4 70/50 ‐10/‐10 35/28.7 72/62 88/78.2 78.4/69.7 297.4 167.8 80.2/69.7 53.3/53.2 103.5 70/59.6 450 360 35 93.2 90 67.2 460/3 5000 1,2,4,5,6,7 ERV‐2 DAIKIN DPS025A 5,700 1.75" 6.79 10 4,200 1.5" 2.59 4 70/50 ‐10/‐10 35/28.7 72/62 88/78.2 78.4/69.7 297.4 167.8 80.2/69.7 53.3/53.2 103.5 70/59.6 450 360 35 93.2 90 67.2 460/3 5000 1,2,4,5,6,7 ERV‐3 DAIKIN DPS020A 4,750 1.5" 4.62 10 3,800 1" 1.7 4 70/50 ‐10/‐10 38/30.7 72/62 88/78.2 77.8/69.1 249.4 132 77.8/69.1 51.8/51.8 91.6 70/58.8 300 240 38 85.6 80 54.8 460/3 5000 1,2,3,5,6,7 ERV‐4 DAIKIN DPS020A 4,750 1.5" 4.62 10 3,500 1" 1.7 4 70/50 ‐10/‐10 38/30.7 72/62 88/78.2 77.8/69.1 249.4 132 77.8/69.1 51.8/51.8 91.6 70/58.8 300 240 38 85.6 80 54.8 460/3 5000 1,2,3,5,6,7 HP LAT   DB/WB 4. PROVIDE WITH ROOF CURB W/SIDEWALL DUCT CONNECTIONS 5. PROVIDE W/HOT GAS REHEAT WITH DUCT HUMIDITY SENSOR. BHP ESP LAT    DB/WB 3. PROVIDE WITH 14" ROOF CURB MODEL BHPHP DX COOLING COIL VOLTS/ PHASE 7. PROVIDE WITH MERV 8 PRE‐FILTERS AND MERV 13 SECONDARY FILTERS. 6. BAS INTERFACE CARDS EAT   DB/WB EAT   DB/WB REMARKS: EAT  DB/WBESP TOTAL  MBH 1. PROVIDE WITH UNIT MOUNTED DISCONNECT, SINGLE‐POINT  ELECTRICAL CONNECTION  AND CONVENIENCE  OUTLET EAT    DB/WB ENERGY RECOVERY VENTILATOR SCHEDULE MARK MANUFACTURER SUPPLY  FAN  DATA CFM  SUPPLY LAT  DB/WBCFM  EXHAUST HOT GAS REHEAT MOP EXHAUST FAN DATA SENSIBLE   MBH 2. PROVIDE WITH INVERTER COMPRESSORS EAT  DB/WB WINTER EXHAUST WINTER OUTSIDE SUMMER EXHAUST SUMMER OUTSIDE TOTAL    MBH MCALAT   DB/WB REMARKSWEIGHT  (LBS) GAS HEAT EXCHANGER INPUT  MBH OUTPUT  MBH EAT LAT UNIT ELECTRICAL AHU ‐1 DAIKIN CAH012GDDC KITCHEN 2ND FLR MECH 4,250 2,300 1.5" PLENUM 2.95 5 259.4 132.6 82/71.7 53.5/52.8 375 300 26 86 460/3 3,500 1,2,3,4,5,6,7 BHP  SUPPLY FAN DATA GAS HEATING DATA INPUT  MBH VOLTS/  PHASEMARK MANUFACTURER LOCATION CFM  SUPPLY ESP UNIT  WEIGHT  (LBS) DX COOLING COIL DATA TOTAL    MBH EAT    DB/WB OUTPUT  MBH EAT LAT SENSIBLE  MBH CFM OA  MIN AHU SCHEDULE REMARKS: 1. 0‐100% MODULATING ECONOMIZER W/DRY BULB CONTROL REMARKSSERVESMODELLAT   DB/WBHPTYPE 2. PROVIDE WITH MODULATING GAS HEAT EXCHANGER 3. PROVIDE WITH DUCT STATIC PRESSURE SENSORS 4. PROVIDE W/HOT GAS REHEAT 5. BAS INTERFACE CARDS 6. VFD DUTY FAN MOTOR. 7. PROVIDE WITH MERV 8 OUTDOOR AIR AND EXHAUST FILTERS.